Você está na página 1de 27

PART B Chapter 5 Contents

Vertical Loads 5.1 basis of design

This chapter provides the design requirements for 5.2 design requirements
masonry subject to vertical loads resulting from
superstructure weight and the vertical component of 5.3 standard designs
overturning loads.
It includes the load capacities of unreinforced masonry 5.4 worked example
walls, grouted masonry walls and reinforced masonry
lintels.

PART B:CHAPTER 5
Vertical Loads QUIT
5.1 BASIS OF DESIGN
When vertical loads are applied to masonry
walls, consideration must also be given
to any bending moments induced by
IL IL IL IL
eccentricity of the loads. IL IL
A A
The principal factors affecting the IL IL IL IL IL IL
compressive capacity of a wall or pier are B B
its slenderness ratio, its cross-sectional
properties and compressive strength, the
eccentricity of any load, rotational restraint
and the buckling mode.
PL + IL PL + IL PL + IL
For the design of a cavity wall subjected PL
to vertical loading, each leaf must be
considered separately, therefore assuming PL + IL
A
PL + IL PL + IL
A
that no mutual support is being supplied by PL
the individual leaves.
B B
In multi-storey buildings, the maximum
vertical load on each loadbearing wall would
result from the application of the maximum
imposed load to all floors that contribute
load to the wall, Figure 5.1. However Figure 5.1 Typical Analysis for Maximum Figure 5.2 Typical Analysis for Maximum
this will probably not give the maximum Vertical Load on a Wall in a Multi-storey Eccentricity on a Wall in a Multi-storey
eccentricity and may not necessarily lead Building Building
to the worst case for design. It may be
necessary to check several combinations of
load, eg “chequer board” loading pattern,
Figure 5.2.

PART B:CHAPTER 5
Vertical Loads QUIT
5.2 DESIGN REQUIREMENTS
5.2.1 WALLS SUBJECT TO VERTICAL characteristic unconfined compressive lateral supports. See AS 3700 Clause 2.7. in this manual.
COMPRESSION FROM strength of a masonry wallette by the ■ A wall or pier supporting other systems
For a wall that is supported along one or
UNIFORM LOADS bedded area and the capacity reduction that bear on the top This case covers the
both of its vertical edges, two-way action
factor. If the cores are grout filled, further situation where a steel or timber roof
Behaviour of Walls in Compression will stiffen the wall provided there is
capacity can be included. The capacity of bears directly on the top of the wall.
When relatively squat masonry units (eg sufficient shear capacity at the connection
grouted masonry is substantially less than Generally, the magnitude of the loads
76 mm x 110 mm x 230 mm bricks) are of the panel to its lateral supports. However
the sum of the strengths of the hollow will be relatively low and vertical load
crushed in a compression testing machine, the consideration of this additional support
masonry and the grout core, due to the capacity will not represent a problem. No
the platens tend to hold the unit together, is limited to the “Refined Design” method of
interaction of the core and its surrounding charts are provided for this case.
inhibiting the formation of cracks giving an AS 3600 Clause 7.3.4.
shell. The mechanism of failure is influenced
apparent increase in strength. AS/NZS 4455 ■ A wall or pier supporting a load applied
by the differing deformation characteristics Control joints are not capable of effectively
requires that this apparent confined strength at the face of the masonry This case often
of the materials, and possible shrinkage transmitting shear across the joint and must
be modified by a reduction factor to yield an occurs in town-house construction where
effects between the grout core and the be treated as free ends. Vertical chases in
equivalent unconfined strength. This does timber floors are fixed to the face of
tapered shells. masonry also diminish the shear transfer to
not apply to hollow concrete blocks, since masonry party walls. Charts are provided
adjacent lateral supports.
the tall thin face shells may be considered Fo = ø f’m Ab + kc f’cg Ac 7.3.2(2) for the case of 140 mm blockwork.
to be unconfined. (Initial failure is usually by √ 1.3 AS 3700 provides for two alternative
The slenderness coefficient (av) allows for
splitting of the webs rather than by face- approaches to the design for compression:
This basic compressive capacity must restraint at the top and bottom of the
shell crushing). ■ Design by simple rules (Simplified Design),
be further modified to account for the masonry. For a memberlaterally supported
When relatively squat masonry units (eg or at both top and bottom, av = 1.0 and for a
eccentricity of any load, rotational restraint
76 mm high bricks) are built with mortar and the buckling mode. This is done by ■ Design by refined calculation (Refined member laterally supported and rotationally
into a wallette and subjected to a vertical determining the appropriate value of the Design) This allows for further choice restrained at only its bottom, av = 2.5. One of
load, the mortar expands laterally and tends reduction factor, k. between the assumption of eccentricities the consequences of simplification has been
to split the brick. For tall units (eg 190 mm or their calculation by an equivalent- that, despite appearances to the contrary,
concrete blocks) the widely spaced mortar For a wall that incorportes engaged piers, frame approach. these values for av do not relate to the
joints have less effect. AS 3700 accounts the thickness may be increased by a factor, values used for the Refined Design Method.
kt from Table 7.2. Simplified Design Method
for this phenomenon by means of a factor, The value of av used in Equations 7.3.4.3(1),
The Simplified Design Method enables
kh (obtained from Table 3.2) which is used Lateral supports must be designed for any 7.3.4.3(2) and 7.3.4.3(4) for Refined Design is
masonry loadbearing walls and piers to be
to modify the characteristic unconfined horizontal forces plus 2.5% of the vertical not the same as the value av = 1.0 used in
designed using tabulated coefficients based
compressive strength of a masonry wallette. load, but not less than a pressure of 0.5 kPa Equations 7.3.3.4(1) for Simplified Design.
on conservative values for the expected
The relationship between the characteristic as set out in Clause 2.6.3. If the thickness of eccentricities and buckling mode of three For a wall that is supported along one or
unconfined compressive strength of the an engaged pier is such that the deflection particular applications, viz: both of its vertical edges, allowance is made
masonry units and characteristic unconfined under design load is less than span/500
■ A wall or pier supporting a concrete slab for the strengthening effect of two-way
compressive strength of a masonry wallette for unreinforced masonry or span/250 for
that bear on the top This is the most action in compression.
is given by AS 3700 Clause 3.3.2. reinforced masonry, it should be treated as a
common case for the loadbearing walls in
The basic compressive capacity, Fo of a lateral support rather than an engaged pier.
medium-rise residential and commercial
stocky wall is given by multipying the Many commonly constructed returns will
buildings. Charts for this case are plotted
not have sufficient length to be effective as

PART B:CHAPTER 5
Vertical Loads QUIT
Refined Design Method Slabs bearing on the walls below
The Refined Design Method permits the W1 (From above) W1
assessment of compressive strength based
on eccentricities and fixity determined by
either of two methods, ie the assumption H H
W 2 (From slab) W2 W3
of eccentricities or their calculation by an
equivalent-frame approach. The results
are generally not as conservative as the
Simplified Design Method, but involve more Slenderness Coefficient, av = 0.75 tw NOTE:
In both cases
rigorous calculation. 3 ‘e’ is measured
from the centreline tw tw tw tw
The value of av used in Equations 7.3.4.3(1), Wall fixed to slab Light floor or roof frame tw of the loaded leaf
7.3.4.3(2) and 7.3.4.3(4) for Refined Design but not supporting it bearing on wall 6 3 3 6
6
(Figure 5.3) is not the same as the value t
W2 w
t
(W 3 – W 2) w
of av = 1.0 used in Equation 7.3.3.4(1) for tw e= 6 e= 3 tw
W1+ W 2 W1 + W 2 + W 3
Simplified Design.
The Refined Design Method permits the H H Figure 5.4 Assumed Eccentricities for Refined Design Method
assessment of eccentricities and fixity by
either of two methods, ie the assumption
of eccentricities (Figure 5.4) or their Imposed load
calculation by an equivalent-frame approach Slenderness Coefficient, av = 0.85 Permanent load PL
(Figure 5.5). Both methods are described in Upward tilt of slab
the worked example. Top free Slab deflects downward
(not connected to any structure)
The bending moments at the top and
Double-curvature Single-curvature
bottom of the wall, ie the effective load
eccentricities, are influenced by a number External leaf
follows internal leaf
of factors. These include the relative rotation H
between the floor and the wall, local IL
crushing in the wall/beam joint, changing Permanent load PL
wall and slab stiffness with load level, Upward tilt of slab
Slab deflects downward Slab deflects downward
non-linear and time-dependent material Slenderness Coefficient, av = 2.5
If deflection of the lower slab
characteristics, two-way slab action, and the is small, there will be no
construction and loading sequence of the Figure 5.3 Values of av for Refined Design significant eccentricity of reaction
floor slab and walls. Method at the base of the wall and the wall
will approach single-curvature

Figure 5.5 Typical Equivalent-Frame Approach for Calculation of Eccentricities in the


Refined Design Method

PART B:CHAPTER 5
Vertical Loads QUIT
A rigid frame analysis can be carried out to Values of k are also tabulated in Table 7.3.
calculate the theoretical moment transferred Crushing failure, independent of member 1.0
from deflecting slabs into the walls above slenderness, is not covered in Table 7.3
and below if the connection was rigid. In 0.9
In long-span heavily-loaded, one-way floor
this analysis, the far ends of the members
systems where large floor deflections are 0.8
(floors and walls) may conservatively be
expected, the eccentricity of load can be
assumed to be pinned. Depending on the
controlled by the use of compressible
relative stiffnesses of the floors and walls 0.7
packing between the floor and its
and the amount of precompression in the
supporting wall adjacent to the most highly-
walls, a joint fixity factor may be determined 0.6
stressed face.
(Figure 5.7). Once the joint fixity is found,
the wall moment can be calculated by 0.5
multiplying the rigid frame moment by the e1 e1 e1
joint fixity factor. 0.4
Compressive
In most cases, eccentricities on internal walls stress on joint
0.3
will be small, and eccentricities on external (MPa) = 1.0
walls will be larger (see Design Chart of
0.2
Calculated Eccentricities). In this case the

Joint Fixity Factor


0.5
wall will usually be bent in double curvature,
and have a higher buckling resistance 0.1
0.25
(Figures 5.5 and 5.6).
e2= e 1 e2= 0 e2= - e 1 0
Where the wall compression is low, such as 0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
e2 e2 e2
e 1 = -1
occurs at the top of a building, excessive Slab Stiffness/Wall Stiffness
e1 = 1 e1 = 0
eccentricities will be indicated by a rigid
frame analysis. The eccentricity can be Figure 5.6 Typical Wall Buckling Modes Figure 5.7 Joint Fixity Factor for use in Refined Design Method
minimised by the use of flexible packing
near the loaded edge of the wall.
The reduction factor for slenderness and
eccentricity (k), is given by the following
equation: 7.3.4.5(1)
e2 e e e e
k = 0.5{1 + } { 1 - 2.083 1} - {0.025 - 0.037 1} (1.33 Sr - 8) + 0.5{1 - 0.6 1}{1 - 2}(1.18 - 0.03 Sr)
e1 tw tw tw e1

PART B:CHAPTER 5
Vertical Loads QUIT
5.2.2 WALLS SUBJECT TO VERTICAL This chapter includes values for the shear Corrosion protection requirements in ■ Steel lintels with an inorganic zinc silicate
COMPRESSION FROM and bending moment capacity of 140 mm AS/NZS 2699.3 are as follows: coating, abrasive blast cleaned to a
CONCENTRATED LOADS and 190 mm reinforced concrete masonry minimum of AS 1627.4 Class 2.5, and a
R0, R1, R2, R3 – For all applications except
lintels. Part B:Chapter 6 of this manual coating of 100 microns average and not
Concentrated loads are imposed by beams, as listed for R4 and R5.
includes a worked example showing lesss than 75 microns of inorganic zinc
lintels, columns, anchorages, etc. An analysis ■ Steel lintels, hot dip galvanised in
for concentrated loads must be carried the derivation of the shear and moment silicate in compliance with
capacities of reinforced masonry. accordance with AS/NZS 4680 or AS/NZS 3750.15 Type 3 or Type 6, plus at
out immediately under the load and at a AS/NZS 4791, except that the minimum
distance below of 0.5 times the height of the least 125 microns of two-pack high-build
5.2.4 Steel Lintels and Arch Bars coating mass shall be 300 g/m2 for R0, R1 epoxy micaceous iron oxide to AS 3750.14
wall. The concentrated load is assumed to and R2 and be 600 g/m2 for R3.
disperse at an angle of 45° from the area of Loads on Lintels ■ Steel lintels with a mastic coating,
load application. ■ Steel lintels with an inorganic zinc silicate abrasive blast cleaned to a minimum of
Masonry constructed in stretcher bond will
coating, abrasive blast cleaned to a AS 1627.4 Class 2.5, and a coating of at
The basic compressive strength capacity, Fo arch over an opening, provided there are
minimum of AS 1627.4 Class 2.5, and a least 400 microns of two-part high-build
should be calculated using the area which sufficient number of masonry courses above
coating of at least 75 microns of inorganic epoxy mastic to AS 3750.11
lies within the zone of dispersion at the and sufficient strength at the supports.
zinc silicate in compliance with
cross-section under consideration. If the load AS 3700 Commentary suggests that the load ■ Steel lintels with a duplex coating, hot-
AS/NZS 3750.15 Type 3 or Type 4, except
capacity immediately beneath a bearing exerted on the lintel can be assumed to be dip galvanised in accordance with
that for R3 the average coating thickness
plate is being calculated, the bearing area exerted by a triangle of masonry above the AS/NZS 4680 with a coating mass of
shall be not less than 100 microns in
should be used rather than the full bedded opening. 600 g/m2 and a coating of at least 50
compliance with AS/NZS 3750.15 Type 3.
area of the member microns of two-pack non-inhibitive epoxy
End Support ■ Steel lintels with a duplex coating, hot- primer to AS/NZS 3750.13 and at least 200
The factor kb allows for the enhancement of AS 3700 Clause 4.12 requires that lintels be dip galvanised in accordance with microns of two-pack high-build epoxy
strength in the region beneath the load but supported on the masonry abutments for a AS/NZS 4680 or AS/NZS 4791, except that micaceous iron oxide to AS 3750.14.
is limited to solid, cored or grouted hollow distance of at least 100 mm. hot-dip galvanising to be at least
masonry. For ungrouted hollow blockwork, 300 g/m2 and a coating to be at least R5 – For applications in saline or
Corrosion Resistance
no enhancement is permitted and kb is unity. 50 microns of two pack non-inhibitive contaminated water including tidal splash
Steel lintels and arch bars must comply
epoxy primer to AS/NZS 3750.13 and at zones and within 1 km of an industry
with the durability requirements of AS 3700
5.2.3 REINFORCED MASONRY LINTELS least 125 microns of two-pack high-build producing chemical pollutants.
Table 5.1 for the particular exposure
SUBJECT TO VERTICAL BENDING epoxy micaceous iron oxide to
classification. AS 3700 Clause 5.4.1 makes Detailing and Capacities
Reinforced concrete masonry lintels can be it clear that lintels or arch bars supporting AS 3750.14. Detailing information is given in Part
used to span over door, window or other the external leaf of a cavity wall or veneer C:Chapter 3, while permissible spans for
R4 – For applications subject to saline
openings and carry roof, floor or masonry wall are considered to be in an “exterior certain applications, in accordance with
wetting and drying, in aggressive soils, in
loads. If several courses of masonry are environment”. NCC–BCA Volume Two, are given in Steel
severe marine environments.
constructed above the lintel, the vertical Lintels and Arch Bars – Permissible Spans.
load may be calculated assuming a ■ Stainless steel lintels manufactured to
triangular area of masonry acting vertically AS 1449 Grade 316 or AS 1449 Grade
on the lintel and a substantial load 316L (UNS S31600 and UNS S31603
transferred by arching action back to the respectively)
supports.

PART B:CHAPTER 5
Vertical Loads QUIT
5.3 STANDARD DESIGNS
5.3.1 General Face-shell bedded 5.3.2 Standard design charts 5.3.3 INDEX OF CHARTS
Design and Detailing Minimum face-shell thickness, How to Read Vertical Moment and Shear Capacities,
All design and detailing shall comply with ts = 25 mm for 90 mm, 110 mm and The general procedure with most charts is as Reinforced Masonry Lintels:
the requirements of AS 3700 and, where 140 mm units follows: 140 mm and 190 mm leaves
appropriate, AS/NZS 1170. ts = 40 mm for some 140 mm units ■ Select the required wall thickness and Permissible Spans,
ts = 30 mm for 190 mm units material details.
All charts in this chapter (except the Steel Lintels and Arch Bars
Calculated Eccentricities Table) are based Minimum characteristic compressive ■ Select the appropriate support conditions
Simplified Design Method, Compressive
on the Simplified Design approach set out in strength, (eg, supported on four sides).
Capacity, Unreinforced Masonry,
AS 3700 Clause 7.3.3. f’uc = 15 MPa ■ Project the length of the wall between Supporting a Concrete Slab,
The basic compressive capacity, Fo Minimum characteristic lateral modulus of vertical supports and the height of 190 mm High, Face-Shell Bedded,
representing the compressive strength rupture, wall between horizontal supports to Ungrouted:
of the masonry before consideration of f’ut = 0.8 MPa determine the design point. 90 mm leaf
slenderness or eccentricity is noted with ■ Select a curve which is above or to the 110 mm leaf
Solid or cored concrete bricks
each chart. right of the design point. Read off the 140 mm leaf
Width 110 mm
load capacity corresponding to the 190 mm leaf
It is the designer’s responsibility to allow
Height 76 mm selected curve. If necessary, interpolate Grouted:
for the effects of control joints, chases,
between curves. 140 mm leaf
openings, strength and stiffness of Length 230 mm
■ Check that the masonry wall is adequate 190 mm leaf
ties and connectors, and strength and
Fully bedded for other loadings, design requirements 76 mm high, 110 mm leaf, fully bedded
stiffness of supports, in addition to normal
Minimum characteristic compressive and construction requirements. Some 162 mm high, 110 mm leaf, face-shell
considerations of loads and masonry
strength, charts have superimposed the robustness bedded
properties. Control joints and openings
f’uc = 10 MPa requirements for the same conditions. Supporting a Load Applied at the Face:
must be treated as free ends as specified by
140 mm leaf, 25 mm face-shell bedded
AS 3700. Minimum characteristic lateral modulus of 140 mm leaf, 40 mm face-shell bedded
Masonry Properties rupture,
f’ut = 0.8 MPa Refined Design Method – Reduction
The standard designs in this chapter are
Factors for Eccentricity and Slenderness
based on minimum masonry properties Mortar joints Using Calculated Eccentricities:
complying with the General Specification set Mortar type M3 (or M4) Various Wall Locations, Heights
out in Part C:Chapter 2, modified as noted
Joint thickness 10 mm and Thicknesses
on the standard design chart and as noted
below. Concrete grout
Hollow concrete blocks Minimum characteristic compressive
Width 90 mm, 110 mm, 140 mm and 190 mm strength,
f’c = 20 MPa
Height 190 mm
Minimum cement content 300 kg/m3
Length 390 mm

PART B:CHAPTER 5
Vertical Loads QUIT
REINFORCED MASONRY LINTELS – Vertical Moment and Shear Capacities

140-mm leaf 190-mm leaf


BARS Vc Mc BARS Vc Mc BARS Vc Mc BARS Vc Mc
N12 5.1 2.6 N12 12.5 11.4 N12 6.4 3.4 N12 7.9 3.6
N16 6.3 2.6 N16 13.7 19.4 N16 7.6 3.6 N16 10.2 3.6
N20 9.1 3.6 N20 13.1 3.6

100
300 100 100

70 129 (N12 bars)


95 127 (N16 bars)
125 (Y20 bars)
70

BARS Vc Mc BARS Vc Mc
N12 16.4 11.7 N12 17.9 22.0
N16 17.6 20.2 N16 20.2 32.2
N20 19.0 29.4 N20 23.1 32.2

300 300

NOTES
Vc = Shear capacity (kN) 129 (N12 bars)
95 127 (N16 bars)
Mc = Moment capacity (kN.m)
125 (Y20 bars)
Mortar type, M3
Block characteristic compressive strength,
f'uc = 15 MPa
Grout compressive strength, f'c = 20 MPa

PART B:CHAPTER 5
Vertical Loads QUIT
STEEL LINTELS AND ARCH BARS – Permissible Spans
Maximum clear span (mm) for following loading cases: Maximum clear span (mm) for following loading cases:
Tiles Metal Tiles Tiles Metal Tiles
Roof* Roof* Roof* Roof* Roof* Roof*

Section and Either leaf Section and Either leaf


Arrangement End support Brick Veneer Cavity Brick Single-leaf Wall Single-leaf Wall Arrangement End support Brick Veneer Cavity Brick Single-leaf Wall Single-leaf Wall
75 x 8 flat 100 x 100 x 6 angle
(4.71 kg/m) (9.16 kg/m)
100 mm 490 250 NA NA 100 mm for 3130 2290 2290 1810
spans < 1 m
100
150 mm for
8 6 spans > 1 m

75 100

75 x 10 flat 100 x 100 x 8 angle


(5.89 kg/m) (11.8 kg/m)
100 mm 610 250 250 250 100 mm for 3370 2410 2410 1930
spans < 1 m
100
150 mm for
8 spans > 1 m
10
75 100

90 x 90 x 6 angle 150 x 90 x 8 angle


(8.22 kg/m) (14.3 kg/m)
100 mm for 3010 2050 2050 1570 150 mm 4210 3370 3370 2770
spans < 1 m
150
90
150 mm for
6 spans > 1 m
8
90 90

90 x 90 x 8 angle 150 x 100 x 10 angle


(10.6 kg/m) (18.0 kg/m)
100 mm for 3010 2170 2170 1810 150 mm 4330 3490 3610 3010
spans < 1 m
90 150
150 mm for
8 spans > 1 m
10
90 100
* Maximum span 10 m, N3 wind * Maximum span 10 m, N3 wind

PART B:CHAPTER 5
Vertical Loads QUIT
UNGROUTED UNREINFORCED HOLLOW MASONRY 90-mm leaf (Strength grade 15 MPa, Height 190 mm, Fo = 202 kN/m)
av = 1.0 , ø=0.5 Simplified Design Method

Laterally-supported at
Height

top and supporting a


concrete slab

Design compressive force, Fd (kN/m)


Length

Face-shell bedded, 25 mm face shell


9.0

8.0

7.0

6.0
0.5 kPa
Robustness governs
in shaded area
5.0

4.0 15
Height of Wall Between Supports (m)

30
45
3.0 60
75
90
2.0 105
120
135
1.0 150 = Fd

0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)

NOTE: It is the designer's responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties and connectors, and strength and stiffness of supports, in addition to normal considerations of loads and masonry properties

PART B:CHAPTER 5
Vertical Loads QUIT
UNGROUTED UNREINFORCED HOLLOW MASONRY 110-mm leaf (Strength grade 15 MPa, Height 190 mm, Fo = 202 kN/m)
av = 1.0 , ø=0.5 Simplified Design Method

Laterally-supported at
Height

top and supporting a


concrete slab

Design compressive force, Fd (kN/m)


Length

Face-shell bedded, 25 mm face shell


9.0

8.0

7.0 0.5 kPa


Robustness governs
in shaded area
6.0

5.0
15
Height of Wall Between Supports (m)

30
4.0 45
60
75
3.0
90
105
2.0 120
135
1.0 150 = Fd

0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)

NOTE: It is the designer's responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties and connectors, and strength and stiffness of supports, in addition to normal considerations of loads and masonry properties

PART B:CHAPTER 5
Vertical Loads QUIT
UNGROUTED UNREINFORCED HOLLOW MASONRY 140-mm leaf (Strength grade 15 MPa, Height 190 mm, Fo = 202 kN/m)
av = 1.0 , ø=0.5 Simplified Design Method

Laterally-supported at
Height

top and supporting a


concrete slab

Design compressive force, Fd (kN/m)


Length

Face-shell bedded, 25 mm face shell


9.0

8.0

7.0
0.5 kPa
Robustness governs
15 in shaded area
6.0
30

5.0 45
60
Height of Wall Between Supports (m)

4.0 75
90
3.0 105
120
2.0 135
150 = Fd
1.0

0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)

NOTE: It is the designer's responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties and connectors, and strength and stiffness of supports, in addition to normal considerations of loads and masonry properties

PART B:CHAPTER 5
Vertical Loads QUIT
UNGROUTED UNREINFORCED HOLLOW MASONRY 190-mm leaf (Strength grade 15 MPa, Height 190 mm, Fo = 242 kN/m)
av = 1.0 , ø=0.5 Simplified Design Method

Laterally-supported at
Height

top and supporting a


concrete slab

Design compressive force, Fd (kN/m)


Length

Face-shell bedded, 25 mm face shell


9.0

20
8.0
40
7.0
60 0.5 kPa
Robustness governs
in shaded area
6.0 80

5.0 100
Height of Wall Between Supports (m)

120
4.0
140
3.0
160

2.0 180

1.0 200 = Fd

0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)

NOTE: It is the designer's responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties and connectors, and strength and stiffness of supports, in addition to normal considerations of loads and masonry properties

PART B:CHAPTER 5
Vertical Loads QUIT
GROUTED UNREINFORCED HOLLOW MASONRY 140-mm leaf (Strength grade 15 MPa, Height 190 mm, Fo = 445 kN/m)
av = 1.0 , ø=0.5 Simplified Design Method

Laterally-supported at
Height

top and supporting a


concrete slab

Design compressive force, Fd (kN/m)


Length

Face-shell bedded, 25 mm face shell


9.0

8.0

7.0
0.5 kPa
Robustness governs
30 in shaded area
6.0
60
90
5.0
120
Height of Wall Between Supports (m)

150
4.0
180
210
3.0 240
270
2.0 300 = Fd

1.0

0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)

NOTE: It is the designer's responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties and connectors, and strength and stiffness of supports, in addition to normal considerations of loads and masonry properties

PART B:CHAPTER 5
Vertical Loads QUIT
GROUTED UNREINFORCED HOLLOW MASONRY 190-mm leaf (Strength grade 15 MPa, Height 190 mm, Fo = 594 kN/m)
av = 1.0 , ø=0.5 Simplified Design Method

Laterally-supported at
Height

top and supporting a


concrete slab

Design compressive force, Fd (kN/m)


Length

Face-shell bedded, 25 mm face shell


9.0

0.5 kPa
8.0 Robustness governs
in shaded area

7.0 120

160
6.0
200

240
5.0
280
Height of Wall Between Supports (m)

4.0 320

360
3.0
400

2.0 440

480 = Fd
1.0

0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)

NOTE: It is the designer's responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties and connectors, and strength and stiffness of supports, in addition to normal considerations of loads and masonry properties

PART B:CHAPTER 5
Vertical Loads QUIT
UNGROUTED UNREINFORCED SOLID OR CORED MASONRY 110-mm leaf (Strength grade 10 MPa, Height 76 mm, Fo = 363 kN/m)
av = 1.0 , ø=0.75 Simplified Design Method

Laterally-supported at
Height

top and supporting a


concrete slab

Design compressive force, Fd (kN/m)


Length

Face-shell bedded, 25 mm face shell


9.0

0.5 kPa
8.0 Robustness governs
in shaded area

7.0 120

160
6.0
200

240
5.0
280
Height of Wall Between Supports (m)

4.0 320

360
3.0
400

2.0 440

480 = Fd
1.0

0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)

NOTE: It is the designer's responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties and connectors, and strength and stiffness of supports, in addition to normal considerations of loads and masonry properties

PART B:CHAPTER 5
Vertical Loads QUIT
UNGROUTED UNREINFORCED HOLLOW MASONRY 110-mm leaf (Strength grade 15 MPa, Height 162 mm, Fo = 192 kN/m)
av = 1.0 , ø=0.5 Simplified Design Method

Laterally-supported at
Height

top and supporting a


concrete slab

Design compressive force, Fd (kN/m)


Length

Face-shell bedded, 25 mm face shell


9.0

0.5 kPa
8.0 Robustness governs
in shaded area

7.0

6.0

5.0
15
Height of Wall Between Supports (m)

30
4.0 45
60
3.0 75
90
105
2.0
120
135
1.0 150 = Fd

0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)

NOTE: It is the designer's responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties and connectors, and strength and stiffness of supports, in addition to normal considerations of loads and masonry properties

PART B:CHAPTER 5
Vertical Loads QUIT
UNGROUTED UNREINFORCED HOLLOW MASONRY 140-mm leaf (Strength grade 15 MPa, Height 190 mm, Fo = 202 kN/m)
av = 1.0 , ø=0.5 Simplified Design Method

1 storey
Timber floor

min.
loading face of wall

Laterally-supported at
Height

top and supporting a


concrete slab
Concrete slab
Design compressive force, Fd (kN/m)
Length

Face-shell bedded, 25 mm face shell


9.0

0.5 kPa
8.0 Robustness governs
in shaded area

7.0

6.0

5.0
Height of Wall Between Supports (m)

4.0

3.0 10 = Fd

2.0

1.0

0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)

NOTE: It is the designer's responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties and connectors, and strength and stiffness of supports, in addition to normal considerations of loads and masonry properties

PART B:CHAPTER 5
Vertical Loads QUIT
UNGROUTED UNREINFORCED HOLLOW MASONRY 140-mm leaf (Strength grade 15 MPa, Height 190 mm, Fo = 322 kN/m)
av = 1.0 , ø=0.5 Simplified Design Method

1 storey
Timber floor

min.
loading face of wall

Laterally-supported at
Height

top and supporting a


concrete slab
Concrete slab
Design compressive force, Fd (kN/m)
Length

Face-shell bedded, 25 mm face shell


9.0

0.5 kPa
8.0 Robustness governs
in shaded area

7.0

6.0

5.0
10
Height of Wall Between Supports (m)

4.0

3.0

20 = Fd
2.0

1.0

0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)

NOTE: It is the designer's responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties and connectors, and strength and stiffness of supports, in addition to normal considerations of loads and masonry properties

PART B:CHAPTER 5
Vertical Loads QUIT
REFINED DESIGN METHOD – Reduction Factors for Eccentricity and Slenderness Using Calculated Eccentricities

BASIS OF TABLE REDUCTION FACTORS (K) USING CALCULATED ECCENTRICITIES


Wall details Slenderness ratios Eccentricity ratios Reduction factors
Height Thickness Above slab Below slab Above slab Below slab Above slab Below slab
Location H (mm) tw (mm) Sr Sr e1/tw e1/tw K K

Internal 2400 90 22.7 20.0 0.02–0.11 0.00–0.02 0.40–0.47 0.55–0.56


110 18.5 16.4 0.01–0.10 0.00–0.02 0.51–0.60 0.65–0.67
140 14.6 12.9 0.03–0.30 0.01–0.07 0.41–0.70 0.71–0.78
7
3000 140 18.2 16.1 0.02–0.17 0.01–0.06 0.46–0.60 0.64–0.68
190 13.4 11.8 0.04–0.40 0.02–0.13 0.33–0.72 0.67–0.80

The values have been reproduced here to give an 3600 190 16.1 14.2 0.03–0.27 0.01–0.10 0.41–0.65 0.64–0.73
indication of the accuracy of the assumed
eccentricities and to assist designers in External 2400 90 22.7 20.0 0.16–0.27 0.03–0.07 0.26–0.35 0.50–0.53
determining the appropriate analysis method to use. 110 18.5 16.4 * 0.08–0.16 * 0.52–0.60
These values of eccentricity to thickness ratios and 140 14.6 12.9 * 0.21–0.30 * 0.45–0.55
reduction factors should not be used for design
without confirmation by the analysis method 3000 140 18.2 16.1 * 0.15–0.22 * 0.46–0.54
described in this manual. 190 13.4 11.8 * 0.32–0.34 * 0.43–0.46
3600 190 16.1 14.2 * 0.25–0.27 * 0.45–0.47
* The calculated eccentricity ratios for external walls above the slab exceed 0.33. In these situations the actual support conditions must be
different from the mechanism implicit in the moment distribution and joint-fixity factor used to calculate these values. Use of the assumed
values is considered reasonable in these cases.

PART B:CHAPTER 5
Vertical Loads QUIT
5.4 WORKED EXAMPLE
5.4.1 General Hollow concrete blocks Concrete grout 5.4.2 Index to worked example
Width 90 mm, 110 mm, 140 mm and 190 mm Minimum characteristic compressive
Purpose of the worked example Worked example includes both Design by
strength,
The purpose of the following worked Height 190 mm Simplified Rules and Design by Refined
f’c = 20 MPa
example is to demonstrate the steps to Calculation, as follows:
Length 390 mm
be followed when performing manual Minimum cement content 300 kg/m3
PART 1 Design brief, vertical loads and
calculations or when preparing computer Face-shell bedded
masonry properties.
software for the analysis and design of
Minimum face-shell thickness,
masonry. The worked example also serves PART 2 Design by Simplified Rules.
ts = 25 mm for 90 mm, 110 mm and
the purpose of demonstrating the origin of
140 mm units PART 3 Design by Refined Calculation.
the Standard Designs which are based on
ts = 30 mm for 190 mm units
similar masonry capacity considerations.
Although comprehensive in its treatment Minimum characteristic compressive
of AS 3700, the worked example is not strength,
intended to analyze or design all parts of f’uc = 15 MPa
the particular structure. It deals only with Minimum characteristic lateral modulus of
enough to demonstrate the design method. rupture,
Design and detailing f’ut = 0.8 MPa
All design and detailing shall comply with Solid or cored concrete bricks
the requirements of AS 3700 and, where Width 110 mm
appropriate, AS/NZS 1170.
Height 76 mm
It is the designer’s responsibility to allow
for the effects of control joints, chases, Length 230 mm
openings, strength and stiffness of Fully bedded
ties and connectors, and strength and
stiffness of supports, in addition to normal Minimum characteristic compressive
considerations of loads and masonry strength,
properties. Control joints and openings must f’uc = 10 MPa
be treated as free ends as specified by Minimum characteristic lateral modulus of
AS 3700. rupture,
Masonry Properties f’ut = 0.8 MPa
The worked examples in this chapter are Mortar joints
based on masonry properties complying Mortar type M3 (or M4)
with the General Specification set out in
Part C:Chapter 2, modified as noted in the Joint thickness 10 mm
calculations and as noted below.

PART B:CHAPTER 5
Vertical Loads QUIT
Worked Example [Page 1 of 6]

1050 PART 1: Floor 1 Walls


Only the internal leaf is loadbearing
DESIGN BRIEF
2700 Design loadbearing wall indicated in the Height of wall
Level 3 accompanying drawings. HW1 = 2.7 m
175

Length of loadbearing leaf


2700
VERTICAL LOADS LW1 = 3.7 m
Level 2
175
Length of wall under consideration Use 90-mm denseweight hollow blockwork
2700 Wall to be L = 3.70 m Density 2180 kg/m3 80% solid
designed
1 face with plasterboard 10 mm thick
Level 1
600 Roof
Area of roof acting on wall Surface density
2100 (90 x 0.8 x 2180 x 9.81) (1 x 10 x 800 x 9.81)
AR = 7.5 x 5.33 gW1 = +
Basement 2 1,000,000 1,000,000
100
= 20.0 m2 = 1.62 kN/m2
SECTION A-A
Permanent load of roof structure Permanent load
gR = 1.2 kPa g H L
2000 GW1 = W1 W1 W1
Floor area = 8.0 m2 LW1
Roof area = 20.0 m2 Imposed load of roof 1.62 x 2.70 x 3.70
Window

=
800 Contributory qR = 0.25 kPa 3.70
area
A A
= 4.37 kN/m
4500 Factored roof loads
Wall to be designed
3700 110 + 90
1.2 gR A R + 1.5 qR A R Factored wall loads
FdR =
cavity walls L FdW1 = 1.2 GW1
1000 (50 cavity)
(1.2 x 1.2 x 20.0) + (1.5 x 0.25 x 20.0) = 1.2 x 4.37
=
3.70 = 5.2 kN/m
PART PLAN AT LEVEL 1 = 9.8 kN/m Cont…

PART B:CHAPTER 5
Vertical Loads QUIT
Worked Example [Page 2 of 6]

Floor 2 Walls Total Factored Loads on Subject Leaf Height ratio


FdW2 = 5.2 kN/m (similar to FdW1) Fd = FdR + FdW1 + FdW2 + FdW3 + FdS1 + FdS2 hu 190
=
= 9.8 + 5.2 + 5.2 + 5.2 + 17.9 + 17.9 tj 10
Floor 3 Walls = 61.2 kN/m = 19.0
FdW3 = 5.2 kN/m (similar to FdW1)
Compressive strength factor
Slab 1 MASONRY PROPERTIES kh = 1.3 Table 3.2
Area Width of masonry unit
(4.5 x 2.0) - (2.0 x 1.0) tu = 90 mm Masonry factor for face-shell bedded
A S1 =
2 concrete units
= 8.0 m 2 km = 1.6 Table 3.1
Face-shell thickness
tfs = 25 mm
Slab thickness Mortar type M3 (1:5 + water thickener)
tS1 = 175 mm Bedded area
Ab = 2 tfs l Area of grout cross section
Permanent load = 2 x 25 x 1000 Ac = 0 Ungrouted walls
gS1 = 25.0 x 0.175 = 4.38 kPa = 50,000 mm2/m
Characteristic unconfined unit strength
Imposed load Block height f'uc = 15 MPa
qS1 = 2.0 kPa hu = 190 mm 4.5.4
Characteristic confined masonry strength
Factored slab loads Mortar joint thickness f'mb = km √f'uc 3.3.2(a)(i)
A tj = 10 mm = 1.6 √ 15
FDS1 = (1.2 gS1 + 1.5 qS1) S1
L = 6.20 MPa
8.0
= (1.2 x 4.38) + (1.5 x 2.0)
3.70 Characteristic unconfined masonry strength
= 17.9 kN/m f'm = kh f'mb 3.3.2(a)(i)
= 1.3 x 6.2
Slab 2 = 8.06 MPa
FdS2 = 17.9 kN/m (similar to FdS1)

PART B:CHAPTER 5
Vertical Loads QUIT
Worked Example [Page 3 of 6]

NOTE: This wall is not grouted. Where grout PART 2: Slenderness ratio
is used elsewhere, it is specified as: a H 7.3.3.4(1)
Srs = v
DESIGN BY SIMPLIFIED RULES kt t
Characteristic grout cylinder strength Vertical coefficient (supports slab) 1.0 x 2700
=
f'c = 20 MPa av = 1.0 7.3.3.4 1.0 x 90
> 12 MPa 10.7.3 = 30.0
Clear height
Design characteristic grout strength H = 2.70 m Slenderness and eccentricity factor
f'cg = 1.3 f'uc k = 0.67 - 0.02 (Srs - 14) 7.3.3.3
= 1.3 x 15 Clear length = 0.67 - 0.02 (30.0 - 14)
= 19.5 MPa L = 3.70 m = 0.35
< 20 MPa 3.5
Thickness coefficient (no engaged piers) Design capacity
Capacity reduction factor kt = 1.0 Table 7.2 fu = k Fo 7.3.3.2
ø = 0.5 Table 4.1 = 0.35 x 201
= 70.4 kN/m
Density factor > 61.2 kN/m OK
kc = 1.4 for density 2180
> 2000 kg/m3 7.3.2 As this result is close, design by refined method

Basic compressive capacity 7.3.2(2)


f'cg
Fo = ø f'm Ab + kc ( ) Ac
√ 1.3
8.06 x 50,000 19.5
= 0.5 ( ) + 1.4 ( 1.3 ) 0
1000 √
= 201 kN/m

PART B:CHAPTER 5
Vertical Loads QUIT
Worked Example [Page 4 of 6]

PART 3: Slab moment


<
1 e
(1 - 2 1 )
7.3.4.5(4)
Mab = FdS1 eS1 tfs tw
2
DESIGN BY REFINED CALCULATION 18.3 x 15 tw
=
Vertical coefficient (supports slab) 1000 = 1.61 OK
av = 0.75 7.3.4.3 = 0.275 kNm/m
Design capacity
Horizontal coefficient (one support) Total factored load at top of wall Fcap = k Fo 7.3.4.2
ah = 2.5 7.3.4.3 FdA = 63.2 - 5.5 = 0.437 x 201
= 57.7 kN/m = 87.8 kN/m
Slenderness ratio > 61.2 kN/m OK
a H 7.3.4.3 Effective eccentricity at top of wall
Srs = v
kt t MAB
e1 =
0.75 x 2700 F dA Option 2 – Modified Rigid Frame Analysis
=
1.0 x 90 0.275 x 1000 Consider members at top of wall
0.7 a H a L =
= 22.5 < v h 57.7 Slab
t √
= 4.8 Thickness
0.7 0.75 x 2700 x 2.5 x 3700 ts = 175 mm
=
90 √
Slenderness and eccentricity factor 7.3.4.5(1)
= 33.7 OK e1 e1 Effective width (continuous)
k = 0.5 (1 + ) (1 - 2.083 ) -
e2 tw bs = 1000 mm
Option 1 – Assumed Eccentricity 7.3.4.4 e1
(0.025 - 0.037 ) (1.33Sr - 8) +
Slab load tw Stiffness factor
FdS1 = 18.3 kN/m Fd = 39.4 e1 e1 R = 0.75
A
0.5 (1 - 0.6 ) (1 - ) (1.18 - 0.03Sr)
tw e2
Eccentricity of slab load = 0.437 Elastic modulus
t t/ = 15 tfs Es = 25,000 MPa
eS1 = 6 1-
6 tw 7.3.4.5(3) Cont…
<
90 Fd = 18.3 tfs e1
= S1
1- +2
6 tw tw
= 15 mm Fd
W1
= 5.5 = 0.872 OK

PART B:CHAPTER 5
Vertical Loads QUIT
Worked Example [Page 5 of 6]

Moment of inertia Walls Stiffness


b s t s3 Thickness R (Ew Iw) 0.75 x 8060 x 42.5 x 106
Is = =
12 tw = 90 mm Hw 2875
6
1000 x 1753 = 89 x 10
=
12 Allowance for openings
= 447 x 106 mm4 p = 0.7 Distribution factor to walls
R(EI)
Length Effective width (allowing for openings) L
DF =
Ls = 3800 mm (approximate) bw = p bs R(EI)
= 0.7 x 1000 L
Stiffness = 700 mm 89
=
R (Es Is) 0.75 x 25,000 x 447 x 106 2206 + 89 + 89
=
Ls 3800 Stiffness factor = 0.0373
= 2206 x 106 R = 0.75
Moment distributed to wall under slab
Permanent load Elastic modulus MAG DF FEM
gs1 = 4.38 kPa Ew = 1000 f'm = 0.0373 x 14.9
= 1000 x 8.06 = 0.56 kNm/m
Permanent load = 8060 MPa
gs1 = 4.38 kPa Axial load on wall
Moment of inertia FdA = 61.2 - 5.2
Imposed load b t 3 = 56.0 kN/m
Iw = w w
qs1 = 2.0 kPa 12
700 x 903 Compressive stress at top of wall
=
Fixed end moment 12 F
fA = dA
L2 = 42.5 x 106 mm4 Ab p
FEM = (1.2 gs1 + 1.5qs1)
8 56.0 x 1000
=
3.82 Height (centre to centre) 50,000 x 0.7
= (1.2 x 4.38) + (1.5 x 2.0)
8 Hw = 2700 + 175 = 1.6 MPa
= 14.9 kNm/m = 2875 mm > 0.25 MPa OK Cont…

PART B:CHAPTER 5
Vertical Loads QUIT
Worked Example [Page 6 of 6]

Ratio slab stiffness to wall stiffness Slenderness and eccentricity factor 7.3.4.5(1)
2206 e e
= k = 0.5 (1 + 2 ) (1 - 2.083 1 ) -
89 + 89 e1 tw
= 12.3 e
(0.025 - 0.037 1 ) (1.33Sr - 8) +
tw
Joint fixity factor Conservative extrapolation e1 e2
0.5 (1 - 0.6 ) (1 - ) (1.18 - 0.03Sr)
J = 0.4 of AS 3700 Commentary tw e1
or FIG 5.7 this manual
= 0.5 (1 + 0 ) (1 - 2.083 4 ) -
4 90
Modified moment at top of wall 4
(0.025 - 0.037 ) (1.33 x 22.5 - 8) +
MABm = J MAB 90
= 0.4 x 0.56 4
0.5 (1 - 0.6 4 ) (1 - ) (1.18 - 0.03 x 22.5)
= 0.22 kNm/m 90 0
= 0.438
Eccentricity at top of wall ts
1-
MABm tw 7.3.4.5(3)
e1 = <
F dA ts e1
1- +2
0.22 x 1000 tw tw
=
56.0 = 0.90 OK
= 4.0 mm
1 e1 7.3.4.5(4)
< (1 - 2 )
Eccentricity ratio at top of wall ts tw
2
e1 4.0 tw
=
tw 90 = 1.66 OK
= 0.044
< 0.05 Almost concentric Design capacity
Fcap = k Fo 7.3.4.2
e2 = 0 = 0.505 x 201
= 101.5 kN/m
> 61.2 kN/m OK

PART B:CHAPTER 5
Vertical Loads QUIT

Você também pode gostar