Escolar Documentos
Profissional Documentos
Cultura Documentos
Introduction
• Calculating the volume correction factor at the tank to calibrate oil meters
The oil flow meter at the separator is not 100% correct. When oil leaves the separator, it still contains
some gas. In addition, the meter may not be correctly calibrated. By comparing the volume reading at the oil
meter with the actual volume measured at the tank, a correction factor can be obtained. This correction
factor, referred to as the "meter combined shrinkage" factor, reflects two adjustments:
• Meter factor
This is a calibration measurement that reflects the meter's inaccuracy.
• Shrinkage factor
The difference in the oil volume read at the separator and the volume measured at the tank is also due to
the loss of gas when the oil is exposed to the atmospheric pressure in the tank. This loss of volume is called
the shrinkage factor. The pure shrinkage factor is measured at the separator using a shrinkage tester.
Principles of Operation
This topic lists the main components of the surge tank and describes how the tank is used to calibrate
meters. Click on the graphic or scroll down for detailed information on each component.
Surge Tank Components
The safety relief valve incorporates a bellows seal that prevents surge tank fluid discharge from
entering the upper part of the valve that's exposed to the atmospheric pressure. The bellows has an effective
area equal to the area of the valve seat so the effect of any back pressure from the valve outlet on set
pressure is eliminated.
The set pressure is the pressure at which you want the safety relief valve to open. The set pressure is
adjusted by the force of a spring on a sealing disk that is exposed to surge tank pressure.
Sight Glass
The sight glass is a visual level indicator. A graduated scale permits level changes to be recorded and
volume changes to be calculated. The sight glass is made of transparent glass housed in a steel chamber to
resist the pressure inside the tank. In the event the glass ruptures, the safety glass is equipped with safety
valves that prevent fluids inside the surge tank from escaping.
The safety valve works using a ball that automatically seals off the tank from the sight glass using
the pressure differential between the tank and the atmosphere. After a broken glass is changed, the ball
needs to be pushed back in its groove so it can seal off the surge tank from the sight glass, in case another
failure occurs. Use the stem tip to push the ball back by moving the handle about one quarter turn. Once the
ball is in position, turn the handle back to return the stem to its original position.
Alarm Level System
This system has a low and a high level alarm system. A horn sounds if the liquid in the tank reaches
the low or the high level. Whenever an alarm sounds, the liquid levels are adjusted manually. So safe
operation of the surge tank requires constant supervision of liquid levels. To be able to run in fully
automatic mode, this alarm system must be connected to the ESD or to a pump.
Flame Arrestor
The job of this optional safety device, mounted on the gas vent line as close as possible to the surge
tank gas outlet, is to stop a fire from propagating inside the tank. It is equipped with steel wool to stop a
flame and to ensure that no oil droplets are carried away with the gas.
Butterfly Valves
The inlet and outlet manifold of the tank are equipped with butterfly valves. These valves are used to
fill or empty the tank.
Grounding Strap
The surge tank is grounded with a grounding strap, allowing static electricity to be discharged, so
flashes can be avoided. The build up of static charges of electricity may be caused by the friction from
flowing fluids. Onshore, the strap is connected to an iron stake driven into the ground. Offshore, it's
connected to a spot on the rig that's free of paint or grease.
For safety purposes, the ACV is normally open. If for any reason the air pressure supply to the valve
is cut, the vessel will not be overpressurized. For a complete descripton of the system, see the gas pressure
controller in the Separator Training page.
Nonreturn Valve
This valve is fitted on the gas vent line. It is mounted downstream of the automatic control valve. It
is closed when there's no pressure in the surge tank. The nonreturn valve prevents any back-pressure from
entering the tank, causing the pressure inside the tank to increase above the maximum working pressure.
Calibration of Meters
Technical and economic considerations related to the development of a new reservoir may depend
on the accuracy of oil flow rates. Incorrect flow rates could cause the client to make incorrect decisions
about the well, which could have very expensive implications.
As explained in the introduction, the oil flow meters at the separator are not 100% correct. It is
important to verify their degree of accuracy. A simple method consists of pumping water through the meter
to be calibrated into a tank of known dimensions. A correction factor called the meter factor (f) is obtained
by dividing the volume of water in the tank by the volume registered on the meter.
The meters on the oil flow line operate under pressure. Gas bubbles in the oil cause the oil meter to
register volume readings that are altered by the presence of the gas. To correct the volume reading at the oil
meter, a correction factor is derived by comparing the volume reading at the oil meter with the volume
measurement obtained at the tank. The volume correction factor is also referred to as the "meter combined
shrinkage" factor.
The following steps are needed to accurately and safely use the surge tank to calculate the volume
correction factor:
2. Divert the oil flow to the tank and simultaneously take a meter reading at the oil flow line and record
the time.
3. Verify that the level of oil in the tank is rising. (This tells you that oil from the separator was
diverted and is flowing properly.)
5. Check frequently at the gas vent line outlets for liquid or foam carryover. To avoid carryover, do not
allow more than 80% of a tank compartment to be filled.
6. Divert the oil flow back to the burners and simultaneously take a meter reading at the oil flow line
and record the time.
7. Before taking the final tank reading, wait until all the gas has escaped from the oil.
8. The volume correction factor is simply the ratio between the volume obtained in the tank and the
volume registered by the meter.
Note:
At the time the final tank reading is taken, the tank temperature is also recorded. A correction for
temperature (temperature coefficient) is applied in order to report flow rates at standard conditions: 14.65
psi (atmospheric) and 60oF.
Equipment
Surge tanks are available in 80- and 100-barrel capacity, although the 80-barrel version is the most
common. The 80-barrel version has one compartment and a working pressure of 50 psi. The 100-barrel
version has two compartments and a working pressure of 150 psi. The range of surge tanks available makes
it possible to select a surge tank that accommodates the required well tests while not being larger, more
complicated or expensive than the overall project demands.
1. Whenever H2S is expected to be in the well effluent, a surge tank must be used instead of a gauge
tank.
2. Before diverting the separator oil to the surge tank, you must check the ability of the gas vent line to
discharge the full volume of gas liberated without creating a back pressure greater than the
maximum pressure rating of the vessel.
3. Refer to the charts in the Tank Operations chapter of the Field Operating Handbook (FOH) for
Surface Well Testing.
4. When diverting the oil to the tank, always limit the flow rate to avoid filling the tank too rapidly. In
case of high flow rates, someone should constantly monitor liquid levels and be ready to divert flow
back to the burners to prevent overflow.
5. Prior to conducting any repair inside the tank, it must be steam cleaned and degassed. The person
repairing the tank must be in constant contact with a person on the outside of the tank.
6. Transport the surge tank when it is empty; even a partially full tank has a much higher weight than
an empty tank.
7. The exhaust for the safety relief valve must be connected to a 4-in. pipe landing that must be located
downstream and far away from the working area.
Self Test