VH

(VH) 16-4

P54x/EN VH/I74
Relay type: P54x …
Software
Version Hardware Original S1 Technical
Description of Changes
Suffix Date of Issue Compatibility Documentation
Major Minor
Released to production
9 Includes all of 05A changes
9 Requirement to use relays 8, 9 & 10 for Trip A, B & C removed
B A Oct 2000 9 MODBUS communication problem when used with P140 fixed V2.0 or Later TG8613B

9 Power measurements read over MODBUS may be incorrect


9 MODBUS status register reports disturbance records
incorrectly following power cycle
Only P543 & P544 builds released for customer tests
C A Mar 2001 V2.0 or Later TG8613B
05 9 PSB now works with single pole open
Cont.
Only P543 & P544 builds released for customer tests
9 Distance directional line fixed at -30º
New PSL will be
D A May 2001 9 PSB block issued when impedance passes into any Z1, Z2 or -
required
Z3
9 PSB unblock via negative sequence current now done via PSL
All builds released to production. Based on 05B software

MiCOM P543, P544, P545, P546

Firmware and Service Manual


9 Resolved a loss of measurements (column 3 & 4) problem that
E A Jun 2001 V2.0 or Later TG8613B
can occur in 3 terminal applications
8 Recommended upgrading to 05K or later

Version History

Você também pode gostar