Escolar Documentos
Profissional Documentos
Cultura Documentos
multi-wing facility
5.1 Introduction
Fans will be selected and sized to minimize noise in order to minimize the need for
sound attenuation.
In fan systems totaling 10 HP or more, capacity will be adjusted using Variable
Frequency Drives (VFD). Use OWNER standard VFD specifications and
instructions.
Fan motors 1 HP and larger will be premium efficiency 1800 RPM unless a different
speed is approved by OWNER. Size motors so that they operate at about 80% load
at maximum anticipated airflow.
If fan HP requirement is ≥10 HP for any single purpose, use multiple direct drive plug
fans in a wall type configuration (Huntair, Trane, Aaon or approved equal) rather than
one large fan.
Packaged Roof Top AHUs will have a minimum R-13 insulation value.
Note: Aaon manufactures AHUs and packaged units with variable speed
compressors, variable speed multiple fan walls and minimum R-13 insulation. All at
a similar price to competitors with conventional features.
AIR FILTERS:
Owner has studied air filters and determined the lowest LCC product for each
application. An approved equal would produce an equal or lower LCC to the
specified filters.
Size filter banks so that only 2’x 2’ and 1’x 2’ filters are used and air velocities should
be no greater than 4500 FPM.
Use 4” deep MERV 8 high capacity filters in typical applications.
Use 22” deep MERV 13 bag filters if needed to acquire LEED points.
Areas requiring higher efficiency air filters shall use 4” deep MERV 8 high capacity
prefilters and 22” deep MERV 15 final filters. It is also acceptable to use 12” deep
rigid filters that provides the lowest total cost of ownership as determined by the
BetterBricks Air Filter Comparison Calculator.
http://www.betterbricks.com/DetailPage.aspx?ID=943
DUCTWORK
Do not use more than 4 feet of flexible ductwork unless it is necessary in retrofit
applications.
Do not expose fiberglass to the ventilation system air stream or to occupied space.
Use full radius or splitter vane elbows only.
Select duct velocities to meet N.C. requirements of each occupied space.
Do not use opposed blade damper registers in occupied spaces. Locate balancing
dampers next to the connection to the main branch or terminal box to minimize noise
levels in occupied spaces. Insure that these dampers are accessible.
For return and exhaust ductwork, select a pressure rating that will avoid damage to
ductwork in event of sudden smoke/fire damper closure during fan operation.
Protect ductwork from overpressure due to the sudden closing of dampers. Provide
accessible, well-sealed pressure relief doors or panels that can be closed and
sealed with out special tools or new parts after they blow open.
DAMPERS:
Construct damper blades of minimum 14 gauge galvanized steel and damper frames
of minimum 16 gauge galvanized steel. Provide opposed blade action with stainless
steel compressible jamb seals and extruded blade edge seals suitable for 0 degrees
F to 250 degrees F. Blades shall rotate on stainless steel sleeve bearings. Damper
blade lengths shall not exceed 60 inches. Leakage rate shall not exceed 5
CFM/square foot at 1-inch water gage and 9 CFM/square foot at 4 inches water
gage. Leakage and pressure ratings shall be based on AMCA Publication 500.
Damper shafts shall have at least one flat facet at the point of connection to the
actuator.
Provide a grooved scribe running parallel to the blades on the end of each damper
shaft.
Outside, Return and Relief air dampers shall be independently driven and controlled.
Large damper assemblies shall be made of individually driven sections that are
small enough to ensure reliable operation and uniform closure across the entire
damper assembly when operated by a single actuator.
HVAC ACTUATORS:
Generally, actuators shall use 24 VAC power, analog control (or floating point control
with position feedback) and mount around a rotating shaft to modulate dampers and
valves.
Provide actuators with at least 150% of the required device torque.
Damper actuators shall be operated and controlled independently so that if one
damper segment or actuator becomes inoperable, the others remain operable.
When adequate control air is available, use pneumatic actuators for large valves.
Two stacked electric actuators may be used with OWNER approval for large valves.
Mount electric actuators horizontally to hot water valves.
ACTUATED VALVES:
Modulating 2-way control valves shall be pressure independent.
3-way valves shall not typically be used. A 2-way controlled bypass may be used to
maintain a minimum water flow.
Pressure independent flow control valves will not generally need circuit setters or
dedicated strainers.
Two-position valves shall be of a rotating type and may be ball, shoe or butterfly
depending on size and application.
Valves 2.5” and smaller shall be stainless steel, brass or bronze.
Valve stems shall have at least one flat facet at the point of connection to the
actuator.
CHILLERS:
In general, variable speed chilled water systems will be used for cooling
applications.
Lowest total cost of chiller ownership will be the primary criteria for purchase so
anticipated energy consumption will be used in conjunction with the installed cost
and anticipated O&M costs to determine the “best bid”.
Typically, variable speed compressors will produce the lowest total cost of
ownership.
OWNER will provide a chiller selection tool characterized for the specific needs of
the project. The mechanical designer will assist in creating a load profile for this
tool.
Air Cooled chillers <200 tons will be considered if LCC justified.
Hybrid systems using indirect evaporative cooling, direct evaporative cooling and/or
refrigerated cooling may be considered to reduce life cycle costs (LCC).
Small DX units may be allowed for small process loads such as data centers or labs.
If practical, cooling equipment should be provided in sizes and configurations so that
hot gas bypass is never needed.
Reciprocating compressors are not allowed.
PUMPS:
Generally, variable speed pumps will be selected for N+1 operation such that all but
one pump can operate at 60 HZ and produce 100% design flow. For example, three
chilled water pumps might be installed and sized so that two pumps must run at
100% speed in order to maintain design flow. Typically all three pumps will operate
in parallel at reduced speed to produce design flow. Pump selection and sequence
of operation must be optimized to minimize energy consumption.
MOTORS:
All electric motors ≥ 1 HP shall be premium efficiency
5.9 HVAC Design Conditions
B. The design guidelines for typical exhaust systems include the following:
1. Establish exhaust requirements per ASHRAE Standard 62.1-2007.
2. Exhaust toilet rooms, darkrooms, battery rooms and any other areas that
contain noxious, harmful, or objectionable fumes.
3. Areas being exhausted are required to be balanced so a slight negative
pressure exists.
4. Exhaust refrigeration machinery rooms to meet the requirements of the
UMC.
5. Use sight proof and non-adjustable louvers.
6. Use special exhaust grilles and door louvers in darkrooms to prevent
passage of light.
A. Clearly define the source of all exhaust air and provide clean tempered air
into the space to replace exhaust air.
B. Design hoods and calculate exhaust requirements based on similar
applications found in the ACGIH, American conference of governmental
industrial hygienists industrial ventilation manual.
C. Local exhaust ventilation systems are to be installed per manufacturer’s
requirements and guidelines set in ACGIH.
D. Coordinate layout requirements of fume hoods with architect. Locate fume
hood faces 10 feet or more from the closest air supply or exhaust point but
not along normal traffic routes. A fume hood should not be located where the
room air currents are greater than 50 feet per minute.
E. Fume hood full open air face velocity settings can be between 80 and 100
feet per minute. Generally, a face velocity of 100 feet per minute is
satisfactory if the quality of supply air distribution is adequate. OWNER may
accept 50 FPM face velocities based upon agreement with the users and
designers. Regulated carcinogens and radiological hoods require higher face
velocities.
F. Install fume hoods with an airflow indicator: a vanometer, differential pressure
gauge or variable air volume control system.
G. Exhaust systems handling particles require minimum transport velocities be
maintained throughout the system.
H. Exhaust systems handling vapors or gases duct velocities of 2000-3000 feet
per minute usually result in a good balance.
I. Calculate exhaust requirements for closed type glove boxes for 50 CFM per
box.
J. Exhaust vacuum pump-oil mist to the outside or to the building exhaust
system.
K. HEPA systems used in radiological applications are to be installed per
manufacturer’s recommendations.
A. The design guidelines for typical exhaust fans include the following:
1. Roof exhausters for general room exhaust are required to be aluminum,
roof mounted, curb type, centrifugal, integral weather cover, bird screen,
back-draft damper, electrical disconnect.
2. Exhaust fans that serve acid, corrosive or fume hoods are required to be
utility and epoxy coated. Design fumes at an exit velocity of 3000 feet per
minute. Extend exhaust stacks at least 10 feet above roof level or air
intakes that are within 50 feet. Do not install weather cap on stacks that
discharge hazardous chemicals.
3. Coordinate design of exhaust stacks with structural and electrical to
ensure proper stack support and lightning protection.
10. For pressures less than negative 4” w.c., greater than positive 10” w.c. and
highly corrosive duct refer to SMACNA Round Industrial Duct Construction
Standards of SMACNA Rectangular Duct Construction Standards.
11. Fire and Smoke dampers are to be specified for dynamic closure to shut
off against airflow at a minimum of 2375 feet per minute and 4 inches of
water.
A. It is preferred to locate air intakes and exhausts on roof and orient them to
minimize adverse wind effects. All outside air intakes are to be at least 10
feet from flues, sewer vents, and exhausts.
B. Provide roof curbs for packaged units and fans.
C. Set up items not suitable for curb mounting at 18 inches above roof surface
on angle iron stand or MIRO support so re-roofing can be done under them.
It may also be acceptable to have unions installed in piping assemblies for
temporary removal of piping when re-roofing occurs.
D. Provide maintenance pads around packaged roof top equipment or larger
equipment requiring periodic maintenance.
E. Whenever mechanical equipment is roof mounted, call out permanent and
secured access ladders leading to the roof.
F. Provide at least a 6 foot clearance between roof mounted equipment and the
edge of roof, or provide suitable rail guards.
G. Provide structural engineer information concerning size, weight, and dynamic
loadings associated with roof mounted equipment.
5.17 Controls
A. OWNER water pressures range from 60 to 110 pounds per square inch
gauge (psig).
B. Natural gas main pressure is 20 psig.
C. Flush valves require a minimum of 25 psig residual pressure. All other
fixtures require a minimum of 15 psig residual pressure.
D. Water velocities in domestic system are required to be designed so velocities
do not exceed 10 feet per second.
E. At a minimum natural gas, liquid propane gas, roof drain leaders and
domestic water piping sized per UPC or other approved engineered method.
F. Hot water to lavatories and sinks design to receive 110 ̊F.
G. Commercial Kitchen Hand Sinks and Dishwashers designed to receive 140 ̊F.
5.25 Mechanical and Plumbing Calculations Required