www.tyco-fire.com
Contacts
1/2"
NPT
7/16"
(11 mm)
1-13/16" NOMINAL ESCUTCHEON
SPRINKLER
(46 mm) MAKE-IN PLATE MOUNTING
BODY
SURFACE
LINK
ASSEMBLY
Technical
Data
Approvals
UL and C-UL Listed
Maximum Working Pressure
175 psi (12,1 bar)
Inlet Thread Connection
1/2 in. NPT
Discharge Coefficient
K=5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
Temperature Rating
165°F (74°C)
Finish
Sprinkler: White or Grey
Escutcheon: White, Grey, Chrome Coated
(Carbon Steel only), or Electropolished*
(Stainless Steel only)
Physical Characteristics
Body �����������������������������������������������������������Brass
Deflector Assembly �����������������������������������Bronze
Sealing Assembly. . Beryllium Nickel w/TEFLON
Link Assembly ������������������������������������������ Copper
Escutcheon ���������������������������������Carbon Steel or
Stainless Steel
* Chrome-coated appearance
TFP651
Page 3 of 10
OUTER
LINK LINK
ASSEMBLY
INNER *
LINK
SPRINKLER
1/2" WRENCHING
NPT NOTCHES
SIDE VIEW FRONT VIEW
3/4" **
(19 mm) * ORIENTATION OF INNER LINK TO
OVERALL SPRINKLER ASSEMBLY,
INCLUDING SPRINKLER WRENCHING
NOTCHES AND TOP OF DEFLECTOR,
ESCUTCHEON MAY VARY. DO NOT USE INNER LINK
PLATE MOUNTING TO DETERMINE TOP OF SPRINKLER
SURFACE DEFLECTOR ORIENTATION; REFER
SPRINKLER
BODY TO FIGURE 4.
CENTERLINE
OF SPRINKLER
WATERWAY
DEFLECTOR ASSEMBLY
IN OPERATED POSITION
ESCUTCHEON PLATE
(SELECT PER
FIGURE 6)
CLEARANCE
HOLE
RAVEN
ESCUTCHEON
PLATE
LINK
ADJUSTMENT ASSEMBLY
SPACER RING
(AS NECESSARY NOTE:
MAXIMUM 2)
1. SIN (SPRINKLER IDENTIFICATION
NUMBER) COLOR DOT INDICATES:
RAVEN
PENDENT COLOR SIN APPLICATION
SPRINKLER BLACK TY3281 PENDENT
STANDARD
COVERAGE
W-TYPE 25 SPRINKLER PROTECTIVE CAP
WRENCH REMOVED ONLY AT INSTALLATION GREEN TY3282 PENDENT
LINK (TO REMOVE, PULL CAP STRAIGHT EXTENDED
ASSEMBLY WITHOUT BENDING IT) COVERAGE
DISREGARD
FOR PENDENT
APPLICATION
WRENCH PRONGS
UNIQUELY SPACED TO
ALIGN WITH SPRINKLER ACCEPTS
WRENCHING NOTCHES 1/2" DRIVE
SPRINKLER WRENCH
BOTTOM VIEW BOTTOM VIEW
FIGURE 3
RAVEN INSTITUTIONAL PENDENT SPRINKLER
INSTALLATION WITH W-TYPE 25 SPRINKLER WRENCH
TFP651
Page 5 of 10
SPRINKLER FITTING
LOCATED AT PROPER SPRINKLER PROTECTIVE CAP
DEPTH FROM AND REMOVED ONLY AT INSTALLATION
PERPENDICULAR TO (TO REMOVE, PULL CAP STRAIGHT
MOUNTING SURFACE WITHOUT BENDING IT)
SIN COLOR DOT
NOMINAL DIA.
1/32" (0,7 mm)
RAVEN (NOTES 1 AND 2)
HORIZONTAL
SIDEWALL
SPRINKLER
CLEARANCE
HOLE
MOUNTING
SURFACE
RAVEN ADJUSTMENT
ESCUTCHEON SPACER RING
PLATE LINK
(AS NECESSARY ASSEMBLY
MAXIMUM 2)
NOTES:
A LEVEL APPLIED HERE 1. SIN (SPRINKLER IDENTIFICATION
ENSURES SPRINKLER W-TYPE 25
NUMBER) COLOR DOT INDICATES:
INSTALLATION WITH DEFLECTOR WRENCH
PARALLEL TO FLOOR. COLOR SIN APPLICATION
TOP OF RED TY3381 HSW
SIN
ENCLOSED STANDARD
COLOR WRENCH EMBOSSED
DEFLECTOR COVERAGE
DOT WITH "UP" INDICATES
PROPER ORIENTATION PURPLE TY3382 HSW
OF SPRINKLER WITH EXTENDED
SIN COLOR DOT FACING UP. COVERAGE
2. FOR HSW SPRINKLERS, SIN COLOR
LINK ACCEPTS DOT ALSO HELPS VERIFY DEFLECTOR
ASSEMBLY 1/2" DRIVE IS IN PROPER ORIENTATION. USING
SPRINKLER WRENCH, POSITION
SPRINKLER SO SIN COLOR DOT
WRENCH PRONGS FACES UP (SEE "WRENCH FRONT
UNIQUELY SPACED TO VIEW").
ALIGN WITH SPRINKLER
WRENCHING NOTCHES
SPRINKLER WRENCH
FRONT VIEW FRONT VIEW
FIGURE 4
RAVEN INSTITUTIONAL HORIZONTAL SIDEWALL SPRINKLER
INSTALLATION WITH W-TYPE 25 SPRINKLER WRENCH
TFP651
Page 6 of 10
2" SCH. 40
1" STEEL PIPE
(25,4 mm) SLEEVE 3" DIA.
-OR- (76,2 mm)
2" (50 mm) I.D.
CORED HOLE
2" SCH. 40
1" STEEL PIPE
(25,4 mm) SLEEVE 4" DIA.
-OR- (101,6 mm)
2" (50 mm) I.D.
CORED HOLE
CENTERLINE
PIPE OF SPRINKLER
SET WATERWAY
SCREW
RAVEN
MODEL 1780 HSW SPRINKLER
RETAINING MODEL 1781
FLANGE CENTERING
GROMMET
* RESULTS IN OPERATED
DEFLECTOR-TO-CEILING
5/8" DISTANCE OF 4"-12"
WALL THICKNESS (101,6 mm TO 304,8 mm)
(15,9 mm)
FIGURE 7
MODEL 1780 RETAINING FLANGE AND MODEL 1781 CENTERING GROMMET
HORIZONTAL INSTALLATION FOR PENDENT
TFP651
Page 8 of 10
Step 5. Ensure that the ceiling/wall Step 7. Wrench-tighten the sprinkler Step 9. After installation is complete,
is smooth for the escutcheon to sit using only the TYCO W-Type 25 Instal- ensure that the RAVEN Escutcheon is
against and that the distance from lation Wrench (Ref. Figure 3). held fast against the mounting surface
the ceiling/wall surface to the sprin- and sits squarely against the ceiling
Insert a 1/2 in. drive ratchet wrench
kler fitting is appropriate. As shown in around its entire perimeter.
(with or without the extension) into the
Figures 5 and 6, the take-out dimen-
TYCO W-Type 25 Installation Wrench. When applied, the technique shown
sions are 1 inch for pendent sprinklers
Ensure the ratchet wrench remains in Figure 7 allows the sprinkler/supply
and 1-5/16 inches for horizontal side-
parallel to the ceiling/wall. A ratchet pipe to be pulled back into the mount-
wall sprinklers.
extension can help to keep the wrench ing surface from behind the wall or
in line with the sprinkler. Torque for the above the ceiling, and the retaining
NOTICE RAVEN Institutional Sprinkler is 7 to 14 flange set flush to the back of the wall
The sprinkler has intentionally been lb-ft. or above the ceiling and secured with
designed to be difficult to grasp by the retaining flange pipe set screws. Do
hand. Therefore, the use of the W-Type NOTICE not over-tighten the wall set screws,
25 Installation Wrench for hand-tight- as over-tightening these screws may
To help prevent slippage of the wrench damage the sprinkler.
ening assists in threading the sprinkler.
and while using a 1/2 in. drive ratchet
Also, use of the W-Type 25 Installation To verify correct sprinkler application,
wrench, place one hand over the TYCO
Wrench helps avoid damage to the refer to the Notes in Figures 3 and 4 on
W-Type 25 Installation Wrench while
sprinkler during installation. SIN color dot indicators.
tightening with the other hand.
A recommended technique to deter- For horizontal sidewall sprinklers, the
Step 6
mine if the torque range is achieved SIN color dot also helps verify deflec-
involves the use of two different tor orientation. In proper installations of
torque wrenches. Adjust first with a RAVEN Horizontal Sidewall Sprinklers,
7 lb-ft torque wrench, followed by SIN color dots face up.
adjusting with a 14 lb-ft wrench.
NOTICE
Step 8 If the escutcheon is not held fast (i.e.,
tight with no movement or gap) to the
mounting surface and as an option to
Step 6. With the escutcheon in place relocating the sprinkler fitting (increas-
and with pipe-thread sealant applied ing the face-of-fitting to face-of-mount-
to the pipe threads, hand-tighten ing surface distance), up to two (2)
the sprinkler into the sprinkler fitting Adjustment Spacer Rings as shown
using the TYCO W-Type 25 Installation in Figure 3 may be utilized. Each
Wrench with the wrench prongs fully Adjustment Spacer Ring can account
engaged with the sprinkler wrench- for 0.075 inches of gap between the
ing notches. The wrench prongs are Step 8. For horizontal sidewall sprin- escutcheon and mounting surface.
designed to engage the wrenching klers, a Level can be placed on top of Therefore, if the gap is greater than
notches in the sprinkler body, and are the flat surface of the TYCO W-Type 25 0.150 inches, the sprinkler fitting will
also uniquely spaced to align with the Installation Wrench to orient the sprin- need to be relocated to assure proper
sprinkler wrenching notches in one kler correctly. installation of both the sprinkler and
position. escutcheon.
TFP651
Page 10 of 10
Procedure
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid Contact your local distributor for avail-
damage to the sprinklers before, ability. When placing an order, indicate
during, and after installation. Sprin- the full product description and part
klers damaged by dropping, striking, number (P/N).
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler Sprinkler Assemblies
that has a cracked bulb or that has lost Specify: RAVEN (Standard or Extended
liquid from its bulb. Refer to the Instal- Coverage), 165°F (74°C), Institutional
lation section for additional information. (Pendent or Horizontal Sidewall)
Sprinkler with (specify) Finish, and P/N
Frequent visual inspections are recom- (specify):
mended to be initially performed for Standard Coverage Pendent (TY3281)
sprinklers installed in potentially cor- White . . . . . . . . . . . . . . . . . . . . . . . 50-314-4-165
rosive atmospheres to verify the integ- Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-314-9-165
rity of the materials of construction as Standard Coverage HSW (TY3381)
they may be affected by the corrosive White . . . . . . . . . . . . . . . . . . . . . . . 50-316-4-165
conditions present for a given installa- Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-316-9-165
Extended Coverage Pendent (TY3282)
tion. Thereafter, annual inspections per White . . . . . . . . . . . . . . . . . . . . . . . 50-315-4-165
NFPA 25 are required. Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-315-9-165
Extended Coverage HSW (TY3382)
The owner is responsible for the inspec- White . . . . . . . . . . . . . . . . . . . . . . . . 50-317-4-165
tion, testing, and maintenance of their Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-317-9-165
fire protection system and devices in
compliance with this document, as well
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;