ontractor SEC-COA SITE TEST RECORD

RIYADH PP4 MOBILE SUBSTATION-1

mer SEC-COA / National Grid

escription CT-INSULATION RESISTANCE TEST : 1-02-2017

A. GENERAL DATA & INFORMATION :

Bay / Location: M01

B. Electrical Tests:

1. CT Insulation Resistance Test:

Applied Voltage: 2500V DC Primary-Secondary

Primary to Secondary:

Measured Value(GΩ)
CORES
Red Yellow Blue

Core-1 85.1 95.1 65.0

Core-2 91.3 91.2 65.5

Core-3 70.2 82.6 65.7

2. CT Insulation Resistance Test:

Applied Voltage: 1000V DC Secondary-Ground

Secondary to Ground:

Measured Value(GΩ)
Applied Between
Red Yellow Blue

Core-1 to Ground 94.76 84.8 91.0


Core-2 to Ground
97.8 65.1 66.0
Core-3 to Ground
91.3 86.9 12.02

TESTED BY : XERVON WITNESSED BY: CSD


NAME : Rhamat Ullah NAME : Engr Hamad al Judai
SIGNATURE: SIGNATURE :
ontractor SEC-COA SITE TEST RECORD
RIYADH PP4 MOBILE SUBSTATION-1

mer SEC-COA / National Grid

escription CT-INSULATION RESISTANCE TEST : 1-02-2017

3. CT Insulation Resistance Test:

Applied Voltage: 1000V DC Secondary-Secondary

Secondary to Secondary :

Measured Value(GΩ)
Applied Between
Red Yellow Blue

Core-1 to Core-2 36.1 79.9 42.7


Core-2 to Core-3
70.9 118.6 79.1
Core-3 to Core-1
87.9 170.3 131.1

4. Testing Equipment Used:

Instrument Used Model SI No. Calibration Valid up to


Insulation Resistance
MEGGER MIT 515 101404274 20-07-2017
Tester

TESTED BY : XERVON WITNESSED BY: CSD


NAME : Rhamat Ullah NAME : Engr Hamad al Judai
SIGNATURE: SIGNATURE :