Escolar Documentos
Profissional Documentos
Cultura Documentos
net/publication/3792738
CITATIONS READS
26 140
1 author:
Mentor Poveda
Quito Electric Distribution Utility
2 PUBLICATIONS 30 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Mentor Poveda on 12 April 2017.
In various electric power utilities of Latin America, a high E,L =E~– ER (1)
percentage of the energy entering the system is aimed at cov-
ering losses, since it is not rare to have losses accounting for The digital registers that are available at present provide
between 20 and zs~. of supplied energy. Naturally, this per- the demand profile in addition to the supplied energy at the
centage cannot correspond to technical losses, that is, losses metering point. The demand profile appears as a matrix with
stemming from the operation of network components. Rather the following column-vectors: date (d), time (t), demand for
most losses come from theft, irregularities in the metering active power (Dp[kW]), and demand for reactive power
systems for billing purposes, and errors in billing information (DQ[kvar]). The demand interval can normally be selected at
processing. In other words, these losses involve an unregis- the operator’s will, but the most commonly used interval is 15
tered load and are called nontechnical losses or black losses. minutes. The register matrix is shown in (2). The register
The determining presence of the latter component of losses period can be one complete year, with column vectors of
makes traditional loss calculation methods obtain estimates 35,040 elements in all. Nevertheless, it is considered that a
that are far removed from the reality of the situation. Beeause minimum register of 672 data be used in one complete sample
of this, the present paper is proposing a new methodology to week of each season of the year.
break down losses into their components in dkribution sys-
tems which is where the majority of these losses can be found.
2/15/98 00:00 2,345 1,225
Additionally, demonstration of the differences are provided.
2./15/98 00:15 2,360 1,325 .
Register =
.... .... .... ....
[ 2/21/98 23:45 2,450 1,345 1“
=dt
[
DpDQ
1 (2)
.kWlz = ~$1 Dpi x (demand - interval) (3) Equation (6) is applied for each one of the load demands
and the demand profile of the resistive losses is obtained. The
The methodology being proposed is supported by the procedure turns out to be correct because demand is a step
nature of each loss component and in its ratio with respect to function in the interval; therefore, the ratio takes place during
demand in the corresponding register interval. As the losses the complete interval and yields as a result the loss demand,
in the maximum demand interval are calculated with models which is another step function.
for load flows or through the modeling of the primary distri- When you have demands of resistive losses, what is
bution feeder; on the basis of this value, the magnitude of each expressed in (3) is obtained, that is, the sum of demands mul-
component is calculated for the rest of the demand intervals of tiplied by the demand interval time is the energy of the resis-
the entire period under consideration. That is, the demand tive loss in the register period.
proiile of each loss component is calculated and then on the
basis of that estimate, by means of integration, the energy of ~~ Since core losses (DCJ depend on
each component is calculated. the magnetic flux density in the core, which in turn depends
The technical losses in the distribution system of the elec- on the voltage feeding the transformer, it can be considered
tric power utility include resistive losses of the primary feed- independent from demand variation, that is, it remains con-
ers, the distribution transformer losses (resistive losses in the stant during the period of analysis.
windings and core losses), resistive losses in secondary net-
works, resistive losses in service drops, and the losses in kwh ‘CL =N#f(D) (7)
meters.
Once the power of the loss in the core of the transformers
&istive losses. The resistive losses are calculated on the is calculated, one has the demand profile corresponding to that
basis of the expression IZR. In each subsystem, the resistive loss, which will be completely flat during the entire register
losses are calculated for the peak load demand by the usual period.
methods and on this basis resistive losses are obtained in a
given interval through the squared ratio between demand in Secondarv network losses. By sampling the secondary net-
this interval and peak demand, as indicated below. The pro- works of the feeder, it is possible to calculate resistive losses
cedure that is described can be applied to all resistive losses, in the group of secondaries (DsJ belonging to this primary.
that is, in transmission and dMribution system lines, for resis- Calculation of losses for the secondaries of the sampling is
tive losses of substation and dMribution transformers, for the made on the basis of the demand profile registered in the low-
secondary lines, and for service drop conductors. voltage terminals of the distribution transformers which feed
In the case of resistive losses of the distribution transform- them for at least one representative week of each season of the
ers, the same demand profile registered at the beginning of the year. Afterwards, a typical curve of each season is obtained
primary feeder is considered to be a good estimate. and the general procedure for resistive losses described above
is applied to it, taking as a basis the losses at peak demand
The resistive loss demand (DW,) at any load demand (DH) is obtained from the modeling of the secondary networks of the
calculat@ by (4). sample.
2 ‘Pi 2 (4)
‘R.L_i = li R ‘( ~ The service drops are grouped in the
&vcos@i ] R most usual sizes and the most frequently used lengths are con-
The ratio between the peak loss and the loss at any load sidered to define the power of the resistive losses at peak
demand will be calculated by (5). demand of the corresponding client. On the basis of the power
of losses at peak demand, the general procedure to determine
losses in the service drops is used with the demand profile reg-
‘Pmax )2 ~ istered in the terminals of the nearest distribution transformer
D lW–max
.—‘max2R . ‘fiVcos@mm . (5) to the corresponding load but considering individual peak
Ii2R ‘Pi 2 demand instead of the maximum diversified demand.
‘RL–i
‘&vcos@i) R
Meter losses. Energy meters have a 10SS(Dti) that is essen-
tially due to the excitation of the voltage coils, that is, it can
be considered that it does not depend on the load. It can be
I
3e%
Table 1
37% !
Losses (Yo)
Non technical losses
Co~onent Demand Enerpy
Total 6.1 5.5
F Resistive Feeder lines and Fig. 2. Loss factor as a function of nontechnical losses
distr. transf windings 0.9 0.5
E
Distr. transf cores and 0.3 0.5 Table 2
nEt ers LOSS COMPONENTli FOR 13.2 kV FEEDER - No. 1
Secondaries and service 1.8 1.4 Losses (Yo)
drops
Co~onent Dermnd Ener~y
Nontechnical 3.1 3.0
Total 8.8 8.2
Resistive: Feeder lines and
This is a feeder that serves a residential sector. It has a The 13.2 kV feeder selected as an example is serving a
pealc demand of 9.12 MW and a supplied energy of 872.1 commercial and residential load. It has a peak demand of 10.7
MWh. The load factor of demand profile of supply is 56.9?Z0. MW and a supplied energy of 1,238.8 MWh. The load factor
The composition of the main losses produces the demand pro- of the demand profile of supply is 70.170. The demand profile
file of Fig. 3.
300,0
1
250,0
200.0
~“
: 150,0
(’i
E
~ 100,0
50,0
0,0
the (h)
500
300
200
100
time (h)
Fig. 3. Composition of the main losses for the 13.2 kV feeder No. 1
registered at the beginning of the feeder with the participation d. Loss factor and constant A variation
of the loss components appears in Fig. 5.
The results of the analysis of the loss components, as a In the above samples, the loss factor and A constant of
percentage of energy supplied to the feeder, is summarized in equation (10) adopt the values shown in Tables 4 and 5,
Table 3. respectively.
Table 1
Table 3 LOSS FACTOR
LOSS COMPONENTS FOR 13.2 kVFEEDER - No. 2
Nontechnical losses
Losses (Y.)
Feeder 0% 5% 10%
Component Demand Energy 22.9 kV 40.3% 44.5% 45.4%
Total 16.2 14.2 13.2 kV - No. 1 52.1% 53.1’%0 53.5%
Resistive: Feeder lines and 13.2 kV - No. 2 58.3% 61.3% 62.9%
distr. transf windings 7.3 5.6
Distr. transf cores and inters 1.4 1.9 Table 5
Secondaries and service 2.4 1.7 A CONSTANT
drops Nontechnical losses
Nontechnical 5.2 5.0 Feeder Ovo I 5’%. I 10’70
22.9 kV 0.561 0.619 0.632
13,2 kV - No. 1 I 0.584 I 0.594 0.599
13.2 kV - No. 2 0.489 0.515 0.528
12000,0
10000,0
8000,0
z
- 6000,0
2
E
~ 4000,0
time (h)
Fig. 4. Loss components in the demand profile of the 13.2 kV feeder No. 2
The method described in the present paper shows the inse- [1] H. Lee Willis, Power Distribution Planning:
curity that the loss factor estimate introduces in the determi- Reference Book, Marcel Dekker, U.S.A., 1997.
[2] Westinghouse, Distribution Systems: Electric Utility
nation of the energy corresponding to power loss calculated at
Engineering Reference Book, Westinghouse Electric
peak demand owing to the particular characteristics of total Corporation, Pittsburgh, Pa., U.S.A., 1965.
loss components. [3] World Bank and Latin American Energy
Resistive losses, as a squared function of demand, empha- Organization, Evolution, Situation, and Prospects of
size load peaks. Constant losses in the core tend to flatten out the Electric Power Sector in the Countries of Latin
the loss curve. And the nontechnical losses, with a demand America and the Caribbean, World Bank and
proiile that is similar to the load curve, introduce another addi- OLADE, 1991 (ISBN 9978-70-012-9).
tional variation. It is clear that, depending on which compo-
Mentor E. Poveda (M’ 1981) was
nent is the most important, loss the demand profile will have
born in Quito, Ecuador, on June 26,
a different shape and, because of this, the loss factor should be 1945. He graduated as an electrical
different. engineer from the Ecuadorian
The estimate that is usually made by adopting a value for National Polytechnic School on 1972
the A constant of equation (10) produces erratic results con- and obtained hk Master of Science
firmed in Tables 4 and 5, and should be replaced by the esti- from Purdue University, USA. Part-
mate of energy of losses based on demand profiles registered time EE Professor at Ecuadorian
National Polytechnic School and
for tAe electric power system.
International Power Consultant with
Finally, knowledge of the demand profiles of each loss the Latin American Energy
component makes it possible to better understand individual Organization (OLADE) and World
participation in both demand and energy and grant due impor- Bank. HIS special fields of interest are power dhibution sys-
tance to each circumstance that is analyzed. tems and rotating machines simulation.