Design of Concentrically Loaded Isolated Footing According to ACI 318-08

+Y
Input Data:
3 2
Material Properties:
Conc. Comp. Strength, fc'= 20.70 Mpa L/2
Reinf. Yeild Strength, fy= 414.00 Mpa
Concrete Unit Wt., gc= 16.00 kN/m^3
+X
Lcy B
Soil Properties: y
Allow. Soil Pressure, SBC = 240.00 kPa Lcx B/2 Bar Diameter
Soil Unit Weight, gs = 15.40 kPa
Depth of Trench, D = 1.20 m
4 L 1
Footing Info:
Footing Length, L = 2600 mm
Footing Width, B = 2400 mm Footing Plan
Footing Thickness, T = 550 mm
Clear Cover, Cc = 75 mm
Reinforcing Bar Diameter = 16 mm Pu

Column Info: Interior


Column Length, Lcx= 300 mm
Column Width, Lcy= 300 mm Q Effective Soil Pressure=
Location along X= 0 mm Required Area=
Location along Y= 0 mm Lcx h
Ph
Loading Data: D
Service Dead Load, D= 650.00 kN (Working) T
Service Live Load, L= 575.00 kN (Working) Wide-beam Action:
Service Surcharge, Q= 5.00 kPa
q
Earthquake Axial Load, E= -100.00 kN (Working)
Wind Axial Load, W = 25.00 kN (Working) L
Col. Horizontal Load, Ph = 120.00 kN (Ultimate)
Nomenclature
USD Load Combinations:
Case 1: 1.4D = 910.00 kN (ACI 318-08 Eq. (9-1)) Two-way Action:
Case 2: 1.2D + 1.6L = 1,700.00 kN (ACI 318-08 Eq. (9-2)) Tributary Area=
Case 3: 1.2D + 1.0E + 1.0L = 1,255.00 kN (ACI 318-08 Eq. (9-4))
Case 4: 1.2D + 1.6W + 1.0L = 1,395.00 kN (ACI 318-08 Eq. (9-5))

Design Procedure: q(net)

Check Soil Bearing Capacity:


Column Working Load, Rv = 1,150.00 kN
Working Bearing Pressure, qv = 184.29 kPa Min
Demand-Capacity Ratio, D/C = 0.85 < 1, …OK (Footing is adequate to carry the loadings)
Design for reinforce
Applied Ultimate Soil Bearing Pressure: Square:
Ultimate Axial Load, Pu = 1,700.00 kN
Ultimate Bearing Pressure, qu = 272.44 kPa

r(gross area)=
r(gross area)=

1 Developed by: Engr. Richard C. Fernandez


Project Name:
Client:
Location:
Designed by: Checked by:
Subject: Date:
Design of Concentrically Loaded Isolated Footing According to ACI 318-08
r(min)=

2 Developed by: Engr. Richard C. Fernandez


Project Name:
Client:
Location:
Designed by: Checked by:
Subject: Date:
Design of Concentrically Loaded Isolated Footing According to ACI 318-08
As along L span=
Design Checks: c1+d As along B span=
1. Wide-beam action along L-Direction
Vu = qs x tributary area No. of Bars=
= 441.35 kN As(act)=
fVc = f0.17l√fc'bwd (ACI 318-08 Eq. (11-3)) Check Net Tensile strain:
= 661.30 kN > Vu = 441.35 kN O.K.
2. Wide-beam action along B-Direction
Vu = qs x tributary area bw c2+d c2
= 407.29 kN
fVc = f0.17l√fc'bwd (ACI 318-08 Eq. (11-3))
= 716.41 kN > Vu = 407.29 kN O.K.
2. Two-way action (Punching Shear)
Vu = qs x tributary area
=1,503.17 kN
fVc = f0.17(1+(2/b))l√fc'bod (ACI 318-08 Eq. (11-31)) d c1
= 2,562.55 kN r(gross area)=
fVc = f0.083(((asd)/bo)+2)√fc'bod (ACI 318-08 Eq. (11-32)) Tributary area for two-way action shearr(gross area)=
= 3,390.15 kN As along L span=
fVc = f0.33lfc'^1/2*bod (ACI 318-08 Eq. (11-33)) Tributary area for wide-beam action shear
As along B span=
= 1,658.12 kN gover > Vu = 1,503.17 kN O.K. No. of Bars=

Check Spacing:
Design for Reinforcement:
1. For L-Direction 2. For B-Direction Max. Sp=
Mu = 432.36 kN-m Mu = 390.47 kN-m No. of Bars=
a= 25.63 mm a= 25.63 mm No. of Bars=
b1 = 0.85 (ACI 318-08 Sec.10.2.7.3) b1 = 0.85 (ACI 318-08 Sec.10.2.7.3)
c= 30.15 mm c= 30.15 mm
et = 0.0443 >= 0.004, Tension-controlled et = 0.0443 >= 0.004, Tension-controlled
For Rectangular footing:
f= 0.90 (ACI 318-08 Sec. 9.3.2) f= 0.90 (ACI 318-08 Sec. 9.3.2)As along L span=
Rn = 0.89 Mpa Rn = 0.74 Mpa No. of Bars=
r = 0.00220 r = 0.00183 As(act)=
r(gross area) = 0.00190 > rho(min) O.K. r(gross area) = 0.00158 < rho(min), use rho(min)
Check Net Tensile strain:
r(min) = 0.00182 (ACI 318-08 Sec.15.10.4) r(min) = 0.00182 (ACI 318-08 Sec.15.10.4)
As = 2507.80 mm^2 As = 2244.18 mm^2

r(gross area)=
As along L span=
No. of Bars=

Check Spacing:

Max. Sp=
Critical Section of Bending Along L-Direction Critical Section for Bending Along B-Direction No. of Bars=
No. of Bars=

As1=
As2=
No. of Bars for As1 =

3 Developed by: Engr. Richard C. Fernandez


Project Name:
Client:
Location:
Designed by: Checked by:
Subject: Date:
Design of Concentrically Loaded Isolated Footing According to ACI 318-08
No. of Bars for As2 =

4 Developed by: Engr. Richard C. Fernandez


Project Name:
Client:
Location:
Designed by: Checked by:
Subject: Date:
Design of Concentrically Loaded Isolated Footing According to ACI 318-08
Total No. of Bars =
Design Summary:

Footing Plan

Footing Size:
Use 2.40 m x 2.60 m x 0.55 m Footing Dimension.
Reinforcements:
Use 13 pcs 16 mm diam. RSB for Long Direction.
Use 13 pcs 16 mm diam. RSB for Short Direction

Note: Maximum bar spacing (s), must not exceed 450mm (ACI 318-08 Sec.15.10.4).