Escolar Documentos
Profissional Documentos
Cultura Documentos
For larger systems that support many loads, the requirements of all loads need
to be considered, as well as the potential interactions between them, to decide
the appropriate enhancement equipment and system construction.
Contents:
1. Isolation transformers
2. Noise filters
3. Harmonic current solutions
1. Passive harmonic filters
2. Phase-shifting transformers
3. Active harmonic filters
4. Transient voltage surge suppression
5. Voltage regulators
1. Tap Changers
2. Buck Boost
3. Ferroresonant constant voltage transformers
6. Power line conditioners
7. Computer power distribution units
8. Magnetic synthesizer
9. Motor – alternator / generators
10. Static transfer switches (STSs)
11. Standby power systems (SPSs)
12. Uninterruptible power supplies (UPSs)
1. Isolation transformers
Isolation transformers are one of the most widely used power correction
devices. Figure 1 depicts the configuration of an isolation transformer. They
incorporate separate primary (or input) and secondary (or output) windings.
Other positive and negative sequence harmonic currents are affected by the
30° fundamental frequency phase shift of the delta-wye transformer.
For example, the 5th and 7th harmonic load currents
are inverted, which can be beneficial in providing
cancellation of these harmonic currents at
the primary voltage level.
Simple shielding adds little to the cost, size, or weight of the transformer.
Go back to contents ↑
2. Noise lters
Most types of electronic equipment have some form of filters to limit the high-
frequency noise, usually needed to comply with Federal Communications
Commission (FCC) equipment emission limits.
Figure 3 – LC noise filter
The simplest form of filter is a “low pass” filter designed to pass 60 Hz voltage
but to block the higher frequencies or steep wavefront surges. These devices
contain series inductors followed by capacitors to ground. The inductor forms a
low-impedance path for the 60 Hz utility power, but a high-impedance path
to the high-frequency noise.
Go back to contents ↑
3. Harmonic current solutions
Passive harmonic current filters are used to prevent the harmonic currents of
nonlinear loads from being fed back into the power source where they cause
heating of conductors and transformers and corresponding voltage distortion.
The filter is placed in parallel with the load, and the filter is tuned for the lowest
predominant harmonic frequency generated by the load or observed in the
power system.
For diode rectifier nonlinear loads, there are significant levels of harmonic
currents without any appreciable fundamental reactive power (VARs).
A potential disadvantage of passive series-resonant harmonic filters in this
case is the leading power factor due to the fundamental VARs of the filter’s
capacitors. For changing loads, a stepped filter can be obtained that switches
in and out the requisite number of filter steps as the load increases or
decreases.
The filter eliminates the need for oversized neutral wires to handle the
combined triplen currents from the phases, and standard wiring practices can
be used.
Go back to contents ↑
Go back to contents ↑
Zigzag transformers
However, triplen harmonic currents continue to flow in all the wires downstream
of the zigzag transformer, and doubled neutrals or other harmonic current
coping means are still required.
Figure 6 – Zigzag auto transformer applied to divert triplen harmonic current flow
Go back to contents ↑
Thus a single transformer can cancel triplen, 5th, and 7th harmonic load
currents. Since the reduction in the harmonic currents is by cancellation, the
loading on each transformer output needs to be equal and balanced.
Go back to contents ↑
Active harmonic current filters are electronic devices that sense on a real-time
basis the harmonic load currents and inject equal and opposite harmonic
currents to cancel harmonic load currents. Figure 8 depicts a typical
implementation of an active harmonic current filter.
Harmonic current flows are generally reactive
current flows and require minimal levels of real
power to cancel.
Properly sized and designed active filters can correct the current
distortion to less than 1% total harmonic distortion. Active filters use
some power for their operation and are generally less efficient than
passive filters.
However, they can adapt to changing load conditions. Being electronic circuits,
they are inherently more complex and less reliable than passive filters and, to
date, have been significantly more expensive.
Figure 8 – Active harmonic current filter
Go back to contents ↑
4. Surge suppressors
The service entrance devices are intended to lower the energy level of a very
large surge to that which can be handled by other devices closer to the loads. If
improperly coordinated, excess energy can destroy the
downstream suppressors and damage the connected load equipment.
The smaller surge suppressors are generally simple, and relatively low-cost,
devices. They usually contain metal-oxide varistors, avalanche diodes, or other
voltage-clamping devices that are connected across the power line or from one
phase-voltage lead to another or to ground.
Because of their small size and low cost as compared with the equipment they
serve and the cost of determining if such surges exist at a given installation (or
even if this feature is already built into the computer itself), they are often
routinely used as low-cost insurance against the chance of severe surges.
The better units include fusing, agency listing, and surge capability in
the form of clamping voltages and energy ratings. Most of the lower-
cost units have limited ability to survive multiple large surges.
The bad thing is that SPD may fail without any indication, leaving the load
unprotected.
Go back to contents ↑
5. Voltage regulators
Most low-frequency voltage disturbances, except very deep sags or outages,
can be handled by appropriate application of a voltage regulator. There are a
number of types of voltage regulators in use today.
These units are not suitable to protect electronic loads against rapid changes in
voltage.
Go back to contents ↑
Fast response regulators divide into two generic classes: tap changers and
buck boost. The first is the tapchanging regulator shown in Figure 11.
Quality tap changers are designed to adjust for varying input voltages by
automatically transferring taps on a power transformer (either isolating type or
auto-transformer type).
Figure 11 – Tap-changing regulator
The number of taps determines the magnitude of the steps and the range of
regulation possible. An acceptable regulator should have at least four taps
below normal and two taps above normal for seven total steps. The taps are
typically in 4% to 10% steps, depending on specific designs.
Response time is usually less than two cycles and is limited to that speed
because of the zero current-switching and controls-stability criteria.
Go back to contents ↑
This is done by comparing the output voltage to the desired (set) level
and by the use of feedback to modify the level of boost or buck so
that the desired level is maintained.
A parametric filter provides a path for nonlinear currents generated by the load
and by the regulator itself and produces a sine wave output with low total
harmonic distortion.
Go back to contents ↑
Often these units can only supply 125% to 200% of their full load
rating. If inrush or starting currents exceed these limits, the output
voltage will be significantly reduced, which may not be compatible with
many loads.
The other devices on the output of the CVT will see this sag in the voltage and
may shut down due to an undervoltage. These devices should be oversized if
they are expected to provide for heavy starting or inrush currents or to provide
very deep sag protection.
Ferroresonant transformers create more audible noise than regular
transformers and may require special enclosures before they can be installed in
office environments.
Go back to contents ↑
Typical power line conditioners combine one or more of the basic power
correction technologies to provide more complete protection from power
disturbances.
Go back to contents ↑
The load cables are terminated with mating connectors for connecting to the
ITE. Some manufacturers include power conditioners such as tap changers,
motor – alternator / generator (M-Gs) sets, or magnetic synthesizers internal to
the PDU to further enhance performance.
The PDU greatly reduces the time required to install
the average information technology system and
allows for relatively easy relocation of equipment as
compared to hard wiring methods. This can translate
into significant cost and time savings.
The isolation provided by the transformer (or M-G) in the PDU allows
the creation of a separately derived source and common grounding point.
PDUs with internal voltage regulators can be used to reduce the effects of long
distribution feeds from central power conditioning or uninterruptible power
supply (UPS) equipment.
Go back to contents ↑
8. Magnetic synthesizer
These units draw power from the source and generate an output
voltage waveform by combining the pulses of the saturating transformers in a
step-wave manner.
They provide for noise and surge rejection and regulation of the output
voltage to within 5% over large swings in input, up to ±50%. These
units generally incorporate shielding into the pulse transformers to
attenuate common-mode disturbances.
Sudden large load changes, even within the unit’s rating, can cause significant
output voltage variations. These units are best applied when the load does not
make large step changes. The ferroresonant circuit has stored energy and may
ride through outages of one half-cycle or more depending on unit loading.
Magnetic synthesizers tend to be large and heavy due to the magnetics
involved and can be acoustically noisy without special packaging. Some of the
larger units display good efficiencies as long as they are operated at close to
full load.
Go back to contents ↑
9. Motor-alternator/generators
M-Gs provide the function of a line conditioner and can also provide for
conversion of the input frequency to a different frequency that is required by
the load. Figure 18 depicts one configuration of an M-G.
This totally mechanical coupling of the input and the output allows the M-G
to provide total electrical noise isolation of the load from the input power
source.
Although most of today’s computer power supplies can operate with a wide
range of frequency, some loads may be frequency sensitive (e.g., ±0.5 Hz
tolerance). For critical frequency applications, low slip induction motors or
synchronous motors should be used.
The output frequency of a synchronous M-G is the same as the input frequency.
However, the synchronous M-G output voltage is not in-phase with the input
power source and varies proportionate to the loading. Uninterrupted transfers
between the M-G and bypass source for maintenance must accommodate the
varying output phase angle of the M-G.
[/info_box]M-Gs protect the load from voltage sags, swells, and surges. For
short-term power line voltage changes of ±20% to ±50%, voltage to the load is
still maintained at nominal. A useful feature of the M-G is its ability to bridge
severe short-term deep sags or outages.[/info_box]
Products are available that are able to maintain output frequency even while the
shaft speed is slowing down. These devices do not have fixed poles in the
generator. Instead, the poles are created or “written” as the device rotates.
When input power is lost and the shaft speed starts to decay, the spacing of
the poles is reduced and their number is increased so that the frequency
remains constant.
This method achieves ride-through times that are significantly longer than other
M-G sets with the same rotating energy at the cost of increased complexity and
lower efficiency.
Also both input sources need to be nominally available so that the STS has an
alternate source available to transfer to in case of switch failure (analogous to
having a bypass source available for UPS systems).
STSs have been applied at both the medium (up to 34 kV) and low (<600 V)
voltages.
As with most power conditioners, application as
close to the protected load as possible yields the
greatest protection.
Go back to contents ↑
Standby power supplies are back-up power systems in which the load is
normally supplied by the input power source. Figure 20 shows one
configuration of the standby power supply.
The standby power supply only supplies the load when the input
power source is determined to be not acceptable.
These power systems are intended for loads that can tolerate a discontinuity of
power during the transfer. They come in a number of configurations using a
number of technologies and are used for a variety of loads ranging from
personal computers to emergency lighting.
The design of this type of supply allows several economies. First, the inverter is
not supporting the load on a continuous basis. It only has to operate for the
duration of the power outage or for the support time of the batteries.
The quality of the inverter output waveform is generally less than for an on-line
UPS. Second, the rectifier section only has to recharge the battery and not
support the full load of the inverter.
Normal operating efficiency of this type of unit is high since the load is being
fed from the utility under normal operation. The losses are those associated
with the line conditioning element (if used) and the battery charging circuit.
A major requirement of this type of unit is its ability to sense all types of power
failures and transfer to the inverter without an unacceptably long input-power
loss to the load equipment.
A common enhancement of the standby power supply involves the use of some
form of power conditioner in series with the load to provide conditioning of the
supply voltage during normal operation as shown in Figure 21 above.
The conditioner can be one of the types that were previously discussed.
Most commonly available standby power supplies use some form of
transient voltage surge suppression and/or noise filtering. Another
variation of the standby power supply uses a tap changer that powers
the load under normal operation to provide some voltage regulation.
Continuous regulated output power can be achieved by this method if the line
conditioner has sufficient ride-through to power the load during the interruption
time.
Go back to contents ↑
Go back to contents ↑
About Author
Edvard Csanyi