The Control Talk Blog provides guidance from a user's viewpoint on the design of automation
systems, equipment, and piping for process control improvement. Details are offered on the
selection and installation of PID controllers, control valves, variable speed drives, and
measurements to maximize loop performance. The blogs are often more intensive and extensive
and less vendor specific than a white paper. The goal is an advancement of the profession by
sharing conceptual principle based knowledge.

Greg McMillan is a retired Senior Fellow from Solutia/Monsanto and an ISA Fellow. At present,
McMillan is a part time modeling and control consultant in Technology for Process Simulation for
Emerson Automation Solutions specializing in the use of the Virtual Plant for exploring new
opportunities. He spends most of his time writing, teaching and leading the ISA Mentor Program
he founded in 2011. He received the ISA Kermit Fischer Environmental Award for pH control in
1991, received the Control magazine Engineer of the Year Award for the Process Industry in
1994, was inducted into the Control magazine Process Automation Hall of Fame in 2001, was
honored by InTech magazine in 2003 as one of the most influential innovators in automation, and
received the ISA Life Achievement Award in 2010.

Also, you can read McMillan's monthly Control Talk Column printed in Control magazine.

Category: Dead Time Gain Process Dynamics Response Time Time Constant Tips
Submitted by Greg McMillan on Mon, 08/24/2015 - 23:04

The automation profession suffers from the lack of a common understanding of the terms used
and their units. By taking a closer look at key terms for plant dynamics, we can have more
intelligent discussions and better recognition of the contributing factors so that we can find
what part of the loop is the leading cause of poor performance whether it be excessive
nonlinearity, delay, or deception.

I recommend every user get a copy of The Automation System and Instrumentation Dictionary 4th
Edition published by International Society of Automation (ISA). Here I give a perspective of the
role played and offer some descriptive words preceding the common terms to create more
useable and descriptive terms seen in my publications and presentations but not much
elsewhere. Let’s start with general terms and once we have that under our belts using a Texas
size belt buckle if necessary, move on to specific terms. You can also use your cowboy boots to
kick all that bull you now see out of your trail to success.

General Terms

https://www.controlglobal.com/blogs/controltalkblog/understanding-terminology-to-a... 20/12/2018
Understanding Terminology to Advance Yourself and the Automation Profession Page 2 of 8

The 3 key general terms used for describing all types of dynamics are dead time, time constant,
and gain. There are two types of time constants. In almost every case we are talking about a
negative feedback time constant. An important and not well understood case for a positive
feedback time constant is a runaway reactor with extraordinary performance and safety
considerations. A system is nonlinear if the dead time, time constant, or gain changes. Nearly all
loops are nonlinear. The most common linear loops are flow or level loops (constant diameter
vessel) manipulating the speed of a pump with low static head. Composition, pH, pressure, and
temperature loops are nonlinear.

Dead time (delay) (sec) is the time after a change in PID output till there is a recognizable
change in PID input. Dead time is detrimental wherever it exists because it prevents any
recognition of an impending change in a process variable. For an unmeasured disturbance the
peak and integrated errors are proportional to dead time and dead time squared, respectively.
An increase in dead time makes a loop closer to instability unless retuned. Dead time slows
down the setpoint response.

Time constant (lag) (sec) is the time for a variable to reach 63% of the final value once the
variable starts to change (after the dead time has expired). For runaway processes it is a positive
feedback time constant that is the time for a variable to reach 172% of the process value
predicted by process gain. A time constant in the process is beneficial in terms of slowing down
the effect of an unmeasured disturbance upstream of the time constant (most prevalent case is
a disturbance at process input instead of process output as shown in control theory text books).
A time constant in the automation system or path of the manipulated flow to the point of entry
of the disturbance slows down the recognition and correction. A time constant anywhere slows
down the setpoint response. An increase in the largest time constant can reduce the peak and
integrated errors observed if the PID is retuned. If the time constant is in the measurement
instead of the process, the actual process errors are greater than the observed errors due to
filtering action. An increase in any of smaller time constants increase the dead time in a first
order plus dead time (single time constant and dead time) approximation.

Gain is the change in output divided by the change in input to a part of the process or
component in the automation system. The units depend upon the part or component. For the
PID whose internal algorithm uses % inputs and % outputs, the gains used to reflect what the
plant does and how the PID reacts are dimensionless (%/%). For a steady state response, the
gain is a final change in output divided by a given change in the input. The gain here is the slope
on the plot of the output versus the input. For an integrating response, the gain is a ramp rate
divided by the given change. For the PID, an integrating gain reflecting the response of a process
is 1/sec (%/sec per %). A high control valve gain (steep slope of installed characteristic) can
magnify signal error, deadband, and resolution or threshold sensitivity limits. A low control valve
gain (flat slope of the installed characteristic) can cause wandering and excessive wear of the
valve. A high process gain is beneficial in terms of increasing sensitivity to detection of
disturbances but if too high like in pH can cause excessive variability from valve deadband or
resolution or threshold sensitivity limits and measurement noise. In general a high measurement
gain is desirable because it corresponds to a smaller span and better accuracy when error is % of
span.

Specific Terms

https://www.controlglobal.com/blogs/controltalkblog/understanding-terminology-to-a... 20/12/2018
Understanding Terminology to Advance Yourself and the Automation Profession Page 3 of 8

Total loop dead time (total delay) (sec) is the sum of all the sources of dead time in the loop
that can originate in the process and automation system including the PID controller (termed
the process dead time in most of the literature). A fraction of all time constants smaller than the
largest are converted to dead time. The fraction approaches one as the ratio of the small to
large time constant approaches zero. For practical purposes, small time constants are simply
summed with all pure delays to estimate the total loop dead time since we usually
underestimate the total loop dead time. Dead times from transportation delays are inversely
proportional to flow and can dramatically increase at low production rates. The delay from
discontinuous devices is ½ the cycle time plus the latency (time after that start of the cycle until
the result is available). Thus, the delay from digital controllers is ½ the module execution time
and for digital transmitters is ½ the update time. For chromatographs and most at-line analyzers
the delay is 1.5 times the cycle time plus any delay from sample transportation and multiplexing.

Primary time constant (primary lag) (sec) is the largest time constant in the loop. Hopefully it is
in the process but it can be in the automation system (termed the open loop time constant in
my publications and presentations but is termed process time constant in most of the control
literature). This time constant is defined by making a test with the controller in manual (open
loop).

Secondary time constant (secondary lag) (sec) is the second largest time constant in the loop.
Hopefully it is in the process but it can be in the automation system. This time constant is
defined by making a test with the controller in manual (open loop). For integrating processes
(e.g. batch) and runaway processes (e.g. highly exothermic reactors), the secondary time
constant has a huge effect that can be compensated by derivative action (PID rate time =
secondary time constant).

Open loop self-regulating (steady state) process gain (%/%) is the final change in the PID input
in % divided by a fixed change in the PID output in % for a self-regulating process (termed the
process gain in most of the control literature) with no disturbances. An open loop gain is the
product of the manipulated variable gain (e.g. valve or variable speed drive gain), process gain,
and measurement gain. For self-regulating processes the time units of a manipulated flow are
cancelled by time units in the process gain. This is not the case for an open loop integrating
process gain.

Open loop integrating process gain (1/sec) is the ramp rate of the PID input in %/sec divided by
a fixed change in the PID output in %. In the control literature, the integrating process gain may
have engineering units because the academic is looking only at the process. The integrating
process gain is the product of the manipulated variable gain (e.g. valve or variable speed drive
gain), process gain, and measurement gain. The units of 1/sec result from time units from the
manipulated flow not cancelled out by the units in the process gain. For level the manipulated
gain of kg/sec per % PID output are not cancelled by the process gain units of meters level per kg
or the measurement gain units of % PID input per meters level.

Manipulated variable gain (e.u./%) is the change in manipulated variable per % change in PID
output. For loops directly affecting the process, the manipulated variable is flow. The
manipulated process input is almost always flow (exceptions are power for electrical heaters or
speed for agitators). Thus, the manipulated variable gain is the slope of the installed
characteristic of the valve, damper, guide vanes or variable speed pump, fan, or compressor.

https://www.controlglobal.com/blogs/controltalkblog/understanding-terminology-to-a... 20/12/2018
Understanding Terminology to Advance Yourself and the Automation Profession Page 4 of 8

Here, I use the more specific term valve gain or variable speed drive gain in my publications and
presentations. For upper level loops in cascade control or model predictive control manipulating
the setpoint of the secondary loop directly affecting the process, the manipulated variable gain
takes on the units of the process variable of the secondary loop. Here the manipulated variable
gain is the secondary PID process variable scale span in engineering units divided by 100% PID
output. Thus a change in secondary PID measurement calibration, valve trim and valve to system
pressure drop ratio or variable speed drive capacity and static head will affect tuning.

Measurement gain (%/e.u.) is the change in % change in PID input for a change in the process
variable in engineering units. Since nearly all smart measurements are linear, the measurement
gain is 100% divided by the PID process variable scale span in engineering units. Thus a change in
secondary PID measurement calibration will affect tuning.

Process gain (e.u./e.u.) is the change in the process variable in engineering units divided by the
change in the manipulated variable in engineering units. The most common manipulated
variable is flow. The process gain for continuous composition and temperature control is the
slope of a plot of the change in process variable versus a change in the ratio of the manipulated
flow to feed flow. Since the slope is nonlinear often getting steeper at low ratios and the
required abscissa being a ratio to feed flow, the process gain tends to increase dramatically at
low production rates.

Response Time (sec) is meaningless unless the % of final response is specified. It is used to
quantify the dynamic response of an automation system component or steady state process. It
cannot be used to describe an integrating or runaway process. 63% Response Time (T63) is the
time to reach 63% of the final response (total loop dead time plus primary time constant in a
first order plus dead time model). 86% Response Time (T63) is the time to reach 86% of the final
response (total loop dead time plus 2 times the primary time constant). 95% Response Time
(T95) is the time to reach 86% of the final response (total loop dead time plus 3 times the primary
time constant). 98% Response Time (T98) is the time to reach 98% of the final response (total
loop dead time plus 4 times the primary time constant).

Finally, take heart that while sometimes like this last week for me you may be called the “tail
wagging the dog”, by more intelligent discussion you can graduate from the tail of the dog to the
eye of the dog.

• Permalink

Show Comments

https://www.controlglobal.com/blogs/controltalkblog/understanding-terminology-to-a... 20/12/2018
Understanding Terminology to Advance Yourself and the Automation Profession Page 5 of 8

E-Newsletters Digital Editions

Biweekly updates delivering feature articles, headlines with direct links to the top news stories that are
critical to staying up to date on the industry — company news, product announcements, technical
issues and more. Subscribe Today.

https://www.controlglobal.com/blogs/controltalkblog/understanding-terminology-to-a... 20/12/2018
Understanding Terminology to Advance Yourself and the Automation Profession Page 6 of 8

Past 7 Days Past 30 Days Past 6 Months All Time

https://www.controlglobal.com/blogs/controltalkblog/understanding-terminology-to-a... 20/12/2018
Understanding Terminology to Advance Yourself and the Automation Profession Page 7 of 8

Contact Us
Advertise
Media Kit
Rates & Spec
Privacy Policy
Legal / T&C

Voices
Blogs
Out of Control Cartoons

Webinar series
White Papers
Multimedia

Events
Products
Technology Roundups
E-lits

Subscribe
Digital Edition
Issue Archive
Reprints

Knowledge Center
Microsites
Company Profiles
Site Map

My Account
Newsletters

https://www.controlglobal.com/blogs/controltalkblog/understanding-terminology-to-a... 20/12/2018
Understanding Terminology to Advance Yourself and the Automation Profession Page 8 of 8

Social Media
RSS

Contact Us | Advertise | Privacy Policy | Legal Disclaimers, Terms & Conditions


Copyright © 2004 - 2018 Control Global. All rights reserved.
P: 630-467-1300 | 1501 E. Woodfield Road, Suite 400N, Schaumburg, IL 60173

Chemical Processing | Control | Control Design | Food Processing | Pharmaceutical Manufacturing | Plant Services
| Smart Industry

https://www.controlglobal.com/blogs/controltalkblog/understanding-terminology-to-a... 20/12/2018