LSG2-150 2V150Ah

Gel SLA Battery


Range Summary
By combining the newly developed nano gel electrolyte with up-to-date
AGM structures, BSB created the innovative LSG range of batteries. The
range offers 20 years design life with very high deep cycling capabilities.
This range is highy suited to telecom outdoor applications, renewable
energy system and other harsh environment applications.

Application
Correspondence exchange and transmission system Emergency power system
Mobile communication system UPS
Power plant and power transformer system Other spare, circulatory system
Radio and broadcasting station
Navigation and signaling system

General Features
Sealed and maintenance free operation.
Non-Spillable construction design.
ABS containers and covers (UL94 V0, optional). 20mm (0.79inch)

Safety valve installation for explosion proof.

7mm (0.28inch)
High quality and high reliability. M8mm (0.31inch)

Exceptional deep discharge recovery performance.


Low self discharge characteristic.
Flexible design for multiple installation positions.

Construction
Positive ...... Lead dioxide Safety valve ...... EPDR
Negative ...... Lead Terminal ...... Copper
Container ...... ABS Separator ...... AGM
Cover ...... ABS Electrolyte ...... Acid with gel Terminal Dimensions
Sealant ...... Epoxy Resin
221mm(8.70inch)

172mm(6.77inch)

Battery Model LSG2-150


Designed Floating Life 20 Years
20HR(7.94A,1.80V) 10HR(15A,1.80V) 5HR(25.6A,1.75V) 1HR(94.1A,1.60V)
Capacity(20oC)
159Ah 150Ah 128Ah 94.1Ah
Length Width Height Total Height
Dimensions
172mm(6.77inch) 102mm(4.02inch) 206mm(8.11inch) 221mm(8.70inch)
Approx. Weight 8.7Kg (19.2 lbs)
Internal Resistance Full charged at 20oC :0.00082 Ohm
Self Discharge < 3% of capacity declined per month at (20oC)

Capacity Affected 40oC 20oC 0oC -15oC


by Temp.(10HR) 109% 100% 85% 65%
Cycle use Float use
Charge Voltage(20oC)
2.35V-2.40V(-5mV/ oC), max. Current: 37.5A 2.25-2.29V(-3mV/ oC)

Page 1 of 2
LSG2-150 2V150Ah

Gel SLA Battery


Capacity

Current

Voltage
Charge

Charge

Charge
Charge Characteristic Discharge Characteristic (20oC)
o
(%) (CA) (V/Cell) Constant Charge at 0.25CA-2.35V (20 C)

Discharge Voltage (V/Cell)


120 2.17
Charge Charge
2.35 Capacity
100 Voltage 2.00

80 2.17 1.83
0.25
100%Discharge 0.25CA 0.1CA 0.05CA
1.67
60 0.20
2.00 50%Discharge 3CA 2CA 1CA 0.6CA
0.15 1.60
40
0.10 1.83 1.33
20 0.05
Charge Current
0 0 0 2 6 12 30 60 3 10 20
0 2 4 6 8 10 12 Min Hour
Time(hour)

Relationship of OCV and state of charge Self Discharge Characteristics


110
Battery Voltage (V/Cell)

2.25 105
100
2.17 95
Capacity (%)

90
85
2.08 80
75
70
2.00
65
60
1.92 55
50
40 C
o o
30 C 20oC
45
1.83 40 0
0 10 20 30 40 50 60 70 80 90 100 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Remained Capacity(%) Storage time:months

Constant current discharge ratings - amperes at 20 C

F.V/ Tim e 5MI N 10MI N 15MI N 30MIN 1HR 3HR 5HR 10HR 20HR
1.60V 525 360 263 158 94.1 41.0 26.2 15.9 8.30
1.67V 473 329 255 153 93.9 40.8 26.0 15.7 8.27
1.70V 449 317 246 150 93.6 40.7 25.8 15.5 8.25
1.75V 399 293 233 147 92.6 40.5 25.6 15.3 8.23
1.80V 360 272 222 143 91.5 40.4 25.4 15.0 7.94
1.85V 273 224 192 131 90.5 40.2 25.2 14.7 7.47

Constant power discharge ratings - watts at 20 C

F.V/ Tim e 5MI N 10MI N 15MI N 30MIN 1HR 3HR 5HR 10HR 20HR
1.60V 866 597 465 297 185 78.6 49.8 31.8 16.6
1.67V 821 590 461 291 179 78.2 49.5 31.3 16.5
1.70V 767 575 453 284 174 78.0 19.3 31.1 16.3
1.75V 714 537 426 276 173 77.4 49.0 30.6 16.1
1.80V 641 500 401 269 170 76.4 48.5 30.0 15.9
1.85V 513 414 350 246 168 76.1 47.8 29.5 14.9

ISO9001

COPYRIGHT BSB POWER COMPANY LIMITED

Page 2 of 2 (Updated: 1-Nov-2010)