120 THK.

SLAB
1900 BEAM (230X300)
1600
DETAIL 'X'

300
120
15 THK. CEMENT PLASTER
IN 1:4 CM
1700

1580
COLUMN
+550 FGL IN ELECTRICAL YARD +550 FGL IN ELECTRICAL YARD
SECTION 'A-A'
SECTION 'B-B'
LV SIDE B
230 T
16 Nos. 8 O T
(8+4) Nos. 8 O
230 1440 T
4 Nos. 12 O (ONEWAY) ALL STRAIGHT 400
COLUMN

230
(230X230) STIRRUPS 8 T
O
@ 200 C/C
1600

80
120
DETAILS OF
A COLUMN
1600

A B1 B1
S1
X X
REINFORCEMENT DETAIL OF SLAB (DETAIL 'X')
230 T TOP
3 Nos.12 O
SLAB DETAILS:- BEAM DETAILS:- COLUMN DETAILS:-
S1- ONE WAY SLAB - 120 THK. B1 - 230X300 SIMPLY SUPPORTED SIZE - 230X230 - 4 No.
T T
BTM BARS - 3 - 12 O T

300
MAIN STEEL- 16 No. 8 O MAIN REINF. - 4 - 12 O
T @ 150 C/C
STIRRUPS 8 O
T
TOP BARS - 3 - 12 O
B DISTRIBUTION STEEL - (8+4) No. 8 T
O RING - 8 OT @ 200 c/c
1900 T @ 150 c/c
STIRRUPS - 8 O
HV SIDE 3 Nos.12 T
O BOTTOM
ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE STATED,,DO NOT SCALE THE DRAWING,ASK IF IN DOUBT
DETAILS OF
PLAN BELOW SLAB LEVEL BEAM (X-X) SUZLON ENERGY LTD. Subject :
Godrej Millenium Bldg, 5th Floor, TRANSFORMER PLINTH OF 2100 KW WTG
9, Koregaon Park, Pune - 411 001
NOTES :- Tel No.020-40122000 Fax No. 020-40122100 FOR MAHARASHTRA SITES
1) THE STARTER BARS FOR COLUMN SHOULD BE TAKEN Date Sign Description :
FROM THE RAFT FOUNDATION REINF.
Appd.by PLAN & SECTIONAL ELEVATION
2) TOTAL LENGTH OF LADDER = 1.90 m.
Revd. by
3) CLEAR COVER TO REINFORCEMENT IN SLAB, COLUMN & BEAM = 20mm. Sht.No.
Chd. by Drawing No: PEC.2100.48.36.EC.D.01
4) ALL RCC SHALL BE OF 1:1.5:3 AS PER VOLUMETRIC MIX. 1/1
Drn. by Ref. Drg No : Rev. 00