Appendix 3 Menu Structure Of The Monitoring Module 53

Appendix 3 Menu Structure Of The Monitoring Module

Main Menu

Status Maintenance Settings

DC Voltage FC Alarm Type


Alarm
DC Current Start BC Level
Type
AC on/off Test Relate Relay
DC on/off
Rectifiers Reconnect DI No.
AC Voltage Battery Alarms Alarm
Disconnect Mode Mode
Curr Limit Settings
Set DI Name
AC Derated Reconnect
Load
Temp Derated Disconnect Audible alarm
Alarm
Control Clear Hist Alarm
Alarm serial No. Rect Trim
Block Alarm
Active Alarm level
Rect Limit Battery
Alarm Alarm name --See Figure 2
Settings
Alarm time DC ON
OverVolt 280V
DC OFF
AC LowVolt 180V
Alarm serial No. Rectifier AC ON Settings UnderVolt None
Alarm Alarm name AC OFF AC Input None
History Reset
Start time
End time Over Volt alarm 58.5V
Low Volt alarm 45.0V
Under Volt alarm 45.0V
DC
AMB.Temp High Alarm 40 
Settings
AMB.Temp Low Alarm -5 
Load Shunt None
Shunt Coeff None

Note: Walk-in Enabled N


1. "Status" information can be queried only. Refer to Walk-in Time 8s
Figure 2 for system information. Rect Over Volt 59V
2. Operator level authority is compatible with user level Rectifier Default Volt 53.5V
authority. Administrator level authority is compatible Settings Curr In Lim 30A
with operator level authority.
Fan Speed Half Speed
3. Parameters on the right side are default values set
before delivery. HVSD Time 300s

Temp Sensor None


Start temp 1 35  C
Fan Stop temp 1 30  C
Settings Start temp 2 45  C
Stop temp 2 40  C
No AC fan off Yes

Address 1
Text Chinese
Comm Mode RS232
User level
BaudRate 9600bps
Set Date
Set Time
System
Settings Init PWD N
Operator
level Init Param N
System Type 48V/30A/300/NONE

Administrator Change Password


level Con Alarm voice Constant

Figure 1 Menu structure of the monitoring module (1)

EPC48180/1800-F1700A Outdoor Power Supply System User Manual


54 Appendix 3 Menu Structure Of The Monitoring Module

Battery Settings System information

Mode Auto AC voltage


Batt String 4 DC voltage
Batt. Capacity 300Ah Normal
System
Selection Batt Name Alarm
operation
Batt Shunt1 Y state Battery AUTO
Batt Shunt2 N manageme MANUAL
nt mode
LLVD Enable Y Power
FC
management
LVD BLVD Enable Y mode BC
Setting LVD Mode Voltage Temperature compensation
Battery
LLVD Volt 44.0V Cyclic Boost
state
BLVD Volt 43.2V Test
LLVD Time 300min Short test
BLVD Time 600min Scheduled test
Battery1 current
Float charge 53.5V
Battery1 remaining capacity
Boost charge 56.4V
Current limit Battery2 current
0.1C10
Over current point 0.15C10 Battery2 remaining capacity

Automatic Boost Y AC voltage


System Power
Cyclic Boost Y
Cyc BC After
Charge To Boost capacity 80%
0.06C10 Bat. Temp
To Boost current
Constant BC Current 0.01C10 Amb. Temp

Duration of constanct BC 180min


Cyclic Boost Interval 2400h Note:
Cyclic Boost Time 720min 1. System information is queried in system
Boost Limit 1080min information page.

Battery test volt. 2. Press ESC at system information page, you can
45.2V
query the serial number and software version of
Battery test time 300min the monitoring module.
Test end Cap 0.7C10
Scheduled Test N 3. Basic parameters should be reset according to
actual configuration.
Planned Test1 00:00, Jan.1st
Planned Test2 00:00, April1st 4. Parameters on the right side are default values
set before delivery.
st
Planned Test3 00:00, July1
Batt. Test
Planned Test4 00:00, Oct.1st
ShortTest Enable Y
Alarm Current 10A
ShortTest Cycle 720h
ShortTest Duration 5min
StableTest Enable N
StableTest Current 9999A
Temperature1 Ambient Temp
Temperature2 Battery Temp
Center Temp 25
Temp
Temp Comp 72mv/
Comp
Over Temp alarm 50
High Temp alarm 50
Low Temp alarm 0

Figure 2 Menu structure of the monitoring module (2)

EPC48180/1800-F1700A Outdoor Power Supply System User Manual