Escolar Documentos
Profissional Documentos
Cultura Documentos
2 The system is loose laid but partially bonded The system is partially bonded below base slab and
through waterbars at construction joints, expansion fully bonded on walls and roof with no provisions for
joints and compartments, with the provision of the remedial work to the waterproofing membrane in
control and injection flanges that can provide an case of any defect.
access to the membrane in order to carry out the The only method of repair in case of leakage is by
remedial work by injecting the compartment in case the injection of the cracks in the concrete by using
of defect in the waterproofing barrier (if required). bored packer method and that is sealing the cracks
internally only while the structure remains exposed to
aggressive ground water.
Refer to the below extracts from the BS
8102:2009
6.2.3 Water table classification and grades
of waterproofing protection.
When selecting a type of waterproofing protection,
Table1 and Table 2 should be taken into account in
conjunction with the following points:
a) During the life of the structure some degree of
groundwater pressure is likely to build up against
the chosen waterproofing system.
b) Cracking or defective construction joints can
provide a potential path for water ingress.
c) Water ingress can occur where there is
groundwater pressure, if this is not consistent with
the required performance level (see Table2):
1) consideration should be given to the form and
feasibility of remedial work;
2) If remedial work is not possible the design
should be altered.
d) There are a number of risks associated with not
carrying out planned maintenance or structures
with Type C protection e.g. pump failure (see 10.3).
10.3.1 Design
In order to maximize the long-term integrity and
effectiveness of a waterproofing system
incorporating Type C protection, the
waterproofing system should be designed to be
maintainable. Access points that allow routine
maintenance of channels and outlets should be
incorporated into the design of the waterproofing
system.
3 The system is loose laid with higher capability of The post applied spray Methacrylate has a limited
bridging any crack in pre or post application to the crack bridging ability, special care should be
concrete substrate, in addition to the high capability considered for the repair of any existing cracks prior
for accommodating any expansion joint movement. application and any future crack development after
the application.
In addition the tanking system is not continuous over
the expansion joints and is interrupted every joint (no
continuity of the waterproofing barrier).
4 The membrane shall be protected by a protection The membrane is not protected on the horizontal,
screed on the horizontal and a protection board on directly exposed to the rebar installation and that
the vertical. may cause damage to the membrane, not detectable
and not accessible for repair.
The membrane on the vertical shall be protected with
a protection board.
No limitations on the application with regard to For the spray membrane the concrete has to be
surface preparation, moisture content, cracks completely cured, surface preparation is a must prior
repair, time restraint after completion of concrete application, moisture content should not exceed 4%,
curing, etc. cracks should be repaired, etc.
7 Sika has more than 50 years of experience with Newly introduced system with no long term durability
the proposed system and globally wide references. / compatibility experience.
9 The complete system is manufactured by a single Multiple manufacturers are involved with the
manufacturer, long term compatibility between the proposed system, long term compatibility cannot be
products from a single source can be guaranteed. guaranteed.
The waterproofing system is not a designated
system to a single manufacturer, it is a combination
of products from different manufacturers.