Contents
Essential features pag. 4
Regulation pag. 16
Accessories pag. 38
Series guide:
• With direct expansion coil: series OHA …..
• With chilled water coil: series OHU …..
• With direct expansion coil and hydronic heat recovery: series OHA …. HR
• With chilled water coil and hydronic heat recovery: series OHU …. HR
• With chilled water coil and direct expansion post-cooling: series OHU …. PC
• With chilled water coil, hydronic heat recovery
and direct expansion post-cooling: series OHU …. HR PC
3
Essential features - Diagnostic imaging rooms
- BSL laboratories for the treatment of viruses or
substances which are toxic, radioactive,
General information nuclear, flammable or contaminating in
plant and the need to install absolute filters - Anatomical pathology laboratories
- Section for air suction from the rooms, “H” Series, equipped with controls,
partial recycle or total exhaust to the microprocessor and software, has been
room compared to a reference environment. rooms, intensive care units, wards etc.
The units are equipped with controls, In fact, in these applications where there
electrical panel, microprocessor and dedicated is neither open wound nor high-level
- General surgery rooms and therefore neither is high static pressure for
- Orthopaedic surgery rooms the supply fan and the suction/exhaust fan.
- Very low-temperature heart surgery rooms The standard version of the new “H” Series
- Sterilization rooms facilities and clean rooms has low static pressure
4
of approximately 250-300 Pa on both the supply Version with chilled
and suction fans. High performance fans can be water coil: OHU
provided as accessories: up to 1,000 Pa, with
Uses the water supplied from a remote chiller
epoxy painting of the fins in order to satisfy
as the source of cooling. Equipped with a three-
even the most critical applications.
way regulation valve as standard (two-way
In practice, the entry level unit (which is in any
accessory) controlled by microprocessor.
case dimensioned to treat full or almost full fresh
air) is suitable for diagnostic imaging rooms or
hospital wards. With the appropriate options Version with direct expansion
added, the unit can be configured to fulfil the
circuit: OHA
requirements of the most demanding plant
design conditions such as those for surgical The “H” Series air conditioners with direct
rooms where highly specialized operations are expansion coil are equipped with one or two
to be performed. independent cooling circuits. Low noise, high-
efficiency, scroll-type compressors are used.
TUV Certification Compliance The standard expansion valve is electronic and
with Standard DIN 1946/4 can therefore guarantee maximum control of
the temperature with minimum energy
The “H” Series air conditioners, configured with
consumption and effective antifreeze control
the accessories mentioned above, conform to
of the evaporating coil.
the German Standard DIN 1946 part 4. They are
The cooling circuits have all the components
certified to be in compliance by TUV.
necessary for regulation, protection and safety.
They are positioned, together with the
electrical panel and all the controls, in a
technical compartment on the right side, out of
5
the treated airflow. They use the ecological No risk of
refrigerant R410A which is completely harmless Legionella Pneumophila
to the ozone layer and has a very low impact on
During the design and construction of the “H”
the environment. The OHA models to be
Series air conditioners, all possible measures
matched with remote condensers are supplied
have been taken to exclude any chance of the
with a nitrogen pressurization charge. The final
formation of Legionella Pneumophila bacterial
charge together with any oil top-up is done by
colonies inside the unit. Very high-level interior
the installer on-site. The refrigerant and oil
conditions of hygiene are ensured by the
charges are done in our factory if the water
materials used, the easy cleaning of the most
cooled condenser (accessory) is incorporated.
at-risk components, and the units’ operating
ranges.
Easy hygienization and
sterilization High quantity constant
All the internal components of the “H” Series fresh air flow
air conditioners which are in direct contact with
Chemical contamination, present in particular
the airflow can easily be rendered hygienic as
in surgical rooms, cannot be filtered out
they can be reached and extracted by simply
but must be diluted with large quantities of
opening the access doors.
constant fresh air flow. The management of the
The entire machine is made accessible in this
airflow is entrusted, via a microprocessor, to
way. This means that maintenance and cleaning
an inverter which controls the rotation speed
operations can be carried out correctly as
of the air supply fan depending on the air
scheduled, easily and quickly.
flow setting and the degree of clogging of the
machine’s own filters and other filters external
to it. The desired air flow is directly selectable
by the user and can vary from a minimum to a
maximum value according to the model of the
air conditioner.
6
Very high air filtration Indoor or outdoor installation
To prevent airborne bacterial contamination of The air conditioners have been designed
the room, the fresh air flow is passed through, for both indoor and outdoor (accessory)
in compliance with the applicable Regulations, installation. Their extreme compactness,
standard G4 efficiency filters at the air intake of reduced noise level and pleasing appearance
the machine (F7 as an accessory) and through F7 all make them suitable for installation near the
standard post-filters (F9 as an accessory) after rooms to be conditioned, thus avoiding lengthy
the fan at the entrance of the air supply ducts. An expensive duct work. External installation
M5 filter is also provided at the entrance of the however requires the air conditioners to be
suction air duct before the exhaust fan in order positioned under a protective canopy to ensure
to keep the interior of the machine clean. The comfortable access when maintenance has to
standard unit supplies approximately 250/300 Pa be performed during bad weather.
and can reach the 800/1,000 Pa static pressure
(accessory) necessary for the essential sound
Easy installation
damper and any terminal absolute filter. If this
filter is present, it has to be installed directly The machine has been designed to be easy
in the room to be controlled as any other to install. Once positioned where it is to be
aeraulic element after it may contaminate the installed, it only needs electrical, hydraulic,
air flow.Selecting high static pressure exhaust cooling, ducting and remote accessory
fans also allows the installation of an absolute connections. The relevant manual gives all
filter at the inlet of the re-suction air ducts the necessary procedures for the perfect
before the sound damper; this, together with installation, subsequent checking and final
the management of the depression in the room, testing of the equipment.
is necessary in order to avoid polluting the
external environment if toxic substances are to
be treated or septic operations carried out.
7
OHU 2200
8
OHU 2200
9
OHU 2200 HR
10
OHU 2200 HR
11
Construction opening and therefore stopping it. It should
be remembered that in some cases such as
characteristics surgical rooms, these machines must operate
continuously so that they do not lose their
overpressure and compromise the air quality.
Structure of the unit The panels can be opened by keys for access
The structure is made of welded metal plates and maintenance and the closing mechanisms
which are surface treated with epoxy-resin can also be padlocked for greater safety. The
paint (60 microns, white) after cataphoresis. panels have elastomer seals which do not react
12
Return and exhaust fan section Motorised dampers on fresh
Also this section has either one or two air inlet and gravitational
inverter-controlled plug fans to guarantee dampers on the exhaust outlet
the required level of overpressure or
To prevent the wind from blowing pollution
depression in the area to be controlled.
into the machine during shutdown.
The standard external static pressure of the
suction/exhaust fans is approximately 250 Pa.
Fans with much higher static pressure can be Motorised dampers
installed (accessory) in order to manage, for on all vents
example, external absolute filters: infectious Motorised dampers (as accessories) can be
departments etc. Double fans, with double fitted to the vents going to and coming from
inverters, can also be provided for use in the controlled room. In this case the standard
13
Motorised recirculation damper In this case, the pressure sensors are located
on the outside of the electrical panel.
For partial recirculation installations, a
motorised by-pass modulated damper
(accessory) is available counter-opposed to Immersed-electrode humidifier
the fresh air one. This saves a considerable
The standard humidification system is the
amount of energy and reduces running costs
immersed-electrode type. A characteristic
significantly. When the recirculation damper
of these humidifiers is the proportional
is fitted, the fresh air filter is substituted with
production of steam between 10% and 100%
other pleated filters of efficiency standard G4
of their capacity. The capacity of the humidifier
or F7 (accessory) in order to improve the size of
can be selected depending on the quantity and
the section for mixing with the fresh air.
condition of the fresh air.
14
Centralised steam system Condensate supply
regulation and distribution and siphons
All the air conditioners (both direct expansion
If the Hospital has a centralised steam
and chilled water type) need their condensate
distribution system at a pressure of 1 bar
and humidifier drainage systems to be
(relative), a stainless steel steam controller and
connected to the building’s waste system.
distributor can be installed as an option. This
The siphon, which is essential for the supply
system allows modulation of the steam supply
of condensate from the relevant drip tray
from 0% to 100%.
because it is positioned in a depression point,
is supplied ready-fitted inside the unit.
15
Regulation Static control of overpressure
or depression
This is to prevent any kind of contamination
Temperature and humidity entering or leaving the designated space.
sensors The static control of overpressure or
The control of the unit is based on the depression (standard) is carried out by
information from the temperature and respectively reducing or increasing the re-
humidity sensors. In the standard machines, suction fan airflow using manual settings of the
these are installed in the air suction and electronic control of the fan. This regulation,
Alternatively, the temperature sensor can be for example, is not sufficient for areas with
installed in the supply fan compartment and the higher air quality requirements such as surgical
16
Dynamic control of overpressure enter the room from the surrounding areas.
17
Management of constant real-time reading of the concurrent airflow.
18
Integrated temperature Modulating regulation of the
and humidity control cooling capacity: OHU
(for machines with chilled water coil)
The standard machines are equipped with
The three-way valve (two way as accessory),
all the components necessary to regulate
controlled by microprocessor, allows perfect
cooling, heating, humidification and
modulating regulation of both cooling and
dehumidification. These components are
dehumidification.
sized for the treatment of full fresh air or with
partial air recirculation, and in particular:
- Hot water heating coil with modulating Modulating regulation of the
control valve. cooling capacity: OHA
- Chilled water cooling coil with modulating (for machines with cooling circuit)
valve, OHU Series, or as an alternative. The standard electronic expansion valve
- Direct expansion coil with cooling circuit, guarantees reasonable control of the cooling
OHA Series. capacity. If the required temperature tolerance
- Post-heating coil: hot water coil with is very tight, or if a lot of, or indeed full, fresh air
three-way modulating valve for machines is treated, the accessory to control the cooling
with chilled water cooling coils; electric capacity of the compressor can be installed.
modulating as an accessory. Electric This is able to modulate the capacity between
modulating coil as standard for direct 100% and 10% of the nominal capacity of
expansion machines. the circuit.
- Independent modulating i m m e r s e d-
electrode humidifier, immersed-resistence
or as an alternative.
- Modulating centralized steam distribution
system.
19
Microprocessor Serial communication and
supervision system: BMS
and software With the development of BMS (Building
Management System), the problem of
All operating and safety functions of the communication between the control systems
“H” Series air conditioners are managed by the of different companies becomes ever more
standard microprocessor. This allows the frequent. Today in fact, it is not only the
temperature and relative humidity to be quality and reliability of the instruments that
controlled in three ways: proportionally, is important, but also the degree of external
proportional-integrally or proportional- connectability that they can offer.
integral-derivatively. PID activation is assisted This is why the controls This is why the controls
by an auto-tuning programme. The control of can:
relative humidity is proportional. The - Be integrated into a system consisting of
microprocessor also controls overpressure and instruments from different constructors
depression and can be easily connected to the which share information via the integrated
BMS of all the major constructors. RS485 Modbus card and a gateway
specifically designed for BACnet and
LonWorks (accessories).
20
- Be managed remotely through a specific User interface terminal
gateway (accessory), via modem and internet
The powerful microprocessor of the system
using a simple browser.
that manages and regulates the unit allows
- Inform authorised personnel wherever they
a remote terminal to be installed (as an
are of any alarm situations through a specific
accessory). This is identical to that fitted
gateway (accessory), also by SMS.
to the machine and is for installation in
the control room. This terminal enables
the direct detection from the room of the
operational state of the unit and modification
of the temperature and humidity set points.
There is also an integrated function which
displays trend graphics of the ambient
temperature and humidity for the current day
and the previous seven days.
21
Emergency activation system Complete electrical panel
of room depression The electrical board is equipped with a door-
Can be activated through a digital port. Enables locking main switch and all the components
the ambient pressure setting to be forced necessary for the protection and normal
immediately in order to obtain depression operation of the unit.
compared to the surrounding rooms and so There are terminals for the remote connection
avoid any infective agents being spread if they of a cumulative alarm signal and others for the
are detected during normal operations. remote control of start-up and stop functions.
Double fan
The machine can be fitted with a second fan
for supply air and a second fan for return air
Operational safety
The “H” Series air conditioners have been
designed, from both the mechanical and
software points of view, to guarantee maximum
operational reliability and therefore to avoid
any risk of suspending a surgical operation in
progress.
22
and exhaust (accessory) to function in stops the operation of components which are
emergency. This solution guarantees that the not indispensable such as compressors,
machine can continue to run in complete safety humidifiers and electrical coils, leaving in
even if one of the two fans breaks down. Both operation only the supply fans, the suction and
fans are intercepted by a damper fitted exhaust fan and the regulation.
upstream of them to prevent recirculation if
only one of them is in operation. The two fans
Antifreeze system
are controlled by microprocessor via the
This system guarantees active protection
electronic regulation of their rotation speed,
from the risk of freezing thanks to the
based on the measurement of the internal
presence of a relative temperature sensor,
airflow of the unit. They provide the total
installed downstream of the pre-heating coil
nominal airflow of the machine. If one of the
and upstream of the cooling one. If the
fans breaks down, the microprocessor
antifreeze sensor detects a temperature
registers the reduced airflow and increases
below that of a pre-set value, it activates
the speed of the other to guarantee the
emergency intervention by opening the
maximum airflow compatible with one-fan
heating 100%. If after a set amount of time
operation, in any case equal or very close to
the temperature is still under the alarm level,
the nominal value.
the fresh air damper is closed and fans are
Uninterruptible power supply: switched off. The anomaly is displayed on
UPS the main mask of the microprocessor. The
Two terminals are available on the electrical fans start again as soon as the temperature
panel to be connected to a clean contact of the returns above the pre-set value.
23
Version with the machine’s microprocessor. The axial-fan
type air cooled condenser is installed outside
direct expansion and has to be connected to the cooling circuit on
24
OHU 6800 HR - PC
25
Energy saving Versions with hydronic heat
recovery system
Night stand-by Made up of two water coils, one in the suction
When the room in not in use the flow of fresh air section and an identical one in the fresh air
can be reduced to set limits, maintaining the treatment section, connected by a hydraulic
area in overpressure and increasing the interval circuit with pump and expansion tank. The
of inactivity for the control of temperature and microprocessor starts the pump when the
humidity. The room is thus kept sterile without temperatures are favourable to energy saving.
wasting energy. It should be noted that the The hydraulic circuit is supplied empty as the
supply airflow reduction can only be carried out percentage of glycol has to be determined as a
if the dynamic control of overpressure has been function of the minimum temperature of the
selected as the room would otherwise go into place of installation. It must therefore be filled
for in the standard software and managed by The hydronic heat recovery system, although
the microprocessor, can be called up manually, its performance is lower than that of a counter-
via BMS or time slots. In emergency operations current plate or rotary system, is capable of
return the unit rapidly to standard function between exhaust air and supply air.
values.
System for the deactivation of
components depending on the
fresh air temperature
Depending on the temperature of the fresh
air, the operation of some components
which correct it is inhibited in order to avoid
wasting energy.
26
27
One machine only one room would be put out of action.
Finally, this plant design philosophy makes the
for each room ducting and regulation much simpler. Also the
financial savings at first installation are not
The most modern air conditioning plant
what they initially seem. In fact, the economic
technology calls for one machine to be installed
advantage of installing only one machine
in each surgical room. This makes it easy to
instead of three is greatly scaled down by the
manage the temperature and humidity required
cost of additional components, the installation
by the type of operation being carried out. In
of many regulation systems (possibly in the
addition, the night-time stand-by can therefore
difficult-to-get-at false ceiling space) and by
be managed to provide maximum energy
the management problems of a more complex
efficiency because the individual room does
plant. For example, in the case of an operating
not have to be tied to the operation of any
block with six surgical rooms the optimum
other rooms and can exploit to the maximum
solution is to provide six identical installations
the opportunity of being ventilated with
- one for each room - and a seventh for all the
untreated air: for the same reasons it can also
ancillary rooms. The six machines are normally
be sterilized without affecting the working
without heat recovery systems while the
operation of the other rooms. It is also worth
seventh has also an emergency double fan
taking into consideration the fact that, in the
section for both supply and return/exhaust air.
event of a machine component breaking down,
28
Air conditioning plant for surgical room with
unidirectional air filtration ceiling
29
One machine - Supply air humidity: regulated by a sensor
installed inside the machine in the return air
for multiple rooms section. This sensor detects the humidity in
the returning air, which is the average
It is possible however, if the layout of the plant
humidity of the individual rooms.
requires it, to install a single air conditioner to
- Airflow to the individual rooms: a CAV
serve several rooms. The following regulation
(constant air volume) damper with three
systems have to be provided:
positions is installed at the entrance to the
- supply airflow: controlled by the microprocessor
individual controlled rooms: nominal airflow,
to maintain constant pressure in the relative
reduced airflow (night-time stand-by) and
ducting. This means that if one of the controlled
stopped. The position of the damper is
rooms is closed and the pressure rises, the
commanded from the room or via the BMS of
microprocessor reduces the rotation speed so
the hospital.
as to guarantee constant airflow to the rooms
- Overpressure of each individual room: a VAV
which remain open.
(variable air volume) damper is installed in
- Supply air temperature: controlled to set
the return air duct of each room, regulated
point, through a sensor installed at the mouth
by information coming from a differential
of the duct. The set temperature has to be
pressure sensor installed astride the wall
cold enough to satisfy for the requirements
separating the controlled rooms and a
of the room with the greatest need of cooling.
reference area, normally the clean corridor.
Only available with chilled water versions.
- Return/exhaust airflow: regulated by the
- Air temperature in individual rooms:
machine microprocessor to maintain constant
regulated by a hot water or electric post-
depression in the return/exhaust duct in
heating coil installed in the duct going to the
order to be able to activate the VAV dampers
individual room, regulated by information
in each individual room.
coming from a sensor installed in the room
itself.
30
Air conditioning plant for three surgical rooms with
unidirectional filtration ceilings
31
Plant for diagnostic The characteristics of the air conditioning plant
for this room are as follows:
imaging - supply airflow (full fresh air), approx. 10
volumes per hour, therefore about 1,200
m3/h.
General characteristics - Air filtration: standard F7, maximum F9,
The air conditioning plant for a magnetic already guaranteed by the air conditioner, so
resonance department serves three separate without final air filtration.
areas, all of which have quite different - Exhaust airflow: approx. 1,000 m3/h, 60%
characteristics and requirements: of which is from the magnet and the rest is
1. Examination room returned air expelled from the air conditioner;
2. Control room - Ambient conditions: temperature 24°C ± 2°C;
3. Technical room humidity 50% ± 5%.
- Sensible cooling: approx. 5 kW.
32
Air conditioning plant for magnetic resonance
departments
33
2. Control room 3. Technical room
3
This has a volume of approx. 70 m . This has a volume of approx. 70 m3; it
Plant characteristics: normally has a raised floor and therefore the
- supply airflow (full fresh air); 6 volumes/hour, air conditioner treating the recirculation air
3
so about 450 m /h; discharges downwards.
- air filtration: standard F7, maximum F9; Plant characteristics:
3
- exhaust airflow: about 400 m /h; - supply airflow (full fresh air): 2 volumes/hour,
- ambient conditions: temperature 22°C ± 2°C; therefore about 150 m3/h;
humidity: 50% ± 5%; - recirculation airflow: about 4,000 m3/h;
- sensible cooling: about 1.5 kW. - air filtration: F7, maximum F9 for the fresh
air; G4 for the recirculation air;
- exhaust airflow: about 50 m3/h;
- ambient conditions: temperature 22°C ± 2°C;
humidity: 50% ± 5%;
- sensible cooling: about 20 kW.
34
Construction alternative.
- Normally without a heat recovery system, due
characteristics to both the low airflow and to the fact that
part of the exhaust is done by the magnet and
1. Plant therefore is not returned to the air conditioner.
The plant, which is normally completely - Motorised damper on the fresh air intake.
separate from the air conditioning system of - G4 fresh air pre-filter.
the hospital, uses full fresh air with integrated - Hot water heating coil with microprocessor-
local recirculation only in the machine room. controlled three way valve functioning in
Temperature regulation is by set point with mixing and the related spill-back pump.
the sensor in the supply compartment and the - Chilled water cooling coil with microprocessor-
humidity sensor in the return air compartment. controlled three way valve functioning in
The constancy of the supply airflow is deviation.
guaranteed by a continuous measurement - Post-heating coil with microprocessor-
device and correction by an inverter on the fan. controlled three way valve functioning in
deviation.
- Modulating steam humidifier with immersed
2. Air conditioner for fresh air electrodes controlled by microprocessor.
Air conditioner for the treatment of full fresh - Supply fan with electronic speed regulator and
air, having the following characteristics, model airflow meter.
OHU 2200: - F7 or F9 efficiency supply air filter.
- mono-block unit complete with controls, - F5 efficiency return air filter.
electrical panel, microprocessor and - Return/exhaust fan with inverter to regulate
specialized software, certified to UNI/EN 1886. the necessary room overpressure.
- The air conditioner normally has a chilled water - RS485 board to connect to the remote control
coil; direct expansion coil available as an system of the hospital.
35
3. Supply and return air ducting 4. Air conditioner for the
and accessories machine room
Externally insulated galvanized sheet metal, Chilled water with downward discharge of the
airtight to at least class B: supply air, model UCU 30. The supply air flow
- always fitted with a sound damper in the is regulated automatically as a function of the
supply and return air duct. power required by the electronic equipment.
- The necessity of having sound dampers A sensor in the air conditioner installed in
installed in the fresh air intake and the the return duct regulates the temperature.
exhaust air outlet duct is dependent upon Post-heating and humidification is not
the evaluation of the impact on the external necessary as these functions are already
surrounding area. guaranteed by the treatment of the fresh air.
- Post-heating coil on the supply duct to the
examination and control rooms; it is not
essential on the duct to the machine room
because that area always produces enough
heat itself; normally a hot water coil is used,
regulated by a three way modulating valve
which is controlled by a sensor installed in
the controlled room, alternatively an electric
coil with TRIAC regulation can be used.
36
37
Accessories • Water cooled plate condenser.
• Two-way pressure sensor valve.
• Temperature and humidity sensors supplied
Numerous accessories are available to loose instead of installed in the return
customise the unit according to the section.
requirements of the application: • Temperature sensor in the supply fan
section (cold point regulation) and humidity
• Second user interface terminal for remote sensor in the return section.
control of the machine. • Pressure sensor to read the supply airflow
• Cooling capacity control of the compressor with constant pressure regulation.
(OHA model only), for perfect modulation of • Specific gateways for integration with
the cooling circuits as a function of the BACnet or Lonworks systems.
external conditions. This is indispensable • Specific gateways for remote management
for the treatment of full fresh air. via internet (TCP/IP) and via GSM modem
• Double electronic supply fan installed in with SMS sending capability.
parallel with the standard fan to guarantee • Hydronic heat recovery system.
maximum operating safety. • Epoxy painted coil fins.
• Double electronic return air and exhaust fan • Direct expansion post-cooling system for
installed in parallel with the standard fan to heart surgery.
guarantee maximum operating safety. • Modulating centralized steam distributor
• F7 filter instead of the standard G4 at the instead of an autonomous immersed-
inlet of the machine. electrode version.
• F9 filter instead of the standard F7 at the • Immersed resistance humidifier instead of
outlet of the machine. the immersed-electrode type.
• Air recirculation damper, motorized, • Sealed internal lighting to enable correct-
modulating and counter-opposed to the function checks of the machine without
fresh air one. having to open it.
• Motorized dampers on all vents. • Water presence alarm.
• Motorized dampers on all vents, airtight
level 4 to standard DIN 1751.
38
Operating performance
(without heat recovery)
Models 2.200 3.600 4.600 6.800 11.400 Net weight (OHU) kg 600 800 800 1000 1300
39
We are in the business of building efficiency
Johnson Controls creates buildings and environments that help people achieve. We do that by making environments
healthier. Saving energy. Enhancing operations. And creating sustainable solutions for our partners all over the world.
Building on a legacy over of 125 years, we’re experts at delivering solutions for commercial buildings, institutions, hospitals,
schools, district cooling plants, process facilities and more. And as challenges arise for greater energy efficiency and more
sustainable facilities, we’ll help you overcome them with the widest technology and service portfolio in the world.
middleeast.johnsoncontrols.com