Escolar Documentos
Profissional Documentos
Cultura Documentos
ä
ä
rd/qf/09.04/2000
Michael Riedel
t
t
Transformatorenbau GmbH
i
i
Transformatorenbau GmbH
l
l
a
a
Produktion: www.querformat.info
u
u
Q
Q
r
r
ü
ü
f
f
w
w
o
o
h
h
-
-
w
w
o
o
n
n
K
K
s
s
a
a
d
d
n
n
e
e
b
b
Michael Riedel
a
a
2004
h
h
r
r
www.riedel-trafobau.de · info@riedel-trafobau.de
i
i
W
W
t
ä
Michael Riedel
t
i
Transformatorenbau GmbH
l
a
u
Q
r
ü
f
w
o
h
-
2005
Introduction
w
o
n
K
s
a
d
n
e
b
a
h
r
i
W
allg_041014.qxd 14.10.2004 09:58 Seite 1
A
Isolation transformers
Safety transformers
Miniaturized transformers
Universal control transformers
Anti-interference transformers with special screening
High-power transformers
Speed regulators
Portable transformers
B
Isolation transformers
Safety transformers
Dry-type transformers
Starter-transformers
C
Single-phase compact power packs, non-stabilized and stabilized
Single-phase switch power packs stabilized, primary- and secondary switched
UPS D.C.-UPS-modules
Product group Three-phase D.C. power supplies Three-phase compact rectifier transformers
Three-phase universal compact rectifier transformers
D
Three-phase compact rectifier transformers, covered
Three-phase compact rectifier transformers, in housing
Three-phase switch power packs stabilized, primary- and secondary switched
UPS D.C.-UPS-modules
Product group Variable ratio ring transformers Single-phase variable ratio ring transformers
Three-phase variable ratio ring transformers
E
Motor drives
Accessories
Voltage stabilizers electro-motorial
F
Three-phase filter circuit chokes
Three-phase line chokes
G
Inrush current limiters
1/1
allg_041014.qxd 14.10.2004 09:58 Seite 2
1/2
allg_041014.qxd 14.10.2004 09:58 Seite 1
Welcome at Riedel!
1/1
allg_041014.qxd 14.10.2004 09:58 Seite 2
In general
The stated technical explanations indicate many application areas besides also valid special and exceptional rules. The
following is intended as a short introduction into the complex subject.
CE mark
The council of the European Community (EC) has issued EC-directives basing on the founding contract of the Europe-
an Economy Community (EEC), in particular article 100. EC-directives serve to adapt legal and administrative rules in
the diverse European Union (EU) member states whenever differences in national rules cause commercial handicaps
or in any other way obstruct EU-interior market. The directives are to be translated into national law by respective natio-
nal legislative authorities within a given deadline. Manufacturers must CE mark their products to demonstrate confor-
mity once products fall within certain EC-directives. Concerned are all products contained in the 'new conception' di-
rectives (decree May 8, 1985), which state requirements for technical condition.
EC-directives are obligatory legal rules within the European Union and meeting these requirements are precondition
for any product sale in Europe. The remaining world trade market is not affected. As soon as a product is CE marked, it
indicates its conformity with respective fundamental requirements of all relevant directives. The CE mark merely is a di-
rective conformity proof for supervisory authorities. Quite often it is misinterpreted as a 'quality symbol' though and the-
refore frequently requested, yet lacking any legal basis.
As such we refrain from printing the CE mark as a marketing tool in our catalogue and brochures. EC-directives must
be adhered to as a matter of course by all manufacturers or importers.
Although manufacturers must provide EC conformity declarations only for the supervisory authority (for at least 10
years counting from last delivery date) our customers may certainly request a respective copy.
The directive in question is stated in each respective product's EC conformity declaration. The most frequent directives
concerning our product spectrum are:
1. Low tension directive (73/23/EEC) for electric appliances in rated voltages between 50 VAC and 1000 VAC and between
75VDC and 1500VDC.
Title: Directive by council for adaptation of legal rules among member states pertaining electric appliances for applica-
tion within certain voltage limits 73/23/EEC, Feb. 19, 1973.
Just about all Riedel products fall within the scope of the low tension directive. Conformity with directive's protection re-
quirements for each electric appliance, device, each system and each equipment must be confirmed by the manufac-
turer via EC conformity declaration and product or packing must be marked with EC conformity mark CE.
2.EMC directive (89/336/EEC) for devices which can cause electromagnetic interference or of which operation can be
impaired by such interference.
Title: Directive by council for adaptation of legal rules among member states pertaining electromagnetic compatibility
89/336/EEC, May 03, 1989.
Legal basis:
On May 03, 1989, the council of the European Community (EC) issued an obligatory directive to adapt legal rules in its
member states. The Federal Republic of Germany has translated same into national law November 09, 1992 by virtue
of law about electromagnetic compatibility (EMVG). The settlement authority for mail and telecommunication (formerly
BAPT) and their branch offices have been appointed for it's enforcement (supervision).
1/2
allg_041014.qxd 14.10.2004 09:58 Seite 3
Principle of procedure:
As of Jan. 01, 1992 (transition time until Dec. 31, 1995) only such electrical and electronic equipment, system and appli-
ance may be traded with or put into operation in the European Union that meets EMC-protection requirements laid
down in the directive. Conformity with directive's protection requirements for each electric appliance, each system and
each equipment must be confirmed by the manufacturer via EC conformity declaration and the product must be mar-
ked with an EC conformity mark CE.
Examples:
a. components (for pcb, units, switch cabinets), as integrated components not obligatory CE marked - for example re-
sistors, capacitors, inductivities, integrated circuits, chokes, transformers
b. components obligatory CE marked (incl. cabinet and protected against accidental contact), which are independent-
ly operable and/or for sale to ultimate customers - for example plug-in power supplies, battery chargers, personal
computers, test sets and meters, isolating transformers for construction sites or service, transformers for halogen
lamps
Norms
The norm scope concerning inductivities has simplified resp. will simplify.
The essential norms for the manufacture of dry-type transformers (safety and isolating transformers, formerly DIN VDE
0551 / EN 60742; control and power transformers, formerly DIN VDE 0550) have been integrated into the new norm
structure DIN VDE 0570 / EN 61558.
Special inductivities, for example transformers for switch power packs, are treated separately in the directive.
We adapt all concerned products within transition deadlines.
If not agreed otherwise, we manufacture in "uptodate technical standard" complying to norms as stated on each cata-
logue page on headline or complying to norms on overleaf pages.
Standard stock items can be delivered within transition deadlines in the norm valid at manufacturing date and applied by you
without problem.
1/3
allg_041014.qxd 14.10.2004 09:58 Seite 4
Norm references
DIN VDE 0100 DIN VDE 0532 part 6 (01.94) DIN EN 60999/VDE 0609 part 1 (12.00)
Erection of power installations with rated voltages Transformers and reactors - dry-type power trans- Connecting devices - safety requirements for
up to 1000V formers screw-type and screwless-type clamping units
EN 60289 / DIN VDE 0532 part 20 (05.94) for electrical copper conductors
DIN VDE 0100 part 410 (01.97) Reactors
Erection of power installations with rated voltages IEC 445
up to 1000V DIN VDE 0532 part 21 (03.82) DIN 42404
Protection against electric shock Transformers and reactors - Starting transfor- Terminal markings for transformers, safety trans-
mers and starting reaktors formers, variable transformers, small reactors
DIN VDE 0105 part 1 (10.97)
Operation of power installations; DIN VDE 0532 part 23 (08.94) IEC 947-7-1 (1989) EN 60947-7-1 (1991) /
general specifications Transformers and reactors - stationary trans- DIN VDE 0611 part 1 (08.92)
formers in traction systems Low-voltage switchgear and controlgear
DIN VDE 0106 part 100 (03.83) Part 7: ancillary equipment, terminal blocks for
Protection against electric shock; EN 60076-1 / DIN VDE 0532 part 101 (12.97) copper conductors
actuating members positioned close to parts Power transformers - general
liable to shock DIN VDE 0611 part 3 (05.00)
EN 60950 / DIN VDE 0805 (12.01) Modular terminal blocks for connection of copper
DIN VDE 0107 (10.94) Safety for equipment of the information technique conductors; protective conductor terminal blocks
Electrical installations in hospitals and locations for for copper conductors
medical use outside hospitals DIN VDE 0558 part 1 (07.87)
Semiconductors - converters DIN VDE 0635 (02.84)
DIN VDE 0108 part 1 (10.89) Low-voltage fuses -
Power installations and safety power supplies in EN 61558-1 / DIN VDE 0570 part 1 (07.98) D-fuses E 16 up to 25 A, 500 V;
communal facilities; general Safety of power transformers, power supply units D-fuses up to 100A, 750 V;
D-fuses up to 100A, 500 V
and similar - general requirements and tests
DIN VDE 0110 part 1 (04.97)
Insulation coordination for electrical equipment EN 60947-1/VDE 0660 part 100 (12.99)
EN 61558-2-1 / DIN VDE 0570 part 2-1 (07.98)
within low-voltage systems - Principles require- Low-voltage switchgear and controlgear -
Safety of power transformers, power supply units
ments and tests general rules
and similar - particular requirements for separa-
ting transformers for general use
IEC 204-1 / EN 60204 part 1 / DIN VDE 0113 part 1 IEC 439-1 / EN 60439-1 /
(11.98) DIN VDE 0660 part 500 (08.00)
EN 61558-2-2 / DIN VDE 0570 part 2-2 (10.98)
Electrical equipment of industrial machines; Low-voltage switchgear and controlgear assem-
Safety of power transformers, power supply units
general requirements blies; requirements for type-tested and partially
and similar - particular requirements for control
type-tested assemblies
transformers
DIN VDE 0118 part 1 (11.01)
Erection of electrical installations in mines -General DIN EN 60127-2
EN 61558-2-4 / DIN VDE 0570 part 2-4 (07.98) DIN VDE 0820 part 2 (09.01)
requirements Safety of power transformers, power supply units Miniature fuses - Cartridge fuse-links
and similar - particular requirements for isolating
DIN VDE 0160 (04.98) transformers for general use EN 50 022 (1977) / DIN EN 50022 (05.78)
Electronic equipment for use in power installa-
Low-voltage switchgear and controlgear for
tions EN 61558-2-6 / DIN VDE 0570 part 2-6 (07.98) industrial use; mounting rails, top hat rails 35 mm
Safety of power transformers, power supply units wide for snap-on mounting of equipment
EN 50014 / DIN VDE 0170/0171 part 1 (02.00) and similar - particular requirements for safety
Electrical apparatus for potentially explosive isolating transformers for general use EN 50 035 (1978) / DIN EN 50035 (04.80)
atmospheres - general requirements Low-voltage switchgear and controlgear for
EN 61558-2-13 / DIN VDE 0570 part 2-13 (08.00) industrial use; mounting rails; mounting rails for
EN 50019 (1978) / DIN VDE 0170/0171 part 6 terminal blocks
Safety of power transformers, power supply units
(06.01)
and similar - particular requirements for auto
Electrical apparatus for potentially explosive EN 50 045 (1980) / DIN EN 50045 (04.82)
transformers for general use
atmospheres - increased safety "e" Low-voltage switchgear and controlgear for
industrial use; mounting rails, top hat rails 15 mm
EN 61558-2-15 / DIN VDE 0570 part 2-15 (11.01)
EN 50020 (1978) / DIN VDE 0170/0171 part 7 wide for mounting of terminal blocks
Particular requirements for isolating transformers
(04.96)
for medical rooms DIN EN 50081-1 (03.93)
Electrical apparatus for potentially explosive
atmospheres - intrinsic safety "i" Electromagnetic compatibility (EMC) - generic
EN 61558-2-17 / DIN VDE 0570 part 2-17 (07.98) emission standard - residential, commercial and
DIN VDE 0220 part 1 (11.71) Safety of power transformers, power supply units light industry (VDE 0839 part 81-1)
Specifications for detachable cable clamps to and similar - particular requirements for trans-
be used in power cable installations up to 1000V formers for switch mode power supplies DIN EN 50081-2 (03.94)
Electromagnetic compatibility (EMC) - generic
EN 61558-2-19 / DIN VDE 0570 part 2-19 (09.01) emission standard - part 2: industrial environment
IEC 112 (1979) / DIN VDE 0303 part 1 (06.84)
Particular requirements for interference reduction (VDE 0839 part 81-2)
Method for determining the comparative and the
proof tracking indices of solid insulating materials transformers
DIN EN 50082-1 (11.97)
under moist conditions
Electromagnetic compatibility (EMC) - generic
EN 61558-2-20 / DIN VDE 0570 part 2-20 (04.01)
immunity standard - residential, commercial and
IEC 529 (1989) / DIN VDE 0470 part 1 (09.00) Particular requirements for miniaturized reactors
light industry (VDE 0839 part 82-1)
Degrees of protection provided by enclosures
(IP Code) EN 50091-1-2 / DIN VDE 0558 part 512 (05.99) DIN EN 61000-6-2 (03.00)
Uninterruptible power systems (UPS) - general and Electromagnetic compatibility (EMC) - generic
DIN VDE 0550 part 3 (12.69) safety requirements for UPS used in restricted immunity standard - industrial range (VDE 0839
Particular requirements for control transformers as access location part 6-2)
well as for mains-supply and insulating transformers
above 1000V
1/4
allg_041014.qxd 14.10.2004 09:58 Seite 5
DIN EN 61000-3-2 (12.01) / VDE 0838 part 2 DIN 41576 DIN 43714 (06.79)
Electromagnetic compatibility (EMC) - limits for Instrument fuses Measuring, control; electric temperature detec-
harmonic current emissions Indicating fuse links 250 V, interchangeable tors; compensating leads for thermocouples
IEC 38 (1983) / DIN IEC 38 (05.87) DIN 41611 part 4 (04.86) DIN 46234 (03.80)
IEC-standard voltages Solderless electrical connections, clip connec- Cable sockets for solderless connections; ring-
tions, terminology, requirements, tests shape without protective sleeve for copper
IEC 326-3 (1980) / IEC 326-3A (1982) conductors
DIN IEC 326 part 3 (03.85) IEC 512-3 (1976) / DIN 41640 part 3 (07.84)
Printed circuits, circuit boards, design and use of Testing procedures and measuring methods for DIN 46237 (07.70)
circuit boards electromechanical components; Crimp-type cable sockets for solderless
Test 5 b: current-carrying capacity connections, insulated, for copper conductors
IEC 352-1 (1983)
DIN IEC 352 part 1 (05.87) IEC 127 (1974) / DIN 41660 (05.79) DIN 46247
Solderless electric connections, wire-wrap con- Instrument fuses Pin bushings without protective sleeve
nections, general requirements, testing methods Fuse links 5 mm x 20 mm, quick, high breaking
and practical guidance capacity IEC 304 (1982) / DIN 47002 (08.87)
Colors for low frequency cables and wires
IEC 760 (1989) / IEC 127 (1974) / DIN 41661 (05.79)
DIN IEC 760 (04.91), draft, Instrument fuses DIN 49515 (12.83)
rectangular cable connections Fuse links 5 mm x 20 mm, quick, low breaking D-fuse links D II, D III, D IV H, 500 V
capacity
DIN 40802 part 2 (02.76) DIN 49522 (04.81)
Metal laminated base materials for printed IEC 127 (1974) / DIN 41661 (05.79) D-fuse links D 01, D 02, D 03, 380 V, 250 V ~
circuits, types Instrument fuses
Fuse links 5 mm x 20 mm, slow, low breaking DIN 49360
IEC 740 / DIN 41302 capacity D-fuses
Laminations for transformers and inductivities for
use in telecommunication and electronic equip- IEC 127 (1974) / DIN 41668 (05.79) ISO/DIS 8820 (1988) / DIN 72581 part 3 (08.87)
ment Instrument fuses Fuses for low voltage installations; blade type
Fuse links 6,3 mm x 32 mm, quick, low breaking fuse links
DIN 41571 capacity
Instrument fuses VBG 4 (04.79)
Fuse links 250 V, interchangeable Electrical installations and appliances
1/5
allg_041014.qxd 14.10.2004 09:58 Seite 6
Public power supply companies have largely completed their conversion to the new standardized voltages.
Accordingly, Riedel has converted all series products to the new standardized voltages and voltage tolerances.
All Riedel transformers and power packs featuring the old standard voltages 220V/380V can also be operated without
impairment on mains with 230V/400V. The output voltage proportionally increases very slightly.
All Riedel standard products feature +-5% tappings allowing voltage adaptation to the new mains.
until 1987
from 1988
until 2003
from 2003
onwards
Limit values for rated direct voltage comp. to DIN EN 61131-2 / part 2 (05.95)
Riedel power packs provide electronic controls with the permissible operational voltage independent from load and
line voltage fluctuations comp. to DIN IEC 38. Thanks to close magnetic coupling and a generous design, Riedel power
packs provide a stable voltage remaining within limit values for direct voltages laid down in DIN EN 61131-2.
Annotation 1: Apart from voltage tolerances a total alternating voltage component with peak value of 5% of rated vol-
tage is permissible. Absolute limits are: 30/19,2V direct voltage for 24V direct voltage and 60/38,4V di-
rect voltage for 48V direct voltage.
1/6
allg_041014.qxd 14.10.2004 09:58 Seite 7
Protection systems
Protection systems are indicated by abbreviations always starting with code letters IP followed by two code numbers
for the protection rate (comp. to EN 60529).
Protection ratings for protection against accidental contact and foreign bodies
First Protection degree
code
no. Designation Definition
0 No protection No special protection of persons against direct contact with active parts.
No protection against penetration of solid foreign bodies.
2 Protection against me- Protection against finger contact with active parts.
dium-sized foreign bodies Protection against penetration of solid foreign bodies (diameter greater 12 mm).
4 Protection against grain Protection against contact with active parts via tools, wires or similar with a thickness greater 1 mm.
shaped foreign bodies Protection against penetration of solid foreign bodies (diameter greater 1 mm).
1 Protection against Water drops striking vertical must have no harmful effect.
water drops
falling vertical
3 Protection against Water falling at any angle up to 60° from the vertical must have no harmful effect.
spraying water
4 Protection against Water splashing from any direction must have no harmful effect.
splashing water
5 Protection against Water projected by a nozzle against transformer from any direction must have no harmful effect.
water jets
6 Protection at Water must not penetrate transformer in harmful quantities at temporary overflow.
overflow
. . . bar
For firedamp and explosion-proof transformers initials SCH respectively EX are used also.
Protection classes
Protection class is a constructional equipment feature about safety against dangerous body flows.
Open frame transformers destined to be installed in switch cabinets or systems do not possess a protection class.
They can only be prepared for it.
Protection class I: System with protective earth terminal and basic insulation
Protection class II: System without protective earth terminal with double or reinforced insulation
Protection class III: System without protective earth terminal whereby protection against dangerous body flows rests
on supply with protection low voltage (SELV) and no higher voltage can be produced than protec-
tion low voltage.
1/7
allg_041014.qxd 14.10.2004 09:58 Seite 8
Finger-safe
Annotation: Equipment and appliances operated with protection low voltage up to 25 V ~ or 60 V - are considered
"protected against direct contact".
According to VBG 4, § 5 / section 4, system inspection for due order prior to first startup may be scraped when the
company receives confirmation from the manufacturer or installer stating that electric system and appliances concur
with regulations VBG 4. The required confirmation refers to installed, ready to service systems and appliances and may
only be submitted by the installer or assembly company. The manufacturer of electric appliances may just confirm that
his products comply to relevant electrotechnical DIN VDE regulations stated in VBG 4. It is the installer's duty to select
fitting appliances according to these aspects.
1/8
allg_041014.qxd 14.10.2004 09:58 Seite 9
Transformers in general
A transformer is a static unit featuring two or more windings which by electromagnetic induction transforms a system
of alternating voltage and alternating current, usually with different values at the same frequency, as a means to trans-
mit electric energy (ref: VDE 0570, IEV 421-01-01).
Insulation
Transformers' constructive differences are principally determined by their designated application. Corresponding
requirements are stated in installation and appliance norms (for example VDE 0100, VDE 0113, VDE 0700, VDE 0800)
and transformer norms (for example VDE 0550, VDE 0551, VDE 0570).
An important criteria for selection is the insulation layout between input and output circuits:
Primary voltage
Secondary voltage
Tappings
Transformers may be designed with primary as well as secondary tappings.
Primary tappings serve to adjust and apply a transformer in diverse supply voltages. The increased winding space
requirement frequently necessitates turning to the next larger transformer type. There is no need for enlargements at
mains adaption of app. 5 %.
2 primary voltages
Secondary voltage
The need for further winding space also does not occur when a second primary voltage halved results in the first (for
example 115 V - 230 V).
1/9
allg_041014.qxd 14.10.2004 09:58 Seite 10
If two equal winding parts are connected in series or parallel the transformer can be used for both secondary voltages
while retaining full output. Observe stated polarity!
In case of several secondary voltages, rated secondary current intensity is calculated based upon the highest secon-
dary voltage. Therefore tappings can only be loaded with current intensity calculated from power and highest secon-
dary voltage.
If full power is required for each individual secondary voltage, power or current intensity must be stated individually. It
calls for further space requirement and possibly the next larger transformer type.
Secondary voltage
Therefore instead of a 1000 VA-sized transformer just one 425 VA in size is needed.
Operation modes
All Riedel standard transformers are designed for continuous operation S1. S1-operation is at hand, when a transformer
operates any given time under permissible thermal rated current and the other remaining rated values. The declaration
corresponds to 100% ED (on-period). Additionally, there are transformers that may be loaded higher for some time
when a lower load has preceded.
Duty cycle (off-time period + load duration) must not exceed 10 min., duty cycle > 10 min. is continuous operation.
NT = N x
冪 ED (%)
100
NT = type power
N = nominal power
1/10
allg_041014.qxd 14.10.2004 09:58 Seite 11
Power
All stated power data refers to collected secondary power in VA resp. kVA at continuous operation, excitation with
rated voltage, rated frequency, cos. phi = 1, an ambient temperature of max. 40°C and a set-up altitude up to 1000 m
above sea level (NN).
Power is calculated from rated secondary voltage (volt) and rated secondary current (ampere) into VA or kVA.
Frequency
Transformers stated in catalogue are suitable for mains with rated frequency 50 - 60 Hz. The rating plate states 50/60 Hz.
Stated losses, voltage drops and efficiency refer to rated frequency 50 Hz. Frequencies other than 50 Hz cause a
change in type power according to following chart:
f (Hz) 16 2/3 40 42 50 60 75 100 200 300
N (%) 35 80 84 100 110 115 130 135 140
Rated power in mains with 60 Hz must not be exceeded, if it is a normal transformer with rating plate statement of
50/60 Hz.
Heating
Free access of cooling air must be ensured. At ambient temperatures above 40°C rated power must be reduced
according to following chart:
°C 45 50 55 60
N (%) 95 85 80 75
Temperature rise
Principally transformers can be operated at higher power for a short time, but only if highest permitted medium tem-
perature rise is adhered to and prior continuous load was beneath 100%..
Overload chart:
Prior continuous Permissible duration of overload in % of rated power
load in %
of rated power 150 % 140 % 130 % 120 % 110 %
1/11
allg_041014.qxd 14.10.2004 09:58 Seite 12
Temperatures
During rated conditions transformers produce losses which transpose into heat. According to regulations this "self -
heating" resp. "overtemperature" is bound to limit values by insulation class of insulating material and under considera-
tion of ambient temperature. These values concern the winding and components directly in contact to it. Following
chart refers to the medium temperature rise of overtemperatures at an ambient temperature of 40°C.
According to regulations the "hot spot" of class A can exceed following chart value 5K and class H 15K depending on
insulation class. We manufacture in all stated insulation classes on request.
A 105°C
E 1 1 5°C
B 120°C
F 140°C
H 175°C
Fusing
Observe the following for transformer fusing:
1. Selection of fuse media is determined by their ratings such as permissible voltage and current, their release charac-
teristics and breaking capacity.
In this connection consider that depending on fuse selection eventually back-up protection (advance fuse) may be
necessary to cover the entire current / time spectrum.
2. To pinpoint fuse value normally one must differentiate between primary and secondary side of transformer.
The "safe release" of a fuse in connection with transformers is more simple via the secondary side, i.e. fuse selection is
easier because rated current is close to rated current of fuse. The fuse protects transformers reliably against short
circuit and excess output overload. The overcurrent protection of a transformer, for example caused by interturn short
circuit, can only be realized via primary-side fuses. But because of the inrush any fuse value must usually be calculated
several times higher than rated current of transformer would demand. Therefore such fuses function more as short
circuit protection than overload protection.
Concerning this there are remedies though such as inrush current limiters to select fuse value close to rated current of
transformer.
1/12
allg_041014.qxd 14.10.2004 09:58 Seite 13
There is a causal link between fuse value, fuse type, (large) line lengths, ambient temperature and permissible trans-
former temperature (acc. to regulation) in order to achieve optimal protection and operational conditions. Recom-
mended fuse values stated on rating plates and data sheets of Riedel- transformers solely refer to transformer protec-
tion. The fuses must be placed directly after resp. in front of the transformer. When rated conditions deviate (for example
ambient temperature) fuse values must be corrected. In priority our fuse recommendations base on instrument fuses
(blow-out fuses), automatic circuit breakers and motor circuit breakers. Optimal protection is ensured with transformer
circuit breakers available on the market because they are adjusted to inrush characteristic of transformers.
Remark: Observe current translation during overload in case of primary fusing for variable ratio ring transformers and
transformers with several output voltages or output windings.
Three-phase transformers
The capital letter refers to the input winding, the small 10% load
capacity
to the output winding. The upper voltage is marked by
1 in front, the undervoltage by a 2 in front, regardless
of input- or output voltage. A 1 in back, on the con- full load
capacity
trary, marks the beginning of a winding, a 2 in back the
end. Tabs are marked 3 and 4 in back. The numbers full load
correlate to letters U V W and distinguish the 3 capacity
full load
capacity
full load
capacity
none
full load
capacity
10% load
capacity
1/13
allg_041014.qxd 14.10.2004 09:58 Seite 14
Output parameters
Output value
The output value at constant voltage operation is the output voltage, at constant current operation it is the output current.
Rated output voltage
Rated output voltage is the voltage available at connection point. Connection point at operation with sense-lines is the user itself,
in any other case it is the unit's socket.
Rated output current
Rated output current is the current available at the unit's output, allowing constant operation of unit.
Rated output power P
Product of rated voltage times rated current. At multiple output: sum total of all products.
Output power reduction at higher ambient temperatures
Is stated in % / K.
Parallel operation and series operation of units
For higher output power identical units can be switched in parallel or series. At series operation stated maximal constant voltage
between output and housing should be observed.
Redundancy
a. When outputs are switched in parallel by individual units only reduced redundancy is achieved. When a defect occurs in the
primary circuit of a unit, the other unit takes over complete current supply automatically and without interruption.
b. 100% redundancy requires decoupling diodes. For series RPL types 125 W and 250W we offer our customers internal decoup-
ling diodes (at a surcharge), for the rest of the units an external additional module featuring decoupling diodes and interferen-
ce reports.
Adjustment range of output size
The term adjustment range is relevant for controllable units only.
a. the adjustment range is stated at rated supply voltage and at half rated load. The user should remember, that when the out-
put voltage is raised the output current by rule reduces according to rated output power.
b. b. Solution of adjustment is stated as relative value in %.
Changing the output value
a. via internal potentiometer
b. via external potentiometer
c. via analog input such as 0 - 10 VDC or 4 - 20 mA.
Periodical and non-periodical tolerances = ripple and noise voltage
a. low frequency noise = power line hum. Plays no role in D.C./D.C.-converters. Only relevant at connection of unit to alternating
current mains resp. three-phase mains.
b. Switching noise. Only switching frequency and its harmonics
c. Complete noise inclusive overshoot peaks (application of measuring devices featuring adequate bandwidth necessary).
1/14
allg_041014.qxd 14.10.2004 09:58 Seite 15
Line correction
Relative change of output size, in % for set range of supply voltage and supply frequency at constant load, according to norm at
50 % of rated load. Line correction of 0,1% at output voltage of 24 VDC signifies that the absolute change of the output voltage
at change of supply voltage of minimal to maximal value is (0,1 % x 24V) /100 % = 24 mV.
Load correction
Relative change of output size, in % for set load range at constant supply voltage. The most unfavorable value of supply voltage
is stated.
Temperature coefficient
Relative change of output size, in % / K for set temperature range.
Tolerance of output size
Is stated in % for units with set rated supply voltage and at half rated load.
Dynamic behavior at load changes for a set range
a. deviation of output size is the maximal change of output size, set as percentage, which was caused by a load change.
b. recovering time (correction time) is the time span between load leap and the time when the output size returns to the set tole-
rance width.
The rise- and fall flanks of the load change should be less than a tenth of the set recovering time.
Output overcurrent protection
a. constant current characteristics
b. reverse characteristics
c. trigger characteristics
d. short-circuit proof characteristics (not protected against continued overload).
Our linear controllers realize reverse characteristics. Our switched units feature short-circuit proof and overload proof characte-
ristics.
Output overvoltage protection
a. protection circuit with short circuit of output
b. electronic lock
c. lock with 'reset'-system
Most of our units feature a breakdown-protection circuit.
Input parameters
Rated voltage
Standard value of supply voltage, for which the unit is designed.
Voltage range
From the minimal value to the maximal value of voltage
Supply current
a. effective value of supply current
b. peak value of supply current (only alternating voltage- resp. three-phase sources).
c. Highest inrush current. The charging current of the suppression capacitors in the first milli second is to be ignored.
d. The harmonic factor of the supply ripple.
Power factor (only alternating voltage- resp. three-phase sources).
Power factor is the rate of true power PE and vector power SE at input.
= PE / SE
If voltage and current are sinusoidal, then power factor is as the cos between voltage and current. Because the power supplies
feature a pulse shaped current pickup following is valid:
= * cos
- distortion factor of supply current
Distortion factor is the ratio of effective value of the fundamental wave and effective value of the total current.
Efficiency
Efficiency is the ratio of true powers at output and input:
= PA /PE,
PA - true power at output
PE - true power at input
Power-line failure bridging time (hold time)
This time is named retention time in the norm (switch-off-decay time) and should be stated in +10% at rated output voltage, rated
output power and minimum supply voltage.
1/15
allg_041014.qxd 14.10.2004 09:58 Seite 16
1/16
allg_041014.qxd 14.10.2004 09:58 Seite 17
1. All parts or services where a Defect becomes apparent within existence of an infringement and (iii) leaves any protective me-
the limitation period shall, at the discretion of the Supplier, be asures and settlement negotiations to the discretion of the
repaired, replaced or provided again free of charge irrespecti- Supplier. If the Purchaser stops using the Supplies in order to
ve of the hours of operation elapsed, provided that the reason reduce the damage or for other good reason, it shall be obli-
for the Defect had already existed at the time when the risk ged to point out to the third party that no acknowledgement of
passed. the alleged infringement may be inferred from the fact that the
2. Claims based on Defects are subject to a limitation period of use has been discontinued.
24 months. This provision shall not apply where longer periods 2. Claims of the Purchaser shall be excluded if it is itself responsi-
are prescribed by law according to Sec. 438 para. 1 No. 2 (buil- ble for the infringement of an IPR.
dings and things used for a building), Sec. 479 para. 1 (right of 3. Claims of the Purchaser shall also be excluded if the infringe-
recourse), and Sec. 634a para. 1 No. 2 (defects of a building) ment of the IPR is caused by specifications made by the Pur-
German Civil Code ("BGB"), as well as in cases of injury of life, chaser, to a type of use not fore-seeable by the Supplier or to
body or health, or where the Supplier intentionally or grossly the Supplies being modified by the Purchaser or being used
negligently fails to fulfil its obligation or fraudulently conceals a together with products not provided by the Supplier.
Defect. The legal provisions regarding suspension of expira- 4. In addition, with respect to claims by the Purchaser pursuant
tion ("Ablaufhemmung"), suspension ("Hemmung") and re- to No. 1 a) above, Art. VIII Nos. 4, 5, and 9 shall apply mutatis
commencement of limitation periods remain unaffected. mutandis in the event of an infringement of an IPR.
3. The Purchaser shall notify Defects to the Supplier in writing and 5. Where other defects in title occur, Art. VIII shall apply mutatis
without undue delay. mutandis.
4. In the case of notification of a Defect, the Purchaser may with- 6. Any other claims of the Purchaser against the Supplier or its
hold payments to a reasonable extent taking into account the agents or any such claims exceeding the claims provided for in
Defect occurred. The Purchaser, however, may withhold pay- this Art. IX, based on a defect in title, shall be excluded.
ments only if the subject-matter of the notification of the De- X. IMPOSSIBILITY OF PERFORMANCE; ADAPTATION OF CON-
fect occurred is justified beyond doubt. Unjustified notifications TRACT
of Defect shall entitle the Supplier to have its expenses reim-
bursed by the Purchaser. 1. To the extent that Supplies are impossible to be carried out,
5. The Supplier shall first be given the opportunity to supplement the Purchaser shall be entitled to claim damages, unless the
its performance ("Nacherfüllung") within a reasonable period Supplier is not responsible for the impossibility. The Purchaser-
of time. 's claim for damages shall, however, be limited to an amount of
6. If supplementary performance is unsuccessful, the Purchaser 10 % of the value of the part of the Supplies which, owing to the
shall be entitled to cancel the contract or reduce the remune- impossibility, cannot be put to the intended use. This limitation
ration, irrespective of any claims for damages it may have ac- shall not apply in the case of mandatory liability based on in-
cording to Art. XI. tent, gross negligence or injury of life, body or health; this does
7. There shall be no claims based on Defect in cases of insignifi- not imply a change in the burden of proof to the detriment of
cant deviations from the agreed quality, of only minor impair- the Purchaser. The right of the Purchaser to cancel the con-
ment of usefulness, of natural wear and tear or damage arising tract shall remain unaffected.
after the transfer of risk from faulty or negligent handling, ex- 2. Where unforeseeable events within the meaning of Art. IV No.
cessive strain, unsuitable equipment, defective workman- 2 substantially change the economic importance or the con-
ship, inappropriate foundation soil or from particular external tents of the Supplies or considerably affect the Supplier's busi-
influences not assumed under the contract, or from non-re- ness, the contract shall be adapted taking into account the
producible software errors. Claims based on defects attributa- principles of reasonableness and good faith. Where doing so is
ble to improper modifications or repair work carried out by the economically unreasonable, the Supplier shall have the right to
Purchaser or third parties and the consequences thereof shall cancel the contract. If the Supplier intends to exercise its right
be likewise excluded. to cancel the contract, it shall notify the Purchaser thereof wi-
8. The Purchaser shall have no claim with respect to expenses thout undue delay after having realised the repercussions of
incurred in the course of supplementary performance, inclu- the event; this shall also apply even where an extension of the
ding costs of travel and transport, labour, and material, to the delivery period had previously been agreed with the Purcha-
extent that expenses are increased because the subject-mat- ser.
ter of the Supplies was subsequently brought to another loca- XI. OTHER CLAIMS FOR DAMAGES
tion than the Purchaser's branch office, unless doing so com- 1. Any claims for damages and reimbursement of expenses the
plies with the intended use of the Supplies. Purchaser may have (hereinafter referred to as "Claims for Da-
9. The Purchaser's right of recourse against the Supplier pursu- mages"), based on whatever legal reason, including infringe-
ant to Sec. 478 BGB is limited to cases where the Purchaser ment of duties arising in connection with the contract or tort,
has not concluded an agreement with its customers excee- shall be excluded.
ding the scope of the statutory provisions governing claims 2. The above shall not apply in the case of mandatory liability, e. g.
based on Defects. Moreover, No. 8 above shall apply mutatis under the German Product Liability Act ("Produkthaftungsge-
mutandis to the scope of the right of recourse the Purchaser setz"), in the case of intent, gross negligence, injury of life, bo-
has against the Supplier pursuant to Sec. 478 para. 2 BGB. dy or health, or breach of a condition which goes to the root of
10. Furthermore, the provisions of Art. XI (Other Claims for Dama- the contract ("wesentliche Vertragspflichten"). However,
ges) shall apply in respect of claims of damages. Any other Claims for Damages arising from a breach of a condition which
claims of the Purchaser against the Supplier or its agents or goes to the root of the contract shall be limited to the foresee-
any such claims exceeding the claims provided for in this Art. able damage which is intrinsic to the contract, unless caused
VIII, based on a Defect, shall be excluded. by intent or gross negligence or based on liability for injury of li-
IX. INDUSTRIAL PROPERTY RIGHTS AND COPYRIGHT; DEFECTS IN fe, body or health. The above provision does not imply a chan-
TITLE ge in the burden of proof to the detriment of the Purchaser.
1. Unless otherwise agreed, the Supplier shall provide the Sup- 3. To the extent that the Purchaser has a valid Claim for Dama-
plies free from third parties' industrial property rights and copy- ges according to this Art. XI, it shall be time-barred upon expi-
rights (hereinafter referred to as "IPR") with respect to the ration of the limitation period applicable to Defects pursuant to
country of the place of destination. If a third party asserts a ju- Art. VIII No. 2. In the case of claims for damages under the Ger-
stified claim against the Purchaser based on an infringement man Product Liability Act, the statutory provisions governing li-
of an IPR with respect to the Supplies made by the Supplier mitation periods shall apply.
and then used in conformity with the contract, the Supplier XII. VENUE AND APPLICABLE LAW
shall be liable to the Purchaser within the time period stipulated 1. If the Purchaser is a businessperson, sole venue for all dispu-
in Art. VIII No. 2 as follows: tes arising directly or indirectly out of the contract shall be the
a) The Supplier shall choose whether to acquire, at its own ex- Supplier's place of business. However, the Supplier may also
pense, the right to use the IPR with respect to the Supplies bring an action at the Purchaser's place of business.
concerned or whether to modify the Supplies such that they 2. Legal relations existing in connection with this contract shall be
no longer infringe the IPR or replace them. If this would be un- governed by German substantive law, to the exclusion of the
reasonable to demand from the Supplier, the Purchaser may United Nations Convention on Contracts for the International
cancel the contract or reduce the remuneration pursuant to Sale of Goods (CISG).
the applicable statutory provisions. XIII.SEVERABILITY CLAUSE
b) The Supplier's liability to pay damages shall be governed by
Art. XI. The legal invalidity of one or more provisions of this contract
c) The above obligations of the Supplier shall only apply if the Pur- shall in no way affect the validity of the remaining provisions.
chaser (i) immediately notifies the Supplier of any such claim This shall not apply if it would be unreasonable for one of the
asserted by the third party in writing, (ii) does not concede the parties to continue the contract.
1/17
allg_041014.qxd 14.10.2004 09:58 Seite 18
1/18
A
Copyright: BASF/Riedel Product group
Series RSTN
. . . makes for tension in purchase and engineering
In general
RSTN-transformers can be applied worldwide, meet national and international regulations and are ready for those up-
coming. Following designs are available:
Control transformers comp. to VDE 0570 part 2-2, EN 61558-2-2
Isolation transformers comp. to VDE 0570 part 2-4, EN 61558-2-4, (for sec. 230V only)
Safety transformers comp. to VDE 0570 part 2-6, EN 61558-2-6, (for sec. 24V only)
Fusing recommendation:
Below stated fusing recommendations refer to transformer's secondary side and safety fuse cartridges comp. to IEC
127 / EN 60127 (A time-lag), or comp. to IEC 60269 (AgL). Concerning this and also for primary fusing please observe
paragraph 'Fusing', catalogue section 'In General'.
RSTN 50 – 3000
Design: Open frame, stationary, for installation and set-up in dry rooms, separate windings, sturdy mounting brackets.
Connection to non-tracking transformer terminals with screw connection. The terminals are protected against finger
touch or contact with the back of the hand in compliance with accident prevention regulations (VBG 4). Ground connec-
tion via tab blade connection 6.3 x 0.8 mm. Accessory ground screw connection terminal available.
IP 00, suitable for installation up to protection rating IP 23 with natural cooling, insulation class E, max. ambient tempera-
ture 40°C.
Available in stated voltages only, for other voltages please see identical design type REIA.
A 1/3
A_TEIL_041014.qxd 14.10.2004 11:34 Seite 4
Industrial control transformer UL 506 / CSA 22.2 approbated (sum total sec. voltages max. 250V)
Power transformers comp. to VDE 0570 part 2-1, EN 61558-2-1, (50VA...1kVA), > 1kVA = special transformer
Control transformers comp. to VDE 0570 part 2-2, EN 61558-2-2,
Isolation transformers comp. to VDE 0570 part 2-4, EN 61558-2-4, (sec. 50V up to 500V max.)
Safety transformers comp. to VDE 0570 part 2-6, EN 61558-2-6, (sum total sec. voltages max. 50V)
Short-term delivery
A 1/4
A_TEIL_041014.qxd 14.10.2004 11:34 Seite 5
Short-term delivery
A 1/5
A_TEIL_041014.qxd 14.10.2004 11:34 Seite 6
d e
Vertical design a b
Copper Total
Approx. dimensions in mm
Model Size weight weight
app. kg app. kg a b c d e f Attachm.
RSTS 1200 UI 120/ 51 4,40 13,60 160 105 2 15 100 79 58 M 6
RSTS 1500 UI 120/ 61 4,50 15,00 160 115 2 15 100 89 63 M 6
RSTS 1800 UI 120/ 75 5,50 17,00 160 129 2 15 100 103 70 M 6
RSTS 2200 UI 150/ 52 6,60 21,00 200 122 262 124 94 58 M10
RSTS 2500 UI 150/ 65 7,20 24,80 200 135 262 124 107 65 M10
RSTS 3000 UI 150/ 77 7,60 28,00 200 147 262 124 119 71 M10
RSTS 4200 UI 150/ 92 9,20 31,00 200 162 262 124 134 78 M10
RSTS 5000 UI 150/103 12,90 38,50 200 173 262 124 145 83 M10
RSTS 6300 UI 180/ 78 16,80 48,00 240 168 360 144 140 - M10
RSTS 8000 UI 180/ 93 20,70 57,00 240 183 360 144 155 - M10
Fusing recommendation: Below stated fusing recommendations refer to transformer's secondary side and safety fuse
cartridges comp. to IEC 127 / EN 60127 (A time-lag), or comp. to IEC 60269 (AgL). Concerning this and also for primary
fusing please observe paragraph 'Fusing', catalogue section 'In General'.
c
e
d
Horizontal design a b
Copper Total
Approx. dimensions in mm
Model Size weight weight
app. kg app. kg a b c d e f Attachm.
RSTL 1200 UI 120/ 51 4,40 13,60 1 66 1 43 230 1 46 1 60 80 M6
RSTL 1500 UI 120/ 61 4,50 15,00 1 66 1 53 230 1 46 1 60 85 M6
RSTL 1800 UI 120/ 75 5,50 17,00 1 66 1 67 230 1 46 1 60 92 M6
RSTL 2200 UI 150/ 52 6,60 2 1,00 200 1 47 285 1 74 200 80 M6
RSTL 2500 UI 150/ 65 7,20 24,80 200 1 60 285 1 74 200 87 M6
RSTL 3000 UI 150/ 77 7,60 28,00 200 1 72 285 1 74 200 93 M6
RSTL 4200 UI 150/ 92 9,20 3 1,00 200 1 87 285 1 74 200 1 01 M6
RSTL 5000 UI 150/103 12,90 38,50 200 200 285 1 74 200 106 M6
RSTL 6300 UI 180/ 78 16,80 48,00 240 1 85 340 204 240 100 M8
RSTL 8000 UI 180/ 93 20,70 57,00 240 200 340 204 240 108 M8
A 1/7
A_TEIL_041014.qxd 14.10.2004 11:35 Seite 8
Series REIA
Miniaturized transformers
In general
REIA-transformers can be applied worldwide, meet national and international regulations and are ready for those up-
coming. Following designs are available:
Power transformers comp. to VDE 0570 part 2-1, EN 61558-2-1, (15VA...1kVA), > 1kVA = special transformer
Control transformers comp. to VDE 0570 part 2-2, EN 61558-2-2, (30VA and up)
Isolation transformers comp. to VDE 0570 part 2-4, EN 61558-2-4, (sec. 50V up to 500V max.)
Safety transformers comp. to VDE 0570 part 2-6, EN 61558-2-6, (sum total sec. no-load voltages max. 50V)
REIA 15 – 3000
Design: Open frame, stationary, for installation and set-up in dry rooms, separate windings, sturdy mounting brackets.
Connection to non-tracking transformer terminals with screw connection. For currents above 20A terminal blocks with
screw connections may be used also. In this case dimensions b and c increase. The terminals are protected against fin-
ger touch or contact with the back of the hand in compliance with accident prevention regulations (VBG 4).
Standard design for translation up to max. 600 V resp. 20A.
Further designs available on request (voltages, currents, connections, mounting etc.).
Ground connection via tab blade connection 6.3 x 0.8 mm. Accessory ground screw connection terminal available.
IP 00, suitable for installation up to protection rating IP 23 with natural cooling, insulation class E, max. ambient tempera-
ture 40°C.
f
Sek. Pri.
d e
a b
Short-term delivery *) Models without integral attachment bar Subject to technical modifications
A 1/9
A_TEIL_041014.qxd 14.10.2004 11:35 Seite 10
Series URST
Universal control transformers
In general
We recommend universal control transformers in cases of cramped storage space combined with the need for high
variety, making the use of many diverse single-phase control transformers insensible.
The multiple choices in primary connection (200...550V) for different mains input voltages featured by universal control
transformers, do not allow as optimal a design as control transformers series RSTN or REIA. And bearing the higher
purchase price in mind, one should consider prior to ordering, whether applying universal control transformers is ne-
cessary, since we guarantee short-term deliveries for special makes also.
Regulations and instructions for single-phase control transformers regarding mechanical and electrical requirements
are valid for universal control transformers also. The main difference to single-phase control transformers, apart from
the wide range of primary voltages, is the extended secondary range. The provided 2 - 6 output voltages increase ap-
plication possibilities even further. On output-side, only the current allocated to each winding section may flow in each
connection mode (parallel connection 2 x rated current, series connection 1 x rated current).
When this rule is observed, further output voltages can be drawn apart from those stated. However, the rated output
for the size in question is no longer achieved in such cases.
Therefore, this solution recommends itself only in individual cases where a different voltage has to be made available
quickly.
URST-transformers can be applied worldwide, meet national and international regulations and are ready for those up-
coming. Following design is available:
Control transformers comp. to VDE 0570 part 2-2, EN 61558-2-2
Fusing recommendation:
Below stated fusing recommendations refer to transformer's secondary side and safety fuse cartridges comp. to IEC 127
/ EN 60127 (A time-lag) or comp. to IEC 60269 (AgL). Concerning this and also for primary fusing please observe para-
graph 'Fusing', catalogue section 'In General'.
Voltage series:
Interchangeable input connections:
200/220/230/250/270/280/330/350/370/380/390/400/420/430/440/450/470/490/500/550V
Interchangeable output connections:
115/230V resp. 21/24/30//42/48/60V
Corresponding to connection diagram on rating plate, transformers are to be operated partly in parallel- or series con-
nection.
d e
a b
Copper Total
Model Approx. dimensions in mm
weight weight
A 1/11
A_TEIL_041014.qxd 14.10.2004 11:35 Seite 12
Series RSST
Anti-interference transformers with special screening
In general
RSST-transformers can be applied worldwide, meet national and international regulations and are ready for those up-
coming. Following designs are available:
Control transformers comp. to VDE 0570 part 2-2, EN 61558-2-2,
Isolation transformers comp. to VDE 0570 part 2-4, EN 61558-2-4,
Available accessories: fully integrated ground screw terminal Standard stock items
A 1/12
A_TEIL_041014.qxd 14.10.2004 11:35 Seite 13
Fusing recommendation:
Below stated fusing recommendations refer to transformer's secondary side and safety fuse cartridges comp. to IEC
127 / EN 60127 (A time-lag). Concerning this and also for primary fusing please observe paragraph 'Fusing', catalogue
section 'In General'.
Rated current input Current secondary and fusing recommendation
I 1 max. in I2 in Fusing
Model Model
A A A
pri. voltage 220/230/240 V sec. voltage 230V
RSST 100 0,52 RSST 100 0,43 0,315 At
RSST 130 0,65 RSST 130 0,56 0,40 At
RSST 200 1 ,00 RSST 200 0,86 0,63 At
RSST 250 1 ,23 RSST 250 1,08 0,80 At
RSST 320 1 ,57 RSST 320 1,39 1,00 At
RSST 400 1 ,94 RSST 400 1, 73 1,25 At
RSST 500 2,42 RSST 500 2, 17 1,60 At
RSST 630 3,05 RSST 630 2,73 2,00 At
RSST 800 3,83 RSST 800 3,47 2,50 At
RSST 1000 4,78 RSST 1000 4,34 3,1 5 At
A 1/13
A_TEIL_041014.qxd 14.10.2004 11:35 Seite 14
Design:
Open frame, vertical design, stationary, for installation and set-up in dry rooms, separate windings, sturdy mounting
brackets. Connection to non-tracking transformer terminals with screw connection. Above 20A transformer terminal
blocks or terminal blocks with screw connections are used, (dimensions b1 and c1 increase). The terminals are pro-
tected against finger touch or contact with the back of the hand in compliance with accident prevention regulations
(VBG 4).
Standard design for translation up to max. 550 V resp. 65A.
Further designs available on request (voltages, currents, connections, mounting etc.).
IP 00, suitable for installation up to protection rating IP 23 with natural cooling, insulation class E, max. ambient tempe-
rature 40°C.
Below stated dimensions and weights may show currently valid standards only. They remain subject to change.
c c1
d e
a b
b1
Copper Total
Power Approx. dimensions in mm
Model Size Article no. weight weight
VA
app. kg app. kg a b b1 c c1 d e Attachm.
RUE 280 280 UI 75 / 4 1 0059-00000280 0,95 3,60 100 81 98 1 32 197 63 64 M 5
RUE 630 630 UI 90/ 5 1 0059-00000630 1 ,65 6,30 120 95 113 1 57 222 76 76 M 6
RUE 980 980 UI 102 / 57 0059-00000980 2,50 7,70 140 103 117 1 77 242 76 87 M 6
RUE 1200 1200 UI 120 / 5 1 0059-0000 1200 4,40 13,60 160 105 117 208 273 100 79 M 6
RUE 1400 1400 UI 114 / 64 0059-0000 1400 3,50 13,00 154 1 14 129 1 98 263 100 95 M 6
RUE 1500 1500 UI 120 / 6 1 0059-0000 1500 4,50 15,00 160 1 15 1 27 208 273 100 89 M 6
RUE 1800 1800 UI 120 / 75 0059-0000 1800 5,50 17,00 160 129 141 208 273 100 103 M 6
RUE 2000 2000 UI 132 / 72 0059-00002000 5,85 20,00 178 132 143 228 293 11 2 102 M 8
RUE 2200 2200 UI 150 / 52 0059-00002200 6,60 21 ,00 200 122 128 260 325 124 94 M 8
RUE 2500 2500 UI 150 / 65 0059-00002500 7,20 24,80 200 135 141 260 325 124 107 M 8
RUE 3000 3000 UI 150 / 77 0059-00003000 7,60 28,00 200 147 153 260 325 124 1 19 M 8
RUE 4200 4200 UI 150 / 92 0059-00004200 9,20 31 ,00 200 162 168 260 325 124 134 M 8
RUE 5000 5000 UI 150 /103 0059-00005000 12,90 38,50 200 173 180 260 325 124 145 M 8
RUE 6000 6000 UI 168 / 92 0059-00006000 15,00 42,00 228 172 175 287 352 136 144 M 8
RUE 6300 6300 UI 180 / 78 0059-00006300 16,80 48,00 240 168 168 305 370 144 140 M 8
RUE 8000 8000 UI 180 / 93 0059-00008000 20,70 57,00 240 183 183 305 370 144 155 M 8
RUE 10000 10000 UI 210 / 88 0059-000 10000 29,1 0 78,00 280 188 188 360 425 176 158 M10
RUE 13000 13000 UI 210 /103 0059-000 13000 33,00 89,00 280 203 203 360 425 176 173 M10
RUE 16000 16000 UI 210 /133 0059-000 16000 4 1,90 1 1 2,00 280 233 233 360 425 176 203 M10
RUE 20000 20000 UI 240/140 0059-00020000 42,00 129,00 320 250 250 41 0 475 196 21 4 M14
Subject to technical modifications Short-term delivery
A 1/14
A_TEIL_041014.qxd 14.10.2004 11:35 Seite 15
REST 20 – 120
In general:
The rectangular core stacks of our single-phase high-power transformers are made of two-layered grain-oriented
low-loss strips. The windings consist of high-grade insulated double-lacquered massive copper. Core and windings
are vacuum impregnated together and subsequently baked in the drying oven for several hours.
The transformer's electrical design ensures best possible efficiency and a temperature rise remaining far below the li-
mits specified in regulation VDE. A sound design guarantees almost unlimited service life even at occurring overload.
REST-transformers can be applied worldwide, meet national and international regulations and are ready for those up-
coming. Following design is available:
High-power transformers comp. to VDE 0532
Design:
Open frame, vertical design, stationary, for installation and set-up in dry rooms, separate windings, sturdy mounting
brackets. Connection to robust terminal blocks (up to 450 A) resp. studs, line bars or cable lugs (not measured). Maxi-
mal voltage (phase-phase) 2000V.
IP 00, suitable for installation up to protection rating IP 23 with natural cooling, max. ambient temperature 40°C.
Insulation class F (average value temperature 140°C)
Attention: higher thermal load at lower efficiency
Because each high power transformer is individually designed, below stated dimensions and weights may show the
currently valid state only and remain subject to modification.
* depending on design and winding type of special currents all measurement may vary, especial-
ly measurement b may enlarge up to 100mm!
Measurment d and e on request
A 1/15
A_TEIL_041014.qxd 14.10.2004 11:35 Seite 16
RLTS 80 – 900
Single-phase auto transformers for single-phase fan-motors
In general: Transformers series RLTS are single-phase auto transformers featuring 7 stages and were specially desi-
gned for air conditioning and air engineering. Following design is available:
Auto transformers comp. to VDE 0570
Design: Open frame, stationary, for installation and set-up in dry rooms, economy winding, sturdy mounting brackets.
Connection to non-tracking transformer terminals with screw- and tab connection 2.8 x 0.8 mm up to 5 A, and 6.3 x 0.8
mm up to 20A. According to DIN 46249 tab connection 2.8 x 0.8 mm can only be loaded up to 5 A, and 6.3 x 0.8 up to
20 A. Above 20A terminal blocks with screw connections are used. The terminals are protected against finger touch or
contact with the back of the hand in compliance with accident prevention regulations (VBG 4).
Ground connection via tab blade connection 6.3 x 0.8 mm. Accessory ground screw connection terminal available.
IP 00, suitable for installation up to protection rating IP 23 with natural cooling, insulation class E, max. ambient tempe-
rature 40°C.
Special design: Series RLTS is also available in housing protection class IP 23 with following option:
Option: multicontact switch, operation indication lamp, housing etc.
(prices on request).
Copper Total
Model Current Article no. Approx. dimensions in mm
weight weight
Model Power Article no. Article no. Copper Total Approx. dimensions in mm
weight weight
VA 24V-230V (CEE) 230V (Schuko) kg kg a b c
RGTT 250 250 0010-60020-00 0011-60021-00 0,65 7,5 166 250 219
RGTT 500 500 0010-60020-0 1 0011-60021-0 1 1,10 10,0 166 250 219
RGTT 800 800 0010-60020-02 0011-60021-02 2,50 14,5 192 276 259
RGTT 1000 1000 0010-60020-03 0011-60021-03 2,60 1 7,5 192 276 259
RGTT 1600 1600 0010-60020-04 0011-60021-04 3,40 23,0 340 265 280
RGTT 2000 2000 0010-60020-05 0011-60021-05 5,00 3 1,5 340 265 280
RGTT 2500 2500 0010-60020-06 0011-60021-06 6,00 34,0 340 265 280
RGTT 3000 3000 0010-60020-07 0011-60021-07 6,60 37,5 340 265 280
A 1/17
A_TEIL_041014.qxd 14.10.2004 11:35 Seite 18
B
Copyright: Deutsche Bundesbahn/Riedel Product group
The safety of rail traffic and the punctuality of trains are of prime
importance to German Rail. Extensive electric and electronic
switch plants guarantee smooth running around the clock.
German Rail cannot afford breakdowns in its power supply – a
good reason to apply Riedel products.
B_TEIL_041014.qxd 14.10.2004 16:18 Seite 2
Three-phase transformers
number.
10% load
The capital letter refers to the input capacity
winding, the small to the output
winding. The upper voltage is mar-
ked by 1 in front, the undervoltage full load
capacity
by a 2 in front, regardless of input-
or output voltage. A 1 in back on the
contrary, marks the beginning of a
full load
winding, a 2 in back the end. Tabs capacity
are marked 3 and 4 in back. The
numbers correlate to letters U V W
and distinguish the 3 phases. The none
neutral point (star point) is always
marked N. full load
capacity
The most common vector groups
are summarized alongside, input
left-hand, output right-hand.
Unless otherwise requested, none
none
full load
capacity
10% load
capacity
B_TEIL_041014.qxd 14.10.2004 16:18 Seite 1
RDLTS 95 – 1800
Single-phase auto transformers in V-circuit arrangement for three-phase fan-motors
(1 set consisting of 2 individual transformers)
In general: Transformers series RDLTS are single-phase auto transformers featuring 5 stages and were specially desi-
gned for air conditioning and air engineering. Following design is available:
Auto transformers comp. to VDE 0570
Design: Open frame, stationary, for installation and set-up in dry rooms, economy winding, sturdy mounting brackets.
Connection to non-tracking transformer terminals with screw- and tab connection 2.8 x 0.8 mm up to 5 A, and 6.3 x 0.8
mm up to 20A. According to DIN 46249 tab connection 2.8 x 0.8 mm can only be loaded up to 5 A, and 6.3 x 0.8 up to 20
A. Above 20A terminal blocks with screw connections are used. The terminals are protected against finger touch or con-
tact with the back of the hand in compliance with accident prevention regulations (VBG 4).
Ground connection via tab blade connection 6.3 x 0.8 mm. Accessory ground screw connection terminal available.
IP 00, suitable for installation up to protection rating IP 23 with natural air self-cooling, insulation class E, max. ambient
temperature 40°C.
Voltage range: Input voltage: 400V 3~
Output voltages: 140/180/230/280/400V
Special design: Series RDLTS is also available in housing protection class IP 23 with following option:
Option: multicontact switch, operation indication lamp, housing etc.
(prices on request).
Further designs available on request (voltages, currents, connections, mounting etc.).
V-circuit:
Copper Total
Model Current Article no. Approx. dimensions in mm
weight weight
B 1/1
B_TEIL_041014.qxd 14.10.2004 16:18 Seite 2
Design: Open frame, vertical design, stationary, for installation and set-up in dry rooms, separate windings, sturdy
mounting brackets. Connection to non-tracking transformer terminals with screw connection. Above 60A non-trak-
king terminal blocks are mounted on head angles (attention: dimensions b and c will increase, not stated below). The
terminals are protected against finger touch or contact with the back of the hand in compliance with accident preven-
tion regulations (VBG 4).
Standard design for translation up to max. 550 V resp. 105A.
Further designs available on request (voltages, currents, connections, mounting etc.).
IP 00, suitable for installation up to protection rating IP 23 with natural air self-cooling, max. ambient temperature 40°C.
Insulation class E (average value temperature 115°C)
Insulation class F (average value temperature 140°C)
Attention: Higher thermal stress at lower efficiency
We manufacture these three-phase miniaturized transformers in all requested protection classes up to IP 65.
All types are also available as three-phase auto transformers (please find calculation method in catalogue section 'In gene-
ral', paragraph 'Transformers in economy winding').
Preferential circuitry: YNyn0; Dyn 5; Yd5
Copper Total
Model Power ⬇ Core Article no. Approx. dimensions in mm
weight weight
VA % kg kg a b c d e Attach.
DRUE 50 50 85,0 3 UI 48/ 26 13–000–01 E 0,22 1 ,2 96 86 100 71 48 M 4
DRUE 110 110 86,0 3 UI 60/ 21 13-000-02 E 0,7 1 ,7 120 81 1 10 90 39 M 4
DRUE 150 150 87,0 3 UI 60/ 31 13-000-03 E 0,8 2,4 120 91 11 0 90 49 M 4
DRUE 260 260 91,0 3 UI 75/ 26 13-000-04 E 1,1 3,9 150 86 135 11 3 49 M 5
DRUE 4 10 410 92,0 3 UI 75/ 41 13-000-05 E 1,5 5,7 150 10 1 135 11 3 64 M 5
DRUE 500 500 92,5 3 UI 90/ 31 13-000-06 E 2,2 6,6 180 91 155 136 57 M 6
DRUE 630 630 93,5 3 UI 90/ 41 13-000-07 E 2,5 8,4 180 101 155 136 67 M 6
DRUE 800 800 94,0 3 UI 90/ 51 13-000-08 E 2,8 10,2 180 1 11 155 136 77 M 6
DRUE 1 000 1 000 94,0 3 UI 102/ 46 13-000-09 E 3,2 1 1,3 21 0 108 175 150 80 M 8
DRUE 1 1 00 1 100 94,0 3 UI 114/ 40 13-000-10 E 4,2 1 3, 1 228 11 0 195 176 71 M 6
DRUE 1 200 1 200 94,5 3 UI 102/ 57 13-000-11 E 3,6 13,4 21 0 11 9 175 150 91 M 8
DRUE 1 500 1 500 95,0 3UI 120/ 51 13-000-12 E 4,6 1 7,0 240 12 1 205 185 81 M 8
DRUE 1 750 1 750 95,5 3UI 114/ 64 13-000-13 E 5,2 18,9 228 134 1 95 176 95 M 6
DRUE 2 000 2 000 95,5 3UI 120/ 61 13-000-14 E 6,3 2 1,0 240 13 1 205 185 91 M 8
DRUE 2 200 2 200 96,0 3UI 120/ 66 13-000-15 E 6,8 22,6 240 136 205 185 96 M 8
DRUE 2 400 2 400 96,0 3UI 120/ 71 13-000-16 E 8,0 25,0 240 14 1 205 185 101 M 8
DRUE 2 700 2 700 96,5 3UI 120/ 75 13-000-17 E 8,9 26,8 240 145 205 185 105 M 8
DRUE 3 000 3 000 96,5 3UI 132/ 72 13-000-18 E 8,4 29,2 265 152 230 200 102 M 8
DRUE 3 400 3 400 96,0 3UI 150/ 52 13-000-19 E 11,3 3 1,2 300 140 260 224 94 M 8
DRUE 4 400 4 400 96,5 3UI 150/ 65 13-000-20 E 12,2 36,6 300 153 260 224 108 M 8
DRUE 5 000 5 000 96,6 3UI 150/ 77 13-000-21 E 12,6 41,1 300 165 260 224 120 M 8
DRUE 6 000 6 000 96,8 3UI 150/ 92 13-000-22 E 15,6 49,6 300 180 260 224 134 M 8
DRUE 6 300 6 300 96,8 3UI 168/ 75 13-000-23 E 16,4 5 1,3 336 150 290 248 127 M 8
DRUE 8 000 8 000 97,1 3UI 168/ 92 13-000-24 E 20,2 62,5 336 170 290 248 144 M 8
DRUE 8 200 8 200 97,0 3UI 180/ 78 13-000-25 E 20,5 62,0 360 180 31 0 264 140 M 8
DRUE 10 000 10 000 97,4 3UI 180/ 93 13-000-26 E 26,6 76,0 360 195 31 0 264 155 M 8
DRUE 13 000 13 000 97, 1 3UI 210/ 73 13-000-27 E 37,7 90,0 420 180 360 31 6 143 M 10
DRUE 16 000 16 000 97,6 3UI 210/ 88 13-000-28 E 46,8 1 10,0 420 195 360 31 6 158 M 10
DRUE 18 000 18 000 97,8 3UI 210/103 13-000-29 E 48,6 122,0 420 21 0 360 31 6 173 M 10
DRUE 20 000 20 000 97,8 3UI 210/133 13-000-30 E 49,8 144,0 420 240 360 31 6 203 M 10
DRUE 25 000 25 000 98,2 3UI 210/133 13-000-31 E 54,8 146,0 420 240 360 31 6 203 M 10
DRUE 30 000 30 000 98,0 3UI 240/110 13-000-32 E 79,4 181,0 480 240 41 5 356 184 M 14
DRUE 36 000 36 000 98,1 3UI 240/140 13-000-33 E 88,9 218,0 480 270 41 5 356 214 M 14
Copper Total
Model Power ⬇ Core Article no. Approx. dimensions in mm
weight weight
VA % kg kg a b c d e Attach.
DRUF 6 000 6 000 95,2 3UI 150/ 77 13-000-01 F 1 2,6 4 1 ,1 300 165 260 224 120 M 8
DRUF 7 500 7 500 95,4 3UI 150/ 92 13-000-02 F 1 5,6 49,6 300 180 260 224 134 M 8
DRUF 8 000 8 000 95,6 3UI 168/ 75 13-000-03 F 1 6,4 5 1,3 336 150 290 248 127 M 8
DRUF 9 600 9 600 95,8 3UI 168/ 92 13-000-04 F 20,2 62,5 336 170 290 248 144 M 8
DRUF 10 000 10 000 95,9 3UI 180/ 78 13-000-05 F 20,5 62,0 360 180 3 10 264 140 M 8
DRUF 12 000 12 000 96,3 3UI 180/ 93 13-000-06 F 26,6 76,0 360 195 3 10 264 155 M 8
DRUF 16 000 16 000 96,8 3UI 210/ 73 13-000-07 F 33,9 86,0 420 180 360 31 6 143 M 10
DRUF 19 000 19 000 96,8 3UI 21 0/ 88 13-000-08 F 46,8 11 0,0 420 1 95 360 31 6 158 M 10
DRUF 21 500 2 1 500 97,0 3UI 2 10/103 13-000-09 F 48,6 122,0 420 2 10 360 3 16 173 M 10
DRUF 25 000 25 000 97,5 3UI 2 10/133 13-000-10 F 55,6 150,0 420 240 360 3 16 203 M 10
DRUF 30 000 30 000 98,0 3UI 2 10/133 13-000-11 F 54,8 146,0 420 240 360 3 16 203 M 10
DRUF 36 000 36 000 97,8 3UI 240/1 10 13-000-12 F 79,4 1 8 1,0 480 240 41 5 356 184 M 14
DRUF 40 000 40 000 97,9 3UI 240/140 13-000-13 F 88,9 218,0 480 270 41 5 356 2 14 M 14
B 1/3
B_TEIL_041014.qxd 14.10.2004 16:18 Seite 4
RDST 40 – 320
In general:
The rectangular core stacks of our three-phase high power transformers are made of two-layered grain-oriented low-
loss strips. The windings consist of high-grade insulated double-lacquered massive copper. Core and windings are va-
cuum impregnated together and subsequently baked in the drying oven for several hours.
The electrical layout of the transformers is such, that high efficiency is achieved and that transformers remain well be-
low the permissible heating limit specified in VDE regulation. Sound planning guarantees an almost unlimited service life,
even when overload of transformers occurs.
RDST-transformers can be applied worldwide, meet national and international regulations and are ready for those up-
coming. Following design is available:
Three-phase dry-type transformers comp. to VDE 0532
Design:
Open frame, vertical design, stationary, for installation and set-up in dry rooms, separate windings, sturdy mounting
brackets. Connection to sturdy connection terminals (up to 450A) resp. line bars or cable terminals (measurements
are not stated below). Maximal voltage (phase-phase) 2000V.
IP 00, suitable for installation up to protection rating IP 23 naturally air self-cooling, ambient temperature 40°C.
Insulation class F (average value temperature 140°C)
Attention: Higher thermal stress at lower efficiency
Because each high power transformer is individually designed, below stated dimensions and weights may show the
currently valid state only and remains subject to modification
All types are also available as three-phase auto transformers (please find calculation method in catalogue section 'In gene-
ral', paragraph 'Transformers in economy winding').
* Depending on design and winding type of special currents all measurements may vary, especi-
ally measurement b may enlarge up to 100mm!
Measurement d and e on request
Voltage 3AC 400V (50/60Hz), max. 15 starts/hour, max. 24 starts/day, starting time max.15 seconds, 3 steps for vol-
tage reduction to 50%, 65% and 80%, motor rush 8 x Irated, transformer-star point (2U/2V/2W) with abated cross-
section open on terminal (Korndörfer circuit), open design IP00, prepared for installation up to IP23 at natural con-
vection, version RATE features lower losses and end temperatures than RATF
* Depending on design and winding type of special currents all measurements may vary, especi-
ally measurement b may enlarge up to 100mm!
Measurement d and e on request
B 1/5
B_TEIL_041014.qxd 14.10.2004 16:18 Seite 6
kW kg kg a b c d e Attach.
RATE 15 15 0321-000-015 5 19 240 130 265 185 81 M8
RATE 19 19 0321-000-019 6 23 240 140 265 185 91 M8
RATE 22 22 0321-000-022 9 27 240 150 265 185 101 M8
RATE 30 30 0321-000-030 12 33 300 155 360 224 94 M8
RATE 45 45 0321-000-045 14 44 300 165 360 224 108 M8
RATE 55 55 0321-000-055 17 55 336 180 390 248 127 M8
RATE 75 75 0321-000-075 23 66 336 200 390 248 144 M8
RATE 90 90 0321-000-090 28 80 360 230 410 264 155 M8
RATE 1 1 0 1 10 0321-000-110 39 94 420 220 460 316 143 M 10
RATE 132 1 32 0321-000-132 48 114 420 270 460 316 173 M 10
RATE 160 1 60 0321-000-160 50 127 420 290 460 316 203 M 10
RATE 220 220 0321-000-220 58 151 420 320 460 316 203 M 10
RATE 280 280 0321-000-280 80 186 480 300 530 356 184 M 14
RATE 320 320 0321-000-320 91 224 480 330 530 356 214 M 14
RATE 350 350 0321-000-350 91 224 480 340 530 356 214 M 14
RATE 375 375 0321-000-375 95 228 480 360 530 356 214 M 14
RATE 400 400 0321-000-400 86 250 550 400 600 450 ~190 M 12
RATE 630 630 0321-000-630 103 260 550 450 600 450 ~190 M 12
RATE 720 720 0321-000-720 118 300 650 400 700 560 ~190 M 12
RATE 830 830 0321-000-830 138 380 650 460 700 560 ~210 M 12
RATE 900 900 0321-000-900 145 420 720 450 730 590 ~210 M 12
kW kg kg a b c d e Attach.
RATF 55 55 0322-000-055 14 44 300 165 360 224 108 M8
RATF 75 75 0322-000-075 17 55 336 180 390 248 127 M8
RATF 90 90 0322-000-090 23 66 360 210 410 264 140 M8
RATF 1 1 0 1 10 0322-000-110 28 80 360 230 410 264 155 M8
RATF 132 1 32 0322-000-132 39 94 420 270 460 316 143 M 10
RATF 160 1 60 0322-000-160 48 114 420 290 460 316 173 M 10
RATF 220 220 0322-000-220 50 127 420 320 460 316 203 M 10
RATF 280 280 0322-000-280 58 151 420 340 460 316 203 M 10
RATF 320 320 0322-000-320 80 186 480 300 530 356 184 M 14
RATF 350 350 0322-000-350 91 224 480 330 530 356 214 M 14
RATF 375 375 0322-000-375 91 224 480 340 530 356 214 M 14
RATF 400 400 0322-000-400 95 228 480 360 530 356 214 M 14
RATF 630 630 0322-000-630 86 250 550 400 600 450 ~190 M 12
RATF 720 720 0322-000-720 103 260 550 450 600 450 ~190 M 12
RATF 830 830 0322-000-830 118 300 650 450 700 560 ~190 M 12
RATF 900 900 0322-000-900 138 380 650 470 700 560 ~210 M 12
On request other voltages, designs, sizes or also complete circuit arrangements incl. switch cabinet according to your
specifications.
Examples of available
special application units
Apart from our standard delivery program we develop and manufacture custom makes. Please inquire with us.
C 1/2
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 1
We specialize in the manufacture of D.C. power supplies and offer in addition to special designs the following selec-
tion as standard delivery program:
Both single- and three-phase rectifier transformers are tapped ± 5% primary for adaptation to the respective mains
supply.
The transformer´s secondary side is designed to suit a follow-up bridge rectifier. Suitable are silicon rectifiers or thyris-
tors.
Compact rectifier transformers are equipped with silicon compact bridge rectifiers and must be protected accordingly.
The D.C. voltage delivered by single-phase bridge rectifiers has a residual ripple of 48%. A lower ripple can be achieved
with a filtered protection circuit, by using three-phase transformers with subsequent three-phase bridge rectifiers (resi-
dual ripple <5%) and by using compact power packs. Stabilized power supplies achieve the lowest residual ripple.
When using rectifier transformers always take care of proper heat dissipation.
On request we supply single- and three-phase power packs as rack units, and special rectifier transformers up to
15000 A.
C 1/1
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 2
Design: Open frame, stationary, for installation and set-up in dry rooms, sepa-
rate windings, sturdy mounting brackets. Connection to non-tracking trans-
former terminals with screw connections. The terminals are protected
against finger touch or contact with the back of the hand in compliance to ac-
cident prevention regulations (VBG 4). All types are designed for use with
bridge rectifiers under resistive load.
380/400/420 V 220/230/240 V
Watt at Current
Model Power 29 V AC 29 V AC Approx. dimensions in mm
24 V DC for
Article-no. Article-no.
VA W ADC a b c d e f Attachment
RGT 100 100 72 3 15–400–29–0 1 15–230–29–0 1 85 76 95 64 61 53 M4
RGT 130 130 96 4 15–400–29–02 15–230–29–02 96 77 104 84 61 50 M5
RGT 200 200 144 6 15–400–29–03 15–230–29–03 96 87 104 84 71 54 M5
RGT 320 320 216 9 15–400–29–05 15–230–29–05 120 88 120 90 70 53 M5
RGT 400 400 288 12 15–400–29–06 15–230–29–06 120 103 120 90 82 58 M5
RGT 500 500 360 15 15–400–29–07 15–230–29–07 120 121 120 90 102 69 M5
RGT 630 630 432 18 15–400–29–08 15–230–29–08 135 116 133 104 97 63 M5
Single-phase compact
rectifier transformers
Safety transformers comp. VDE 0570 part 2-6, EN 61558-2-6
GGT 100 – 630 new types with higher current
380/400/420 V 220/230/240 V
Watt at
Model Output 24 V DC Current 24 V DC 24 V DC Approx. dimensions in mm
Article-no. Article-no.
VA W ADC a b c d e Attachment
GGT 100 100 72 3 16–400–024–0 1 16–230–024–0 1 84 76 100 64 61 M4
GGT 130 130 96 4 16–400–024–02 16–230–024–02 100 77 104 84 61 M5
GGT 200 200 144 6 16–400–024–03 16–230–024–03 100 87 150 84 71 M5
GGT 320 320 216 9 16–400–024–05 16–230–024–05 120 93 150 90 70 M5
GGT 400 400 288 12 16–400–024–06 16–230–024–06 120 108 160 90 82 M5
GGT 500 500 360 15 16–400–024–07 16–230–024–07 120 125 160 90 102 M5
GGT 630 630 432 18 16–400–024–08 16–230–024–08 135 138 175 104 97 M5
Subject to technical modifications Standard stock items
C 1/2
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 3
Design: Open vertical design, stationary, for installation and set-up in dry rooms, stur-
dy mounting brackets, quick-snap-on for 35 mm DIN rail on request, connec-
tions to non-tracking transformer terminals. The terminals are protected
against finger touch or contact with the back of the hand in compliance to
accident prevention regulations (VBG 4).
On request these units can be provided with extended mounting brackets (as
illustrated below). Further to standard types, RTSNL can also be supplied in
various primary voltages up to max. AC 690 V and secondary voltages from
DC 10 V to DC 50 V at a surcharge. Other voltages and designs available on
request.
Harmonic rule EN 61000-3-2 is observed.
IP 00 suitable for installation up to protection rating IP 23, insulation class E,
max. ambient temperature ta 40°C.
Power supplies
Standard model:
Substructure/ sturdy mounting brackets, on request metal fastener for 35 mm DIN rail.
quick-snap-on:
Printed circuit board: epoxy resin FR 4/70 µm Cu, with solder resist and protective lacquer, 1.5 mm,
circuit traces fully solder-coated.
Terminals: polyamide 6.6, screw terminals with wire protection. The terminals are finger
and back of hand safe comp. to accident prevention regulations (VBG4)
Two-way rectification: special rectifier with particularly low flow voltage, resulting in high efficiency.
LED: green LED, 5 mm.
Fuses: primary and secondary fuses 5 x 20mm, design comp. to DIN.
Transformer: safety transformer comp. to VDE 0570, protection rating IP 00.
Varistor: S 10 K 30, protective varistor against induction peaks.
Residual ripple: at rated current and 24 V DC < 5%.
Temperature range: -20°C to +65°C
Input voltage: 220/230/240 V, 50/60 Hz
Output voltage: 24 VDC
C 1/3
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 4
The enclosed construction of the compact and space-saving power packs series RNTU provides comprehensive protection against
accidental contact. The power packs meet the safety requirements for protection against electric shock comp. to VDE 0106 part 101.
The modules can be snapped onto the DIN EN 50 022 mounting rail quickly and easily. From DC 5 A upwards there is additional provi-
sion for screw-fastening. Identical units can be connected in parallel up to max. 90% load per unit.
The integrated fuses (see table) exclusively deliver short circuit protection and guarantee safe operation even under worst-case con-
ditions. Units are to be loaded only with rated current as indicated.
Series RNTU clearly surpasses the requirements for power packs stated in DIN EN 61131-2 / part 2 and guarantees safe operation wi-
thout alterations even after the low voltage networks will have converted pursuant to DIN IEC 38 from the year 2003 onwards. Brief
dips in line voltage are bridged by large-scale capacitors.
Apart from the specifications listed below, series RNTU can also be supplied in various primary voltages up to max. AC 400 V and se-
condary voltages ranging from DC 10 V to DC 60 V at a surcharge. However, indicated currents must not be exceeded.
Power supplies
Technical data for model RNTU 24 S RNTU 48 S RNTU 72 S RNTU 120 S RNTU 180 S RNTU 240 S
Input
Mains input voltage AC 230 V or AC 400 V
Mains input voltage range + 10 % to – 10 % comp. to DIN IEC 38
Frequency 50 Hz/60 Hz
Input fuses 5 x 20 mm 5 x 20 mm 5 x 20 mm 5 x 20 mm 6,3 x 32 mm 6,3 x 32 mm
AC 230 V 0,4 time lag 0,8 time lag 1,25 time lag 2,0 time lag 2,5 time lag 4,0 time lag
AC 400 V external external external external 1,6 time lag 2,5 time lag
Output
Output voltage EN 61131-2/part 2 DC 24 V or DC 12 V, twin terminals
Status display green LED
Output fuse 5 x 20 mm 5 x 20 mm 5 x 20 mm 5 x 20 mm 6,3 x 32 mm 6,3 x 32 mm
1,25 time lag 2,5 time lag 4,0 time lag 6,3 time lag 10 time lag 12 time lag
Power 24 W 48 W 72 W 120 W 180 W 240 W
Permissible permanent output current DC 1 A DC 2 A DC 3 A DC 5 A DC 7,5 A DC 10 A
Residual ripple < 5%
Ambient temperature range – 10 ° C/+ 60° C
Output protection circuitry varistor
General data
Test voltage between input and output circuit comp. to regulations (safety transformers)
Directives VDE 0570 part 2-6, EN 61558-2-6, EN 61000-3-2, EN 61131-2/part 2
CE-mark yes
Installation orientation any position
Type of connection screw-type terminal, finger-safe comp. to VBG4
2
Connection data fine strand max. 2,5 mm
Mounting mounting rail (DIN EN 50 022), beginning with RNTU 120S additional
screw-connection possible, in rows spaced > 8 mm
TS 35 x 7,5 TS 35 x 15
Protection rating comp. VDE 0470 / EN 60529 IP 20
Safety class comp. IEC 536 / VDE 0106 T1 prepared for protection class II
Insulation class E
Dimensions in mm approx. Length L 77 77 82 134 157 157
Width W 62,5 62,5 90 125 175 175
Mounting depth D 122 122 128 153 185 185
Article no. AC 230 V/DC 1 2 V 223-024S 223-048S 223-072S 223-120S 223-180S 223-240S
Article no. AC 230 V/DC 24 V 224-024S 224-048S 224-072S 224-120S 224-180S 224-240S
Article no. AC 400 V/DC 24 V 226-024S 226-048S 226-072S 226-120S 226-180S 226-240S
Total weight in kg 0,95 1 ,20 2,35 3,9 5,2 6,3
Subject to technical modifications Standard stock items
C 1/4
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 5
Series RNTU-UL provides efficient power packs featuring high reliability and compact measurements. Series RNTU-UL distinctly sur-
passes power pack requirements DIN EN 61131-2 / part 2 and guarantees safe operation without alterations even after the low volta-
ge networks have converted pursuant to DIN IEC 38 from the year 2003 onwards. Brief dips in line voltage are bridged up to 10 ms by
large-scale electrolytic capacitors.
Apart from the specifications listed below, series RNTU-UL can also be supplied in secondary voltages ranging from DC 10 V to DC 60
V and on request also with various primary voltages. However, indicated currents must not be exceeded.
Identical units can be connected in parallel up to max. 90% load per unit.
The integrated fuses (see table) exclusively deliver short circuit protection and guarantee safe operation even under worst-case con-
ditions. Units are to be loaded only with rated current as indicated.
The enclosed construction of the space-saving power packs series RNTU-UL provides comprehensive protection against accidental
contact. The power packs meet the safety requirements for protection against electric shock comp. to VDE 0106 part 101. The modu-
les can be snapped onto DIN EN 50 022 mounting rails quickly and easily. From DC 5 A upwards there is additional provision for screw-
fastening.
Power supplies
RNTU 72S UL, 24S UL RNTU 240S UL, 120S UL
Technical data for model RNTU 24 S UL RNTU 72 S UL RNTU 120 S UL RNTU 180 S UL RNTU 240 S UL
Input
Mains input voltage AC 230 V and AC 115 V (AC 240 V and AC 120 V)
Mains input voltage range + 10 % to – 10 %
Frequency 60 Hz
Input fuses 5 x 20 mm 5 x 20 mm 5 x 20 mm 6,3 x 32 mm 6,3 x 32 mm
0,7 time lag 1,6 time lag 3,2 time lag 4,0 time lag 5,0 time lag
Output
Output voltage EN 61131-2/part 2 DC 24 V
Status display green LED
Output fuse 5 x 20 mm 5 x 20 mm 5 x 20 mm 6,3 x 32 mm 6,3 x 32 mm
1,25 A quick 4,0 A quick 6,3 A quick 10 A m. time lag 12 A m. time lag
Power 24 W 72 W 120 W 180 W 240 W
Permissible permanent output current DC 1 A DC 3 A DC 5 A DC 7,5 A DC 10 A
Residual ripple < 5%
Ambient temperature range – 10 ° C/+ 40° C
Output protection circuitry varistor
General data
Test voltage between input and output circuit comp. to regulations
Directives UL 508, CSA 22.2 No. 14, comp. to EN 61558-2-1, EN 61000-3-2, EN 61131-2/part 2
Test mark UL + CSA - File-No. E242971
CE- mark yes
Installation orientation any position
Type of connection screw-type terminal, finger-safe comp. to VBG4
2
Connection data fine strand max. 2,5 mm
Mounting mounting rail (DIN EN 50 022), beginning with RNTU 120S UL, additional
screw-connection possible, in rows spaced > 8 mm
TS 35 x 7,5 TS 35 x 15
Protection rating comp. VDE 0470 / EN 60529 IP 20
Safety class comp. IEC 536 / VDE 0106 T1 I
Insulation class E
Dimensions in mm approx. Length L 77 82 134 157 157
Width W 62,5 90 125 175 175
Mounting depth D 122 128 153 185 185
Article no. 0284-00024SUL 0284-00072SUL 0284-000120SUL 0284-000180SUL 0284-000240SUL
Copper weight in kg 0,1 2 0,36 0,6 0,97 1 , 18
Total weight in kg 0,95 2,35 3,9 5,2 6,3
C 1/5
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 6
The enclosed construction of the compact and space-saving power packs series RNTG provides comprehensive protection against
accidental contact. The power packs meet the safety requirements for protection against electric shock comp. to VDE 0106 part 101
and can be snapped onto DIN EN 50 022 mounting rail quickly and easily. RNTG120S / DC 5 A shows additional provision for screw-fa-
stening.
Identical units can be connected in parallel up to max. 80% load per unit.
The integrated fuses (see table) exclusively deliver short circuit protection and guarantee safe operation even under worst-case con-
ditions. Units are to be loaded only with rated current as indicated.
Series RNTG clearly surpasses the requirements for power packs stated in EN 61131-2 / part 2 and guarantees safe operation without
alterations even after the low voltage networks have converted pursuant to DIN IEC 38 from the year 2003 onwards. Brief dips in line
voltage are bridged up to 10 ms at rated duty.
Apart from the specifications listed below, series RNTG can also be supplied in various primary voltages up to max. AC 400 V and se-
condary voltages ranging from DC 5 V to DC 30 V at a surcharge. However, indicated currents must not be exceeded.
Power supplies
Technical data for model RNTG 12 S RNTG 24 S RNTG 48 S RNTG 72 S RNTG 120 S
Input
Mains input voltage AC 230 V
Mains input voltage range + 10 % to – 10 % comp. to DIN IEC 38
Frequency 50 Hz/60 Hz
Input fuses 5 x 20 mm 5 x 20 mm 5 x 20 mm 5 x 20 mm 5 x 20 mm
0,2 A time lag 0,4 A time lag 0,8 A time lag 1,25 A time lag 2,0 A time lag
Output
Output voltage EN 61131-2/part 2 24 V DC, twin terminals, adjustable +/- 2 V
Status display green LED
Output fuse 5 x 20 mm 5 x 20 mm 5 x 20 mm 5 x 20 mm 5 x 20 mm
0,7 A quick 1,25 A quick 2,5 A quick 3,15 A quick 5,0 A quick
Power 12 W 24 W 48 W 72 W 120 W
Permissible permanent current 0,5 A 1,0 A 2,0 A 3,0 A 5,0 A
Residual ripple < 2 m V RMS
Load stabilization < 0,1 %
Stability under constant conditions < 0,1 %
Ambient temperature – 10 ° C/+ 40° C
Output power reduction at 40°C and above > 1.5% / degree
Output protection circuitry varistor
General data
Test voltage between input and output circuit comp. to regulations (safety transformers)
Directives VDE 0570 part 2-6, EN 61558-2-6, EN 61000-3-2, EN 61131-2/part 2
CE-mark yes
Installation orientation any position
Type of connection screw-type terminal, finger-safe comp. to VBG4
2
Connection data fine strand max. 2,5 mm
Mounting mounting rail (DIN EN 50022), RNTG 120S has additional screw-connection,
in rows spaced > 8 mm
Protection rating comp. VDE 0470 / EN 60529 IP 20
Safety class comp. IEC 536 / VDE 0106 T1 prepared for protection class II
Insulation class E
Dimensions in mm approx. Length L 77 77 82 82 134
Width W 62,5 62,5 90 90 125
Mounting depth D 122 122 138 153 178
Article no. 225-012S 225-024S 225-048S 225-072S 225-120S
Copper weight in kg 0,12 0,36 0,6 0,97 1,18
Total weight in kg 0,9 0,95 1,9 2,6 4,3
Series RNTG-UL provides stabilized power packs showing high reliability and compact measurements. Series RNTG-UL distinctly sur-
passes power pack requirements EN 61131-2 / part 2 and guarantees safe operation without alterations even after the low voltage
networks have converted pursuant to DIN IEC 38 from the year 2003 onwards. Brief dips in line voltage are bridged up to 10 ms.
Apart from the specifications listed below, series RNTG-UL can also be supplied in secondary voltages ranging from DC 5 V to DC 30 V
and on request also with various primary voltages. However, indicated currents must not be exceeded.
Identical units can be connected in parallel up to max. 80% load per unit.
The integrated fuses (see table) exclusively deliver short circuit protection and guarantee safe operation even under worst-case con-
ditions. Units are to be loaded only with rated current as indicated.
The enclosed construction of the space-saving power packs series RNTG-UL provides comprehensive protection against accidental
contact. The power packs meet the safety requirements for protection against electric shock comp. to VDE 0106 part 101. The modu-
les can be snapped onto DIN EN 50 022 mounting rails quickly and easily. RNTG120S UL / DC 5 A shows additional provision for
screw-fastening.
Power supplies
Technical data for model RNTG 12 S UL RNTG 24 S UL RNTG 48 S UL RNTG 72 S UL RNTG 120 S UL
Input
Mains input voltage AC 230 V and AC 115 V (AC 240 V and AC 120 V)
Mains input voltage range + 10 % to – 10 %
Frequency 60 Hz
Input fuses 5 x 20 mm 5 x 20 mm 5 x 20 mm 5 x 20 mm 5 x 20 mm
0,4 A time lag 0,8 A time lag 1,25 A time lag 2,0 A time lag 3,5 A time lag
Output
Output voltage EN 61131-2/part 2 24 V DC, adjustable +/– 2 V
Status display green LED
Output fuse 5 x 20 mm 5 x 20 mm 5 x 20 mm 5 x 20 mm 5 x 20 mm
0,7 A quick 1,25 A quick 2,5 A quick 3,15 A quick 5,0 A quick
Power 12 W 24 W 48 W 72 W 120 W
Permissible permanent current 0,5 A 1,0 A 2,0 A 3,0 A 5,0 A
Residual ripple < 2 m V RMS
Load stabilization < 0,1 %
Stability under constant conditions < 0,1 %
Ambient temperature – 10 ° C/+ 40° C
Output power reduction ab 40° C > 1,5 % / Grad
Output protection circuitry varistor, inverse diode
General data
Test voltage between input and output circuit comp. to regulations
Directives UL 508, CSA 22.2 No. 14, comp. EN 61558-2-1, EN 61000-3-2, EN 61131-2/part 2
Test mark UL + CSA - File-No. E242971
CE-mark yes
Installation orientation any position
Type of connection screw-type terminal, finger-safe comp. to VBG4
2
Connection data fine strand max. 2,5 mm
Mounting mounting rail (DIN EN 50022), RNTG 120S UL shows additional
screw-connection, in rows spaced >8mm
Protection rating comp. VDE 0470 / EN 60529 IP 20
Safety class comp. IEC 536 / VDE 0106 T1 prepared for safety class II
Insulation class E
Dimensions in mm approx. Length L 77 77 82 82 134
Width W 62,5 62,5 90 90 125
Mounting depth D 122 122 138 153 178
Article no. 0285-00012SUL 0285-00024SUL 0285-00048SUL 0285-00072SUL 0285-000120SUL
Copper weight in kg 0,12 0,36 0,6 0,97 1,18
Total weight in kg 0,9 1,2 1,9 2,6 4,3
C 1/7
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 8
Technical data for model RSNT 10S RSNT 15S RSNT 5 RSNT 10 RSNT 15
Input
Mains input voltage AC 230 V or AC 400V AC 230V and AC 400V
Mains input voltage range + 15 % to – 15 %
Frequency 50 Hz/60 Hz
Input fuses 5 x 20 mm 6,3 x 32 mm external external external
AC 230V 4,0 A time lag 6,3 A time lag 4,0 Agl 4,0 Agl 6,0 Agl
AC 400V external external 2,0 Agl 2,0 Agl 4,0 Agl
Output
Output voltage DC 24 V stabilzed, twin terminals, DC 24 V stabilzed, twin terminals,
adjustable 0...DC30V adjustable 5...DC28V
Status display green / yellow LED (U / I) green LED: constant voltage / red LED: error
Adjustable output current 0...10 A 0...15 A 1...5 A 2...10 A 3...15 A
Residual ripple < 30 mV RMS < 50 mV RMS
Short-circuit proofing constant current operation constant current operation / off after 3 s.
switch back on with Reset-button
Load stabilization dynamic < 100 mVss / 500us. < 300 mVss / 500us.
Stability under constant conditions < 0,05 % < 0,1 %
Mains stabilization < 0,05 %
Overtemperature protection thermal switch-off when unit > 85°C
Suppression grade EN 55011 Klasse B
Ambient temperature -10... +40°C
General data
Transformer test voltage between input and output circuit comp. to regulations (safety transformers)
Directives VDE 0570 part 2-6, EN 61558-2-6, EN 61000-3-2, EN 61131-2/part 2
CE-mark yes
Installation orientation vertical any position
on EN 50022 rail
Type of connection screw-type terminal, finger-safe comp. to VBG4
2 2
Connection data fine strand max. 2,5 mm fine strand max. 4 mm
Mounting on mounting rail, mounting brackets
screw-fasten in addition
Protection rating comp. VDE 0470 / EN 60529 IP 20 IP 00
Safety class comp. IEC 536 / VDE 0106 T1 I
Insulation class E
Dimensions in mm approx. ( L x W x D ) 134 x 125 x 180 157 x 175 x 197 125 x 132 x 150 170 x 170 x 175 190 x 180 x 190
Mounting template in mm, approx. 87 x 120 130 x 154 x 154 84 x 71 90 x 84 104 x 97
Article no. AC 230V 0219-00000010S 0219-00000015S valid for both primary voltages
AC 400V 0319-00000010S 0319-00000015S 24-230-SNT-01 24-230-SNT-02 24-230-SNT-03
Copper weight in kg 0,75 1 ,2 0,6 1 ,2 1 ,4
Total weight in kg 5,0 9,2 5,5 6,5 7,5
Options
Remote control 0 - 10V for U / I for U / I - - for U
Remote control 4mA - 20mA for U / I for U / I - - -
Switch-off input yes yes - - yes
Signal contact "Ready" yes yes - - yes
Subject to technical modifications Standard stock items
C 1/8
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 9
In General: Within the scope of European norms limit values for harmonic currents are defined and must be adhered to in all
units: > 75 Watt and < 1000 Watt (EN 61 000-3-2). Units applied in systems possessing their own medium voltage
transformer are exempted from this norm.
All power supplies marked PFC are fitted with harmonic filters when applied within the scope of the norm. The filter
is active at mains input voltage range 184 V - 264 V.
Features: - wide input voltage range for 30 W and 60 W units, 125 W and up input 230 VAC and/or 115 VAC
30W units available in 85 up to 265VAC (type...W) or 195 up to 460VAC (type...W1)
- output voltage 12, 24 or 48 VDC, over a wide range adjustable
- connection in parallel or series
- high efficiency
- compact and robust design in metal housing, 30 W units in plastic enclosure
- easy installation on DIN mounting rail, alternative screw fastening
- safety class I
- interference emission EN 55011 class B (industry), EN 55022 class B (Telecom)
- interference immunity EN 50082-2: ESD, electromagnetic irradiation, burst, conducted interference immunity,
mains voltage dips
- excess current limiter, short-circuit protection, overvoltage limitation and overtemperature protection
Power supplies
- inrush current limiter
- status display: LED
- all power packs series RPL can be also delivered as battery chargers (type ...WL)
- power packs 30 W, 60 W and 480 W can be applied without alterations as D.C./D.C.-converters
Chart:
C 1/9
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 10
Rated current I2 (at U2 rated) 2.5A 1.25A 0.65A 2.5A 1.25A 0.65A
Protection overload, short circuit, no-load yes yes
Overcurrent limit typical 2.6A 1.3A 0.7A 2.6A 1.3A 0.7A
Short circuit current typical < 5A < 3A < 2A < 5A < 3A < 2A
Overvoltage protection yes yes
Residual ripple f=20Hz...300kHz, Ta=25°C < 10mV RMS < 10mV RMS
Mains stabilization U1 min - U1 max < 0,1 % < 0,1 %
Load stabilization load alteration < 0,5 % < 0,5 %
10% <-> 90%
Overshoot/control time load leap < 3.0% < 3ms < 3.0% < 3ms
10% <-> 90%"
Temp. stability < 0.03% / K < 0.03% / K
Operation in parallel and series yes yes
Status reports LED green LED green
DIRECTIVES
Mains harmonics limit EN 61000-3-2 not necessary not necessary
Interference emission EN 50081-1, EN 55011 class B, EN 55022 class B EN 50081-1, EN 55011 class B, EN 55022 class B
Interference immunity EN 50082-2 EN 50082-2
Safety EN 60950 class I EN 60950 class I
Test voltage input/housing - -
Test voltage input/output 3000VAC RMS 50Hz, 1min 3000VAC RMS 50Hz, 1min
Test voltage output/housing - -
Humidity 85% RH IEC 68-2-30 85% RH IEC 68-2-30
Vibration and shock ETS 300 019-2-4, class 4M5 ETS 300 019-2-4, class 4M5
CE mark yes yes
OPERATING DETAILS
Efficiency typical > 80% > 82% > 82% > 80% > 82% > 82%
Protection rating comp. VDE 0470 / EN 60529 IP 20 IP 20
Protection class comp. IEC 536, VDE 0106 T1 I I
Overtemperature protection yes yes
Ambient temperature 0°C up to +55°C -20°C up to +55°C
Storage temperature -40°C up to +85°C -40°C up to +85°C
Cooling free convection free convection
MECHANICS
Connection input voltage connector RM7,62mm to screw connector RM7,62mm to screw
3-pole 0,75-2,5mm2 (L1-N-PE) 3-pole 0,75-2,5mm2 (L1-N-PE)
for D.C./D.C.-converter: + on L1, - on N for D.C./D.C.-converter: + on L1, - on N
Connection output voltage connector RM5,08mm to screw connector RM5,08mm to screw
2-pole 0,75-2,5mm2 (+ -) 2-pole 0,75-2,5mm2 (+ -)
Housing design plastic plastic
Mounting snap-on onto mounting rail snap-on onto mounting rail
DIN EN 50022 DIN EN 50022
Installation orientation vertical vertical
Approx. dimensions (W x H x D) 40 x 80 x 85 mm 40 x 80 x 85 mm
Approx. total weight 0,14kg 0,14kg
Power supplies
Rated current I2 (at U2 rated) 5.0A 2.5A 1.25A 10A 5A 2.5A
Protection overload, short circuit, no-load yes yes
Overcurrent limit typical < 8A < 4A < 2A < 11A < 6A < 3A
Short circuit current typical < 12A < 9A < 6A < 16A < 10A < 6A
Overvoltage protection yes yes
Residual ripple f=20Hz...300kHz, Ta=25°C < 15mV RMS < 10mV RMS < 15mV RMS < 10mV RMS
Mains stabilization U1 min - U1 max < 0,15 % < 0,15 %
Load stabilization load alteration < 1,0 % < 0,5 % < 1,0 % < 0,5 %
10% <-> 90%
Overshoot/control time load leap < 3.0% < 3ms < 3.0% < 3ms
10% <-> 90%"
Temp. stability < 0.02% / K < 0.02% / K
Operation in parallel and series series operation yes. For parallel operation extern yes
series diode necessary
Statusmeldungen LED - green LED - green
Noise output zero potential change-over contact yes yes
Temperature compensation (battery charger) 2,2k⍀-NTC (f.example Siemens B57045K222K) 2,2k⍀-NTC (f.example Siemens B57045K222K)
external NTC-resistor
DIRECTIVES
Mains harmonics limit EN 61000-3-2 not necessary yes
Interference emission EN 50081-1, EN 55011 class B, EN 55022 class B EN 50081-1, EN 55011 class B, EN 55022 class B
Interference immunity EN 50082-2 EN 50082-2
Safety EN 60950 class I EN 60950 class 1
Test voltage input/housing 1500VAC RMS 50Hz, 1min 1500VAC RMS 50Hz, 1min
Test voltage input/output 3000VAC RMS 50Hz, 1min 3000VAC RMS 50Hz, 1min
Test voltage output/housing 500VDC 500VDC
Humidity 85% RH IEC 68-2-30 85% RH IEC 68-2-30
Vibration and shock ETS 300 019-2-4, class 4M5 ETS 300 019-2-4, class 4M5
CE mark yes yes
OPERATING DETAILS
Efficiency typical > 82% > 83% > 84% > 85% > 88% > 89%
Protection rating comp. VDE 0470 / EN 60529 IP 20 IP 20
Protection class comp. IEC 536, VDE 0106 T1 I I
Overtemperature protection yes yes
Ambient temperature -40°C up to +55°C -40°C up to +55°C
Storage temperature -40°C up to +85°C -40°C up to +85°C
Cooling free convection free convection
MECHANICS
Connection input voltage connector RM7,62mm to screw connector RM7,62mm to screw
3-pole 0,75-2,5mm2 (L1-N-PE) 3-pole 0,75-2,5mm2 (L1-N-PE)
for D.C./D.C.-converter: + on L1, - on N
Connection output voltage connector RM5,08mm to screw connector RM5,08mm to screw
2-pole 0,75-2,5mm2 (+ -) 2-pole 0,75-2,5mm2 (+ -)
Connection noise output connector RM5,08mm to screw connector RM5,08mm to screw
temperature compensation 5-pole 0,75-2,5mm2 (COM-NO-NC-1-2) 5-pole 0,75-2,5mm2 (COM-NO-NC-1-2)
Housing design aluminum / steel aluminum / steel
Mounting snap-on onto mounting rail snap-on onto mounting rail
DIN EN 50022 DIN EN 50022
Installation orientation vertical any position
Approx. dimensions (W x H x D) 51 x 121 x 81 mm 66 x 148 x 113 mm
Approx. total weight 0,36kg 0,84kg
Standard stock items Subject to technical modifications
C 1/11
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 12
Power supplies
Rated current I2 (at U2 rated) 20A 10A 5A 20.0A 10.0A 20.0A 10.0A
Protection overload, short circuit, no-load yes yes
Overcurrent limit typical < 22A < 11A < 6A 20.5A 11.0A 20.5A 11.0A
Short circuit current typical < 27A < 14A < 7A < 22A < 12A < 22A < 12A
Overvoltage protection yes yes
Residual ripple f=20Hz...300kHz, Ta=25°C < 15mV RMS < 10mV RMS < 60mV RMS
Mains stabilization U1 min - U1 max < 0,15 % < 0,05 %
Load stabilization load alteration < 1,0 % < 0,5 % < 0,25%
10% <-> 90%
Overshoot/control time load leap < 3.0% < 3ms < 3.0% < 3ms
10% <-> 90%"
Temp. stability < 0.02% / K < 0,02% / K
Operation in parallel and series yes yes
Status reports LED green LED green
Noise output zero potential change-over contact yes -
Temperature compensation (battery charger) 2,2k⍀-NTC -
external NTC-resistor (f. example Siemens B57045K222K)
DIRECTIVES
Mains harmonics limit EN 61000-3-2 no no not necessary
Interference emission EN 50081-1, EN 55011 class B, EN 50081-1, EN 55011 class B,
EN 55022 class B EN 55022 class B
Interference immunity EN 50082-2 EN 50082-2
Safety EN 60950 class I EN 60950 class I
Test mark / approbation - cUL - -
Test voltage input/housing 1500VAC RMS 50Hz, 1min 1500VAC RMS 50Hz, 1min
Test voltage input/output 3000VAC RMS 50Hz, 1min 3000VAC RMS 50Hz, 1min
Test voltage output/housing 500VDC 500VDC
Humidity 85% RH IEC 68-2-30 85% RH IEC 68-2-30
Vibration and shock ETS 300 019-2-4, class 4M5 ETS 300 019-2-4, class 4M5
CE mark no no not necessary
OPERATING DETAILS
Efficiency typical > 85% > 89% > 90% > 92%
Protection rating comp. VDE 0470 / EN 60529 IP 20 IP 20
Protection class comp. IEC 536, VDE 0106 T1 I I
Overtemperature protection yes yes
Ambient temperature -40°C up to +55°C 0 up to +55°C
Storage temperature -40°C up to +85°C -40°C up to +85°C
Cooling free convection free convection
MECHANICS
Connection input voltage connector RM7,62mm to screw connector RM7,62mm to screw
3-pole 0,75-2,5mm2 (L1-N-PE) 3-pole 0,75-2,5mm2 (L1-N-PE)
for D.C./D.C.-converter: + on L1, - on N
Connection output voltage connector RM5,08mm to screw connector RM7,62mm to screw
4-pole 0,75-2,5mm2 (+ -) 4-pole 0,75-4,0mm2 (+ + - -)
Connection noise output connector RM5,08mm to screw -
temperature compensation 5-pole 0,75-2,5mm2 (COM-NO-NC-1-2)
Housing design aluminum / steel aluminum / steel
Mounting snap-on onto mounting rail snap-on onto mounting rail
DIN EN 50022 DIN EN 50022
Installation orientation any position front plate horizontal, connections below
Approx. dimensions (W x H x D) 75 x 173 x 122 mm 245 x 138 x 100 mm
Approx. total weight 1,3kg 2,0kg
Standard stock items Subject to technical modifications
C 1/13
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 14
C 1/14
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 15
The battery chargers series RLG..S charge maintenance-free lead acid batteries swiftly and gently using IU characteri-
stic.
An internal electronic regulation ensures that units always work within safe operating range (SOA protection), thereby
enabling permanent operation without maintenance.
Buffer-battery system is fully guaranteed, i.e. energy can also be drawn during mains connection. The reverse current
is <=1mA during switch off condition.
Battery chargers RLG 1205S to RLG 2415S feature IUoU charging characteristic, which charges a battery with constant
current to just below gaseous voltage. Then this output voltage is maintained (see diagram) for a factory-set period of
time. At the end of this period the constant voltage is reduced to trickle voltage. An additional LED (yellow) lights up
when unit reduces the output voltage to trickle voltage thereby indicating that charging procedure is completed.
Such a characteristic charges lead acid batteries optimally, resulting in high capacity while treating the connected bat-
tery gently and preventing sulphate build-up.
The battery chargers are installed in compact plastic enclosures ensuring full protection against accidental contact.
They meet requirements VDE 0106 part 101 for protection against electric shock.
The enclosure is designed for quick and simple mounting on DIN EN 50022 mounting rails.
battery chargers
IUoU charging characteristic
IU charging characteristic
yellow
C 1/15
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 16
Technical data for model RLG 1203S RLG 1205S RLG 1208S RLG 1210S RLG 1215S
RLG 2403S RLG 2405S - RLG 2410S RLG 2415S
Input
Mains input voltage AC 230 V or AC 400V
Mains input voltage range + 10 % up to – 10 % comp. to IEC 38 +- 15%
Frequency 50 Hz/60 Hz
Input fuses 5 x 20 mm 5 x 20 mm 5 x 20 mm 5 x 20 mm 6,3 x 32 mm
AC 230V / DC 12V 0,80 A time lag 1,25 A time lag 2,0 A time lag 2,0 A time lag 4,0 A time lag
AC 230V / DC 24V 1,25 A time lag 2,50 A time lag - 4,0 A time lag 6,3 A time lag
AC 400V / DC 12V external external external external external
AC 400V / DC 24V external external - external external
Output
Rated battery voltage DC 12 V DC 12 V DC 12 V DC 12 V DC 12 V
DC 24 V DC 24 V - DC 24 V DC 24 V
Max. charge current DC 3 A DC 5 A DC 8 A DC 10 A DC 15 A
Battery type lead acid batteries
Status display twin-colour LED red: charging red: charging yellow: constant current
green: I < 10%IN green: I < 10%IN green: constant voltage
yellow LED - maintaining charge maintaining charge
Residual ripple of charge voltage < 0,5%
Charging characteristic IU IUoU; preset time 4 h
Overload protection internal electronic current limiter
Reverse current when mains off, I = < 1 mA
Reverse polarity protection integrated (reverse polarity current < 1 mA)
battery chargers
In General: Within the scope of European norms limit values for harmonic currents are defined and must be adhered to in all
units: > 75 Watt and < 1000 Watt (EN 61 000-3-2). Units applied in systems possessing their own medium voltage
transformer are exempted from this norm.
All battery chargers marked PFC are fitted with harmonic filters when applied within the scope of the norm. The filter
is active at mains input voltage range 184 V - 264 V.
Features: - wide input voltage range for 30 W and 60 W units, 125 W and up input 230 VAC and/or 115 VAC
30W units available in 85 up to 265VAC (type...WL) or 195 up to 460VAC (type...W1L)
- output voltage 13,7, 27,4 or 54,8 VDC, over a wide range adjustable
- connection in parallel or series
- high efficiency
- compact and robust design in metal housing, 30 W units in plastic enclosure
- easy installation on DIN mounting rail, alternative screw fastening
- safety class I
- interference emission EN 55011 class B (industry), EN 55022 class B (Telecom)
- interference immunity EN 50082-2: ESD, electromagnetic irradiation, burst, conducted interference immunity,
mains voltage dips
- excess current limiter, short-circuit protection, overvoltage limitation and overtemperature protection
- inrush current limiter
- status display: LED
- all battery chargers series RPL can be also delivered as power supplies (type ...W)
- battery chargers 30 W, 60 W and 480 W can be applied without alterations as D.C./D.C.-converters
battery chargers
Chart:
C 1/17
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 18
battery chargers
Load stabilization load alteration < 1,0 % < 0,5 % < 1,0 % < 0,5 %
10% <-> 90%
Overshoot/control time load leap < 3.0% < 3ms < 3.0% < 3ms
10% <-> 90%"
Temp. stability < 0.02% / K < 0.02% / K
Operation in parallel and series series operation yes. For parallel operation extern yes
series diode necessary
Statusmeldungen LED - green LED - green
Noise output zero potential change-over contact yes yes
Temperature compensation (battery charger) 2,2k⍀-NTC (f. example Siemens B57045K222K) 2,2k⍀-NTC (f. example Siemens B57045K222K)
external NTC-resistor
DIRECTIVES
Mains harmonics limit EN 61000-3-2 not necessary yes
Interference emission EN 50081-1, EN 55011 class B, EN 55022 class B EN 50081-1, EN 55011 class B, EN 55022 class B
Interference immunity EN 50082-2 EN 50082-2
Safety EN 60950 class I EN 60950 class 1
Test voltage input/housing 1500VAC RMS 50Hz, 1min 1500VAC RMS 50Hz, 1min
Test voltage input/output 3000VAC RMS 50Hz, 1min 3000VAC RMS 50Hz, 1min
Test voltage output/housing 500VDC 500VDC
Humidity 85% RH IEC 68-2-30 85% RH IEC 68-2-30
Vibration and shock ETS 300 019-2-4, class 4M5 ETS 300 019-2-4, class 4M5
CE mark yes yes
OPERATING DETAILS
Efficiency typical > 82% > 83% > 84% > 85% > 88% > 89%
Protection rating comp. VDE 0470 / EN 60529 IP 20 IP 20
Protection class comp. IEC 536, VDE 0106 T1 I I
Overtemperature protection yes yes
Ambient temperature -40°C up to +55°C -40°C up to +55°C
Storage temperature -40°C up to +85°C -40°C up to +85°C
Cooling free convection free convection
MECHANICS
Connection input voltage connector RM7,62mm to screw connector RM7,62mm to screw
3-pole 0,75-2,5mm2 (L1-N-PE) 3-pole 0,75-2,5mm2 (L1-N-PE)
for D.C./D.C.-converter: + on L1, - on N
Connection output voltage connector RM5,08mm to screw connector RM5,08mm to screw
2-pole 0,75-2,5mm2 (+ -) 2-pole 0,75-2,5mm2 (+ -)
Connection noise output connector RM5,08mm to screw connector RM5,08mm to screw
temperature compensation 5-pole 0,75-2,5mm2 (COM-NO-NC-1-2) 5-pole 0,75-2,5mm2 (COM-NO-NC-1-2)
Housing design aluminum / steel aluminum / steel
Mounting snap-on onto mounting rail snap-on onto mounting rail
DIN EN 50022 DIN EN 50022
Installation orientation vertical any position
Approx. dimensions (W x H x D) 51 x 121 x 81 mm 66 x 148 x 113 mm
Approx. total weight 0,36kg 0,84kg
Standard stock items Subject to technical modifications
C 1/19
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 20
Load stabilization load alteration < 1,0 % < 0,5 % < 0,25 %
10% <-> 90%
Overshoot/control time load leap < 3.0% < 3ms < 3.0% < 3ms
10% <-> 90%"
Temp. stability < 0.02% / K < 0.02% / K
Operation in parallel and series yes yes
Status reports LED green LED green
Noise output zero potential change-over contact yes no
Temperature compensation (battery charger) 2,2k⍀-NTC (f. example Siemens B57045K222K) -
external NTC-resistor
DIRECTIVES
Mains harmonics limit EN 61000-3-2 yes yes
Interference emission EN 50081-1, EN 55011 class B, EN 55022 class B EN 50081-1, EN 55011 class B, EN 55022 class B
Interference immunity EN 50082-2 EN 50082-2
Safety EN 60950 class I EN 60950 class I
Test voltage input/housing 1500VAC RMS 50Hz, 1min 1500VAC RMS 50Hz, 1min
Test voltage input/output 3000VAC RMS 50Hz, 1min 3000VAC RMS 50Hz, 1min
Test voltage output/housing 500VDC 500VDC
Humidity 85% RH IEC 68-2-30 85% RH IEC 68-2-30
Vibration and shock ETS 300 019-2-4, class 4M5 ETS 300 019-2-4, class 4M5
CE mark yes yes
OPERATING DETAILS
Efficiency typical > 85% > 89% > 90% > 92%
Protection rating comp. VDE 0470 / EN 60529 IP 20 IP 20
Protection class comp. IEC 536, VDE 0106 T1 I I
Overtemperature protection yes yes
Ambient temperature -40°C up to +55°C 0°C up to +55°C
Storage temperature -40°C up to +85°C -40°C up to +85°C
Cooling free convection free convection
MECHANICS
Connection input voltage connector RM7,62mm to screw connector RM7,62mm to screw
3-pole 0,75-2,5mm2 (L1-N-PE) 3-pole 0,75-2,5mm2 (L1-N-PE)
for D.C./D.C.-converter: + on L1, - on N
Connection output voltage connector RM5,08mm to screw connector RM5,08mm to screw
4-pole 0,75-2,5mm2 (++ --) 4-pole 0,75-4,0mm2 (++ --)
Connection noise output connector RM5,08mm to screw -
temperature compensation 5-pole 0,75-2,5mm2 (COM-NO-NC-1-2)
Housing design aluminum / steel aluminum / steel
Mounting snap-on onto mounting rail snap-on onto mounting rail
DIN EN 50022 DIN EN 50022
Installation orientation any position front plate horizontal, connections below
Approx. dimensions (W x H x D) 75 x 173 x 122 mm 245 x 138 x 100 mm
Approx. total weight 1,5kg 2,4kg
battery chargers
Load stabilization load alteration < 1,0 % < 0,5 % < 0,25%
10% <-> 90%
Overshoot/control time load leap < 3.0% < 3ms < 3.0% < 3ms
10% <-> 90%"
Temp. stability < 0.02% / K < 0,02% / K
Operation in parallel and series yes yes
Status reports LED green LED green
Noise output zero potential change-over contact yes -
Temperature compensation (battery charger) 2,2k⍀-NTC -
external NTC-resistor (f. example Siemens B57045K222K)
DIRECTIVES
Mains harmonics limit EN 61000-3-2 no no not necessary
Interference emission EN 50081-1, EN 55011 class B, EN 50081-1, EN 55011 class B,
EN 55022 class B EN 55022 class B
Interference immunity EN 50082-2 EN 50082-2
Safety EN 60950 class I EN 60950 class I
Test mark / approbation - cUL - -
Test voltage input/housing 1500VAC RMS 50Hz, 1min 1500VAC RMS 50Hz, 1min
Test voltage input/output 3000VAC RMS 50Hz, 1min 3000VAC RMS 50Hz, 1min
Test voltage output/housing 500VDC 500VDC
Humidity 85% RH IEC 68-2-30 85% RH IEC 68-2-30
Vibration and shock ETS 300 019-2-4, class 4M5 ETS 300 019-2-4, class 4M5
CE mark no no not necessary
OPERATING DETAILS
Efficiency typical > 85% > 89% > 90% > 92%
Protection rating comp. VDE 0470 / EN 60529 IP 20 IP 20
Protection class comp. IEC 536, VDE 0106 T1 I I
Overtemperature protection yes yes
Ambient temperature -40°C up to +55°C 0 up to +55°C
Storage temperature -40°C up to +85°C -40°C up to +85°C
Cooling free convection free convection
MECHANICS
Connection input voltage connector RM7,62mm to screw connector RM7,62mm to screw
3-pole 0,75-2,5mm2 (L1-N-PE) 3-pole 0,75-2,5mm2 (L1-N-PE)
for D.C./D.C.-converter: + on L1, - on N
Connection output voltage connector RM5,08mm to screw connector RM7,62mm to screw
4-pole 0,75-2,5mm2 (+ -) 4-pole 0,75-4,0mm2 (+ + - -)
Connection noise output connector RM5,08mm to screw -
temperature compensation 5-pole 0,75-2,5mm2 (COM-NO-NC-1-2)
Housing design aluminum / steel aluminum / steel
Mounting snap-on onto mounting rail snap-on onto mounting rail
DIN EN 50022 DIN EN 50022
Installation orientation any position front plate horizontal, connections below
Approx. dimensions (W x H x D) 75 x 173 x 122 mm 245 x 138 x 100 mm
Approx. total weight 1,5kg 2,0kg
Lagertypen Technische Änderungen vorbehalten
C 1/21
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 22
The battery chargers series RLEC apply the ECS charging system which, in conjunction with our patented switching
concept, is considered the optimum charging method available at present. All stock items are adjusted to NiCd-accumu-
lators. Internal programming on manufacturer´s part permits both maintenance-free lead acid and NiCd storage batte-
ries as well as open Pb-batteries to be charged 100% without prior discharging.
The ECS charging system adapts itself perfectly to the individual nature of the battery to be charged, so any exemplary
leakage or the history of the battery become irrelevant. The battery itself controls the charging process, because the
momentary state of the battery is measured continually and charging is controlled according to these measured va-
lues. This way the battery always draws the exact amount of energy it is able to store at the moment. This results in high
efficiency without causing any damaging heat to the cells. Moreover charging time is reduced considerably as the
charging process constantly adapts to the amount of energy the battery can absorb.
The battery's number of charging cycles is increased significantly which in turn increases battery's service life consider-
ably.
Even older batteries can be regenerated with the ECS charging method as the charging pulses format the individual
cells and remove sulfating, minimizing the memory effect.
Precise determination of the end of charging process prevents short-time overcharging of battery. That way repeated
attempts to recharge full batteries are detected and do not lead to detrimental overcharging. When the charging pro-
cess has been completed the charger continues to take care of the battery, monitoring it continuously and providing
the ideal float charge. The battery is always ready for use.
Buffer-battery system is fully guaranteed, i.e. energy can also be drawn during mains connection. The reverse current
is <=1mA during switch off.
battery chargers
Battery with
Akkua Nennkapazität
rated capacity of 1000 mAh
1000mAh
1000
980
900
800
770
700
600
620
(mAh)
500
500
400
300
200
100
0
before
vorher 1 2 3
yellow green
Cell temperature
charge voltage (V)
Temperature
at dU/dt
switch-off
Float charge
charge current (A)
battery chargers
Current pulse
Float charge
Measuring
Series RLEC...S
As an optional extra, the battery chargers can be equipped with a centralized alarm via zero potential contact (contact is closed
during battery charging).
On request the chargers can also be provided for different cell quantities
(Pb max. 12 cells, NiCd max. 20 cells)
The battery chargers come in a compact plastic housing that provides comprehensive protection against accidental contact and
meets safety requirements for protection against electric shock comp. to VDE 0106 part 101.
The housing is designed for snap-on attachment to DIN EN 50022 rails for easy mounting.
Series RLEC
The battery chargers are fitted into a robust plastic-coated steel housing.
C 1/23
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 24
Technical data for model RLEC 2403S RLEC 2405S RLEC 2410S
Input
Mains input voltage AC 230V or AC 400V
Mains input voltage range + 10 % to - 10 % comp. to DIN IEC 38
Frequency 50Hz / 60Hz
Input fuses 5 x 20 mm 5 x 20 mm 5 x 20 mm
AC 230V 1,25 A time lag 2,5 A time lag 4,0 A time lag
AC 400V external external external
Output
Battery rated voltage DC 24 V DC 24 V DC 24 V
Max. charge current DC 3 A DC 5 A DC 10 A
battery chargers
Battery type NiCd batteries (factory internal programming for Pb-batteries possible)
Status display two-color LED yellow: charging / green: charged
red LED trouble (battery defective or outside tolerance range)
Charging characteristic ECS method in conjunction with patented switching concept
Temperature control during charging charge dependent on battery temperature
Overload protection via internal electronic current limiter
Reverse current when mains off, I =< 1mA
Reverse polarity protection integrated (reverse polarity current < 1mA)
Overtemperature protection automatic cut-off if battery or electronics overheats
RFI suppression better than EN 55011 class B
Temperature range 0° C to + 40° C
General data
Transformer test voltage between input and output comp. to regulation (safety transformer)
Directives VDE 0570 part 2-6, EN 61558-2-6, EN 61131-2/part 2
CE-mark yes
Installation orientation vertical
Cooling convection
Type of connection PC terminals
Connection data fine strand max. 2,5mm2
Mounting on DIN EN 50022 mounting rail, spacing > 8mm
Protection rating comp. VDE 0470 IP 20
Protection class comp. VDE 0106 T1 prepared for protection class II
Insulation class E
Dimensions in mm approx.
(Length/Width/Depth) 82 x 90 x 153 134 x 125 x 175 134 x 125 x 175
Mounting template in mm, approx. - 87 x 120 87 x 120
Article no. AC 230 V 0239-0002403S 0239-0002405S 0239-0002410S
AC 400 V 0240-0002403S 0240-0002405S 0240-0002410S
Copper weight in kg 0,97 1,18 1,18
Weight in kg 2,5 4,3 4,5
Technical data for model RLEC 1220 RLEC 2420 RLEC 1240 RLEC 2440
Input
Mains input voltage AC 230V
Mains input voltage range + 10 % to - 10 % comp. to DIN IEC 38
Frequency 50Hz / 60Hz
Input fuses 230V ETA 3 A ETA 5 A ETA 5 A ETA 8 A
Output
battery chargers
Battery rated voltage DC 12V DC 24V DC 12V DC 24V
Max. charge current 20ADC 20ADC 40ADC 40ADC
Battery type lead acid or NiCd batteries (battery type can be programmed internally)
Status display green charged
LEDs yellow charging
red trouble (battery defective or outside temperature range)
Charging characteristic ECS method in conjunction with patented switching concept
Temperature control during charging charge dependent on battery temperature
Overload protection via internal electronic current limiter
Reverse current when mains off, I =< 1mA
Reverse polarity protection integrated (reverse polarity current < 1mA)
Overtemperature protection automatic cut-off if battery or electronics overheat
RFI suppression better than EN 55011 class B
Temperature range 0° C to + 40° C
Efficiency 90 %
General data
Transformer test voltage between input and output comp. to regulation (safety transformers)
Directives VDE 0570 part 2-6, EN 61558-2-6, EN 61131-2/part 2
CE-mark yes
Installation orientation any position
Cooling convection forced air
Type of connection terminal blocks (protected against finger touch comp. to VBG 4)
Connection data fine strand fine strand
primary max. 4 mm2 primary max. 4 mm2
secondary max. 10 mm2 secondary max. 16 mm2
Mounting integrated mounting brackets
Protection rating comp. VDE 0470 IP 20
Protection class comp. VDE 0106 T1 I
Insulation class E
Dimensions in mm approx.
(Length / Width / Height) 210 / 225 / 190 195 / 315 / 175 195 / 315 / 175 240 / 350 / 195
Mounting template in mm, approx. 200 / 115 290 / 125 290 / 125 330 / 140
Article no. Pri. 230V 0237-230-012-01 0237-230-024-02 0237-230-012-03 0237-230-024-04
Pri. 400V 0238-400-012-01 0238-400-024-02 0238-400-012-03 0238-400-024-04
Copper weight in kg 1,03 1,68 1,68 2,50
Weight in kg 8,00 15,00 15,00 18,00
C 1/25
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 26
Product description
RALG 240G car battery charger is an individual development for motorcar application. It is a universal automatic char-
ger for 12V, 24V and 42V batteries with a maximal charging power of 240 Watt.
Its integrated intelligence recognizes the battery´s voltage level and adjusts to optimal charging characteristic acc. to
ECS-method.
Essential features:
- Fast and gentle battery charging
- Optimized charging process, optimized charging current
- Avoids overcharge via float charge
- Reverse polarity protection
- Automatic ON/OFF, i.e. minimizes sparking / fire hazards or damage to
battery poles
- Extensive protection mechanisms, such as overtemperature switch-off,
undervoltage switch-off, reference control and comparison setpoint and
actual values
- Other designs available, for example as wall- or base frame unit
Technical data for model RALG 240
Input
Mains input voltage AC 230V
battery chargers
DC - UPS modules
RDCUSV 3S to RDCUSV 50S
Product description
We are faced daily with trouble in our mains supply systems which can add up to 10% of total operation time. Fluctua-
tions and voltage dips occur, occasionally even total power failures, for example caused by strokes of lightning or faulty
maintenance. A suitable UPS-system (Uninterruptible Power Supply) provides protection against such faults.
According to EN 61131-2 / part 2 (limit values for rated D.C. voltage at DC 24 V) the currently valid operational voltage for
electronic controls is DC 24V (DC 20.4V - DC 28.8V RMS). Power packs have to be designed accordingly.
In connection with our D.C. power supplies we produce DC UPS modules for such cases. They can be connected easi-
ly secondary in parallel, thereby providing reliable protection for your control units.
The patented technology of our UPS modules make switching controllers such as boost choppers unnecessary. EMC
problems therefore do not occur.
All Riedel-UPS modules, inclusive battery, are fitted into compact housings and easy to mount.
The DC UPS modules can be snapped onto mounting rails according to DIN EN 50022. The module is available in ver-
sions 24 VDC 3A 30s, 24 VDC 10A 30s, 24 VDC 20A 30s and 24 VDC 40A 30s. Other types are available on request.
For application the module is to be connected in parallel to the D.C. voltage output of a DC 24V power pack (see sche-
matic diagram) and the "OFF" terminal is connected to the minus terminal.
When switching off this "OFF"-contact must be opened via the auxiliary contact of the main switch, so that the UPS-module
is deactivated!
UPS
The module's electronics monitors the output voltage and switches the battery on when previously set threshold value
(22VDC) is not reached. The internal battery serves as supply source for the power consumer over a defined period
(up to 30 seconds) providing a maximum current of 3A, 10A, 20A or 40A which is limited internally. The output voltage is
stabilized to a threshold value of 22 VDC (see diagram).
LEDs provide a visual indicator, signaling Ready (green), UPS-operation (yellow) and battery undervoltage (red). A zero
potential contact opens when UPS-operation begins, so signaling a mains power failure.
For control of the UPS module an input terminal is provided, which must be connected to the minus-terminal to activate the
module.
For non-stabilized D.C. supplies we offer a more reasonable version of DC UPS modules, featuring an activation thres-
hold voltage of 20.6VDC. At 20.6VDC the output voltage of the module is still within limit values for D.C. voltage of
24VDC comp. to EN 61131-2 / part 2 in the event of UPS activation.
The standard product range can be extended to include custom designs.
C 1/27
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 28
DC - UPS modules
RDCUSV 3S to RDCUSV 50S
Function - In the event of mains failure, stabilized output voltage (22 VDC resp. 20.6 VDC)
- Short circuit proof
- Automatic cut-off in the event of:
• overtemperature
• low battery voltage (17 VDC)
- Automatic charging
• IU characteristic
Back-up times
RDCUSV 3S RDCUSV 10S / 16S RDCUSV 20S /30S RDCUSV 40S / 50S
6 min 2,8 A 8,0 A 21,0 A 22,0 A
10 min 1,9 A 5,9 A 16,0 A 17,0 A
30 min 0,8 A 2,3 A 6,0 A 7,0 A
60 min 0,5 A 1,8 A 3,8 A 4,2 A
120 min 0,3 A 0,75 A 2,0 A 2,6 A
UPS
Top view
Discharge time in min
Discharge current in A
DC - UPS modules
RDCUSV 3S to RDCUSV 50S
RDCUSV 3S RDCUSV 10S, RDCUSV 16S RDCUSV 20S, RDCUSV 30S RDCUSV 40S, RDCUSV 50S
UPS
Protection rating comp. VDE 0470 IP 20
Protection class comp. VDE 0106 T1 SELV
Weight in kg approx. 0,9 approx. 3,5 approx. 4,4 approx. 6,5
Article no. 22,0 V 0250-0000003S 0250-0000010S 0250-0000020S 0250-0000040S
Dimensions in mm (L/W/H) 82 / 90 / 120 134 / 125 / 150 157 / 175 / 185 200 / 180 / 185
C 1/29
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 30
DC - UPS module
RIPCUSV 5S supply for industrial PCs (IPC)
Product description:
RIPCUSV 5S complements series RDCUSV. RIPCUSV-modules are equipped with a serial interface, which, connected to a 24VDC
supplied industrial-PC (IPC) and the operation system Microsoft Windows NT/2000/XP, enables setup of a computer controlled non-
interruptible power supply. Communication between UPS and IPC takes place via interface, i.e. the IPC receives a signal after UPS-ti-
me limit has been reached. The IPC then closes the system. As soon as the computer has shut down the UPS receives a report and in
turn shuts off the computer's supply voltage.
The patented method of DC-UPS-modules makes any application of switching controllers, for example boost choppers, unnecessa-
ry. EMC-problems do not occur.
All Riedel IPC-UPS-modules are installed together with the accumulator in compact housings and are easy to assemble. IPC-UPS-
modules are snapped onto supporting rails according to DIN EN 50022. For operation connect them to the DC-output of the DC 24V-
power supply (see block diagram) and connect terminal "AUS / OFF" with the minus-terminal.
The module's electronics guards the output voltage and switches on the accumulator when pre-adjusted threshold (20,6VDC) falls
short. The internal accumulator serves as supply source to the consumer for a defined time range with 5A maximal current, which is li-
mited internally. The output voltage will be controlled to threshold value (20,6VDC). For visual control LEDs signal readiness (green),
UPS-operation (yellow) and accumulator undervoltage (red).
Construction: - Plastic housing for snap-on assembly (DIN EN 50022)
- Unit status display via LED on front side
• Ready: LED green - UPS can deliver current
• Operation: LED yellow - accu delivers current
• Accu is charging: LED red - undervoltage accu
- Opening for UPS switch-on via screw-terminal
For switch-on connect terminal "AUS / OFF" with minus-terminal
Function: - During power-line failure stabilized output voltage ( 20,6 VDC)
- Boot time bridging adjustable (2-3-4-5min)
- Adjustable UPS-time (0,5 up to 30s), after that signal to IPC via interface
- UPS switch-off via signal from computer;
automatic switch-off after adjustable waiting period (4-6-8-10min)
- Short circuit proof
- Automatic switch-off at:
• · Undervoltage accu (17 VDC)
- Automatic charge
• · IU-characteristic
UPS
Accu-packs
Series RAP in 2Ah, 5Ah, 7Ah
In general:
The compact and space-saving industrial design of the enclosed accu-packs series RAP
provides comprehensive protection against accidental contact. The units snap easily on-
to DIN EN 50022 mounting rails and can be fixated additionally with screws. Units of the
same type can be switched in parallel or in series.
Riedel-accu-packs contain valve compatible, maintenance free industrial lead acid batte-
ries showing high current delivery which originally had been specially developed for appli-
cation in danger report systems, emergency lighting, medicine, alarms, non-interruptible po-
wer supplies and Telecom-systems.
The accu-packs can be fitted in any position except upside down. Do not operate these
units in upside down position.
Input and output are protected with flat-plug fuses readily available all over the world.
Power supplies
with back-up battery
RADA 4730 - RADA 4990
Features:
- 12VDC and 24VDC - Small size
- Safe design - EMC EN55022B
- Temperature controlled - Total discharge protection
- Signal power line failure - Mains connection via clamp terminal or screw terminal
- 15A output switch - Optional sabotage switch against undue opening of housing
Article numbers:
RADA 4730 = 0260-00004730 RADA 4980 = 0260-00004980 RADA 4990 = 0260-00004990
RADA 4740 = 0260-00004740 RADA 4570 = 0260-00004570
Technical data
INPUT
Input range 184...264 VAC
Frequency 45...65Hz
Efficiency (Uin = 230 VAC, 100% load) 12V 24V 48V
RADA 4730 85% RADA 4740 87% RADA 4570 87%
RADA 4980 88% RADA 4990 89%
Protection EN 60950 class 1
Insulation input / grounding 1500 VAC RMS 50Hz, 1min
input / output 3000 VAC RMS 50Hz, 1min
output / grounding 500 VDC
EMC EN 55022 class B
Inrush current limited via 7R NTC-resistor
Overvoltages protected via 275V 72J VDR-resistor
Input fuse RADA 4830 and RADA 4570 T6.3A, all others T4A
CE-mark yes
OUTPUT 12V 24V 48V
Charge voltage (50% load) 13.7 V 27.3 V 54.6 V
Output adjustment (select) 11...15 V 23...29 V 45…58VDC
Minimum voltage (total discharge protection) 10V±0.3V 20V±0.5V 40V±0.5V
Ripple voltage (f = 20Hz...300kHz, Tamb = 25°C) < 15mVrms < 15mVrms < 15mVrms
Load stabilization (Iout = 10...100%) ±1.5 % ±1 % ±0.5 %
Mains stabilization (Uinmin...Uinmax) ±0.1 % ±0.1 % ±0.1 %
Output current, charger 10 A 5 A (4740), 10A (4980) 2.5A (4570), 5A (4990)
Current limiting, charger < 11 A < 6 A (4740), < 11A (4980) < 3 A (4570), < 6A (4990)
Short circuit limitation, charger and battery Fuse 15A
OUTPUT 12V 24V 48V
Others
Battery capacity 14Ah 7Ah 2Ah
Battery type / Yuasa NP 7-12 7Ah 12V NP 7-12 7Ah 12V NP 2-12 2Ah 12V
UPS-time (approx. values) 10A / 45min, 2A / 5h 5A / 45min, 1A / 5 h 2A / 25 min, 0.5A / 2.5 h
Temperature compensation for battery 2k2 NTC-resistor
Total discharge protection for battery trigger at 10V trigger at 20V trigger at 40V
DISPLAYS AND ALARM REPORTS
Charger output OK green LED is on
Power line failure zero potential opening and closing relay contact, relay 24VDC/0.3A or 30VAC/0.5A
Sabotage switch against undue opening of housing microswitch, opening and closing contact
MECHANICS
Measurements RADA 4740, 4980, 4990 wall / 188 x 317 x 110mm
RADA 4730, 4570 wall / 188 x 277 x 110mm
Installation wall / screw connection
Weight without batteries <3kg (with batteries 12V/8kg, 24V/8kg, 48V/5kg)
Shutting of door with tool (screw driver)
Enclosure steel housing IP21
OPERATING CONDITIONS
Operating temperature -40°C...+55°C without batteries (-20°C...+45°C with standard batteries)
Humidity 85% RH IEC68-2-30
Cooling convection
CONNECTIONS
Input RADA 4740, RADA 4980, RADA 4990 2,5mm2 3-pole screw terminal (L-N-PE)
RADA 4730, RADA 4570 6mm2 3-pole screw terminal (L-N-PE)
All types cable inlet on top, incl. 1,5 m line cable
Output RADA 4740, 4980, 4990 2,5mm2 9-pole screw terminal (++, - -, alarm, battery)
2,5mm2 2-pole screw terminal (door alarm)
RADA 4730, 4570 6mm2 8-pole screw terminal (+, -, alarm, door alarm)
All types cable inlet on top
C 1/31
C_TEIL_041018.qxd 19.10.2004 10:32 Seite 32
Application example:
Protection against total
discharge
Power
RLG 2405 RCV
consumer
3x 380/400/420 V 3x 380/400/420 V
Copper Total
Model Current 24 VDC 24 VDC Approx. dimensions in mm
weight weight
without capacitor with capacitor
A DC Article-no. Article-no. kg kg a b c d e f Attachment
RDRK 2,5 2,5 21–400–024–0 1 21–400–024–K0 1 0,70 2,50 130 75 160 84 46 45 M 5
RDRK 5 5 21–400–024–0 2 21–400–024–K02 0,80 3,00 130 85 165 84 56 45 M 5
RDRK 7,5 7,5 21–400–024–03 21–400–024–K03 1,20 4,40 155 70 195 90 55 55 M 5
RDRK 1 0 10 21–400–024–04 21–400–024–K04 1,40 6,00 155 85 195 90 70 55 M 5
RDRK 1 6 16 21–400–024–05 21–400–024–K05 2,30 7,00 190 170 165 128 72 60 M 6
RDRK 20 20 21–400–024–06 21–400–024–K06 2,50 8,40 190 180 165 128 82 60 M 6
RDRK 25 25 21–400–024–07 21–400–024–K07 3,00 1 1 ,30 190 190 165 128 92 70 M 6
RDRK 30 30 21–400–024–08 21–400–024–K08 4,00 1 1 ,40 190 190 165 128 92 70 M 6
RDRK 40 40 21–400–024–09 21–400–024–K09 4,80 17,10 230 190 210 176 71 - M 6
RDRK 60 60 21–400–024–1 0 21–400–024–K1 0 5,00 21,00 290 200 240 190 120 85 M 10
Subject to technical modifications Standard stock items
D 1/2
D_TEIL_041018.qxd 19.10.2004 10:33 Seite 3
Three-phase
compact rectifier transformers
Safety transformers comp. VDE 0570 part 2-6, EN 61558-2-6
RDRKL 10 – 120
Power packs
Design: Open horizontal design, stationary, for installation and set-up in dry rooms, separate
windings, sturdy mounting brackets. All connections to non-tracking terminal
blocks with screw connections. The terminals are protected against finger touch or
contact with the back of the hand in compliance to accident prevention regulations
(VBG 4).
IP 00, suitable for installation up to protection rating IP 23, insulation class E, max.
ambient temperature ta40°C, color grey, heat sink black anodized.
Capacitor versions show a slight diversion from stated measurements but attach-
ments remain the same.
Further designs available on request (fuses, voltages, connections, etc.)
D 1/3
D_TEIL_041018.qxd 19.10.2004 10:33 Seite 4
Three-phase-universal-
compact-rectifier transformers
Safety transformers comp. VDE 0570 part 2-6, EN 61558-2-6
RDRKU 5 – 25
A DC Article-no. kg kg a b c d e Attachment
RDRKU 5 5 3 UI 75/26 22–400–U–0 1 1 ,5 4,9 200 90 195 130 57 M6
RDRKU 1 0 10 3 UI 75/41 22–400–U–02 2,0 7,0 200 115 195 130 72 M6
RDRKU 1 5 15 3 UI 90/41 22–400–U–03 3,0 8,0 230 175 195 170 68 M6
RDRKU 20 20 3 UI 90/51 22–400–U–04 3,5 11,5 230 195 195 170 78 M6
RDRKU 25 25 3 UI 90/51 22–400–U–05 4,0 12,0 230 195 195 170 78 M6
Three-phase
compact rectifier transformers
Safety transformers comp. VDE 0570 part 2-6, EN 61558-2-6
RDRKN 10 – 60
Power packs
short-time duty, mounting brackets comp. to DIN 41307, attachment dimen-
sions comp. to DIN 41308.
Standard version:
3⳯380/400/420 V Copper Total
Model Current Approx. dimensions in mm
24 V DC weight weight
ADC Article-no. kg kg a b c d e Attachment
RDRKN 1 0 10 28–400–024–0 1 1,6 4,9 156 165 110 140 100 M5
RDRKN 1 6 16 28–400–024–02 1,9 6,5 156 165 125 140 100 M5
RDRKN 20 20 28–400–024–03 2,4 9,8 206 190 140 184 120 M6
RDRKN 25 25 28–400–024–04 3,2 10,7 206 200 160 184 120 M6
RDRKN 30 30 28–400–024–05 3,9 1 1 ,5 206 200 160 184 120 M6
RDRKN 40 40 28–400–024–06 6,0 17,0 254 235 155 228 152 M6
RDRKN 60 60 28–400–024–07 6,9 22,0 254 235 180 228 152 M6
Capacitor version:
3⳯380/400/420 V Copper Total
Model Current Approx. dimensions in mm
24 V DC weight weight
ADC Article-no. kg kg a b c d e Attachment
RDRKN 1 0 K 10 28–400–024–K 0 1 1,6 4,9 156 165 110 140 100 M5
RDRKN 1 6 K 16 28–400–024–K 02 1,9 6,5 156 165 125 140 100 M5
RDRKN 20 K 20 28–400–024–K 03 2,4 9,8 206 190 140 184 120 M6
RDRKN 25 K 25 28–400–024–K 04 3,2 10,7 206 200 160 184 120 M6
RDRKN 30 K 30 28–400–024–K 05 3,9 1 1 ,5 206 200 160 184 120 M6
RDRKN 40 K 40 28–400–024–K 06 6,0 17,0 254 235 155 228 152 M6
RDRKN 60 K 60 28–400–024–K 07 6,9 22,0 254 235 180 228 152 M6
D 1/5
D_TEIL_041018.qxd 19.10.2004 10:33 Seite 6
Three-phase
compact rectifier transformers
Safety transformers comp. VDE 0570 part 2-6, EN 61558-2-6
RDRKS 7,5 – 30
Three-phase
compact rectifier transformers
Safety transformers comp. VDE 0570 part 2-6, EN 61558-2-6
RDRKS 7,5 – 30
In general: Series RDRKS in modern industrial design, meets national, international and
upcoming regulations. It was designed bearing following aspects in mind:
Design: Covered, stationary, for installation and set-up in dry rooms, separate win-
dings, open-ended mounting slot integrated in cover. Connection to non-
tracking transformer terminals with screw connection. Terminals are protected
against finger touch or contact with the back of the hand in compliance to acci-
Power packs
dent prevention regulations (VBG 4).
Standard version:
3 x 380/400/420 V 3 x 380/400/420 V
Model Current Approx. dimensions in mm
24 V DC 24 V DC
ADC Article no. Article no. (K) a b c d e f Attachment
RDRKS 7,5 (K) 7,5 0256-400-24-0 1 0257-400-24-K01 125 105 200 90 90 165 M5
RDRKS 10 (K) 10 0256-400-24-02 0257-400-24-K02 125 105 200 90 90 165 M5
RDRKS 15 (K) 15 0256-400-24-03 0257-400-24-K03 125 130 200 90 115 165 M5
RDRKS 20 (K) 20 0256-400-24-04 0257-400-24-K04 190 130 200 150 115 165 M6
RDRKS 30 (K) 30 0256-400-24-05 0257-400-24-K05 190 165 200 150 135 165 M6
D 1/7
D_TEIL_041018.qxd 19.10.2004 10:33 Seite 8
Three-phase
compact rectifier transformers
Safety transformers comp. VDE 0570 part 2-6, EN 61558-2-6
RDRKG 5 – 60
Irrespective of operation mode, series RDRKG remains well below the limit va-
lues for rated voltage 24 V DC, laid down in EN61131-2 / part 2 (D.C. power
supplies for electronic control units). It even applies for mains fluctuations of
+ 10% / -10% acc. to DIN IEC 38. Generously dimensioned electrolytic capaci-
tors achieve a minimal residual ripple of ≤ 2% required for exacting demands.
Consumers are comprehensively protected against interference voltage spi-
kes, overvoltage, HF interference voltages and capacitor residual charges. All
models of series RDRKG are manufactured with high performance ICs in hy-
brid technology on aluminum-oxide ceramic-basis and are fused on output si-
de.
Harmonic rule EN 61000-3-2 is observed.
Units RDRKG 5 - 10 are protected by quick safety fuses and from 16 A upwards
with high-performance automatic circuit breakers comp. to VDE 0660 Part 104
featuring thermal release for overload protection and electromagnetic instant-
aneous trip for short-circuits.
The compact power packs of series RDRKG base on transformers comp. VDE
Power packs
0570. They meet the requirements for protection against electric shock comp.
to DIN VDE 0106 Part 101.
The safe separation of protection low voltage (SELV)- and functional low volta-
ge (FELV)- circuits from other circuits is thereby ensured.
Developed for "worst case"-conditions, these units are way above rating and
can be operated in any position at ta 60°C.
The sensitive parts are encased in well-ventilated housings.
Design: Closed design, stationary, for installation and set-up in dry rooms, separate
windings, sturdy mounting brackets. Connections to non-tracking terminal
blocks with screw connections. The terminals are protected against finger
touch or contact with the back of the hand in compliance to accident preven-
tion regulations (VBG 4).
Input 3 x 380/400/420 V
Output 24 VDC, residual ripple < 2%
IP 00, suitable for installation up to protection rating IP 23, insulation class E,
max. ambient temperature ta 60°C.
A DC Article-no. kg kg a b c d1 d e Befestigung
RDRKG 5 5 21–400–024–G 2 0,80 3,30 145 85 157 135 90 50 M5
RDRKG 7,5 7,5 21–400–024–G 3 1 ,20 4,50 180 105 190 170 113 50 M5
RDRKG 1 0 10 21–400–024–G 4 1 ,40 5,50 180 105 190 170 113 64 M5
RDRKG 1 6 16 21–400–024–G 5 2,50 7,80 200 200 175 185 134 166 M6
RDRKG 20 20 21–400–024–G 6 2,80 1 1 ,30 200 210 175 185 134 176 M6
RDRKG 25 25 21–400–024–G 7 3,00 1 1 ,80 200 210 175 185 134 176 M6
RDRKG 30 30 21–400–024–G 8 4,00 14,00 200 210 175 185 134 176 M6
RDRKG 40 40 21–400–024–G 9 5,80 23,00 285 220 220 260 185 195 M8
RDRKG 60 60 21–400–024–G 10 6,60 25,00 285 234 220 260 185 210 M8
Subject to technical modifications Standard stock items
D 1/8
D_TEIL_041018.qxd 19.10.2004 10:33 Seite 9
Power packs
Technical data RSNT 20G RSNT 30G RSNT 40G RSNT 50G RSNT 60G
Input
Mains input voltage 3 x AC 400 V
Mains input voltage range + 15 % to – 15 %
Frequency 50 Hz/60 Hz
Input current 1,3 A 2,0 A 2,6 A 3,2 A 3,7 A
Input fuses external (thermal-magnetic overload release)
Output
Output voltage DC 24 V stabilized, twin terminals, externally adjustable 0... DC30 V
Status display LED green / yellow (U / I)
Ready signal (terminal B) DC 24V / max. load DC 0.1A when unit is in constant voltage mode
Adjustable output current 0...20 A 0...30 A 0...40 A 0...50 A 0...60 A
Residual ripple < 30 mV RMS
Short-circuit protection constant current operation
Load stabilization dynamic < 100 mVss / 500µs.
Stability under constant conditions < 0,05 %
Mains stabilization < 0,05 %
Overtemperature protection thermal switch-off when overtemperature > 85°C
RFI suppression VDE 0875 / EN 55011
Ambient temperature -10... +40°C
General data
Test voltage transformer between input and output circuit comp. to regulations (safety transformer)
Directives VDE 0570 part 2-6, EN 61558-2-6, EN 61000-3-2, EN 61131-2/part 2
CE mark yes
Installation orientation vertical
Cooling convection forced air
Type of connection screw-type terminal, finger-safe comp. to VBG4
2 2
Connection data fine strand, max. 4 / 10 mm fine strand, max. 4 / 16 mm
Mounting mounting brackets with keyhole attachment
Protection rating comp. DIN 0470 / EN 60529 IP 20
Safety class comp. IEC 536 / VDE 0106 part 1 I
Insulation class E
Dimensions in mm approx. (axbxc) 250 x 202 x 200 300 x 220 x 222 330 x 250 x 237
Mounting template in mm approx. (dxe) 228 x 161 278 x 179 308 x 209
Article no. 24-400-SNT-01-G 24-400-SNT-02-G 24-400-SNT-03-G 24-400-SNT-04-G 24-400-SNT-05-G
Copper weight in kg 3,4 3,8 5,8 8,5 8,5
Total weight in kg 13,0 21,0 22,5 25,0 26,5
Options
Remote control 0 - 10V for U / I
Remote control 4mA - 20mA for U / I
Switch-off input to take unit out of service connect terminal with 0V
Zero potential contact for centralized alarm for trouble (overtemperature, undervoltage and overload)
D 1/9
D_TEIL_041018.qxd 19.10.2004 10:33 Seite 10
Power packs:
Model Output voltage Output current Article no.
rated voltage (VDC) setting range (VDC) ADC
RPL 2420 D 24 23... 29 20,0 0505-0002420D
RPL 2440 D 24 23... 28 40,0 0505-0002440D
Developments in process:
- units with higher performance up to app. 1500 W with three-phase supply
- units with multiple output voltages
Power packs
Protection overload, short circuit, no-load yes yes
Overcurrent limit typical 20.5A 40.5A
Short circuit current typical < 22A < 45A
Overvoltage protection yes yes
Residual ripple f=20Hz...300kHz, Ta=25°C < 60mV RMS < 60mV RMS
Mains stabilization U1min - U1max < 0,05 % < 0,05 %
Load stabilization load alteration < 0,25% < 0,25%
10% <-> 90%
Overshoot/control time load leap < 3.0% < 3ms < 3.0% < 3ms
10% <-> 90%"
Temp. stability < 0,02% / K < 0,02% / K
Operation in parallel and series yes yes
Status reports LED green LED green
Noise output zero potential change-over contact optional optional
Temperature compensation (battery charger) optional optional
external NTC-resistor
DIRECTIVES
Mains harmonics limit EN 61000-3-2 yes yes
Noise transmission EN 550081-1, EN 55011 class B, EN 550081-1, EN 55011 class B,
EN 55022 class B EN 55022 class B
Interference immunity EN 50082-2 EN 50082-2
Safety EN 60950 class I EN 60950 class I
Test voltage input/housing 3750VAC RMS 50Hz, 1min 3750VAC RMS 50Hz, 1min
Test voltage input/output 3750VAC RMS 50Hz, 1min 3750VAC RMS 50Hz, 1min
Test voltage output/housing 500VDC 500VDC
Humidity 85% RH IEC 68-2-30 85% RH IEC 68-2-30
Vibration and shock ETS 300 019-2-4, class 4M5 ETS 300 019-2-4, class 4M5
CE mark yes yes
OPERATING DETAILS
Efficiency typical > 92% at 400VAC and 100%-load > 94% at 400VAC and 100%-load
Protection rating comp. VDE 0470 / EN 60529 IP 20 IP 20
Protection class comp. IEC 536, VDE 0106 T1 I I
Overtemperature protection yes yes
Ambient temperature 0 up to +55°C 0 up to +55°C
Storage temperature -24°C up to +85°C -24°C up to +85°C
Cooling free convection free convection
MECHANICS
Connection input voltage connector RM7,62mm to screw connector RM7,62mm to screw
4-pole 0,75-2,5mm2 (L1/L2/L3/PE) 4-pole 0,75-2,5mm2 (L1/L2/L3/PE)
for D.C./D.C.-converter: + on L1, - on L2 for D.C./D.C.-converter: + on L1, - on L2
Connection output voltage connector RM7,62mm to screw print terminal RM10, 16mm to screw
4-pole 0,75-4,0mm2 (+ + - -) 4-pole 0,75-10,0mm2 (+ + - -)
Connection noise output and optional optional
temperature compensation
Housing design aluminum / steel aluminum / steel
Mounting snap-on onto mounting rail snap-on onto mounting rail
DIN EN 50022 DIN EN 50022
Installation orientation front plate horizontal, connections below front plate horizontal, connections below
Approx. dimensions in mm (W x H x D) 245 x 138 x 100 mm ca. 285 x 174 x 110 (mm)
Approx. total weight 2,2kg ca. 3,3kg
Standard stock items Subject to technical modifications
D 1/11
D_TEIL_041018.qxd 19.10.2004 10:33 Seite 12
D 1/12
D_TEIL_041018.qxd 19.10.2004 10:33 Seite 13
The IU charging method combined with our patented switching concept is particularly efficient for lead acid batteries
because it is best adapted to their charging characteristic.
The service life of maintenance-free lead acid batteries increases considerably by this gentle charging method. Two
LEDs indicate operation modes. Buffer-battery operation is fully guaranteed.
Battery chargers series RLSN are enclosed in a plastic coated steel housing providing comprehensive protection
against accidental contact. The battery chargers in modern industrial design fulfill safety requirements for protection
against electric shock comp. to VDE 0106 part 101.
Battery chargers
RLSN 2420 RLSN 2440 RLSN 2460
Technical data for model RLSN 1220 RLSN 2420 RLSN 1240 RLSN 2440 RLSN 1260 RLSN 2460
Input
Mains input voltage AC 3x 400V
Mains input voltage range + 15 % to - 15 %
Frequency 50Hz / 60Hz
Input fuses external (thermal/magnetic overload release)
Input current 1,3 A 1,3 A 2,6 A 2,6 A 3,7 A 3,7 A
Output
Battery rated voltage DC 12 V DC 24 V DC 12 V DC 24 V DC 12 V DC 24 V
Max. charge current DC 20A DC 20A DC 40A DC 40A DC 60A DC 60A
Battery type all types of lead acid batteries
Status display yellow constant current mode
LEDs green constant voltage mode
Residual ripple of charge current < 0,5%
Charging characteristic IU
Overload protection internal electronic current limiter
Reverse current when mains off, I =< 30mA
Overtemperature protection automatic cut-off with reset at overtemperature
RFI suppression better than VDE 0871, limit curve B / EN 55 011
Temperature range -10° C to + 40° C
Efficiency >90%
General data
Transformer test voltage between input and output comp. to regulation (safety transformers)
Directives VDE 0570 part 2-6, EN 61558-2-6, EN 61000-3-2, EN 61131-2/part 2
CE mark yes
Installation orientation cooling fins vertical
Cooling convection Zwangskühlung
Type of connection terminal blocks (protected against finger touch comp. UVV (VBG 4)
Connection data fine strand fine strand fine strand
primary max. 4 mm2 primary max. 4 mm2 primary max. 4 mm2
2
secondary max. 10 mm secondary max. 10 mm2 secondary max. 16 mm2
Mounting integrated mounting brackets with keyhole attachment
Protection rating (VDE 0470 / EN 60529) IP 20
Safety class I
Insulation class E
Dimensions in mm approx.
(Length/Width/Height) 250 / 202 / 200 300 / 220 / 222 330 / 250 / 237
Mounting template in mm approx. 228 / 161 278 / 179 308 / 209
Article no. 0234-400-012-01 0233-400-024-01 0234-400-012-02 0233-400-024-02 0234-400-012-03 0233-400-024-03
Copper-weight in kg 3,4 5,8 8,5
Weight in kg 13,0 22,5 26,5
Subject to technical modifications Standard stock items
D 1/13
D_TEIL_041018.qxd 19.10.2004 10:33 Seite 14
- safety class I
- noise transmission EN 50081-1, EN 55011 class B (industry),
EN 55022 class B (Telecom)
- interference immunity EN 50082-2: ESD, electromagnetic irradiation, burst, con-
ducted interference immunity, mains voltage dips
- overcurrent limiter and short-circuit proofing
- overtemperature protection
- inrush current limiter, enabling the use of conventional thermo-magnetic circuit
breakers with B- characteristic
- overvoltage limiter
- electronic overvoltage limiter
- status display: LED
- ambient temperature 0°C...+ 55°C without power reduction
- optional -25°C... +55°C
Battery chargers:
Model Output voltage Output current Article no.
rated voltage (VDC) setting range (VDC) ADC
RPL 2420 DL 27,4 23... 29 20,0 0525-002420DL
RPL 2440 DL 27,4 23... 28 40,0 0525-002440DL
Developments in process:
- units with higher performance up to app. 1500 W with three-phase supply
- units with multiple output voltages
Battery chargers
Load stabilization load alteration < 0,25% < 0,25%
10% <-> 90%
Overshoot/control time load leap < 3.0% < 3ms < 3.0% < 3ms
10% <-> 90%"
Temp. stability < 0,02% / K < 0,02% / K
Operation in parallel and series yes yes
Status reports LED green LED green
Noise output zero potential change-over contact optional optional
Temperature compensation (battery charger) optional optional
external NTC-resistor
DIRECTIVES
Mains harmonics limit EN 61000-3-2 yes yes
Noise transmission EN 550081-1, EN 55011 class B, EN 550081-1, EN 55011 class B,
EN 55022 class B EN 55022 class B
Interference immunity EN 50082-2 EN 50082-2
Safety EN 60950 class I EN 60950 class I
Test voltage input/housing 3750VAC RMS 50Hz, 1min 3750VAC RMS 50Hz, 1min
Test voltage input/output 3750VAC RMS 50Hz, 1min 3750VAC RMS 50Hz, 1min
Test voltage output/housing 500VDC 500VDC
Humidity 85% RH IEC 68-2-30 85% RH IEC 68-2-30
Vibration and shock ETS 300 019-2-4, class 4M5 ETS 300 019-2-4, class 4M5
CE mark yes yes
OPERATING DETAILS
Efficiency typical > 92% at 400VAC and 100%-load > 94% at 400VAC and 100%-load
Protection rating comp. VDE 0470 / EN 60529 IP 20 IP 20
Protection class comp. IEC 536, VDE 0106 T1 I I
Overtemperature protection yes yes
Ambient temperature 0 bis +55°C 0 bis +55°C
Storage temperature -24°C up to +85°C -24°C up to +85°C
Cooling free convection free convection
MECHANICS
Connection input voltage connector RM7,62mm to screw connector RM7,62mm to screw
4-pole 0,75-2,5mm2 (L1/L2/L3/PE) 4-pole 0,75-2,5mm2 (L1/L2/L3/PE)
for D.C./D.C.-converter: + on L1, - on L2 for D.C./D.C.-converter: + on L1, - on L2
Connection output voltage connector RM7,62mm to screw print terminal RM10, 16mm to screw
4-pole 0,75-4,0mm2 (+ + - -) 4-pole 0,75-10,0mm2 (+ + - -)
Connection noise output and optional optional
temperature compensation
Housing design aluminum / steel aluminum / steel
Mounting snap-on onto mounting rail snap-on onto mounting rail
DIN EN 50022 DIN EN 50022
Installation orientation front plate horizontal, connections below front plate horizontal, connections below
Approx. dimensions in mm (WxHxD) 245 x 138 x 100 mm ca. 285 x 174 x 110 (mm)
Approx. total weight 2,2kg ca. 3,3kg
Standard stock items Subject to technical modifications
D 1/15
D_TEIL_041018.qxd 19.10.2004 10:33 Seite 16
D 1/16
D_TEIL_041018.qxd 19.10.2004 10:33 Seite 17
UPS
Status display LED green / yellow (U / I)
Zero potential contact centralized alarm for trouble (overtemperature, undervoltge and overload)
Switch off input to take unit out of service connect terminal with 0V
Indication UPS-mode break contact to 0V
Output current adjustable 0...20 A 0...40 A 0...60 A
Residual ripple < 30 mV RMS
Short-circuit proofing constant current operation
Load stabilization dynamic < 100 mVss / 500µs
Stability under constant conditions < 0,05 %
Mains stabilization < 0,05 %
Overtemperature protection thermal switch-off when overtemperature > 85°C
RFI suppression VDE 0875 / EN 55011
Ambient temperature -10... +40°C
General data
Test voltage transformer between input and output complying to regulation (safety transformer)
Directives VDE 0570 part 2-6, EN 61558-2-6, EN 61000-3-2, EN 61131-2/part 2
CE mark yes
Installation orientation vertical
Cooling convection forced air
Type of connection screw-type terminal, finger-safe comp. UVV (VBG4)
2 2
Connection data fine strand max. 4 / 10 mm fine strand max. 4 / 16 mm
Mounting mounting brackets with keyhole attachment
Protection rating comp. VDE 0470 / EN 60529 IP 20
Safety class comp. IEC 536, VDE 0106 T1 I
Insulation class E
Dimensions in mm approx. (axbxc) 250 x 202 x 200 300 x 220 x 222 330 x 250 x 237
Mounting template in mm approx (dxe) 228 x 161 278 x 179 308 x 209
Article no. 0255-000020GU 0255-000040GU 0255-000060GU
Copper weight in kg 3,4 5,8 8,5
Total weight in kg 13,0 22,5 26,5
Options
Remote control 0 - 10V for U / I
Remote control 4mA - 20mA for U / I
Product description
Standard switch power packs of series RSNT...G equipped with option U (UPS added) can be operated as control units
with mains identification. Combined with a lead acid or nickel-cadmium-battery of fitting size and capacity, the power
pack RSNT...GU can bridge the output voltage over a defined time period during mains voltage dips or breakdowns.
The possible time period depends solely on the battery's capacity. An undervoltage interruption is integrated for bat-
tery protection.
We recommend Riedel-chargers series RLG or RLEC for battery recharging.
For control of the RSNT...GU a terminal connection (OFF) is attached allowing power pack's switch off (connect termi-
nal to 0V). At mains breakdown an alarm contact (UPS) opens, i.e. information for processing can be taken from its ter-
minal. The contact is connected with 0V in closed condition (UPS-ready = open, UPS-run = 0V).
Block diagram:
24VDC
Power
consumer
RSNT..GU
UPS operation
OFF
F (trouble)
Battery
charger
RLG 27,6 DC
or
RLEC
D 1/18
E
Copyright: Lufthansa/Riedel Product group
Ec Ec Iso
on on lat
om om ew
y y win ind
win din ing
din g,
g, siz
siz e1
e6 14
4- up
96 wa
rds
Seconds Minutes
Short-term delivery
E 1/2
E_TEIL_041018.qxd 19.10.2004 10:35 Seite 3
RRSP 73 - 2912
Design: Open frame, stationary, for installation and set-up in dry rooms, economy circuit, connection to screw termi-
nals. General 3-spot-front attachment, size 65 - 95 central attachment
IP 00, suitable for installation up to protection rating IP 23, up to 2 A insulation class E, above that class B, max. ambient
temperature ta 40°C.
Design with isolate windings available on request
app. kg app. kg D H B F d.
RRSP 65 0,040 1 ,20 74 75 26 M4 6
RRSP 75 0,070 1 ,50 86 75 26 M4 6
RRSP 85 0,1 20 2,00 96 76 26 M4 6
RRSP 94 0,1 60 2,20 106 68 26 M4 6
RRSP 95 0,250 2,60 106 78 26 M4 6
RRSP 114 0,300 3,30 131 90 80 M6 6
RRSP 115 0,370 4,00 131 105 80 M6 6
RRSP 116 0,450 4,70 131 115 80 M6 6
RRSP 136 0,900 6,20 148 120 110 M8 10
RRSP 137 1,000 7,30 148 130 110 M8 10
RRSP 157 1,200 9,30 170 130 110 M8 10
RRSP 178 1,600 13,00 190 150 110 M8 10
RRSP 217 2,1 50 16,00 230 155 150 M8 10
RRSP 257 3,1 50 19,00 270 155 150 M8 10
RRSP 2570 3,250 20,00 270 210 150 M8 10
RRSP 2970 4,500 26,00 315 225 150 M8 10
RRSP 2512 6,000 39,00 270 270 150 M8 10
RRSP 2912 8,000 46,00 315 280 150 M8 10
RRSP 3515 1 0,000 78,00 385 350 150 M 10 10
RSM 1 - RSM 14
Design: Single-phase synchronous motor 230 V, 50 Hz, unipolar reversible, incl. one limit switch each in both final posi-
tions and indexing disks with fine tuning.
Motor drives are available in different regulating times (6/12/30/60 sec.). Please state in order. Other regulating times
and servo drives with d.c. motors on request.
3 x 400 V 3 x 400 V
3 x 400 V
Model Current Current 3 x 0–450 V Current 3 x 0–520 V
3 x 0–400 V–1 % +5 %–1 % +5 %–1 %
3xA Article-no. 3xA Article-no. 3xA Article-no.
RDRSP 73 0,80 27–400–400–01 – – – –
RDRSP 74 1,00 27–400–400–02 – – – –
RDRSP 84 1,60 27–400–400–03 – – – –
RDRSP 94 2,50 27–400–400–04 – – 1,00 27–400–520–06
RDRSP 95 3,20 27–400–400–05 – – – –
RDRSP 114 3,20 27–400–400–06 – – – –
RDRSP 115 5,00 27–400–400–07 4,00 27–400–450–09 – –
RDRSP 116 6,30 27–400–400–08 5,00 27–400–450–10 – –
RDRSP 136 8,00 27–400–400–09 – – – –
RDRSP 137 10,00 27–400–400–10 – – – –
RDRSP 157 12,50 27–400–400– 11 10,00 27–400–450–13 – –
RDRSP 178 16,00 27–400–400–12 12,50 27–400–450–14 8,00 27–400–520–14
RDRSP 217 20,00 27–400–400–13 – – – –
RDRSP 257 25,00 27–400–400–14 – – 12,50 27–400–520–16
RDRSP 2570 32,00 27–400–400–15 – – – –
RDRSP 2970 40,00 27–400–400–16 – – – –
RDRSP 2512 50,00 27–400–400–17 – – – –
RDRSP 2912 63,00 27–400–400–18 50,00 27–400–450–17 32,00 27–400–520–17
RDRSP 3515 80,00 27–400–400–19 – – – –
RSMD 1 - RSMD 19
Design: Single-phase synchronous motor 230V, 50 Hz, unipolar reversible, incl. one limit switch each in both final posi-
tions and indexing disks with fine tuning.
Motor drives are available in different regulating times (6/12/30/60 sec.). Please state in order. Other regulating times
and servo drives with d.c. motors on request.
Connection terminals
Weight without
Motor drive for transformer Approx. dimensions in mm
transformer
Article no. RDRSP kg G H D L M
RSMD 1 73 1,2 155 300 140 150 10
RSMD 2 74 1,2 155 300 140 150 10
RSMD 3 84 1,2 155 300 140 150 10
RSMD 4 94 1,2 155 300 140 150 10
RSMD 5 95 1,2 155 320 140 150 10
RSMD 6 114 1,2 175 330 160 150 10
RSMD 7 115 1,2 175 360 160 150 10
RSMD 8 116 1,2 175 390 160 150 10
RSMD 9 136 1,5 240 435 220 150 12
RSMD 10 137 1,5 240 470 220 150 12
RSMD 11 157 2,0 240 470 220 150 12
RSMD 12 178 2,0 260 535 240 150 16
RSMD 13 2 17 2,0 320 540 300 150 16
RSMD 14 257 2,0 360 590 340 150 16
RSMD 15 2570 2,0 440 695 420 210 16
RSMD 16 2970 2,0 460 750 440 210 16
RSMD 17 2512 2,0 380 970 297 200 20
RSMD 18 2912 2,0 420 970 318 200 20
RSMD 19 3515 4,0 475 1130 360 200 20
Rotating knobs
Model Approx. dimensions in mm
Article no. A B C D d
REK 30–40–6 38 28 12 41 6
REK 30–60–6 48 34 28 58 6
REK 30–60–10 48 34 28 58 10
REK 30–90–6 76 40 28 90 6
REK 30–90–10 76 40 28 90 10
Model Diameter
Labelling
Article no. mm
Available options: Protective system up to IP 65 max., tropic-proof, analog or digital meters, main switch and
fusing, galvanic isolation, maintenance service...
Basic circuit diagram: Three-phase mains with Three-phase mains with master control
individual phase control
M Control
Regler M Control
Regler
M Control
Regler
M Control
Regler
N N N N
Single-phase mains
1L1 2L1
M Control
Regler
N N
Choke coils stand for inductors and in consequence re- Three-phase filter circuit chokes can be found in reacti-
active impedance. The energy created by the magnetic ve current compensation systems. Together with the
field of a current-carrying coil increases considerably system's capacitors they form a series resonant circuit
with high-permeability iron cores. thereby effecting in defined mains conditions. Choking
the reactive current compensating system prevents re-
Riedel – choke coils are designed as iron core chokes
sonance with occurring mains harmonics. Inductivities
with magnet gap.
of filter circuit chokes are selected with the imperative
Apart from a great variety of custom made products that resonant frequency of series resonant circuit for-
designed for specific applications we also offer a stan- med by capacitor and filter circuit choke lies below lo-
dard program comprising: west frequency of occurring harmonics.
Single-phase line chokes Increasing operation of converters and inverters cause
Series RENDr mains harmonics. Operation of 6-pulse bridge circuits
Rated voltage AC 230 V, voltage drop 4 % charge the mains with currents in ordinal numbers of
Single-phase double line chokes
Series RDNDr n = 6 x k +/-1 for k = 1, 2, 3,...
Rated voltage AC 400 V, voltage drop 2 x 2 %
Current amplitudes decrease with increasing ordinal
Three-phase filter circuit chokes number.
Series RFDr 7
Rated voltage 3AC 400 V, filter choke factor 7 % I(n) ~ n1 x l(1)
Three-phase line chokes
Series RNDr Choke factor p is the proportion of filter circuit choke re-
Rated voltage 3AC 400 V, voltage drop 4 % actance and capacitor reactance
p = XL
XC
fR = fmains
⻫P
Line chokes
(Commutation chokes) When selecting a resonant frequency and thereby the
choke factor, consider the circular pilot frequency in the
respective net and coordinate its compatibility with the
Line chokes are necessary for current limiting and sup-
respective utility company.
pression of line reactions respectively commutation
notches. Dimensioning three-phase filter circuit chokes bases on
following premises:
Current IG is limited by the line choke and calculates
with formula Essential load:
F 1/2
F_TEIL_041018.qxd 19.10.2004 10:36 Seite 3
Line chokes are necessary for current limitation, suppression of line reactions
respectively commutation notches.
Current limitation preferably ensues on the 25-fold value of rated current. To
this end line chokes with 4% short circuit voltage must be used.
Line chokes are to be selected according to rated current of consumer.
Design: Open frame, stationary, for installation and set-up in dry rooms, sturdy moun-
ting brackets. Connection to non-tracking transformer terminals with screw-
and tab connection 2.8 x 0.8 mm up to 5 A and 6.3 x 0.8 mm up to 20A. Accor-
ding to DIN 46249 tab connection 2.8 x 0.8 mm can only be loaded up to 5 A
and 6.3 x 0.8 up to 20 A. Above 20A terminal blocks with screw connections
are used. The terminals are protected against finger touch or contact with the
back of the hand in compliance to accident prevention regulations (VBG 4).
Ground connection via tab blade connection 6.3 x 0.8 mm. Accessory ground
screw connection terminal available.
IP 00, suitable for installation up to protection rating IP 23, insulation class E,
max. ambient temperature ta 40°C
Technical data: Rated voltage: AC 230 V
Rated voltage drop (Uk): 4% (4,8% at 60 Hz)
Rated frequency: 50 Hz (60 Hz)
Line chokes with deviating technical data available on request.
Total Copper
Model Current Inductivity Article-no. Approx. dimensions in mm
weight weight
A mH kg kg a b c d e f Attachm.
RENDr 1 1,0 29,300 60–230–01 0,30 0,05 48 44 66 38 34 36 M3
RENDr 2 2,0 14,600 60–230–02 0,35 0,06 55 46 73 44 36 37 M3
RENDr 3 3,0 9,760 60–230–03 0,38 0,07 55 46 73 44 36 37 M3
RENDr 4 4,0 7,320 60–230–04 0,45 0,08 60 48 62 44 38 40 M3
RENDr 5 5,0 5,860 60–230–05 0,65 0,08 60 58 62 44 48 45 M3
RENDr 6 6,0 4,880 60–230–06 0,65 0,12 66 55 67 50 42 42 M4
RENDr 8 8,0 3,660 60–230–07 0,90 0,12 66 67 67 50 54 48 M4
RENDr 10 10,0 2,930 60–230–08 1,10 0,24 78 60 76 56 47 45 M4
RENDr 12,5 12,5 2,340 60–230–09 1,40 0,25 78 69 76 56 56 50 M4
RENDr 16 16,0 1,830 60–230–10 1,90 0,25 85 76 79 64 63 53 M4
RENDr 20 20,0 1,460 60–230–11 2,00 0,35 85 76 79 64 63 53 M4
RENDr 25 25,0 1,1 7 0 60–230–12 2,30 0,45 96 78 92 84 62 50 M5
RENDr 32 32,0 0,915 60–230–13 2,90 0,50 96 88 92 84 72 55 M5
F 1/3
F_TEIL_041018.qxd 19.10.2004 10:36 Seite 4
Double line chokes are necessary for current limitation, suppression of line
reactions respectively commutation notches. Thereby, through inductivity
partition onto both supply lines, symmetric connection of consumer ensues.
On each winding part about half the voltage drop develops. Series and paral-
lel connection of winding offer further applications up to double rated current
and half a voltage drop.
Current limitation preferably ensues on the 25-fold value of rated current. To
this end line chokes with 4% (2 x 2 %) short circuit voltage must be used.
Double line chokes are to be selected according to rated current of consu-
mer.
Design: Open frame, stationary, for installation and set-up in dry rooms, sturdy moun-
ting brackets. Connection to non-tracking transformer terminals with screw-
and tab connection 2.8 x 0.8 mm up to 5 A and 6.3 x 0.8 mm up to 20A.
According to DIN 46249 tab connection 2.8 x 0.8 mm can only be loaded up
to 5 A and 6.3 x 0.8 up to 20 A. Above 20A terminal blocks with screw con-
nections or cable lugs are used. The terminals are protected against finger
touch or contact with the back of the hand complying to accident prevention
regulations (VBG 4).
Winding consists of 2 equivalent winding parts that are insulated against each
other.
Ground connection via tab blade connection 6.3 x 0.8 mm. Accessory ground
screw connection terminal available.
IP 00, suitable for installation up to protection rating IP 23, insulation class E,
max. ambient temperature ta 40°C.
Technical data: Rated voltage: AC 400 V
Rated voltage drop (Uk): 2 x 2 % (2 x 2,4 % at 60 Hz)
(series connection of winding parts: 4 %)
(parallel connection of winding parts: 1 %)
Rated frequency: 50 Hz (60 Hz)
Double line chokes with deviating technical data available on request.
Total Copper
Model Current Inductivity Article-no. Approx. dimensions in mm
weight weight
A mH kg kg a b c d e f Attachm.
RDNDr 2 2,0 2 x 12,700 61–400–01 0,45 0,07 60 48 62 44 38 40 M3
RDNDr 3 3,0 2 x 8,490 61–400–02 0,65 0,08 60 58 62 44 48 45 M3
RDNDr 4 4,0 2 x 6,370 61–400–03 0,85 0,08 66 67 67 50 54 48 M4
RDNDr 5 5,0 2 x 5,090 61–400–04 0,90 0,12 66 67 67 50 54 48 M4
RDNDr 6 6,0 2 x 4,240 61–400–05 1,10 0,24 78 60 76 56 47 45 M4
RDNDr 8 8,0 2 x 3,180 61–400–06 1,40 0,25 78 69 76 56 56 50 M4
RDNDr 10 10,0 2 x 2,550 61–400–07 1,90 0,25 85 76 79 64 63 53 M4
RDNDr 12,5 12,5 2 x 2,040 61–400–08 2,20 0,35 96 78 92 84 62 50 M5
RDNDr 16 16,0 2 x 1,590 61–400–09 2,80 0,40 96 88 92 84 72 55 M5
RDNDr 20 20,0 2 x 1,270 61–400–10 3,50 0,50 96 102 92 84 86 62 M5
RDNDr 25 25,0 2 x 1,020 61–400–11 3,60 0,70 105 86 110 84 70 52 M5
RDNDr 32 32,0 2 x 0,796 61–400–12 4,50 0,80 105 101 110 84 85 60 M5
Three-phase filter circuit chokes are necessary for reactive current compensa-
tion systems. Together with the system's capacitors they create a series reso-
nant circuit which results in defined mains conditions.
Three-phase filter circuit chokes with matching power interconnected with capa-
citors of stated capacity guarantee the designated compensating reactive power.
Three-phase filter circuit chokes lacking matching power are accessed accor-
ding to capacitors in use and lead to deviating compensating reactive power.
With frequently selected choking of 7% the series resonant circuit, formed by
filter circuit chokes and power factor capacitors, creates a resonant frequency
of 189 Hz.
Design: Open frame, stationary, for installation and set-up in dry rooms, sturdy mounting
brackets. Up to 12,5 kVAr connection to non-tracking transformer terminals
with screw- and tab connection 2.8 x 0.8 mm up to 5 A and 6.3 x 0.8 mm up to
20A. According to DIN 46249 tab connection 2.8 x 0.8 mm can only be loaded
up to 5 A and 6.3 x 0.8 up to 20 A. Above 12,5 kVAr up to 25 kVAr universal ter-
minal blocks with screw connections, 30 kVAr and above pressed cable lugs
are used. The terminals are protected against finger touch or contact with the
back of the hand complying to accident prevention regulations (VBG 4).
Temperature switch in center coil at hand.
IP 00, suitable for installation up to protection rating IP 23, insulation class E,
max. ambient temperature ta 40°C.
Technical data: Rated voltage. 3AC 400 V
Choking factor: 7%
Resonant frequency: 189 Hz
Rated frequency: 50 Hz
50 Hz current: 1 ,06 x rated current
1 50 Hz current: 0,04 x rated current
250 Hz current: 0,3 1 x rated current
350 Hz current: 0,13 x rated current
F 1/5
F_TEIL_041018.qxd 19.10.2004 10:36 Seite 6
Line chokes are necessary for current limitation, suppression of line reactions
respectively commutation notches.
Current limitation preferably ensues on the 25-fold value of rated current. To
this end line chokes with 4% short circuit voltage must be used.
Line chokes are to be selected according to rated current of consumer.
Design: Open frame, stationary, for installation and set-up in dry rooms, sturdy moun-
ting brackets. Connection to non-tracking transformer terminals with screw-
and tab connection 2.8 x 0.8 mm up to 5 A and 6.3 x 0.8 mm up to 20A. Accor-
ding to DIN 46249 tab connection 2.8 x 0.8 mm can only be loaded up to 5 A
and 6.3 x 0.8 up to 20 A. Above 20A terminal blocks with screw connections or
cable lugs are used. The terminals are protected against finger touch or con-
tact with the back of the hand complying to accident prevention regulations
(VBG 4).
Terminal connections above 60 A increase measurements b and c.
IP 00, suitable for installation up to protection rating IP 23, insulation class E,
max. ambient temperature ta 40°C
Technical data: Rated voltage: 3AC 400 V
Rated voltage drop (Uk): 4 % (4,8 % at 60 Hz)
Rated frequency: 50 Hz (60 Hz)
Line chokes with deviating technical data available on request.
Total Copper
Model Current Inductivity Article-no. Approx. dimensions in mm
weight weight
A mH kg kg a b c d e f Attachm.
RNDr 2,5 2,5 11,730 63–400–01 1,0 0,2 96 46 95 90 31 40 M4
RNDr 4 4,0 7,330 63–400–02 1,3 0,3 96 55 95 80 40 45 M4
RNDr 6 6,0 4,900 63–400–03 1,7 0,4 125 73 115 100 45 45 M4
RNDr 8 8,0 3,660 63–400–04 1,9 0,6 125 73 115 100 45 45 M4
RNDr 1 0 10,0 2,940 63–400–05 2,8 0,6 125 83 115 100 55 50 M4
RNDr 1 3 13,0 2,260 63–400–06 3,0 0,8 125 83 115 100 55 50 M4
RNDr 1 6 16,0 1,840 63–400–07 3,4 0,9 155 76 140 130 56 45 M6
RNDr 20 20,0 1,470 63–400–08 3,7 1,2 155 76 140 130 56 40 M6
RNDr 25 25,0 1 , 180 63–400–09 5, 1 1,2 155 91 140 130 71 46 M6
RNDr 30 30,0 0,980 63–400–1 0 5,4 1,5 155 91 140 130 71 46 M6
RNDr 40 40,0 0,740 63–400– 11 6,8 2,7 190 85 160 170 57 43 M6
RNDr 50 50,0 0,590 63–400–1 2 8,2 2,7 190 95 160 170 67 48 M6
RNDr 60 60,0 0,490 63–400–1 3 9,8 3, 1 190 105 160 170 77 53 M6
RNDr 80 80,0 0,370 63–400–1 4 13,0 3,5 210 117 180 175 97 59 M6
RNDr 90 90,0 0,330 63–400–1 5 14,0 4,0 240 121 210 190 95 61 M8
RNDr 100 100,0 0,290 63–400–1 6 16,0 4,3 240 131 210 190 105 66 M8
RNDr 120 120,0 0,250 63–400–17 18,0 5,9 240 131 210 190 105 66 M8
RNDr 140 140,0 0, 210 63–400–1 8 22,0 7,5 240 141 210 190 115 115 M8
RNDr 160 160,0 0,1 84 63–400–1 9 25,0 7, 7 240 151 210 190 125 120 M8
RNDr 180 180,0 0, 163 63–400–20 29,0 8,5 265 152 228 215 126 125 M8
RNDr 200 200,0 0, 147 63–400–21 30,0 10,0 265 152 228 215 126 135 M8
R-MED
Single-phase isolating transformers
RMED-E 3.15-8.0 comp. DIN VDE 0570 part 2-15, EN 61558-2-15
Design: Open frame, stationary, for installation and set-up in dry rooms, separate win-
dings, sturdy mounting brackets. Connection to non-tracking transformer ter-
minals with screw connection. The terminals are protected against finger touch
or contact with the back of the hand in compliance to accident prevention regu-
lations (VBG 4).
Necessary settings for display resp. report of warm-up and isolation monitoring
are protruded.
IP 00, suitable for installation up to protection rating IP 23, insulation class E,
max. ambient temperature ta 40°C. Other type of protection and manufacture
comp. to other norms available on request.
G 1/2
G_TEIL_041019.qxd 19.10.2004 10:30 Seite 3
R-MED
Three-phase isolating transformers
RMED-D 3.15-8.0 comp. DIN VDE 0570 part 2-15, EN 61558-2-15
Design: Open frame, stationary, for installation and set-up in dry rooms, separate win-
dings, sturdy mounting brackets. Connection to non-tracking transformer ter-
minals with screw connection. The terminals are protected against finger touch
or contact with the back of the hand in compliance to accident prevention regu-
lations (VBG 4).
Necessary settings for display resp. report of warm-up and isolation monitoring
are protruded.
IP 00, suitable for installation up to protection rating IP 23, insulation class E,
max. ambient temperature ta 40°C. Other type of protection and manufacture
comp. to other norms available on request.
G 1/3
G_TEIL_041019.qxd 19.10.2004 10:30 Seite 4
Design: Portable housings series RG 601 - RG 801 are made of robust and impact resi-
stant glass-fibre reinforced polyester resin. The housings are specially desi-
gned for application with electric units. They are self extinguishing and not hy-
groscopic. A neoprene seal fitted between cover and housing assures ade-
quate tightness. Tests in water depths of 1 m showed that no moisture pene-
trated for 8 consecutive days.
The housings are designed in IP 67 and available in colors blue, red and yellow
(please state in order). Other colors on request.
The housings can be fitted with boreholes and cutouts according to drawing at
a surcharge.
Model RG 601-701
Model RG 801
Total
Model Article no. Approx. dimensions in mm
weight
G 1/4
G_TEIL_041019.qxd 19.10.2004 10:30 Seite 5
Cutout for
cable gland
Bottom Bottom
size 00 - size 3 size 4 - size 4a
Base plate
rubber heels
hole for
cable gland hole for
acc. order cable gland
acc. order
Extra holes on request
Model L B H E E1 H1 H2 Model L B H E E1 H1 H2
Article no. Article no.
RG 0 120 95 90 70 35 10 3 RG 3 180 180 190 100 50 10 6
RG 1 140 110 110 80 40 10 6 RG 4 250 220 190 120 60 12,5 7
RG 2 180 180 150 100 50 10 6 RG 4a 310 220 190 120 60 12,5 7
Material: St. 1203 Plastic-coated color RAL 7032: flint stone grey unpolished
G 1/5
G_TEIL_041019.qxd 19.10.2004 10:30 Seite 6
Model L L1 B B1 H H1
Article no.
RG 5 a 125 127 118 124 75 79
RG 5 b 200 202 118 124 75 79
RG 5 c 125 127 118 124 100 104
RG 5 d 200 202 118 124 100 104
RG 8 a 250 252 160 166 100 104
RG 8 b 250 252 160 166 140 144
RG 10 300 302 220 226 150 154
Material: St. 1203 Plastic-coated color RAL 7032: flint stone grey unpolished
G 1/6
G_TEIL_041019.qxd 19.10.2004 10:30 Seite 7
Housing top
Housing bottom
Transformer housings for wall mounting with punched holes for cable gland
Model
L L1 B B1 H H1 E E1 D PG
Article no.
RG 11 202 199 152 149 122 13 70 50 4,5 13,5
RG 12 202 199 152 149 155 13 70 50 4,5 13,5
RG 13 303 299 222 218 190 13 110 50 5,5 13,5
RG 14 382 379 302 298 220 13 110 60 6,5 16
RG 15 500 498 350 348 272 13 180 95 6,5 16
Material: St. 1203 Plastic-coated color RAL 7032: flint stone grey unpolished
G 1/7
G_TEIL_041019.qxd 19.10.2004 10:30 Seite 8
Floor housing
RG 20-24 RG 20-29
RG 25-29
M4 thread set
Fixing brackets
Model A A1 B C
for wall mounting
Article no. ca. mm ca. mm ca. mm ca. mm Article no.
RG 20 94 118 90 110 WG 20
RG 2 1 114 138 110 130 WG 2 1
RG 22 134 158 130 150 WG 22
RG 23 174 198 160 200 WG 23
RG 24 224 248 180 180 WG 24
RG 25 274 298 220 220 WG 25
RG 26 334 358 250 300 WG 26
RG 27 374 398 280 280 WG 27
RG 28 454 478 350 300 WG 28
RG 29 534 558 380 300 WG 29
Material: St. 1203 Plastic-coated color RAL 7032: flint stone grey unpolished
G 1/8
G_TEIL_041019.qxd 19.10.2004 10:30 Seite 9
M6 thread
cage nuts
adjustable
Transformer Available in:
mounting IP 20 - without lattice hole sheet metal
IP 23 - with lattice hole sheet metal
Housing frame IP 44 - with closed base plate
IP 54 - with closed base plate and hollow
section seal
Material: EPDM quality - self-sealing
M8 thread
Model Material L L1 B B1 H U U1 U2
Article no.
UI 180
RG 110 520 460 460 400 480 500 460 289 –137
UI 210
RG 120 UI 240 580 520 510 450 560 550 510 349 –197
3 UI 150
RG 130 580 520 400 340 420 440 400 349 –197
3 UI 168
3 UI 180
RG 140 640 580 460 400 480 500 460 409 – 257
3 UI 210
RG 150 3 UI 240 740 680 510 450 560 550 510 509 – 357
RG 160 –– 825 765 590 530 620 630 590 616 – 332
RG 170 –– 1020 960 720 660 690 760 720 812 – 428
RG 180 –– 1120 1060 820 760 800 860 820 891 – 407
RG 190 –– 1310 1250 820 760 1250 860 820 1081 – 497
Material: St. 1203 Plastic-coated color RAL 7032: flint stone grey unpolished
G 1/9
G_TEIL_041019.qxd 19.10.2004 10:30 Seite 10
M6 thread
cage nuts
adjustable
Transformer
mounting
Housing frame
M8 thread
Available in:
IP 20 - without lattice hole sheet metal
IP 23 - with lattice hole sheet metal
IP 44 - with closed base plate
IP 54 - with closed base plate and hollow section seal Material: EPDM quality - self-sealing
Model Model L L1 B B1 H U U1 U2
Article no.
RG 210 –– 720 660 550 490 620 590 550 470 – 406
RG 220 –– 810 750 460 400 800 500 460 512 – 448
RG 230 –– 910 850 610 550 730 650 610 590 – 5 1 8
RG 240 –– 1060 1000 560 500 1000 600 560 632 – 568
RG 250 –– 1260 1200 760 700 1100 800 760 812 – 748
Material: St. 1203 Plastic-coated color RAL 7032: flint stone grey unpolished
G 1/10
G_TEIL_041019.qxd 19.10.2004 10:30 Seite 11
M6 thread set
Total
Model A C A1 B1 C1 A2 B2 A3 x B3 Mounting
weight
Article no. kg app. mm app. mm app. mm app. mm app. mm app. mm app. mm app. mm Floor
RG 300 26 340 400 380 380 500 360 360 320 x 300 Ø 13
RG 310 36 410 500 450 450 600 430 430 390 x 370 Ø 13
RG 320 56 560 600 600 600 700 580 580 540 x 520 Ø 13
Material: St. 1203 Color RAL 7032: flint stone grey unpolished
G 1/11
G_TEIL_041019.qxd 19.10.2004 10:30 Seite 12
Custom makes
Apart from our standard stock program we design and manufacture custom
made specials. We assist to realize your ideas until initial operation and docu-
mentation has been reached.
Following some examples of power supply and testing
G 1/12
G_TEIL_041019.qxd 19.10.2004 10:30 Seite 13
Cabinet with galvanized, pre-assembled board, wall mounting (with accessories also floor setup), structured and
powder-coated surface, 100% polyester, tone RAL 7032,
Protection IP66 (IP55 for *2-door cabinets), safety against mechanical damage IK10, door easy to unhinge with
left hinge (right on request), 3 mm double bit lock, earthing screw M6x16 on door and cabinet body, pre-embos-
sed cable gland plates (on top for floor cabinet)
Custom makes: on request different tone, cable glands, earthing strips, transformer and accessories installed,
special labelling, safety- and other locks
Pedestal (100 mm U-sectional steel) re-inforced heavy-duty base plate for floor setup
Article no. Cabinet depth Article no. floor space Article no. floor space Article no. floor space
RGSO200 200 RGSP420 400x200 RGSP525 500x250 RGSP830 800x300
RGSO250 250 RGSP520 500x200 RGSP625 600x250 RGSP103 1000x300
RGSO300 300 RGSP620 600x200 RGSP825 800x250 RGSP640 600x400
RGSO400 400 RGSP425 400x250 RGSP630 600x300 RGSP840 800x400
Typical Typical
Current
Consumer Inrush / Rated Inrush- resp.
abating
Current Start-up time
Transformers 1) 10-40 ms rapid
Dynamo sheet core 0,5mm 10-18 fold
grain-oriented sheet 15-25 fold
Toroidal core transformer 30-50 fold
Commercial fuses and circuit breakers may be used when applying our inrush current limiters series RESBE and
RESBD.
Series RESBE and RESBD are part of our patent application "Inrush current limit including time controlled second swit-
ching element".
To eliminate bridging current rush the load on-period should be higher than the effective inrush current limit. If this is not
the case we recommend option "release output" for loads with release input resp. remote input / output.
ä
ä
rd/qf/09.04/2000
Michael Riedel
t
t
Transformatorenbau GmbH
i
i
Transformatorenbau GmbH
l
l
a
a
Produktion: www.querformat.info
u
u
Q
Q
r
r
ü
ü
f
f
w
w
o
o
h
h
-
-
w
w
o
o
n
n
K
K
s
s
a
a
d
d
n
n
e
e
b
b
Michael Riedel
a
a
2004
h
h
r
r
www.riedel-trafobau.de · info@riedel-trafobau.de
i
i
W
W