Ver. 12.0
by
Mahmoud M. El-Kateb, Ph.D
* Project :
1200 mm
250 mm
700 mm
250 mm
* Project :
Web breadth Spacing Thick Slab th F.C L.L Block One way Two way
Area
b (mm) e (mm) t (mm) ts (mm) (kN/m2) (kN/m2) Wt. (kN) Wu (kN/m2) Wu (kN/m2)
1 120 400 270 70 1.5 2.0 0.15 11.4 12.2
2 120 400 270 70 1.5 2.0 0.15 11.4 12.2
3 120 400 270 70 1.5 2.0 0.15 11.4 12.2
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 9.4
* Project :
* Project :
Columns:
min. Dim. = 250 mm
min. Cover = 40 mm
Walls:
RFT ratio m 0.4 % < < 1 %
min. Dim. = 200 mm
min. Cover = 25 mm
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2
* Project :
Long span Short span min. Slab Slab thick F.C L.L Wsu Code of practice Moments (kN.m) Rft. /m Rft. /m
Area
Span (m) contin. Span (m) contin. thick (mm) (mm) (kN/m 2
) (kN/m 2
) (kN/m 2
) a b Ma Mb short dir. long dir.
1 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
2 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
3 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
4 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
5 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
6 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
7 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
8 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
9 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
10 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
11 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
12 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
13 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
14 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
15 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
16 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
17 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2
* Project :
Long span Short span min. Slab Slab thick F.C L.L Wsu Code of practice Moments (kN.m) Rft. /m Rft. /m
Area
Span (m) contin. Span (m) contin. thick (mm) (mm) (kN/m 2
) (kN/m 2
) (kN/m 2
) a b Ma Mb short dir. long dir.
18 5 1 4 1 114 140 1.50 2.00 10.50 0.475 0.224 9.98 7.35 4 f 10 3 f 10
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2
* Design of Slabs
* Project :
* Design of Slabs
* Project :
* Project :
Page 10 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2
Design of sections:
Page 11 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2
* Project :
Internal columns:
Page 12 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2
Edge columns:
Corner columns:
b
critical perimeter (bo)
Page 13 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 1.1
* Project :
Internal columns:
bb
no. of bra.
parallel to b
no. of bra.
parallel to t
bt
tcol
Ult. Load Col. Dims. Slab Req. no. of Branch Spcaing bb no. of bra. bt no. of bra. no. of RFT
Col.
Nu (kN) b (mm) t (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) parallel to b (mm) parallel to t Rows
1 900 300 600 250 10 12 100 250 2 250 4 3
2 900 300 600 250 10 12 100 250 2 250 4 3
3 900 300 600 250 10 12 100 250 2 250 4 3
4 900 300 600 250 10 12 100 250 2 250 4 3
5 900 300 600 250 10 12 100 250 2 250 4 3
6 900 300 600 250 10 12 100 250 2 250 4 3
7 900 300 600 250 10 12 100 250 2 250 4 3
Page 14 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 1.1
Ult. Load Col. Dims. Slab Req. no. of Branch Spcaing b no. of no. of
Col. Notes
Nu (kN) D (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) branches Rows
1 650 400 250 8 12 100 200 4 2 Safe
2 650 400 250 8 12 100 200 4 2 Safe
3 650 400 250 8 12 100 200 4 2 Safe
4 650 400 250 8 12 100 200 4 2 Safe
Edge columns:
tcol
bcol
Ult. Load Col. Dims. Slab Req. no. of Branch Spcaing bb no. of bra. bt no. of bra. no. of RFT
Col.
Nu (kN) b (mm) t (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) parallel to b (mm) parallel to t Rows
1 500 300 600 250 7 12 100 250 2 250 4 4
2 500 300 600 250 7 12 100 250 2 250 4 4
3 500 300 600 250 7 12 100 250 2 250 4 4
4 500 300 600 250 7 12 100 250 2 250 4 4
Page 15 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 1.1
Corner columns:
Ult. Load Col. Dims. Slab Req. no. of Branch Spcaing bb no. of bra. bt no. of bra. no. of RFT
Col.
Nu (kN) b (mm) t (mm) Thick (mm) branches Dia. (mm) S (mm) (mm) parallel to b (mm) parallel to t Rows
1 250 300 600 250 4 12 100 250 2 250 4 2
2 250 300 600 250 4 12 100 250 2 250 4 2
3 250 300 600 250 4 12 100 250 2 250 4 2
4 250 300 600 250 4 12 100 250 2 250 4 2
5 250 300 600 250 4 12 100 250 2 250 4 2
6 250 300 600 250 4 12 100 250 2 250 4 2
Page 16 of 64
By: Dr. Mahmoud El-Kateb
Notes
qpu
Safe ###
Safe ###
Safe ###
Safe ###
Safe ###
Safe ###
Safe ###
Page 17 of 64
By: Dr. Mahmoud El-Kateb
Safe ###
qpu
###
###
###
###
Notes
qpu
Safe ###
Safe ###
Safe ###
Safe ###
Page 18 of 64
By: Dr. Mahmoud El-Kateb
Safe ###
Safe ###
Notes
qpu
Safe ###
Safe ###
Safe ###
Safe ###
Safe ###
Safe ###
Page 19 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.3
* Design of Beams
* Project :
* Design of Beams
* Project :
* Project :
* Project :
* Project :
* Project :
* Project :
* Project :
* Project :
###
Ult. torsional moment Sec. dim. Ult. shear force ###
Sec. Mu (kN.m) b (mm) t (mm) Qu (kN)
1 20 300 700 150
qcu
qtu Notes qsu Notes qumax
0.94 N/mm 2
need rft. 0.77 N/mm 2
use min Aoh
Ao
qtcu = 0.24 N/mm2 Ph
qcu = 0.98 N/mm2
qumax = 2.86 N/mm2
Calculation of Rft.
5 f 10 /m
7 f 10 /m
0.70 m 0.70 m
4f 8 /m
OR
0.30 m 0.30 m
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.1
* Project :
* Project :
Page 31 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.1
* Project :
Page 32 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.1
* Project :
* Project :
* Project :
Page 35 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
Results:
Nw = 250 kN
Mw = 200 kN.m
0.50 m
0.30 m
0.00
kPa
135
kPa
1.95 m
0.50
/m
1.75 m
2.35 m
0.30
12
0.50
f
6
6 f 12 /m
2.55 m
F1
Page 36 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
* Project :
###
Dims. of P.C : B (mm) L (mm) t (mm) ###
1,700 3,400
Choose dim of P.C 3,000 3,200 300
LRC
3 1
Mwx
tcol
4 2
LPC
Eccentricities:
ex = 0.28 m ey = 0.55 m
P1 Stress (kPa) = 146 Safe secondary case
P2 Stress (kPa) = 84
P3 Stress (kPa) = 29
Page 37 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
Using chart:
ex/B = 0.09 ey/L = 0.17 K= 2.67
Results:
0.50
0.50
F1
/m
2.40 m
3.00 m
0.30
12
f
8
6 f 12 /m
Page 38 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
Page 39 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
* Project :
Page 40 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
Results:
Nw = 63 kN
Mw = 20 kN.m
0.40 m
0.20 m
12
kPa
74
kPa
1.10 m
0.40
/m
1.10 m
1.50 m
0.25
12
0.25
f
5
5 f 12 /m
1.30 m
F1
Page 41 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
* Project :
F9
Column working load Column dim. (mm) Extension
Col Nw (kN) trans. long. of P.C (mm)
Smaller 600 250 500 300
Larger 840 250 700 300
LRC
Dlong Dlong
LPC
Page 42 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
Longitudinal direction:
Transverse direction:
Results:
4.40 m
8 f 12 /m
0.60
/m
/m
1.80 m
2.40 m
12
+
12
1.17 m
f
f
5
5 f 16 /m
Page 43 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
5.00 m
Page 44 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
* Project :
Page 45 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
Transverse direction:
###
Bottom Rft. : Mu /m As /m no. f total no.
External footing 106 744 7 12 /m 15
Internal footing 94 663 6 12 /m 17
Page 46 of 64
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 12.0
* Project :
* Project :
* Project :
g = 18.0 kN/m3
3.00
2.80
C = 0.0 N/mm2
f = 30 o
0.50 1.550 0.000
0.50 R.C
0.20 P.C
2.00
C= 0.0 N/mm2 f = 30 o
Calculation of Rft. :
* Project :
yct = 2.87 m
Ww = 200.0 kN/m
Mw = 400.0 kN.m
Qw = 280.0 kN
5 f 10 /m
3.40
5 f 10 /m
8 f 16
4.00
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 2.1
* Project :
5 f 20
3.40
5 f 20
4.00 4.00
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2
* Deflection of Cantilever
* Project :
PDL+ PLL
WDL+ WLL
Span
Working loads: PDL (kN) PLL (kN) WDL (kN/m) WLL (kN/m)
2.5 7.0 2.0
Ec = 24,100 MPa
Notes: Safe
By: Dr. Mahmoud El-Kateb
###
###
Ig
###
z2
z
###
z
Inv
Icr
###
a=
###
###
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2
* Project :
PDL+ PLL
WDL+ WLL
Span/2 Span/2
Working loads: PDL (kN) PLL (kN) WDL (kN/m) WLL (kN/m)
50.0 50.0 20.0 10.0
Ec = 22,000 MPa
Notes: Safe
By: Dr. Mahmoud El-Kateb
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2
* Project :
C As top ts
PDL+ PLL
WDL+ WLL b
h
Span/2 Span/2
C As bottom
Working loads: PDL (kN) PLL (kN) WDL (kN/m) WLL (kN/m)
50.0 50.0 20.0 10.0
Ec = 22,000 MPa
Notes: Safe
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2
* Project :
* Project :
Comp. side
Thickness
Z
N.A
Tens. side
Breadth
INPUT:
Breadth (B) = 1000 mm
Thickness (t) = 300 mm
Tension RFT. = 10 T 16 = 2011 mm2
Tension RFT. Cover = 50 mm
Compression RFT. = 10 T 16 = 2011 mm2
Comp. RFT. Cover = 50 mm
Bars type: Ribbed bars
K1 = 0.8
K2 = 0.5 Bending moment
b1 = 0.8
b2 = 0.5
OUTPUT:
Modular ratio (n) = 8.7
Reinforced Concrete design according to ECP 203-2017 By: Dr. Mahmoud El-Kateb
Version 11.2