Você está na página 1de 64

Reinforced Concrete Design©

Using the Ultimate Limit Design Method


according to the ECP 203-2017

Ver. 12.0

Please send your comments & suggestions to improve this tool on


melkateb@hotmail.com

by
Mahmoud M. El-Kateb, Ph.D

Structural Engineering Dept.


Faculty of Engineering - Ain Shams University
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 1.1

* Calculation of T & L Section Inertia

* Project :

1200 mm
250 mm

700 mm

250 mm

I R-sec = 7.15E+09 mm4


yc.g = 220 mm from flange edge
I T-sec = 1.35E+10 mm4 = 1.9 I R-sec
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 9.4

* Calculation of Loads & Coeffecients

* Project :

Load Distribution of Solid Slabs:

Long span Short span Code of practice Marcus Grashoff


Area
Span (m) contin. Span (m) contin. a b a b a b
1 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
2 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
3 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
4 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
5 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
6 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
7 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
8 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
9 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291
10 5 1 4 1 0.475 0.224 0.568 0.232 0.709 0.291

Load Distribution on Beams:

Load on Long Short Load coeff. Load distribution for


Area
slab (kN/m2) span (m) span (m) shear moment shear (kN/m`) moment (kN/m`)
1 8.5 5 4 0.600 0.787 10.2 13.4
2 8.5 5 4 0.600 0.787 10.2 13.4
3 8.5 5 4 0.600 0.787 10.2 13.4
4 8.5 5 4 0.600 0.787 10.2 13.4
5 8.5 5 4 0.600 0.787 10.2 13.4
6 8.5 5 4 0.600 0.787 10.2 13.4
7 8.5 5 4 0.600 0.787 10.2 13.4
8 8.5 5 4 0.600 0.787 10.2 13.4
9 8.5 5 4 0.600 0.787 10.2 13.4
10 8.5 5 4 0.600 0.787 10.2 13.4

Load of Hollow Slabs:

Web breadth Spacing Thick Slab th F.C L.L Block One way Two way
Area
b (mm) e (mm) t (mm) ts (mm) (kN/m2) (kN/m2) Wt. (kN) Wu (kN/m2) Wu (kN/m2)
1 120 400 270 70 1.5 2.0 0.15 11.4 12.2
2 120 400 270 70 1.5 2.0 0.15 11.4 12.2
3 120 400 270 70 1.5 2.0 0.15 11.4 12.2
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 9.4

* Calculation of Loads & Coeffecients

* Project :

4 120 400 270 70 1.5 2.0 0.15 11.4 12.2


5 120 400 270 70 1.5 2.0 0.15 11.4 12.2
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 1.0

* Fire Rating Requirements

* Project :

Design fire rating period: 2 hours


Type of aggregate: ‫متوسط الوزن‬

Traditional slabs: Pre-stressed slabs:


min. Thick = 120 mm min. Cover = 40 mm
min. Cover = 25 mm

Traditional simple beams: Traditional cont. beams:


min. Breadth = 250 mm min. Breadth = 180 mm
min. Cover = 35 mm min. Cover = 30 mm

Columns:
min. Dim. = 250 mm
min. Cover = 40 mm

Walls:
RFT ratio m 0.4 % < < 1 %
min. Dim. = 200 mm
min. Cover = 25 mm
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Empirial Analysis of Solid Slabs

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Long span Short span min. Slab Slab thick F.C L.L Wsu Code of practice Moments (kN.m) Rft. /m Rft. /m
Area
Span (m) contin. Span (m) contin. thick (mm) (mm) (kN/m 2
) (kN/m 2
) (kN/m 2
) a b Ma Mb short dir. long dir.
1 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
2 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
3 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
4 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
5 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
6 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
7 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
8 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
9 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
10 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
11 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
12 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
13 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
14 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
15 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
16 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
17 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Empirial Analysis of Solid Slabs

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Long span Short span min. Slab Slab thick F.C L.L Wsu Code of practice Moments (kN.m) Rft. /m Rft. /m
Area
Span (m) contin. Span (m) contin. thick (mm) (mm) (kN/m 2
) (kN/m 2
) (kN/m 2
) a b Ma Mb short dir. long dir.
18 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Design of Slabs

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Ult. Moment Breadth Depth As Asmin Used


Sec. C1 J Rft. /m Notes
Mu (kN.m) b (mm) d (mm) (mm ) (mm )
2 2
As
1 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
2 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
3 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
4 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
5 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
6 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
7 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
8 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
9 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
10 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
11 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
12 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
13 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
14 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
15 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
16 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
17 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
18 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
19 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
20 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
21 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
22 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
23 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
24 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
25 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
26 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
27 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
28 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
29 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
30 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
31 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
32 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Design of Slabs

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Ult. Moment Breadth Depth As Asmin Used


Sec. C1 J Rft. /m Notes
Mu (kN.m) b (mm) d (mm) (mm ) (mm )
2 2
As
33 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
34 15 1000 120 4.90 0.826 378 180 378 5 f 10 safe
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Empirical Design of Flat Slab

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Slab Module: Long span L1 = 7 m Short span L2 = 6 m


Marginal beams: Yes
Column dim.: with long span 500 mm with short span = 500 mm
Slab thickness: 220 mm
Live load: 4.0 kN/m2 Floor cover + Walls: 2.5 kN/m2
Slab load Wsu = 17.6 kN/m2

Long direction 117.3 1 293.3 3


Column strip 4 176.0 2 146.7

Long direction 58.7 5 117.3 7


Field strip 8 117.3 6 88

Short direction 91.8 9 233.1 11 Modified


Column strip 12 134.2 10 113

Short direction 56.5 13 113.0 15 Modified


Field strip 16 113.0 14 84.8

Page 10 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Empirical Design of Flat Slab

Design of sections:

Ult. Moment Breadth Depth As Asmin Used


Sec. C1 J Rft. /m Notes
Mu (kN.m) b (mm) d (mm) (mm2) (mm2) As
1 176.0 3000 190 3.92 0.801 963 285 963 5 f 16 safe
###
2 293.3 3000 190 3.04 0.747 1722 285 1722 9 f 16 safe
###
3 146.7 3000 190 4.30 0.814 791 285 791 4 f 16 safe
###
4 117.3 3000 190 4.80 0.826 623 285 623 4 f 16 safe
###
5 117.3 3000 190 4.80 0.826 623 285 623 6 f 12 safe
###
6 117.3 3000 190 4.80 0.826 623 285 623 6 f 12 safe
###
7 88.0 3000 190 5.55 0.826 467 285 467 5 f 12 safe
###
8 58.7 3000 190 6.79 0.826 312 285 312 3 f 12 safe
###
9 134.2 3000 190 4.49 0.819 719 285 719 7 f 12 safe
###
10 233.1 3000 190 3.41 0.776 1317 285 1317 7 f 16 safe
###
11 113.0 3000 190 4.89 0.826 600 285 600 6 f 12 safe
###
12 91.8 3000 190 5.43 0.826 488 285 488 5 f 12 safe
###
13 113.0 4000 190 5.65 0.826 450 285 450 4 f 12 safe
###
14 113.0 4000 190 5.65 0.826 450 285 450 4 f 12 safe
###
15 84.8 4000 190 6.53 0.826 338 285 338 3 f 12 safe
###
16 56.5 4000 190 7.99 0.826 225 285 285 3 f 12 safe
###

Page 11 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Check Punching for Flat Slab Columns

* Project :

Concrete fcu = 25 MPa

Internal columns:

b critical perimeter (bo)

Ult. Load Col. Dims. Slab Cover Critical bo qcpu qpu


Col. Notes
Nu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) (N/mm ) 2
(N/mm2)
1 600 300 600 250 30 Auto 2680 1.29 1.17 Safe
2 600 300 600 250 30 Auto 2680 1.29 1.17 Safe
3 600 300 600 250 30 Auto 2680 1.29 1.17 Safe
4 600 300 600 250 30 Auto 2680 1.29 1.17 Safe
5 600 300 600 250 30 Auto 2680 1.29 1.17 Safe
6 600 300 600 250 30 Auto 2680 1.29 1.17 Safe
7 600 300 600 250 30 Auto 2680 1.29 1.17 Safe
8 600 300 600 250 30 Auto 2680 1.29 1.17 Safe
9 600 300 600 250 30 Auto 2680 1.29 1.17 Safe

D critical perimeter (bo)

Ult. Load Col. Dims. Slab Cover Critical bo qcpu qpu


Col. Notes
Nu (kN) D (mm) Thick (mm) (mm) Perimeter (mm) (N/mm2) (N/mm2)
1 450 400 250 30 Auto 1948 1.29 1.21 Safe
2 450 400 250 30 Auto 1948 1.29 1.21 Safe
3 450 400 250 30 Auto 1948 1.29 1.21 Safe

Page 12 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Check Punching for Flat Slab Columns


4 450 400 250 30 Auto 1948 1.29 1.21 Safe

Edge columns:

b critical perimeter (bo)

Ult. Load Col. Dims. Slab Cover Critical bo qcpu qpu


Col. Notes
Nu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) (N/mm2) (N/mm2)
1 300 300 600 250 30 Auto 1640 1.29 1.08 Safe
###
2 300 300 600 250 30 Auto 1640 1.29 1.08 Safe
###
3 300 300 600 250 30 Auto 1640 1.29 1.08 Safe
###
4 300 300 600 250 30 Auto 1640 1.29 1.08 Safe
###
5 300 300 600 250 30 Auto 1640 1.29 1.08 Safe
###
6 300 300 600 250 30 Auto 1640 1.29 1.08 Safe
###
7 300 300 600 250 30 Auto 1640 1.29 1.08 Safe
###

Corner columns:

b
critical perimeter (bo)

Ult. Load Col. Dims. Slab Cover Critical bo qcpu qpu


Col. Notes
Nu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) (N/mm2) (N/mm2)
1 200 300 600 250 30 Auto 1120 1.29 1.22 Safe
2 200 300 600 250 30 Auto 1120 1.29 1.22 Safe
3 200 300 600 250 30 Auto 1120 1.29 1.22 Safe
4 200 300 600 250 30 Auto 1120 1.29 1.22 Safe
5 200 300 600 250 30 Auto 1120 1.29 1.22 Safe
6 200 300 600 250 30 Auto 1120 1.29 1.22 Safe
7 200 300 600 250 30 Auto 1120 1.29 1.22 Safe

Page 13 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 1.1

* Calculation of Punching RFT

* Project :

Concrete fcu = 25 MPa


Steel fy = 350 MPa

Internal columns:
bb

no. of bra.
parallel to b
no. of bra.
parallel to t
bt
tcol

Ult. Load Col. Dims. Slab Req. no. of Branch Spcaing bb no. of bra. bt no. of bra. no. of RFT
Col.
Nu (kN) b (mm) t (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) parallel to b (mm) parallel to t Rows
1 900 300 600 250 10 12 100 250 2 250 4 3
2 900 300 600 250 10 12 100 250 2 250 4 3
3 900 300 600 250 10 12 100 250 2 250 4 3
4 900 300 600 250 10 12 100 250 2 250 4 3
5 900 300 600 250 10 12 100 250 2 250 4 3
6 900 300 600 250 10 12 100 250 2 250 4 3
7 900 300 600 250 10 12 100 250 2 250 4 3

Page 14 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 1.1

* Calculation of Punching RFT


8 900 300 600 250 10 12 100 250 2 250 4 3

Ult. Load Col. Dims. Slab Req. no. of Branch Spcaing b no. of no. of
Col. Notes
Nu (kN) D (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) branches Rows
1 650 400 250 8 12 100 200 4 2 Safe
2 650 400 250 8 12 100 200 4 2 Safe
3 650 400 250 8 12 100 200 4 2 Safe
4 650 400 250 8 12 100 200 4 2 Safe

Edge columns:

tcol

bcol

Ult. Load Col. Dims. Slab Req. no. of Branch Spcaing bb no. of bra. bt no. of bra. no. of RFT
Col.
Nu (kN) b (mm) t (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) parallel to b (mm) parallel to t Rows
1 500 300 600 250 7 12 100 250 2 250 4 4
2 500 300 600 250 7 12 100 250 2 250 4 4
3 500 300 600 250 7 12 100 250 2 250 4 4
4 500 300 600 250 7 12 100 250 2 250 4 4

Page 15 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 1.1

* Calculation of Punching RFT


5 500 300 600 250 7 12 100 250 2 250 4 4
6 500 300 600 250 7 12 100 250 2 250 4 4

Corner columns:

Ult. Load Col. Dims. Slab Req. no. of Branch Spcaing bb no. of bra. bt no. of bra. no. of RFT
Col.
Nu (kN) b (mm) t (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) parallel to b (mm) parallel to t Rows
1 250 300 600 250 4 12 100 250 2 250 4 2
2 250 300 600 250 4 12 100 250 2 250 4 2
3 250 300 600 250 4 12 100 250 2 250 4 2
4 250 300 600 250 4 12 100 250 2 250 4 2
5 250 300 600 250 4 12 100 250 2 250 4 2
6 250 300 600 250 4 12 100 250 2 250 4 2

Page 16 of 64
By: Dr. Mahmoud El-Kateb

Notes
qpu
Safe ###
Safe ###
Safe ###
Safe ###
Safe ###
Safe ###
Safe ###

Page 17 of 64
By: Dr. Mahmoud El-Kateb

Safe ###

qpu
###
###
###
###

Notes
qpu
Safe ###
Safe ###
Safe ###
Safe ###

Page 18 of 64
By: Dr. Mahmoud El-Kateb

Safe ###
Safe ###

Notes
qpu
Safe ###
Safe ###
Safe ###
Safe ###
Safe ###
Safe ###

Page 19 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.3

* Design of Beams

* Project :

Concrete fcu = 30 MPa


Steel fy = 400 MPa

Ult. Moment Breadth Comp.fl. Depth Asmin Used


Sec. C1 J Rft. Notes
Mu (kN.m) b (mm) B (mm) d (mm) (mm2) As
1 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
2 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
3 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
4 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
5 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
6 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
7 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
8 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
9 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
10 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
11 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
12 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
13 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
14 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
15 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
16 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
17 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
18 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
19 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
20 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
21 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
22 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
23 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
24 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
25 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
26 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
27 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
28 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
29 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
30 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
31 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
32 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.3

* Design of Beams

* Project :

Concrete fcu = 30 MPa


Steel fy = 400 MPa

Ult. Moment Breadth Comp.fl. Depth Asmin Used


Sec. C1 J Rft. Notes
Mu (kN.m) b (mm) B (mm) d (mm) (mm2) As
33 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
34 150 250 250 650 4.60 0.821 501 703 4 f 16 safe
###
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Design of Beams with Compression Rft.

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Ult. Moment Breadth Depth Thick Main Comp.


Sec. Main Rft. Comp. Rft. Notes
Mu (kN.m) b (mm) d (mm) t (mm) As As
1 400 250 650 700 2090 6 f 22 339 4 f 12 ok
2 400 250 650 700 2090 6 f 22 339 4 f 12 ok
3 400 250 650 700 2090 6 f 22 339 4 f 12 ok
4 400 250 650 700 2090 6 f 22 339 4 f 12 ok
5 400 250 650 700 2090 6 f 22 339 4 f 12 ok
6 400 250 650 700 2090 6 f 22 339 4 f 12 ok
7 400 250 650 700 2090 6 f 22 339 4 f 12 ok
8 400 250 650 700 2090 6 f 22 339 4 f 12 ok
9 400 250 650 700 2090 6 f 22 339 4 f 12 ok
10 400 250 650 700 2090 6 f 22 339 4 f 12 ok
11 400 250 650 700 2090 6 f 22 339 4 f 12 ok
12 400 250 650 700 2090 6 f 22 339 4 f 12 ok
13 400 250 650 700 2090 6 f 22 339 4 f 12 ok
14 400 250 650 700 2090 6 f 22 339 4 f 12 ok
15 400 250 650 700 2090 6 f 22 339 4 f 12 ok
16 400 250 650 700 2090 6 f 22 339 4 f 12 ok
17 400 250 650 700 2090 6 f 22 339 4 f 12 ok
18 400 250 650 700 2090 6 f 22 339 4 f 12 ok
19 400 250 650 700 2090 6 f 22 339 4 f 12 ok
20 400 250 650 700 2090 6 f 22 339 4 f 12 ok
21 400 250 650 700 2090 6 f 22 339 4 f 12 ok
22 400 250 650 700 2090 6 f 22 339 4 f 12 ok
23 400 250 650 700 2090 6 f 22 339 4 f 12 ok
24 400 250 650 700 2090 6 f 22 339 4 f 12 ok
25 400 250 650 700 2090 6 f 22 339 4 f 12 ok
26 400 250 650 700 2090 6 f 22 339 4 f 12 ok
27 400 250 650 700 2090 6 f 22 339 4 f 12 ok
28 400 250 650 700 2090 6 f 22 339 4 f 12 ok
29 400 250 650 700 2090 6 f 22 339 4 f 12 ok
30 400 250 650 700 2090 6 f 22 339 4 f 12 ok
31 400 250 650 700 2090 6 f 22 339 4 f 12 ok
32 400 250 650 700 2090 6 f 22 339 4 f 12 ok
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Design of Beams with Compression Rft.

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Ult. Moment Breadth Depth Thick Main Comp.


Sec. Main Rft. Comp. Rft. Notes
Mu (kN.m) b (mm) d (mm) t (mm) As As
33 400 250 650 700 2090 6 f 22 339 4 f 12 ok
34 400 250 650 700 2090 6 f 22 339 4 f 12 ok
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Design of Sec. under M,N

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Ult. Moment Normal Breadth Depth Thick As Asmin Used


Sec. ecc. C1 J Rft.
Mu (kN.m) Nu (kN) b (mm) d (mm) t (mm) (mm ) (mm2)
2
As
1 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
2 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
3 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
4 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
5 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
6 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
7 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
8 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
9 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
10 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
11 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
12 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
13 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
14 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
15 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
16 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
17 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
18 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
19 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
20 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
21 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
22 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
23 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
24 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
25 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
26 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
27 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
28 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
29 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
30 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
31 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
32 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Design of Sec. under M,N

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Ult. Moment Normal Breadth Depth Thick As Asmin Used


Sec. ecc. C1 J Rft.
Mu (kN.m) Nu (kN) b (mm) d (mm) t (mm) (mm ) (mm2)
2
As
33 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
34 150 -200 250 650 700 Big 3.55 0.784 455 457 457 3 f ###
16
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.3

* Check Shear in Beams

* Project :

Concrete fcu = 30 MPa


Concrete qcu cracked = 0.54 MPa
Stirrups fy = 240 MPa

Ult. Shear Breadth Depth qu As min. no. of


Sec. stirrup Stirrups /m Notes
Qu (kN) b (mm) d (mm) (N/mm ) 2
S s bran. ###
1 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
2 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
3 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
4 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
5 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
6 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
7 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
8 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
9 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
10 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
11 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
12 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
13 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
14 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
15 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
16 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
17 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
18 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
19 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
20 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
21 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
22 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
23 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
24 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
25 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
26 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
27 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
28 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
29 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
30 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
31 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.3

* Check Shear in Beams

* Project :

Concrete fcu = 30 MPa


Concrete qcu cracked = 0.54 MPa
Stirrups fy = 240 MPa

Ult. Shear Breadth Depth qu As min. no. of


Sec. stirrup Stirrups /m Notes
Qu (kN) b (mm) d (mm) (N/mm ) 2
S s bran. ###
32 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
33 150 250 650 0.92 0.463 0.417 2 5 f 8 safe###
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Design for Torsion

* Project :

Concrete fcu = 25 MPa

Stirrups fy = 240 MPa

Horizontal bars fy = 400 MPa ###

###
Ult. torsional moment Sec. dim. Ult. shear force ###
Sec. Mu (kN.m) b (mm) t (mm) Qu (kN)
1 20 300 700 150
qcu
qtu Notes qsu Notes qumax
0.94 N/mm 2
need rft. 0.77 N/mm 2
use min Aoh
Ao
qtcu = 0.24 N/mm2 Ph
qcu = 0.98 N/mm2
qumax = 2.86 N/mm2

Calculation of Rft.

Stirrups due to shear no. f as/s


4.0 8 /m inner
astr/s
Stirrups due to torsion no. f
4.4 10 /m outer
###
or use total stirrups no. f ###
7 10 /m Asl min
Asl
Horizontal Rft. no. f ###
6 12

5 f 10 /m

7 f 10 /m
0.70 m 0.70 m

4f 8 /m

OR
0.30 m 0.30 m
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.1

* Design of Rectangular Columns

* Project :

Concrete fcu = 30 MPa Braced

Steel fy = 400 MPa Unbraced


###
Type of structure: Unbraced ###
Ult. Load Desired Dim of column As Clear Madd
Col. Reinforcement (K) l Notes m (%) d (mm)
Nu (kN) m (%) b (mm) t (mm) (mm ) 2 Height (m) critical min
(kN.m)
1.0 250 250 625 4 f 16 14.4 Safe 1.00 25.9 18.1
1.3 250 250 813 5 f 16 14.4 Safe 1.00 25.9 18.1
C1 700 3.00 1.20
1.6 250 250 1000 5 f 16 14.4 Safe 1.00 25.9 18.1
1.05 250 250 656 4 f 16 14.4 Safe 1.00 25.9 18.1
1.0 250 350 875 5 f 16 14.4 Safe 1.00 25.9 25.9
1.3 250 350 1138 6 f 16 14.4 Safe 1.00 25.9 25.9
C2 1000 3.00 1.20
1.6 250 350 1400 7 f 16 14.4 Safe 1.00 25.9 25.9
1.1 250 350 963 5 f 16 14.4 Safe 1.00 25.9 25.9
1.0 250 450 1125 6 f 16 14.4 Safe 1.00 25.9 31.1
1.3 250 400 1300 7 f 16 14.4 Safe 1.00 25.9 31.1
C3 1200 3.00 1.20
1.6 250 400 1600 8 f 16 14.4 Safe 1.00 25.9 31.1
1.15 250 400 1150 6 f 16 14.4 Safe 1.00 25.9 31.1
1.0 250 550 1375 7 f 16 14.4 Safe 1.00 25.9 38.9
1.3 250 500 1625 9 f 16 14.4 Safe 1.00 25.9 38.9
C4 1500 3.00 1.20
1.6 250 500 2000 10 f 16 14.4 Safe 1.00 25.9 38.9
1.2 250 500 1500 8 f 16 14.4 Safe 1.00 25.9 38.9
1.0 250 650 1625 9 f 16 14.4 Safe 1.00 25.9 46.7
1.3 250 600 1950 10 f 16 14.4 Safe 1.00 25.9 46.7
C5 1800 3.00 1.20
Page 30 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.1

* Design of Rectangular Columns

* Project :

Concrete fcu = 30 MPa Braced

Steel fy = 400 MPa Unbraced


###
Type of structure: Unbraced ###
Ult. Load Desired Dim of column As Clear Madd
Col. Reinforcement (K) l Notes m (%) d (mm)
Nu (kN) m (%) b (mm) t (mm) (mm ) 2 Height (m) critical min
(kN.m)
C5 1800 3.00 1.20
1.6 250 550 2200 11 f 16 14.4 Safe 1.00 25.9 46.7
1.25 250 600 1875 10 f 16 14.4 Safe 1.00 25.9 46.7
1.0 250 750 1875 10 f 16 14.4 Safe 1.00 25.9 54.4
1.3 250 700 2275 12 f 16 14.4 Safe 1.00 25.9 54.4
W1 2100 3.00 1.20
1.6 250 650 2600 13 f 16 14.4 Safe 1.00 25.9 54.4
1.35 250 700 2363 12 f 16 14.4 Safe 1.00 25.9 54.4
1.0 250 850 2125 11 f 16 14.4 Safe 1.00 25.9 62.2
1.3 250 800 2600 13 f 16 14.4 Safe 1.00 25.9 62.2
W2 2400 3.00 1.20
1.6 250 750 3000 15 f 16 14.4 Safe 1.00 25.9 62.2
1.4 250 800 2800 14 f 16 14.4 Safe 1.00 25.9 62.2
1.0 250 4650 11625 31 f 22 14.4 Safe 1.00 25.9 352.5
1.3 250 4350 14138 38 f 22 14.4 Safe 1.00 25.9 352.5
W3 13600 3.00 1.20
1.6 250 4150 16600 44 f 22 14.4 Safe 1.00 25.9 352.5
1.35 250 4300 14513 39 f 22 14.4 Safe 1.00 25.9 352.5
1.0 250 4550 11375 57 f 16 14.4 Safe 1.00 25.9 344.7
1.3 250 4250 13813 69 f 16 14.4 Safe 1.00 25.9 344.7
W4 13300 3.00 1.20
1.6 250 4050 16200 81 f 16 14.4 Safe 1.00 25.9 344.7
1.06 250 4500 11925 60 f 16 14.4 Safe 1.00 25.9 344.7

Page 31 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.1

* Design of Rectangular Columns

* Project :

Concrete fcu = 30 MPa Braced

Steel fy = 400 MPa Unbraced


###
Type of structure: Unbraced ###
Ult. Load Desired Dim of column As Clear Madd
Col. Reinforcement (K) l Notes m (%) d (mm)
Nu (kN) m (%) b (mm) t (mm) (mm ) 2 Height (m) critical min
(kN.m)
1.0 250 1050 2625 14 f 16 14.4 Safe 1.00 25.9 77.8
1.3 250 1000 3250 17 f 16 14.4 Safe 1.00 25.9 77.8
W5 3000 3.00 1.20
1.6 250 950 3800 19 f 16 14.4 Safe 1.00 25.9 77.8
1.55 250 950 3681 19 f 16 14.4 Safe 1.00 25.9 77.8

Page 32 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.1

* Design of Circular Columns

* Project :

Concrete fcu = 25 MPa Braced

Steel fy = 400 MPa Unbraced


###
Type of structure: Unbraced ###
Ult. Load Desired Diamter As Clear Madd
Col. Reinforcement (K) l Notes m (%) d (mm)
Nu (kN) m (%) D (mm) (mm2) Height (m) critical min
(kN.m)
1.0 300 707 4 f 16 16.0 Safe 1.08 38.4 26.9
1.3 300 918 5 f 16 16.0 Safe 1.08 38.4 26.9
1 700 4.00 1.20
1.6 300 1130 6 f 16 16.0 Safe 1.08 38.4 26.9
1.1 300 777 4 f 16 16.0 Safe 1.08 38.4 26.9
1.0 400 1256 7 f 16 12.0 Safe 0.87 28.8 37.4
1.3 400 1633 9 f 16 12.0 Safe 0.87 28.8 37.4
2 1300 4.00 1.20
1.6 400 2010 11 f 16 12.0 Safe 0.87 28.8 37.4
1.2 400 1507 8 f 16 12.0 Safe 0.87 28.8 37.4
1.0 500 1963 10 f 16 9.6 Safe 0.75 23.0 43.8
1.3 500 2551 13 f 16 9.6 Safe 0.75 23.0 43.8
3 1900 4.00 1.20
1.6 450 2543 13 f 16 10.7 Safe 0.80 25.6 48.6
1.4 500 2748 14 f 16 9.6 Safe 0.75 23.0 43.8
1.0 600 2826 15 f 16 8.0 Safe 0.67 19.2 55.7
1.3 600 3674 19 f 16 8.0 Safe 0.67 19.2 55.7
4 2900 4.00 1.20
1.6 600 4522 23 f 16 8.0 Safe 0.67 19.2 55.7
1.5 600 4239 22 f 16 8.0 Safe 0.67 19.2 55.7
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Isolated Footing

* Project :

Concrete fcu = 25 MPa

Steel fy = 400 MPa

Bearing capacity qall = 150 KPa

Column working load Column dim. Extension


foot Nw (kN) b (mm) t (mm) of P.C (mm)
F1 1000 300 500 300 Working P.C

Dims. of P.C : B (mm) L (mm) t (mm)


2,550 2,750 300

Dims. of R.C : B (mm) L (mm) t (mm)


1,950 2,150 600

Actual soil stress (kPa) Notes


146 safe

Stress above P.C (kPa)


254

Shear stress (N/mm2) qcu (N/mm2) Notes


0.37 < 0.65 safe

Punching stress (N/mm2) qcup (N/mm2) Notes


0.61 < 1.29 safe

Calculation of Rft. : Asmin


795 mm2

Long Direction : Mu /m As /m no. f total no.


122 695 8 12 /m 16

Short Direction : Mu /m As /m no. f total no.


122 695 8 12 /m 18
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Isolated Footing under Moment

* Project :

Concrete fcu = 25 MPa

Steel fy = 400 MPa

Bearing capacity qall = 150 KPa

Column working load Moment Column dim. Extension


foot Nw (kN) Mw (kN.m) b (mm) t (mm) of P.C (mm)
F1 250 200 300 500 300 Working P.C

Dims. of P.C : B (mm) L (mm) Lno tens (mm) t (mm)


2,350 2,550 3,612
Choose dim of P.C 2,350 2,550 300

Dims. of R.C : B (mm) L (mm) t (mm)


1,750 1,950 500

Max. Stress (kPa) = 134 Safe secondary case


Min. Stress (kPa) = -23.1 Tension on soil on 0.15 L
Max. Stress (kPa) = 135 Safe secondary case
After Redistribution
Min. Stress (kPa) = 0.0

Shear stress (N/mm2) qcu (N/mm2) Notes


0.41 < 0.65 safe

Punching stress (N/mm2) qcup (N/mm2) Notes


0.19 < 1.29 safe

Calculation of Rft. : Asmin


645 mm2

Long Direction : Mu /m As /m no. f total no.


85 595 6 12 /m 11

Short Direction : Mu /m As /m no. f total no.


38 270 6 12 /m 12

Page 35 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Isolated Footing under Moment

Results:
Nw = 250 kN

Mw = 200 kN.m

0.50 m

0.30 m

0.00
kPa

135
kPa

1.95 m

0.50
/m
1.75 m

2.35 m
0.30

12

0.50
f
6

6 f 12 /m

2.55 m

F1

Page 36 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Isolated Footing under Double Moment

* Project :

Concrete fcu = 25 MPa ###

Steel fy = 400 MPa ###

Bearing capacity qall = 150 KPa ###

Column working load Moment Moment Column dim. Extension


foot Nw (kN) Mwx (kN.m) Mwy (kN.m) b (mm) t (mm) of P.C (mm)
F1 400 150 300 300 500 300 ###

###
Dims. of P.C : B (mm) L (mm) t (mm) ###
1,700 3,400
Choose dim of P.C 3,000 3,200 300

Dims. of R.C : B (mm) L (mm) t (mm)


2,400 2,600 500

LRC
3 1

Mwx

BRC bcol Mwx Mwy BPC

tcol

4 2
LPC

Eccentricities:
ex = 0.28 m ey = 0.55 m
P1 Stress (kPa) = 146 Safe secondary case
P2 Stress (kPa) = 84
P3 Stress (kPa) = 29

Page 37 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

P4 Stress (kPa) = -33 Tension on soil

Using chart:
ex/B = 0.09 ey/L = 0.17 K= 2.67

Max. Stress (kPa) = 150 Safe secondary case

Using Approximate method:


Beff (mm) = 2446 Leff (cm) = 2092
###
Average Stress (kPa) = 106 Safe primary case ###
###
Shear stress (N/mm2) qcu (N/mm2) Notes
0.36 < 0.65 safe

Punching stress (N/mm2) qcup (N/mm2) Notes ###


0.42 < 1.29 safe
###
Calculation of Rft. : Asmin ###
645 mm2 ###
###
Long Direction : Mu /m As /m no. f total no. ###
82 577 6 12 /m 15 ###
###
Short Direction : Mu /m As /m no. f total no.
126 884 8 12 /m 21

Results:

2.60 m 150 kPa


29 kPa 146 kPa

0.50

0.50
F1
/m
2.40 m

3.00 m
0.30

12
f
8

6 f 12 /m

Page 38 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

-33 kPa 84 kPa


(0.00 kPa) 3.20 m

Page 39 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Fence Footing

* Project :

Concrete fcu = 25 MPa

Steel fy = 400 MPa

Bearing capacity qall = 100 KPa

Column working load Moment Column dim. Ecc. Extension


foot Nw (kN) Mw (kN.m) b (mm) t (mm) e (mm) of P.C (mm)
F1 63 20 250 250 525 200

Dims. of P.C : B (mm) L (mm) Lno tens (mm) t (mm)


1,150 1,150 938
Choose dim of P.C 1,500 1,300 200

Dims. of R.C : B (mm) L (mm) t (mm)


1,100 1,100 400

Max. Stress (kPa) = 74 Safe secondary case


Min. Stress (kPa) = 12 No tension
Max. Stress (kPa) = 74 Safe secondary case
After Redistribution
Min. Stress (kPa) = 12

Shear stress (N/mm2) qcu (N/mm2) Notes


0.11 < 0.65 safe

Punching stress (N/mm2) qcup (N/mm2) Notes


0.36 < 1.29 safe

Calculation of Rft. : Asmin


525 mm2

Long Direction : Mu /m As /m no. f total no.


40 357 5 12 /m 6

Short Direction : Mu /m As /m no. f total no.


9 83 5 12 /m 6

Page 40 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Fence Footing

Results:
Nw = 63 kN

Mw = 20 kN.m

0.40 m

0.20 m

12
kPa

74
kPa

1.10 m

0.40
/m
1.10 m

1.50 m
0.25

12

0.25
f
5

5 f 12 /m

1.30 m

F1

Page 41 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Combined Footing

* Project :

Concrete fcu = 25 MPa

Steel fy = 400 MPa

Bearing capacity qall = 150 KPa

F9
Column working load Column dim. (mm) Extension
Col Nw (kN) trans. long. of P.C (mm)
Smaller 600 250 500 300
Larger 840 250 700 300

Distance from c.g to c.g: 2 m

Resultant of 2 loads is at: 1.17 m from smaller column

Dims. of P.C : B (mm) L (mm) Soil stress (kPa)


minimum 3,100 3,450
chosen 2,400 5,000 137 safe

Dims. of R.C : B (mm) L (mm) t (mm)


1,800 4,400 600

LRC

Distance c.g to c.g

BRC Dtransverse Dtransverse BPC

Dlong Dlong

LPC

Punching stress (N/mm2) qpu (N/mm2) qcup (N/mm2) Notes


Samller column 0.54 < 1.29 safe

Page 42 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Combined Footing


Larger column 0.68 < 1.11 safe

Longitudinal direction:

Shear stress (N/mm2) qu (N/mm2) qcu (N/mm2) Notes


max. shear stress 0.35 < 0.65 safe

Top Rft. : Mu /m As /m no. f total no.


NA 795 8 12 /m 15

Bottom Rft. : Mu /m As /m no. f total no.


141 805 5 16 /m 10

Transverse direction:

Shear stress (N/mm2) qu (N/mm2) qcu (N/mm2) Notes


max. shear stress 0.34 < 0.65 safe

Top Rft. : no. f total no.


5 12 /m 23

Bottom Rft. : Mu /m As /m no. f total no.


106 795 8 12 /m 36

Results:

4.40 m

8 f 12 /m

0.60
/m

/m
1.80 m

2.40 m
12

+
12

1.17 m
f

f
5

5 f 16 /m

Page 43 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Combined Footing

5.00 m

Page 44 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Strap Beam Footing

* Project :

Concrete fcu = 25 MPa ###

Steel fy = 400 MPa ###

Bearing capacity qall = 150 KPa ###

Column working load Column dim. (mm) Extension Thickness


Col Nw (kN) trans. long. of P.C (mm) of P.C (mm)
Exter. 685 300 500 0 300
Inter. 1270 300 900 300 300
Rex
Distance from c.g to c.g: 4.9 m ###

Take eccentricity = 0.85 m ###

Dims. of P.C : B (mm) L (mm) Soil Stress (KPa)


External footing 2,700 2,200 143
Internal footing 2,550 3,150 144
###
Dims. of R.C : B (mm) L (mm) t (mm)
External footing 2,100 1,900 500
Internal footing 1,950 2,550 500

Page 45 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Strap Beam Footing

Longitudinal direction: shr1


shr2
Dim. of strap beam : b (mm) t (mm) shr3
500 1000 shstres1
as/s
Rft. of strap beam : Mu (kN.m) no. f as/s min
Top Rft. 616 6 22 ###
Bottom Rft. 238 4 18 ###
shr1 out
Shear stress (N/mm2) qu (N/mm2) qcu (N/mm2) Notes
max. shear stress inside footing 0.70 > 0.65 cracked

Shear stress (N/mm2) qu (N/mm2) qmax (N/mm2) Notes


max. shear stress on beam 1.68 < 2.86 safe
c1
Stirrups /m : no. f ex
6 10 4 branches in

Transverse direction:
###
Bottom Rft. : Mu /m As /m no. f total no.
External footing 106 744 7 12 /m 15
Internal footing 94 663 6 12 /m 17

Page 46 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Pile Cap

* Project :

Concrete fcu = 30 MPa


Steel fy = 400 MPa

Pile Diameter = 0.50 m

Pile Capacity = 600 kN

Column working column dim. extension


cap load Nw (kN) b (mm) t (mm) of P.C (mm)
PC1 1500 300 700 100

Estimated no. of piles = 3 piles

Pile spacing is taken from 1.25 to 3.0 m = 1.50 m in long direction

Pile spacing is taken from 1.25 to 3.0 m = 1.50 m in short direction

Short dir. Long dir.


Choosen arrangement of piles = 2 x 2 Piles used = 4

Dims. of P.C cap: B (mm) L (mm) t (mm)


3,200 3,200 200

Dims. of R.C cap: B (mm) L (mm) t (mm)


3,000 3,000 900

Actual pile load (kN) Notes


437 safe

Shear stress (N/mm2) qcu (N/mm2) Notes


0.53 < 0.72 safe

Punching stress (N/mm2) qcup (N/mm2) Notes


0.51 < 1.31 safe

Calculation of Rft. : Asmin


1245 mm2

Long Direction : Mu /m As /m no. f total


175 1245 7 16 /m 22

Short Direction : Mu /m As /m no. f total


262 1245 7 16 /m 22
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0

* Design of Pile Cap under Moment

* Project :

Concrete fcu = 30 MPa ###

Steel fy = 400 MPa ###

Pile Diameter = 0.50 m ###

Pile Capacity = 600 kN

Column working column dim. Working moment extension


cap load Nw (kN) b (mm) t (mm) Mw (kN.m) of P.C (mm)
PC1 2000 800 800 2600 100

Spacing of piles in direction of moment = 1.50 m no. of Piles 4

Spacing of piles in transverse direction = 1.50 m no. of Piles 4


Total no. of piles = 16 ###
###
Dims. of P.C cap: B (mm) L (mm) t (mm) ###
6,200 6,200 100 ###
###
Dims. of R.C cap: B (mm) L (mm) t (mm) ###
6,000 6,000 1200 ###

Max. Load (kN) Min. Load (kN)


1st piles row to center, y1 0.75 m 284 111 ###
2nd piles row to center, y2 2.25 m 458 -62 ###
3rd piles row to center, y3 0 m 198 198 ###
4th piles row to center, y4 0 m 198 198 ###
All Safe Tension Appears ###

Shear stress (N/mm2) qcu (N/mm2) Notes


0.66 < 0.72 safe
###
Punching stress (N/mm ) 2 qcup (N/mm ) 2
Notes
0.34 < 1.41 safe ###

Calculation of Rft. : Asmin


1695 mm2 ###
###
Long Direction : Mu /m As /m no. f total ###
946 2535 7 22 /m 43
###
Short Direction : Mu /m As /m no. f total
290 1695 9 16 /m 55
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Design of Retaining Wall

* Project :

Concrete fcu = 25 MPa

Steel fy = 400 MPa 0.25


2.0 kN/m`
Bearing capacity qall = 150 kPa

g = 18.0 kN/m3

3.00

2.80
C = 0.0 N/mm2

f = 30 o
0.50 1.550 0.000

0.50 R.C
0.20 P.C

0.20 1.80 0.00

2.00
C= 0.0 N/mm2 f = 30 o

Factor of safety against sliding = 1.12

Factor of safety against overturning = 1.94

Max. stress on soil = 83.0 kPa Safe stress


Min. stress on soil = -15.4 kPa Tension on soil
Max. stress on soil = 83.5 kPa Safe stress
After Redistribution
Min. stress on soil = 0.0 kPa

Calculation of Rft. :

Mu (kN.m) C1 J As (mm2) As min


For wall 36.8 5.73 0.826 507 330 5 f 12 /m
For Base 58.0 9.35 0.826 390 675 6 f 12 /m
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 2.1

* Design of Simple Deep Beams

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Width (b) = 0.30 m


Span (L) = 4.00 m
Height (H) = 3.40 m
L/H = 1.18 Deep Beam
Empirical analysis accepted

yct = 2.87 m
Ww = 200.0 kN/m
Mw = 400.0 kN.m
Qw = 280.0 kN

As calc = 601 mm2


As min = 1485 mm2
As used = 1485 mm2
8 f 16 Bottom RFT.

Top loaded deep beam

Stirrups = Use min. web RFT


5 f 10 /m 2 Legs Vertical
Safe
5 f 10 /m 2 Legs Horizontal

5 f 10 /m
3.40

5 f 10 /m

8 f 16

4.00
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 2.1

* Design of Continuous Deep Beams

* Project :

Concrete fcu = 25 MPa


Steel fy = 400 MPa

Width (b) = 0.30 m


Span (L) = 4.00 m
Height (H) = 3.40 m
L/H = 1.18 Deep Beam
Empirical analysis accepted

yct +ve = 1.72 m


yct -ve = 1.48 m
Ww = 80.0 kN/m
Mw +ve = 450.0 kN.m
Mw -ve = 400.0 kN.m
Qw = 250.0 kN

As calc = 1128 mm2 As calc = 1166 mm2


As min = 1485 mm2 As min = 1515 mm2
As used = 1485 mm2 As used = 1515 mm2
5 f 20 5 f 20
Bottom RFT. Top RFT.

Top loaded deep beam

Stirrups = Use min. web RFT


5 f 10 /m 2 Legs Vertical
Safe
5 f 10 /m 2 Legs Horizontal

5 f 20
3.40

5 f 20

4.00 4.00
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Deflection of Cantilever

* Project :

Concrete fcu = 30 MPa

PDL+ PLL
WDL+ WLL

Span

Breadth Depth Thickness Span


Sec. Properties of sec: b (mm) d (mm) t (mm) L (m)
1 1000 220 250 2.5

Top Rft.: no. f area


5 16 1005 mm2

Bottom Rft.: no. f area


5 16 1005 mm2

Working loads: PDL (kN) PLL (kN) WDL (kN/m) WLL (kN/m)
2.5 7.0 2.0

Ec = 24,100 MPa

Ieff = 1.29E+09 mm4

Initial deflection: 1.8 mm

After long term: 4.4 mm 5 years

Allowable value: 5.6 mm L/450

Notes: Safe
By: Dr. Mahmoud El-Kateb

###
###
Ig
###

z2
z
###
z
Inv

Icr

###
a=

###

###
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Deflection of Simple R-section

* Project :

Concrete fcu = 25 MPa

PDL+ PLL
WDL+ WLL

Span/2 Span/2

Breadth Depth Thickness Span


Sec. Properties of sec: b (mm) d (mm) t (mm) L (m)
1 300 750 800 8

Top Rft.: no. f area


4 16 804 mm2

Bottom Rft.: no. f area


8 22 3040 mm2

Working loads: PDL (kN) PLL (kN) WDL (kN/m) WLL (kN/m)
50.0 50.0 20.0 10.0

Ec = 22,000 MPa

Ieff = 1.3E+10 mm4

Initial deflection: 9.7 mm

After long term: 19.6 mm 5 years

Allowable value: 32.0 mm L/250

Notes: Safe
By: Dr. Mahmoud El-Kateb
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Deflection of Simple T-section

* Project :

Concrete fcu = 25 MPa B

C As top ts

PDL+ PLL
WDL+ WLL b
h

Span/2 Span/2
C As bottom

Breadth Depth Thickness Span


Sec. Properties of sec: B (mm) b (mm) ts (cm) h (mm) t (mm) L (m)
1 800 300 120 680 800 8

Top Rft.: Cov. (mm) no. f area


50 4 16 804 mm2

Bottom Rft.: Cov. (mm) no. f area


50 8 22 3040 mm2

Working loads: PDL (kN) PLL (kN) WDL (kN/m) WLL (kN/m)
50.0 50.0 20.0 10.0

Ec = 22,000 MPa

Ieff = 1.57E+10 mm4

Initial deflection: 7.7 mm

After long term: 15.7 mm 5 years

Allowable value: 32.0 mm L/250

Notes: Safe
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Design of Water Section

* Project :

Concrete fcu = 30 MPa


Concrete fctr = 3.3 MPa
Steel fy = 400 MPa

Working Moment Normal Force


Sec. Mw (kN.m) Nw (kN)
1 25 31 Tension

Dims of sec: b (mm) t (mm) fct (N/mm2)


1000 250 2.5

Properties of sec: tv (mm) fct all (N/mm2)


263 2.7 Safe

Design of sec: d (mm) C1 J Ascalc Asmin As (mm2)


200 5.94 0.826 648 422 648

use: 9 f 10 bcr = 0.92


Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Calculation of Crack Width

* Project :

Concrete fcu = 30 MPa

Steel fy = 400 MPa

Comp. side
Thickness

Z
N.A

Tens. side
Breadth

INPUT:
Breadth (B) = 1000 mm
Thickness (t) = 300 mm
Tension RFT. = 10 T 16 = 2011 mm2
Tension RFT. Cover = 50 mm
Compression RFT. = 10 T 16 = 2011 mm2
Comp. RFT. Cover = 50 mm
Bars type: Ribbed bars
K1 = 0.8
K2 = 0.5 Bending moment
b1 = 0.8
b2 = 0.5

Mservice = 90.0 kN.m


Nservice = 30.0 kN Tension
Exposure category: Second, unprotected tension surfaces
Max. crack width (wkmax) = 0.20 mm

OUTPUT:
Modular ratio (n) = 8.7
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2

* Calculation of Crack Width

Neutral Axis depth (Z) = 72 mm


Tens. Steel stress (fs) = 208 MPa
Cracking stress (fsr) = 110 MPa
Srm = 110.6 mm
e sm = 0.00088
Crack width (wk) = 0.16 mm Acceptable

Você também pode gostar