2 Open Circuit Cooling Tower + 3 2500 2,400 3 2000 5.0 19,200 21,600 180 1,0a
Water Cooled Chillers
4 Dry Cooler+Air Cooled Chillers 6 1000 Dry Cooler 12 1000 3.0 64,000 64,000 0 4,8a
5 Adiabatic Air Cooled Chillers - - - 6 1000 3.8 25,263 25,263 0.02 4,6a
From the data gained from literature and manufacturers are:
For Open Circuit Cooling Towers, evaporation loss rate is %0,6 of pumped water flowrate, drift loss is %
For Closed Circuit Cooling Towers, evaporation loss rate is %1,0 of pumped water flowrate, drift loss is
Tower Total Water Evaporation Evaporation Drift Loss Drift Loss Blowdown Blowdown
Quantity Flowrate Loss Rate Loss Total Rate Total Loss Rate Loss Total
- m3/h % m3/h % m3/h % m3/h
3 1290 0.6 7.74 0.02 0.26 0.250 3.23
3 1290 1.0 12.90 0.02 0.26 0.025 0.32
16 hours
Total Loss Operation
m3/h m3/24h
11.22 180
13.48 216