3Ø, 200~600VAC, 1–200HP


MULTI-CONTACTOR STARTER
FOR 2-SPEED MOTORS

HAND-OFF-AUTO AND LOW-OFF-HIGH SWITCHES


ON THE DOOR POWER, MONITORING CAPABILITIES

The Starter for 2 Speed Motors.


Using our advanced SCM platform, this patent-pending motor controller integrates timers, controls, overloads and
everything necessary for a complete starter. Plus, power monitoring, motor protection and more make the MCS
unmatched in performance and features.

Integrated Tru-power™ electronic motor Advanced programmable motor control


protection • Automatic fault reset
• Eliminates need for costly motor protection relays • Backspin delay - Prevents start-up while system is draining
• Underload detection using power (nuisance trip-free); • On and Off delay settings
automatic restart for well recovery mode • Well recovery mode (up to 48 hours)
• Wide range class 5-30 electronic overload eliminates • Minimum run time based on last input
call backs due to mis-sized heaters • 12-120 V input for remote start/stop
• Advanced protective features include over/under voltage, • Dry contact input for remote start/stop
phase loss/unbalance, stalled/locked rotor, cycle fault and
UL 1053 ground fault
Optional circuit breaker disconnect
• UL 489 circuit breaker provides branch and short
circuit protection
Built-in power monitoring and fault • No fuses required – saves time and money
logging for easy troubleshooting • Lockable handle for safety
• Last 15 fault types are recorded (e.g. underpower, overload, Integrated controls
voltage/current loss/imbalance, etc.)
• All power condition values are stored • Patent pending design: One overload with two
overload set-points reduces cost and complexity
Internal keypad menu for easy operation • SCM power monitoring technology provides superior
overload protection for all motor windings
• All control and protective functions are easily programmable
• All settings are done from one easy to use plain
English display and keypad
Industrial grade construction for long life
• Door mounted heavy-duty HOA switch
• Housed in an outdoor rated, gasketed, NEMA 3R enclosure
• Multi-tap control power transformer with integrated
secondary protection accommodates common motor
voltages. No fuses required.
• Includes 120 VAC control power for field devices
• NEMA/IEC rated magnetic contactors feature 2.5 million
electrical cycles at full rated current

www.franklin-controls.com | 1.800.962.3787
MCS Wiring Diagram
Ordering and Sizing Information

UL TYPE 4 2 SPEED 1 WINDING MOTORS


STANDARD MAGNETIC H-O-A STARTERS - Electronic Overload
HP
Three Phase NEMA 2 Speed 1 Winding
Size Reconnectable Part Number
200V 230V 460V 600V*
2 3 5 7.5 00 MCS4-2R-S00/J-9
5 7.5 10 15 0 MCS4-2R-S0/J-18
7.5 10 20 25 1 MCS4-2R-S1/J-32
20 25 40 50 2 MCS4-2R-S2/J-50
30 40 60 75 3 MCS4-2R-S3/J-85

UL TYPE 3R AND 4 2 SPEED 2 WINDING MOTORS


STANDARD MAGNETIC H-O-A STARTERS - Electronic Overload
HP
NEMA 2 Speed 2 Winding in 2 Speed 2 Winding in
Three Phase Type 3R Enclosure Type 4 Enclosure
Size
200V 230V 460V 600V*
2 3 5 7.5 00 MCS3R-2S-S00/J-9 MCS4-2S-S00/J-9
5 7.5 10 15 0 MCS3R-2S-S0/J-18 MCS4-2S-S0/J-18
7.5 10 20 25 1 MCS3R-2S-S1/J-32 MCS4-2S-S1/J-32
20 25 40 50 2 MCS3R-2S-S2/J-50 MCS4-2S-S2/J-50
30 40 60 75 3 MCS3R-2S-S3/J-85 MCS4-2S-S3/J-85

* For 600V part numbers please consult


factory. ++ For starters over NEMA Size 3
consult factory.

www.franklin-controls.com | 1.800.962.3787
Ordering and Sizing Information Continued

UL TYPE 3R AND 4 (2 SPEED 2 WINDING & PART WINDING MOTORS)


COMBINATION MAGNETIC H-O-A STARTERS - Electronic Overload
HP
Three Phase NEMA 2 Speed 2 Winding in Type 2 Speed 2 Winding in Type
3R Enclosure 4 Enclosure
208V 230V 460V 600V* Size
- - 3/4 3/4 MCS3R-2S-S00/J-G1.6 MCS4-2S-S00/J-G1.6
1/2 1/2 1 1.5 MCS3R-2S-S00/J-G2.5 MCS4-2S-S00/J-G2.5
3/4 3/4 2 3 00 MCS3R-2S-S00/J-G4 MCS4-2S-S00/J-G4
1 1.5 3 5 MCS3R-2S-S00/J-G6 MCS4-2S-S00/J-G6
2 2 5 5 MCS3R-2S-S00/J-G8 MCS4-2S-S00/J-G8
2 3 5 7.5 MCS3R-2S-S0/J-G10 MCS4-2S-S0/J-G10
3 3 7.5 10 0 MCS3R-2S-S0/J-G13 MCS4-2S-S0/J-G13
3 5 10 15 MCS3R-2S-S0/J-G17 MCS4-2S-S0/J-G17
5 7.5 15 20 MCS3R-2S-S1/J-G22 MCS4-2S-S1/J-G22
7.5 7.5 15 20 1 MCS3R-2S-S1/J-G26 MCS4-2S-S1/J-G26
7.5 10 20 25 MCS3R-2S-S1/J-G32 MCS4-2S-S1/J-G32
10 10 30 30 MCS3R-2S-S2/J-G40 MCS4-2S-S2/J-G40
2
15 15 30 40 MCS3R-2S-S2/J-G50 MCS4-2S-S2/J-G50
20 25 50 60 MCS3R-2S-S3/J-G75 MCS4-2S-S3/J-G75
3
30 30 60 MCS3R-2S-S3/J-G90 MCS4-2S-S3/J-G90

Dimensions
*All measurements in inches

W D

Starter Size H W D
Size 1, Size 2 22.25 15 9.72
Size 3, Size 3+, Size 4 32.24 15.2 9.72
Size 5 42 30 12
Specification
Starter Type
Multi-Contactor Starter
Standard and Combination - Service Rated Available, Suitable for use as a Service Disconnect
NEMA Type 3R, 4 Enclosed
User Interface
Settings Adjustments Internal
Hand-Off-Auto Door mounted 3-position switch
Standard Control Operations
Voltage Auto Accepts 12-130VAC/DC. Applying voltage will send a run command to the starter when in Auto mode.
Dry Contact Auto Normally Open dry contact. When closed, the starter will be commanded to run when in Auto mode.

Inputs Applying voltage will open the contactor and the starter will not accept a run command
Shutdown
Hand/Off/Auto LEDs will flash.
Normally Open dry contact. To be used in series with customer provided actuator contacts which disable the motor starter
Actuator Position Switch
until the actuator is in position. (ie. The contactor will not close unless this contact is closed)
Status Relay Normally Open relay contact, 0.3A @ 125VAC, 1A @ 24VAC
Outputs Fault Relay Normally Open relay contact, 0.3A @ 125VAC, 1A @ 24VAC
Actuator Power 120VAC, 0.25A max.
Overload Type Electronic, I2t trip curve
Restart in last mode (Hand/Off/Auto) with no delay (default)
Power Fail Modes Restart in Off mode
Operational
Restart in Off mode if power failure lasts longer than 2 seconds. Restart in last mode if power failure is less than 2 seconds.
On/Off Time Delay On/Off, Adjustable: 0.1-99 seconds
Fault Reset Adjustable: Manual or Automatic (default differs per motor protection feature)
Environmental
Ambient Operating Temp -5° to 140° F (-20° to 60° C)
Ambient Storage Temp -5° to 185° F (-20° to 85° C)
Relative Humidity 5% to 95% non-condensing
Motor Protection Adjustment / Description Default Setting
Overload Current Setting Range Differs per model Per SFA
Overload Trip Class Adjustable: 5-30 10
Overload Service Factor Adjustable: 0.00-2.00 1.15
Under Power On/Off, Adjustable: 0-99% of measured electrical input On / 60%
Over Power On/Off, Adjustable: 101-200% of measured electrical input On / 120%
Over / Under Voltage On/Off, Adjustable: +5-25% over/under the nominal voltage setting On / 10%
Voltage Phase Unbalance On/Off, Adjustable: 1-20% voltage phase deviation On / 3%
Voltage Phase Loss Always On, Adjustable: 1-50% voltage phase deviation 10%
Voltage Phase Sequence Reversal On/Off, Trips within 0.1 seconds upon voltage phase reversal detection On
Ground Fault (UL 1053 Certified) On/Off, Adjustable: 1.0-9.9A On / 1A
Cycle Fault On/Off, Adjustable: Trip if cycle rate exceeds 20 starts/minute On
Warm Start Provision On/Off, Delays motor restart based on calculated motor temperature On
Protection Adjustment / Description Default Setting
Current Phase Unbalance On/Off, Adjustable: 1-50% current phase unbalance On / 5%
Locked Rotor / Stall On/Off, Trips within 0.5 seconds On