Worldwide

www.tyco-fire.com
Contacts

RAVEN 5.6K Institutional Sprinklers


Pendent and Horizontal Sidewall
Quick Response, Standard and Extended Coverage
General NOTICE
RAVEN Institutional Sprinkler s
Description described herein must be installed
and maintained in compliance with
TYCO RAVEN 5.6K Institutional this document and with the applica-
Pendent and Horizontal Sidewall ble standards of the NATIONAL FIRE
(HSW) Sprinklers are quick response PROTECTION ASSOCIATION (NFPA),
spray sprinklers designed for use in in addition to the standards of any
areas such as correctional, deten- authorities having jurisdiction. Failure
tion, and mental health care facilities to do so may impair the performance
as well as other commercial buildings. of these devices.
Both the pendent and horizontal side-
wall styles are available for Standard Johnson Controls specifically dis-
Coverage (light and ordinary hazard) claims any liability for damages or
or Extended Coverage (light hazard) injury (including death) arising out of or
applications. caused by manipulation, dismantling,
or misuse of RAVEN Institutional Sprin-
• The assembly is designed with tam- klers or the use or attempted use of the
per-resistant features to help prohibit RAVEN Institutional Sprinklers or any
a false activation. component thereof as an instrument
• This sprinkler is designed to operate unrelated to its intended function as a
when the Inner Link (Ref. Figure 1) is fire protection device.
removed manually. While the design The owner is responsible for main-
of this sprinkler makes manual taining their fire protection system
removal of the Inner Link less likely, and devices in proper operating con-
this feature negates the possibility of dition. Contact the installing contrac-
a tampered sprinkler placed in a con- tor or product manufacturer with any
dition where it would not operate in questions.
the event of a fire due to prior part
removal.
• This protected, unobtrusive design
Sprinkler
helps reduce the opportunity for indi-
viduals to injure themselves or oth-
Identification
ers with piecemeal components of
the sprinkler.
Numbers (SINs)
SIN DOT APPLICATION
• The flush design is aesthetically COLOR*
appealing by concealing all operat-
ing parts. TY3281 Black Pendent
Standard Coverage
TY3282 Green Pendent
Extended Coverage
IMPORTANT TY3381 Red HSW
Refer to Technical Data Sheet Standard Coverage
TFP2300 for warnings pertaining to
regulatory and health information. TY3382 Purple HSW
Extended Coverage
Always refer to Technical Data
* Refer to Figures 1 through 4 for SIN Color Dot
Sheet TFP700 for the “INSTALLER location.
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 10 AUGUST 2018 TFP651


TFP651
Page 2 of 10

1/2"
NPT

7/16"
(11 mm)
1-13/16" NOMINAL ESCUTCHEON
SPRINKLER
(46 mm) MAKE-IN PLATE MOUNTING
BODY
SURFACE

LINK
ASSEMBLY

SIN COLOR 5/8" * DEFLECTOR ESCUTCHEON


DOT LOCATION SPRINKLER (16 mm) ASSEMBLY PLATE
OPERATED
(VISIBLE BEFORE AND WRENCHING IN OPERATED SIDE VIEW (SELECT PER
SIDE VIEW
AFTER COMPLETED NOTCHES POSITION FIGURE 5)
INSTALLATION)

* DIMENSION WITHOUT MAXIMUM OF


OUTER 2 ADJUSTMENT SPACER RINGS;
LINK EACH SPACER PROVIDES ADDITIONAL
5/64" (2 mm) OF ADJUSTMENT.
1-3/8" DIA.
(35 mm)
** ORIENTATION OF INNER LINK TO
OVERALL SPRINKLER ASSEMBLY,
INCLUDING SPRINKLER WRENCHING
NOTCHES, MAY VARY.
INNER **
LINK
BOTTOM VIEW
FIGURE 1
RAVEN INSTITUTIONAL PENDENT SPRINKLER
NOMINAL INSTALLATION DIMENSIONS

Technical
Data
Approvals
UL and C-UL Listed
Maximum Working Pressure
175 psi (12,1 bar)
Inlet Thread Connection
1/2 in. NPT
Discharge Coefficient
K=5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
Temperature Rating
165°F (74°C)
Finish
Sprinkler: White or Grey
Escutcheon: White, Grey, Chrome Coated
(Carbon Steel only), or Electropolished*
(Stainless Steel only)
Physical Characteristics
Body �����������������������������������������������������������Brass
Deflector Assembly �����������������������������������Bronze
Sealing Assembly. . Beryllium Nickel w/TEFLON
Link Assembly ������������������������������������������ Copper
Escutcheon ���������������������������������Carbon Steel or
Stainless Steel
* Chrome-coated appearance
TFP651
Page 3 of 10

2-1/8" SIN COLOR 1-3/8" DIA.


(54 mm) DOT LOCATION (35 mm)
(VISIBLE BEFORE AND
7/16" (11 mm) AFTER COMPLETED ENCLOSED
NOMINAL MAKE-IN INSTALLATION) DEFLECTOR

OUTER
LINK LINK
ASSEMBLY

INNER *
LINK

SPRINKLER
1/2" WRENCHING
NPT NOTCHES
SIDE VIEW FRONT VIEW

3/4" **
(19 mm) * ORIENTATION OF INNER LINK TO
OVERALL SPRINKLER ASSEMBLY,
INCLUDING SPRINKLER WRENCHING
NOTCHES AND TOP OF DEFLECTOR,
ESCUTCHEON MAY VARY. DO NOT USE INNER LINK
PLATE MOUNTING TO DETERMINE TOP OF SPRINKLER
SURFACE DEFLECTOR ORIENTATION; REFER
SPRINKLER
BODY TO FIGURE 4.

** DIMENSION WITHOUT MAXIMUM OF


2 ADJUSTMENT SPACER RINGS;
EACH SPACER PROVIDES ADDITIONAL
7/16"
5/64" (2 mm) OF ADJUSTMENT.
(11 mm)

CENTERLINE
OF SPRINKLER
WATERWAY

DEFLECTOR ASSEMBLY
IN OPERATED POSITION

ESCUTCHEON PLATE
(SELECT PER
FIGURE 6)

OPERATED SIDE VIEW


FIGURE 2
RAVEN INSTITUTIONAL HORIZONTAL SIDEWALL SPRINKLER
NOMINAL INSTALLATION DIMENSIONS
TFP651
Page 4 of 10

SIN COLOR DOT


SPRINKLER FITTING NOMINAL DIA.
LOCATED AT PROPER 1/32" (0,7 mm)
DEPTH FROM AND (NOTE 1)
PERPENDICULAR TO MOUNTING
MOUNTING SURFACE SURFACE

CLEARANCE
HOLE

RAVEN
ESCUTCHEON
PLATE
LINK
ADJUSTMENT ASSEMBLY
SPACER RING
(AS NECESSARY NOTE:
MAXIMUM 2)
1. SIN (SPRINKLER IDENTIFICATION
NUMBER) COLOR DOT INDICATES:
RAVEN
PENDENT COLOR SIN APPLICATION
SPRINKLER BLACK TY3281 PENDENT
STANDARD
COVERAGE
W-TYPE 25 SPRINKLER PROTECTIVE CAP
WRENCH REMOVED ONLY AT INSTALLATION GREEN TY3282 PENDENT
LINK (TO REMOVE, PULL CAP STRAIGHT EXTENDED
ASSEMBLY WITHOUT BENDING IT) COVERAGE

DISREGARD
FOR PENDENT
APPLICATION

WRENCH PRONGS
UNIQUELY SPACED TO
ALIGN WITH SPRINKLER ACCEPTS
WRENCHING NOTCHES 1/2" DRIVE
SPRINKLER WRENCH
BOTTOM VIEW BOTTOM VIEW
FIGURE 3
RAVEN INSTITUTIONAL PENDENT SPRINKLER
INSTALLATION WITH W-TYPE 25 SPRINKLER WRENCH
TFP651
Page 5 of 10

SPRINKLER FITTING
LOCATED AT PROPER SPRINKLER PROTECTIVE CAP
DEPTH FROM AND REMOVED ONLY AT INSTALLATION
PERPENDICULAR TO (TO REMOVE, PULL CAP STRAIGHT
MOUNTING SURFACE WITHOUT BENDING IT)
SIN COLOR DOT
NOMINAL DIA.
1/32" (0,7 mm)
RAVEN (NOTES 1 AND 2)
HORIZONTAL
SIDEWALL
SPRINKLER

CLEARANCE
HOLE

MOUNTING
SURFACE

RAVEN ADJUSTMENT
ESCUTCHEON SPACER RING
PLATE LINK
(AS NECESSARY ASSEMBLY
MAXIMUM 2)

NOTES:
A LEVEL APPLIED HERE 1. SIN (SPRINKLER IDENTIFICATION
ENSURES SPRINKLER W-TYPE 25
NUMBER) COLOR DOT INDICATES:
INSTALLATION WITH DEFLECTOR WRENCH
PARALLEL TO FLOOR. COLOR SIN APPLICATION
TOP OF RED TY3381 HSW
SIN
ENCLOSED STANDARD
COLOR WRENCH EMBOSSED
DEFLECTOR COVERAGE
DOT WITH "UP" INDICATES
PROPER ORIENTATION PURPLE TY3382 HSW
OF SPRINKLER WITH EXTENDED
SIN COLOR DOT FACING UP. COVERAGE
2. FOR HSW SPRINKLERS, SIN COLOR
LINK ACCEPTS DOT ALSO HELPS VERIFY DEFLECTOR
ASSEMBLY 1/2" DRIVE IS IN PROPER ORIENTATION. USING
SPRINKLER WRENCH, POSITION
SPRINKLER SO SIN COLOR DOT
WRENCH PRONGS FACES UP (SEE "WRENCH FRONT
UNIQUELY SPACED TO VIEW").
ALIGN WITH SPRINKLER
WRENCHING NOTCHES
SPRINKLER WRENCH
FRONT VIEW FRONT VIEW
FIGURE 4
RAVEN INSTITUTIONAL HORIZONTAL SIDEWALL SPRINKLER
INSTALLATION WITH W-TYPE 25 SPRINKLER WRENCH
TFP651
Page 6 of 10

5.6K Extended Coverage Pendent (TY3282)

Minimum Minimum Deflector-to-Ceiling Sprinkler Minimum


Coverage Area
Response Flow 1 Pressure 2 Distance Temperature Rating Spacing
Rating ft x ft gpm psi Inches °F ft
(m x m) (lpm) (bar) (mm) (°C) (m)
16 x 16 26 21.6 165 8
Quick Flush Mounted
(4,9 x 4,9) (98) (1,49) (74) (2,4)
5.6K Extended Coverage Horizontal Sidewall (TY3382)
Lateral
Minimum Minimum Deflector-to-Ceiling Sprinkler
Coverage Area Minimum
Response Flow 1 Pressure 2 Distance 3 Temperature Rating
ft x ft Spacing 4
Rating gpm psi Inches °F
(m x m) ft
(lpm) (bar) (mm) (°C) (m)
16 x 16 26 21.6 4 to 12 165 8
Quick (4,9 x 4,9) (98) (1,49) (100 to 300) (74) (2,4)
Notes:
1. Requirement is based on minimum flow in gpm (lpm) from each sprinkler.
2. Indicated residual pressures are based on the nominal K-factor.
3. Centerline of the sprinkler waterway is located 7/16 in. (11,1 mm) below the deflector (Ref. Figure 7).
4. Minimum spacing is for lateral distance between sprinklers located along a single wall. Otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall,
on an opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being
utilized.
TABLE A
RAVEN INSTITUTIONAL SPRINKLERS
UL AND C-UL LISTING EXTENDED COVERAGE AND FLOW RATE CRITERIA

Design Extended Coverage Criteria


RAVEN Extended Coverage, Institu- Operation
Criteria tional Pendent and Horizontal Sidewall
Sprinklers (TY3282 and TY3382) must
In standby condition, the unique
assembly of RAVEN Institutional
be installed in accordance with the flow Pendent and Horizontal Sidewall Sprin-
General Criteria
rate criteria provided in Table A. They klers is designed with tamper-resistant
Only escutcheons shown in Figures 5
must be installed and utilized in light features to help prohibit a false activa-
and 6 can be utilized with TYCO RAVEN
hazard occupancies under smooth, tion and help reduce the opportunity
5.6K Institutional Pendent and Horizon-
flat, horizontal ceilings as outlined in for individuals to injure themselves or
tal Sidewall Sprinklers. A maximum of
the applicable installation standard others with components of a fire sprin-
two spacers can be used to adjust the
recognized by the listing or approval kler. RAVEN Institutional Sprinklers are
escutcheons.
agency (e.g., UL Listing is based on specifically designed to minimize com-
NFPA 13 requirements). ponents, as well as holes or shapes,
NOTICE
RAVEN Extended Coverage, Horizon- that could provide a point for securing
Use of more than two spacers may
tal Sidewall Sprinklers (TY3382) must an external non-sprinkler associated
result in disabling the tamper-resistant
be installed with a deflector-to-ceiling object. Also, when properly installed,
design of TYCO RAVEN Institutional
distance of 4 in. to 12 in. (100 mm to the escutcheon is held fast to the
Sprinklers and, thereby, also disable its
300 mm). To meet this requirement, ceiling or wall to deter its removal. The
principle functions of helping to avoid
the centerline of the sprinkler waterway shape of the sprinkler and escutcheon
false sprinkler operations and avoid
must be located 4-7/16 in. to 12-7/16 in. cannot be grasped easily, which further
the opportunity for individuals to injure
(112,7 mm to 315,9 mm) below the deters tampering.
themselves or others with components
of the sprinkler. ceiling (Ref. Figure 7). For information on the break-away
load of RAVEN Institutional Sprinklers,
Standard Coverage Criteria contact Technical Services.
RAVEN Standard Coverage, Institu-
tional Pendent and Horizontal Side- A link assembly covers the sealing
wall Sprinklers (TY3281 and TY3381) assembly. The link is soldered with
are intended for use with fire protec- an eutectic solder that melts when
tion systems designed in accordance exposed to heat. When the link reaches
with the standard installation rules its rated temperature, the link sepa-
recognized by the applicable listing rates and releases the sealing assem-
or approval agency (e.g., UL Listing is bly, allowing the deflector assembly to
based on NFPA 13 requirements). extend from the body and water to flow.
RAVEN Horizontal Sidewall Sprin-
klers (TY3381) must be installed with
a deflector-to-ceiling distance of 4 in.
to 12 in. (100 to 300 mm). To meet this
requirement, the centerline of the sprin-
kler waterway must be located 4-7/16
in. to 12-7/16 in. (112,7 mm to 315,9 mm)
below the ceiling (Ref. Figure 7).
TFP651
Page 7 of 10

STYLE F STYLE F 3/8"


2" SCH. 40 STEEL PIPE SLEEVE (9,5 mm)
-OR-
2" (50 mm) I.D. CORED HOLE

2" SCH. 40
1" STEEL PIPE
(25,4 mm) SLEEVE 3" DIA.
-OR- (76,2 mm)
2" (50 mm) I.D.
CORED HOLE

7/16" 3" DIA. 3/8"


(11,1 mm) (76,2 mm) (9,5 mm)
1-5/16" 7/16"
(33,3 mm) (11,1 mm)

STYLE G STYLE G 3/8"


2" SCH. 40 STEEL PIPE SLEEVE (9,5 mm)
-OR-
2" (50 mm) I.D. CORED HOLE

2" SCH. 40
1" STEEL PIPE
(25,4 mm) SLEEVE 4" DIA.
-OR- (101,6 mm)
2" (50 mm) I.D.
CORED HOLE

7/16" 4" DIA. 3/8"


(11,1 mm) (101,6 mm) (9,5 mm)
1-5/16" 7/16"
(33,3 mm) (11,1 mm)
FIGURE 5 FIGURE 6
RAVEN INSTITUTIONAL PENDENT SPRINKLER RAVEN INSTITUTIONAL HSW SPRINKLER
ESCUTCHEON OPTIONS ESCUTCHEON OPTIONS

2" SCH. 40 STEEL PIPE SLEEVE


(LENGTH TO SUIT WALL THICKNESS)
OR 2" (50 mm) I.D. CORED HOLE FINISHED
CEILING
WALL 1" X 1/2" M.I. CLASS 150
SET SPRINKLER FITTING 4-7/16" (112,7 mm) TO *
1" SCREW
STEEL 12-7/16" (315,9 mm)
PIPE

CENTERLINE
PIPE OF SPRINKLER
SET WATERWAY
SCREW

RAVEN
MODEL 1780 HSW SPRINKLER
RETAINING MODEL 1781
FLANGE CENTERING
GROMMET
* RESULTS IN OPERATED
DEFLECTOR-TO-CEILING
5/8" DISTANCE OF 4"-12"
WALL THICKNESS (101,6 mm TO 304,8 mm)
(15,9 mm)
FIGURE 7
MODEL 1780 RETAINING FLANGE AND MODEL 1781 CENTERING GROMMET
HORIZONTAL INSTALLATION FOR PENDENT
TFP651
Page 8 of 10

Installation It is recommended that flexible sprin-


kler piping is used to connect the
Step 1

TYCO RAVEN 5.6K Institutional sprinkler pipe to the supply piping to


Pendent and Horizontal Sidewall Sprin- maximize installation flexibility and
klers must be installed in accordance to ensure that the sprinkler and the
with this section. escutcheon are installed properly, as
shown in Figure 7.
General Instructions
A 1/2 in. NPT sprinkler joint should be
Integrity of the tamper-resistant design
obtained by applying a minimum-to-
of RAVEN Escutcheons is dependent
maximum torque of 7 to 14 lb-ft (9,5
on the piping installation design. When
to 19,0 N∙m). Higher levels of torque Step 1. Inspect the sprinkler for any
installed properly, the escutcheon is
may damage the sprinkler with con- visible signs of damage that could have
held fast (i.e., tight with no movement
sequent leakage or impairment of the occurred during shipping or handling.
or gap) to the mounting surface (ceiling
sprinkler. Rather than over-torquing to Apply a non-hardening pipe-thread
or wall, as applicable) by tightening
meet proper orientation for the hori- sealant such as TEFLON tape to the
the sprinkler assembly into the sprin-
zontal sidewall sprinkler, stop tighten- NPT thread of the sprinkler. Applying
kler fitting. Be careful not to create too
ing earlier. between two (2) and four (4) full wraps
much force between the escutcheon
and wall, as extensive force may cause Do not attempt to compensate for of tape is recommended.
issues with the pulling of the sprinkler improper location of the sprinkler Carefully remove the orange protec-
body from the stem, possibly causing fitting by under- or over-tightening the tive cap from the sprinkler by pulling it
warping, cracks, and leaks. sprinkler. straight out without bending it.
A tamper-resistant installation requires After installation is complete, ensure Verify that the sprinkler identification
all of the following: the RAVEN Escutcheon is held fast (i.e., number (SIN) and temperature rating
tight with no movement or gap) to the located on the side of the sprinkler
• The sprinkler fitting must be prop-
mounting surface and that the escutch- match installation requirements.
erly located with respect to distance
eon sits squarely against the mounting
from the face of the sprinkler fitting Step 2. Align the TYCO W-Type 25
surface around its entire perimeter.
to the face of the mounting surface Installation Wrench with the sprinkler.
(Ref. Figures 5 & 6). The following tools are recommended The flat surface should be in line with
for proper installation of RAVEN Insti- the small colored dot on the sprinkler.
• The sprinkler fitting must be rigidly
tutional Sprinklers:
secured and immobile through the
use of the retaining flange, installed • TEFLON tape Step 3
flush to the back of the wall or above • TYCO W-Type 25 Installation Wrench
the ceiling and secured with the pipe
set screws. • 1/2 in. drive ratchet wrench
• The centerline of the sprinkler fitting • Torque wrenches
must be perpendicular to the mount- • Ratchet extension (optional)
ing surface to assure that the Insti-
tutional Escutcheon sits squarely • Level
against the mounting surface around
its entire perimeter. NOTICE
Figure 7 illustrates a technique to adjust Install RAVEN Pendent Sprinklers with Step 3. Ensure that the TYCO W-Type
the location of the sprinkler fitting to the centerline of the waterway perpen- 25 Installation Wrench is fully engaged
help assure immobility of the sprinkler dicular to the ceiling. Install RAVEN onto the sprinkler. Fully insert all three
fitting and to help maintain perpen- Horizontal Sidewall sprinklers with the Wrench Prongs into the slots on the
dicularity of the sprinkler fitting to the centerline of their waterway parallel sprinkler body.
mounting surface. with the ceiling and perpendicular to
the back wall. Step 4
While Figure 7 illustrates a horizon-
tal installation, it can be applied to
pendent installations.
When applied, the technique shown
in Figure 7 allows the sprinkler/supply
pipe to be pulled back into the mount-
ing surface from behind the wall or
above the ceiling, and the retaining
flange set flush to the back of the wall or
above the ceiling and secured with the Step 4. With the Wrench on the sprin-
retaining flange pipe set screws. This kler, place the escutcheon over the
technique will help overcome problems sprinkler.
with assuring that the escutcheon is
held fast to the mounting surface (i.e.,
tight with no movement or gap).
TFP651
Page 9 of 10

Step 5 Step 7 Step 9

Step 5. Ensure that the ceiling/wall Step 7. Wrench-tighten the sprinkler Step 9. After installation is complete,
is smooth for the escutcheon to sit using only the TYCO W-Type 25 Instal- ensure that the RAVEN Escutcheon is
against and that the distance from lation Wrench (Ref. Figure 3). held fast against the mounting surface
the ceiling/wall surface to the sprin- and sits squarely against the ceiling
Insert a 1/2 in. drive ratchet wrench
kler fitting is appropriate. As shown in around its entire perimeter.
(with or without the extension) into the
Figures 5 and 6, the take-out dimen-
TYCO W-Type 25 Installation Wrench. When applied, the technique shown
sions are 1 inch for pendent sprinklers
Ensure the ratchet wrench remains in Figure 7 allows the sprinkler/supply
and 1-5/16 inches for horizontal side-
parallel to the ceiling/wall. A ratchet pipe to be pulled back into the mount-
wall sprinklers.
extension can help to keep the wrench ing surface from behind the wall or
in line with the sprinkler. Torque for the above the ceiling, and the retaining
NOTICE RAVEN Institutional Sprinkler is 7 to 14 flange set flush to the back of the wall
The sprinkler has intentionally been lb-ft. or above the ceiling and secured with
designed to be difficult to grasp by the retaining flange pipe set screws. Do
hand. Therefore, the use of the W-Type NOTICE not over-tighten the wall set screws,
25 Installation Wrench for hand-tight- as over-tightening these screws may
To help prevent slippage of the wrench damage the sprinkler.
ening assists in threading the sprinkler.
and while using a 1/2 in. drive ratchet
Also, use of the W-Type 25 Installation To verify correct sprinkler application,
wrench, place one hand over the TYCO
Wrench helps avoid damage to the refer to the Notes in Figures 3 and 4 on
W-Type 25 Installation Wrench while
sprinkler during installation. SIN color dot indicators.
tightening with the other hand.
A recommended technique to deter- For horizontal sidewall sprinklers, the
Step 6
mine if the torque range is achieved SIN color dot also helps verify deflec-
involves the use of two different tor orientation. In proper installations of
torque wrenches. Adjust first with a RAVEN Horizontal Sidewall Sprinklers,
7 lb-ft torque wrench, followed by SIN color dots face up.
adjusting with a 14 lb-ft wrench.
NOTICE
Step 8 If the escutcheon is not held fast (i.e.,
tight with no movement or gap) to the
mounting surface and as an option to
Step 6. With the escutcheon in place relocating the sprinkler fitting (increas-
and with pipe-thread sealant applied ing the face-of-fitting to face-of-mount-
to the pipe threads, hand-tighten ing surface distance), up to two (2)
the sprinkler into the sprinkler fitting Adjustment Spacer Rings as shown
using the TYCO W-Type 25 Installation in Figure 3 may be utilized. Each
Wrench with the wrench prongs fully Adjustment Spacer Ring can account
engaged with the sprinkler wrench- for 0.075 inches of gap between the
ing notches. The wrench prongs are Step 8. For horizontal sidewall sprin- escutcheon and mounting surface.
designed to engage the wrenching klers, a Level can be placed on top of Therefore, if the gap is greater than
notches in the sprinkler body, and are the flat surface of the TYCO W-Type 25 0.150 inches, the sprinkler fitting will
also uniquely spaced to align with the Installation Wrench to orient the sprin- need to be relocated to assure proper
sprinkler wrenching notches in one kler correctly. installation of both the sprinkler and
position. escutcheon.
TFP651
Page 10 of 10

Care and as with the applicable standards of the


NATIONAL FIRE PROTECTION ASSO-
Separately Ordered
Escutcheons Style F
Maintenance CIATION (e.g., NFPA 25), in addition to
the standards of any other authorities
(3 in. Diameter)
Carbon Steel
White . . . . . . . . . . . . . . . . . . . . . . . 56-314-4-010
TYCO RAVEN 5.6K Institutional having jurisdiction. Contact the install-
Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-314-7-010
Pendent and Horizontal Sidewall Sprin- ing contractor or product manufacturer Chrome Coated . . . . . . . . . . . . . . . 56-314-9-010
klers must be maintained and serviced regarding any questions. Stainless Steel
Sprinklers are recommended to be White . . . . . . . . . . . . . . . . . . . . . . . 56-318-4-010
in accordance with this section. Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-318-7-010
inspected, tested, and maintained by
Before closing a fire protection system Electropolished* . . . . . . . . . . . . . . 56-318-9-010
a qualified Inspection Service in accor-
main control valve for maintenance
dance with local requirements and/or Separately Ordered
work on the fire protection system
national codes. Escutcheons Style G
that it controls, obtain permission to
shut down the affected fire protection (4 in. Diameter)
system from the proper authorities Limited Carbon Steel
White . . . . . . . . . . . . . . . . . . . . . . . 56-312-4-010
and notify all personnel who may be
affected by this action. Warranty Grey . . . . . . . . . . . . . . . . . . . . . . . . . 56-312-7-010
Chrome Coated . . . . . . . . . . . . . . . 56-312-9-010
Stainless Steel
Service inspections should be made For warranty terms and conditions, visit White . . . . . . . . . . . . . . . . . . . . . . . 56-319-4-010
on a regular basis to detect possible www.tyco-fire.com. Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-319-7-010
damage or alterations to the sprinkler Electropolished* . . . . . . . . . . . . . . 56-319-9-010
and escutcheon. Inspections should
include making certain that the RAVEN Disclaimer for * Chrome-coated appearance

Institutional Escutcheon is held fast to


the mounting surface. Damaged or RAVEN Separately Ordered
Sprinkler Wrench
altered sprinklers are to be replaced
immediately to avoid personal injury Institutional Specify: W-Type 25 Installation Wrench,
P/N 56-314-1-001
and to prevent use for causing personal
injury, as well as to maintain the sprin- Sprinklers Separately Ordered
Parts for Installation in Concrete
kler system in an operative condition. Johnson Controls specifically dis- Specify: Model 1781 Centering
Sprinklers which are found to be claims any liability for damages or Grommet for installation in concrete,
leaking or exhibiting visible signs of injury (including death) arising out of or P/N 56-000-1-781
corrosion must be replaced. caused by manipulation, dismantling,
Specify: Model 1780 Retaining Flange
or misuse of RAVEN Institutional Sprin-
Automatic sprinklers must never be with Set Screws for installation in con-
klers or the use or attempted use of the
painted, plated, coated, or other- crete, P/N 56-000-1-780
RAVEN Institutional Sprinklers or any
wise altered after leaving the factory. component thereof as an instrument Separately Ordered
Modified sprinklers must be replaced. unrelated to its intended function as a
Sprinklers that have been exposed to Adjustment Spacer Ring
fire protection device. Specify: Adjustment Spacer Ring for
corrosive products of combustion, but
use with RAVEN Institutional Sprinklers,
have not operated, should be replaced
if they cannot be completely cleaned Ordering P/N 56-000-1-755

Procedure
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid Contact your local distributor for avail-
damage to the sprinklers before, ability. When placing an order, indicate
during, and after installation. Sprin- the full product description and part
klers damaged by dropping, striking, number (P/N).
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler Sprinkler Assemblies
that has a cracked bulb or that has lost Specify: RAVEN (Standard or Extended
liquid from its bulb. Refer to the Instal- Coverage), 165°F (74°C), Institutional
lation section for additional information. (Pendent or Horizontal Sidewall)
Sprinkler with (specify) Finish, and P/N
Frequent visual inspections are recom- (specify):
mended to be initially performed for Standard Coverage Pendent (TY3281)
sprinklers installed in potentially cor- White . . . . . . . . . . . . . . . . . . . . . . . 50-314-4-165
rosive atmospheres to verify the integ- Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-314-9-165
rity of the materials of construction as Standard Coverage HSW (TY3381)
they may be affected by the corrosive White . . . . . . . . . . . . . . . . . . . . . . . 50-316-4-165
conditions present for a given installa- Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-316-9-165
Extended Coverage Pendent (TY3282)
tion. Thereafter, annual inspections per White . . . . . . . . . . . . . . . . . . . . . . . 50-315-4-165
NFPA 25 are required. Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-315-9-165
Extended Coverage HSW (TY3382)
The owner is responsible for the inspec- White . . . . . . . . . . . . . . . . . . . . . . . . 50-317-4-165
tion, testing, and maintenance of their Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-317-9-165
fire protection system and devices in
compliance with this document, as well

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;