Date: Reference:

02.03.2015 I 28-1.21.1-14/15 (11/15)

English translation authorized by DIBt – Original version in German language

Approval number: Validity


Z-21.1-1987 from: 2 March 2015
to: 14 May 2018
Applicant:
Hilti Deutschland AG
Hiltistraße 2
86916 Kaufering

Subject of approval:
Hilti Undercut Anchor HDA
for fastenings in nuclear power plants and other nuclear facilities

The subject of approval mentioned above is herewith generally approved in the field of construction.
This allgemeine bauaufsichtliche Zulassung ('national technical approval') comprises nine pages and
20 annexes.
This allgemeine bauaufsichtliche Zulassung ('national technical approval') replaces the allgemeine
bauaufsichtliche Zulassung ('national technical approval') Z-21.1-1987 of 14 May 2013, amended on
22 July 2014. The subject of approval was first issued on 14 May 2013.
Allgemeine bauaufsichtliche Zulassung
Nr. Z-21.1-1987 Page 2 von 9 | 2 March 2015

I GENERAL PROVISIONS

1 With the allgemeine bauaufsichtliche Zulassung ('national technical approval') the fitness for
use and the applicability of the subject of approval according to the Landesbauordnungen
('Building Regulations of the Land') has been verified.

2 If, in the allgemeine bauaufsichtliche Zulassung ('national technical approval') requirements


are made concerning the special expertise and experience of persons entrusted with the
manufacture of construction products and types of construction according to the relevant
regulations of the Land following section 17, sub-section 5 Musterbauordnung ('Model
Building Code'), it is to be noted that this expertise and experience can also be proven by
equivalent verifications from other Member States of the European Union. If necessary, this
also applies to verifications presented within the framework of the Agreement on the
European Economic Area (EEA) or other bilateral agreements.

3 The allgemeine bauaufsichtliche Zulassung ('national technical approval') does not replace
the permits, approvals and certificates prescribed by law for carrying out building projects.

4 The allgemeine bauaufsichtliche Zulassung ('national technical approval') will be granted


without prejudice to the rights of third parties, in particular private property rights.

5 Notwithstanding further regulations in the "Specific Provisions" manufacturers and


distributors of the subject of approval shall make copies of the allgemeine bauaufsichtliche
Zulassung ('national technical approval') available to the user and point out that the
allgemeine bauaufsichtliche Zulassung ('national technical approval') has to be available at
the place of use. Upon request copies of the allgemeine bauaufsichtliche Zulassung
('national technical approval') shall be placed at the disposal of the authorities involved.

6 The allgemeine bauaufsichtliche Zulasssung ('national technical approval') may be


reproduced in full only. Publication in the form of extracts requires the consent of Deutsches
Institut für Bautechnik. Texts and drawings of advertising brochures may not be in
contradiction to the allgemeine bauaufsichtliche Zulassung ('national technical approval').

7 The allgemeine bauaufsichtliche Zulassung ('national technical approval') is granted until


revoked. The provisions of the allgemeine bauaufsichtliche Zulassung ('national technical
approval') can subsequently be supplemented and amended in particular, if this is required
by new technical findings.

Z17608.15/Entwurf 13.03.2015 1.21.1-14/15


Allgemeine bauaufsichtliche Zulassung
Nr. Z-21.1-1987 Page 3 von 9 | 2 March 2015

II SPECIFIC PROVISIONS

1 Subject of approval and field of application

1.1 Subject of approval


The Hilti undercut anchor HDA is a self-cutting undercut anchor. It is available in the sizes
M10, M12, M16 made of galvanised zinc-plated steel (HDA) and made of stainless steel
(HDA-R) in the versions for pre-setting and through-fastening installation.
The anchor for pre-setting (HDA-P and HDA-PR) and the anchor for through-fastening
(HDA-T and HDA-TR) consist of a cone bolt with external thread, an expansion sleeve, a
plastic ring, a hexagon nut with injection washer and spherical washer (filling set), a plastic
cap and optional the Hilti injection mortar HIT-HY 200-A.
The anchor is set by mechanical interlock and anchored by displacement control in a hole
drilled with a special stop drill bit and using a special setting tool intended for this use. During
setting of the anchor the undercut is made. The fixture is fastened by tightening the nut.
Following the injection mortar can be pressed through the injection washer into the annular
gap between the fixture and the anchor for the reduction of the displacements under shear
load.
The installed anchor is shown in Annexes 1 and 2.
1.2 Intended use
The anchor may be used for anchorages subject to static or quasi-static loading for
Requirement Categories A1, A2 and A3 according to the Leitfaden für Dübelbefestigungen in
Kernkraftwerken und anderen kerntechnischen Anlagen1 in reinforced and unreinforced
normal weight concrete of strength classes C20/25 at minimum and C50/60 at maximum
according to DIN EN 206-1:2001-07); it may also be used in concrete of strength class B 25
at minimum and B 55 at maximum according to DIN 1045:1988-07.
It may be used in cracked and non-cracked concrete. Under accidental actions (Requirement
Category A2 and A3) the anchor may be used up to a crack width wk = 1.0 mm. The anchor
must not be used for fastenings in critical structure areas where the concrete could spall or
large cracks could occur under extreme loads, for example, in the area of plastic hinges
(critical areas) of concrete structures.
The anchor made of galvanised zinc-plated steel may only be used in concrete subject to dry
internal conditions.
The anchor made of stainless steel (materials 1.4401, 1.4404 und 1.4571) may be used
according to the corrosion resistance class III of the Allgemeine bauaufsichtliche Zulassung
"Erzeugnisse, Verbindungsmittel und Bauteile aus nichtrostenden Stählen" Nr. Z-30.3-6
('national technical approval Products, connecting elements and components made of
stainless steel' no. Z-30.3-6).
The temperature in the mortar area must not exceed 72°C, short-term 120°C.

1
Deutsches Institut für Bautechnik: „Leitfaden für Dübelbefestigungen in Kernkraftwerken und anderen
kerntechnischen Anlagen“ (‚Guideline for fastenings with anchors in nuclear power plants and nuclear facilities‘),
issued June 2010

Z17608.15/Entwurf 13.03.2015 1.21.1-14/15


Allgemeine bauaufsichtliche Zulassung
Nr. Z-21.1-1987 Page 4 von 9 | 2 March 2015

2 Provisions for the construction product

2.1 Properties and composition


The anchor shall comply with the specifications and drawings given in the annexes. The
material properties, dimensions and tolerances of the anchor not given in this allgemeine
bauaufsichtliche Zulassung shall comply with the information deposited at Deutsches Institut
für Bautechnik, the certification body and the external surveillance body.
Material specifications of the anchor parts are given in Annex 4, Table 2. The mechanical
properties of the cone bolt shall comply with the deposited specifications.
The anchor is made of a non-combustible material of class A according to
DIN 4102-1:1998-05 "Brandverhalten von Baustoffen und Bauteilen; Baustoffe - Begriffe,
Anforderungen und Prüfungen" ('Fire behaviour of building materials and building
components; Building material; terminology, requirements and tests').
2.2 Packaging, storage and marking
2.2.1 Packaging and storage
The anchor shall be supplied as a complete fastening unit. The mortar foil packs and the
filling set are packed separately.
The foil packs shall be protected against sun radiation and shall be stored according to the
manufacturer’s installation instructions in dry conditions at temperatures of at least +5 °C to
not more than +25 °C.
2.2.2 Marking
The packaging, enclosed instructions or delivery note of the anchor shall be marked by the
manufacturer with the conformity mark (Ü-mark) according to the Übereinstimmungszeichen-
Verordnungen der Länder ('Regulations on the conformity mark of the states of the Federal
Republic of Germany'). In addition, the manufacturing mark, the approval number and the
complete anchor designation shall be declared.
The marking may only be carried out if the requirements according to Section 2.3
"Übereinstimmungsnachweis" ('Verification of conformity') have been met.
The anchor is designated by the anchor type (HDA-P KKW, HDA-PR KKW, HDA-T KKW or
HDA-TR KKW), the thread size of the cone bolt, the anchorage depth and the maximum
thickness of fixture.
Each anchor is designated according to Annex 5. For the anchor type HDA-T (through-
fastening anchor) the anchorage depth shall be marked.
The injection washer in the version as cast part is embossed with the lettering "Hilti". The
injection washer made of stainless steel is embossed with "A4".
Each foil pack is marked with the manufacturing mark "HIT-HY 200-A", the batch number
and the expiry date. The foil packs shall be marked in accordance with the Verordnung über
gefährliche Arbeitsstoffe ('Regulation on hazardous materials') and provided with information
about the hazard code and processing. The installation instructions supplied with the mortar
shall contain the information on safety measures for dealing with hazardous materials.
2.3 Übereinstimmungsnachweis ('Verification of conformity')
2.3.1 General
Each manufacturing plant shall confirm that the anchor complies with the provisions of this
allgemeine bauaufsichtliche Zulassung by means of a certificate of conformity based on the
factory production control and a regular external surveillance, including initial testing of the
anchor in accordance with the following provisions.

Z17608.15/Entwurf 13.03.2015 1.21.1-14/15


Allgemeine bauaufsichtliche Zulassung
Nr. Z-21.1-1987 Page 5 von 9 | 2 March 2015

The manufacturer of the anchor shall organise a recognised certification body and a
recognised inspection body to issue a certificate of conformity and for the external
surveillance, including product testing that has to be carried out.
The manufacturer shall state by marking the products with the conformity mark (Ü-mark) with
reference to the intended use, that the certificate of conformity is issued.
The certification body shall send a copy of the issued certificate of conformity to Deutsches
Institut für Bautechnik.
The required verifications for the raw material and for the supplied anchor parts shall be in
accordance with the control plan which is deposited by Deutsches Institut für Bautechnik and
by the external surveillance body.
2.3.2 Factory production control
Each manufacturing plant shall set up and carry out a factory production control. Factory
production control is a continuous surveillance of production by the manufacturer who thus
ensures that the manufactured construction product is in conformity with the provisions of
this allgemeine bauaufsichtliche Zulassung.
Extent, type and frequency of the factory production control shall be in accordance with the
control plan which is deposited by Deutsches Institut für Bautechnik and by the external
surveillance body.
The results of factory production control shall be recorded and evaluated. The records shall
include at least the following information:
- Designation of the construction product respectively the raw material and its components
- Type of control or test
- Date of manufacture and test of the construction product respectively of the raw material
or components
- Results of control and tests and, if applicable, a comparison with requirements
- A signature of the person responsible for factory production control.
The records shall be deposited for at least five years and presented to the recognised
external surveillance body. On request, they shall be submitted to Deutsches Institut für
Bautechnik and to the zuständige oberste Bauaufsichtsbehörde ('responsible building
authority').
If the test results are unsatisfactory, the manufacturer shall immediately take the action
necessary to eliminate the deficiency. Construction products which do not meet
requirements shall be treated in such a way that confusion with conforming products is
excluded. Once the deficiency has been eliminated, the original test shall be repeated
immediately, provided that this is technically possible and also required to verify the
elimination of the deficiency.
2.3.3 External surveillance
In each production plant, external surveillance shall be carried out regularly, but at least once
a year, to check the factory production control.
During external surveillance, initial testing of the anchor shall be carried out and random
samples taken. Sampling and testing are done on responsibility of the recognised
surveillance body.
Extent, type and frequency of the external surveillance shall be in accordance with the
control plan which is deposited by Deutsches Institut für Bautechnik and by the external
surveillance body.

Z17608.15/Entwurf 13.03.2015 1.21.1-14/15


Allgemeine bauaufsichtliche Zulassung
Nr. Z-21.1-1987 Page 6 von 9 | 2 March 2015

The results of certification and external surveillance shall be deposited for at least five years.
On request, they shall be submitted to Deutsches Institut für Bautechnik and the responsible
building authority by the certification body respectively by the surveillance body.

3 Provisions for design

3.1 Design (concept)


For the Requirement Categories A2 and A3 the "Leitfaden für Dübelbefestigungen in
Kernkraftwerken und anderen kerntechnischen Anlagen" 1 shall be observed. The evaluation
regarding the crack width wk = 1.0 mm consider the collective extreme cases, so that a
separate verification of the expected crack width in the anchoring area is not necessary
when minimal reinforcement is present.
The resistance of the anchor to exposure to ionizing radiation has been verified.2
The anchorages shall be designed in accordance with engineering practice. Verifiable
calculation notes and design drawings shall be prepared taking into account the loads to be
anchored. The position of the anchor shall be specified in the design drawings and it is to
specify whether the optional filling is planned to perform.
3.2 Design (dimensioning)
The anchorages are designed under the responsibility of an engineer experienced in
anchorages and concrete work in accordance with ETAG 001 "Guideline for European
Technical Approval of Metal Anchors for Use in Concrete", Annex C (August 2010), Design
method A.
The provisions of Sections 4.2 to 4.9 of the Leitfaden (Guideline)1 shall be considered
deviating or supplementary to the Design method mentioned above.
Partial safety factors and load combination factors of actions of the Requirement Category
A2 and A3 are taken from DIN 25499:2008-02.
The characteristic anchor values for the design of the anchorage according to ETAG 001,
Annex C are given in Annexes 9 to 13 (Requirement Categories A1, A2 and A3).
It is to be ensured that the strength class of the concrete in which the anchor is to be placed
is not lower than that of the concrete to which the characteristic loads apply. The concrete
strength class shall be not lower than B25 or C20/25 and shall not exceed B55 or C50/60.
For design of anchorages in normal weight concrete according to DIN 1045:1988-07, the
value for fck,cube shall be replaced by 0.97 x βWN.
When determining the length of the lever arm of the shear load for anchor types HDA-T and
HDA-TR, the restraint in the concrete shall be assumed at 0.5 x the bold diameter from the
concrete surface. When determining the length of the lever arm of the shear load for anchor
types HDA-P and HDA-PR, the restraint in the concrete shall be assumed according to
Annex 11, Table 10 or Annex 12, Table 11. Furthermore, the possible displacement in the
direction of the tension component shall be considered (see Annex 10, Table 9).
When determining the thickness of the fixture any necessary mortar leveling layer is taken
into account (see Section 4.3 and Annex 5, Table 3).
The verification of the immediate local transmission of the anchor loads into the concrete
member is proven. The transmission of the anchor loads to the supports of the concrete
member shall be proven.

2
TÜV-SÜD-Test Report IS-ETM5-MUC/uh of 17.06.2014

Z17608.15/Entwurf 13.03.2015 1.21.1-14/15


Allgemeine bauaufsichtliche Zulassung
Nr. Z-21.1-1987 Page 7 von 9 | 2 March 2015

4 Provisions for installation

4.1 General
The anchor shall only be used as a complete fastening unit delivered in series. Components
of the anchor must not be exchanged. It may only be installed by appropriately qualified
personnel under the supervision of the construction supervisor.
For installation Section 5.3 of the Leitfaden (Guideline)1 shall be considered.
Before placing the anchor, the quality of the concrete member shall be checked. The
concrete shall be well compacted, e.g. without significant voids.
The anchor shall be installed in accordance with the design drawings according to
Section 3.1. The anchor shall be installed according to the manufacturer's installation
instruction (see Annexes 16 and 17) by using the appropriate specified tools (see
Annexes 14 and 15).
The required distances to edges, openings, steps in ceiling slabs or built-in components shall
be observed, as well as the spacing to other fastenings (e.g. anchor plates with headed
fasteners).
4.2 Drilling the borehole
In order to reduce the risk of aborted drill holes or damage of the reinforcement, the position
of the reinforcement shall be located. The position of the borehole, including the undercut,
shall be determined such that the existing reinforcement is not damaged.
The borehole shall be drilled perpendicular to the surface of the concrete using a hammer
drill equipped with the appropriate stop drill bit for the anchor size (see Annex 14). The
required borehole depth is reached when the stop on the drill bit hits the concrete in case of
pre-setting anchor or it hits the fixture in case of through-fastening anchor. Inclinations from
85° to 95° relative to the existing surface are considered to be perpendicular.
The nominal diameter of the drill bit and the cutting diameter of the drill bit shall comply with
Annex 7. The drilling dust must be removed from the hole.
Aborted drill holes shall be completely closed with high strength mortar. An aborted borehole
also exists if an anchor is removed, because it is not set according to the specifications. If
the aborted drill hole has a depth greater than hef/4, the axial distance to a new borehole
shall be at least twice of the borehole diameter. Pre-stressing or loading of the anchor after
closing of the aborted drill hole with high-strength mortar is only allowed if the strength of the
mortar is at least equal to the concrete strength. If the strength development of the mortar is
not known, the anchor may be pre-stressed or loaded after 24 hours at the earliest.
4.3 Setting the anchor
The surface of the concrete in the area of the steel fixture shall be such that the fixture rests
fully against the concrete after anchor installation. In order to achieve a full contact surface, a
mortar levelling layer with a thickness up to 3 mm may be applied. Torque moments may
only be applied after the curing of the mortar.
After the anchor has been set in the hole, the expansion sleeve shall be driven by using the
specified hammer drill and the appropriate setting tool according to Annex 15, in this process
the undercut is made.
When welding fixtures subsequently on site, restraints on the anchor caused by heat input
shall be avoided.

Z17608.15/Entwurf 13.03.2015 1.21.1-14/15


Allgemeine bauaufsichtliche Zulassung
Nr. Z-21.1-1987 Page 8 von 9 | 2 March 2015

The fixture shall be installed by using a calibrated torque wrench. The torque moment Tinst
according to Annex 7 must be applied.
The anchor has been properly set and may be loaded only when all conditions according to
Table 4.1 are fulfilled. In all other cases, the anchor has to be removed and the borehole
has to be filled with high strength mortar.
Table 4.1 Installation control
Characteristic Through-fastening anchor Pre-setting anchor
HDA-T respectively HDA-TR HDA-P / HDA-PR
Red marking The red marking on the bolt must be visible above the top edge
of the expansion sleeve (see Annexes 1 and 2)
Knurled marking ring The knurled marking ring on the No knurled marking
expansion sleeve must not protrude over ring existing
the concrete surface (see Annex 2,
Figure 4)
Sleeve recess hs The installation tolerance for the sleeve recess hs must comply
with the requirements in Annex 7
Thickness of fixture tfix tfix ≤ maximum thickness of fixture tfix ≤ maximum
according to Annex 5 thickness of fixture
tfix ≥ minimum thickness of fixture according to Annex 5
according to Annex 7
Torque moment Tinst The torque moment Tinst according to Annex 7 must be applied

An anchor may be set only once.


During filling of the annular gap with injection mortar the injection mortar is pressed through
the opening in the injection washer into the annular gap between the fixture and the anchor.
The mortar is mixed when pressing in the static mixer of the mortar cartridges. For injection
of the mortar the devices listed in the manufacturer's installation instructions are to be used.
The mixer flow (mortar leaving the mixer at first) must not be used for fastenings. The first
three full trigger pulls of the new foil pack (mixer flow) shall be discarded and not to use.
For filling the mixer tip is pressed into the filling channel of the injection washer. There are
injected so many mortar trigger pulls until the pressure resistance at the dispenser
increases. After remove the mixer tip the mortar must be visible in the filling opening.
During injection the installation temperature of the mortar (cartridge temperature) shall not be
lower than +5 °C and shall not exceed +40 °C.
The curing of the injection mortar depends on the temperature of the concrete / fixture.
Therefore, the curing time between setting and loading of the anchor shall be observed
according to Annex 3.
After the installation and during the service life the nut of anchors with unfilled annular gap
may be removed and tightened again by applying the torque moment according to Annex 7,
Table 5.

Z17608.15/Entwurf 13.03.2015 1.21.1-14/15


Allgemeine bauaufsichtliche Zulassung
Nr. Z-21.1-1987 Page 9 von 9 | 2 March 2015

4.4 Checking the installation


The quality assurance measures in accordance with Section 5.4 of the Leitfaden (Guideline)1
shall be considered.
During the installation of the anchors the contractor entrusted with anchorages or the
construction supervisor assigned by him or a competent representative of the construction
supervisor have to be present on the job site. He has to ensure the proper installation.
During installation of anchors records about the proper installation of anchors shall be kept
by the construction supervisor or his competent representative. The setting and installation
minutes shall contain at least the information of Annex 18 and 19.
The records must be available on the job site during construction period and they shall be
presented on request for inspection. These records, as well as the delivery notes, shall be
deposited by the company for at least five years after completion of the construction work.
When using the anchorages in nuclear power plants and nuclear facilities, consideration of
additional requirements of the supervisory authorities can be required.

Andreas Kummerow Beglaubigt


Head of Section Aksünger

Z17608.15/Entwurf 13.03.2015 1.21.1-14/15


Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Figure 1: Pre-setting anchor HDA-P(R) KKW

Figure 2: Pre-setting anchor HDA-P(R) KKW: installed condition


a) Annular gap not filled

b) optional: annular gap filled with injection mortar HIT-HY 200-A

Hilti Undercut Anchor HDA KKW

Pre-setting anchor HDA-P(R) KKW Annex 1


product and intended use

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Figure 3: Through-fastening anchor HDA-T(R) KKW


Injection
washer

Figure 4: Through-fastening anchor HDA-T(R) KKW: installed condition


a) annular gap not filled

b) optional: annular gap filled with injection mortar HIT-HY 200-A

Hilti Undercut Anchor HDA KKW

Through-fastening anchor HDA-T(R) KKW Annex 2


product and intended use

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Figure 5: Injection mortar Hilti HIT-HY 200-A:


Hybrid system with resin, hardener, cement, water components

Foil pack 330 ml and 500 ml

Marking
HY200-A
Batch number
Expiry date

Static mixer Hilti HIT-RE-M

dispensers

Hilti HDM 330 Hilti HDE 500-A22


Hilti HDM 500

Table 1: Curing time tcure


Temperature Curing time tcure
of base material / environment Hilti HIT-HY 200-A
-10 °C to -5 °C 7 hours
-4 °C to 0 °C 4 hours
1 °C to 5 °C 2 hours
6 °C to 10 °C 75 minutes
11 °C to 20 °C 45 minutes
21 °C to 30 °C 30 minutes
31 °C to 40 °C 30 minutes

Hilti Undercut Anchor HDA KKW


Annex 3
Injection mortar Hilti HIT-HY 200-A

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Figure 6: Pre-setting anchor HDA-P / HDA-PR KKW

Groove rotated by 90°

Figure 7: Through-fastening anchor HDA-T / HDA-TR KKW

Groove rotated by 90°

Table 2: Materials
HDA-P / HDA-T HDA-PR / HDA-TR
Part Designation
(galvanised  5m) (stainless steel)
1.4401, 1.4404 or 1.4571,
1 Expansion sleeve Machined steel
DIN EN 10088
Cold-formed steel, 1.4401, 1.4404 or 1.4571
2 Bolt
Strength class 8.8 DIN EN 10088
Coating
3 galvanised 5-25m Hardchrome > 10m
of bolt and sleeve
Case-hardened steel 1.1731 1.4401, 1.4404 or 1.4571,
4 Injection washer
or cast part EN-GJMB-550 DIN EN 10088
1.4401, 1.4404 or 1.4571,
5 Spherical washer galvanised 5-25m
DIN EN 10088
6 Hexagon nut Strength class 8, galvanised Strength class A4-80
7 Cutting edges Tungsten carbide Tungsten carbide
8 Ring plastic plastic
9 Cap plastic plastic

Hilti Undercut Anchor HDA KKW


Annex 4
Materials

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Figure 8: Pre-setting anchor HDA-P(R) KKW

Figure 9: Through-fastening anchor HDA-T(R) KKW

tfix

Table 3: Anchor dimensions


tfix1) lB Length lS lK SW dS1 dS2 dS3 dC dB
Anchor designation code
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
HDA-P M10x80/20 20 130 H 80 - 17 19 16,8 18,5 19,5 10
HDA-T M10x80/20 20 130 H 100 17 17 19 16,8 18,5 19,5 10
HDA-P(R) M10x100/20 20 150 I 100 - 17 19 16,8 18,5 19,5 10
HDA-T(R) M10x100/20 20 150 I 120 17 17 19 16,8 18,5 19,5 10
HDA-T M10x160/20 20 210 180 17 17 19 16,8 18,5 19,5 10
HDA-P(R) M12x125/30 30 190 L 125 - 19 21 18,8 20,5 21,4 12
HDA-P(R) M12x125/50 50 210 N 125 - 19 21 18,8 20,5 21,4 12
HDA-T(R) M12x125/30 30 190 L 155 27 19 21 18,8 20,5 21,4 12
HDA-T(R) M12x125/50 50 210 N 175 47 19 21 18,8 20,5 21,4 12
HDA-T M12x185/30 30 250 215 27 19 21 18,8 20,5 21,4 12
HDA-T(R) M16x190/40 40 275 R 230 35,5 24 29 26 29 29 16
HDA-T(R) M16x190/60 60 295 S 250 55,5 24 29 26 29 29 16
HDA-T M16x250/40 40 335 290 35,5 24 29 26 29 29 16
HDA-T M16x270/40 40 355 U 310 35,5 24 29 26 29 29 16
1)
maximum thickness of fixture tfix,max (including thickness of mortar layer if existing)

Hilti Undercut Anchor HDA KKW


Annex 5
Anchor dimensions

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Figure 10: Filling set

Table 4: Filling set size chart


Diameter Thickness
of the injection washer of the injection washer
Anchor size Filling set
dVS hVS
[mm] [mm]
HDA-P/T M10 M10
42
HDA-PR/TR M10 M10-R
5
HDA-P/T M12 M12
44
HDA-PR/TR M12 M12-R
HDA-T M16 M16
52 6
HDA-TR M16 M16-R

Hilti Undercut Anchor HDA KKW


Annex 6
Filling set

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Table 5: Characteristic values of anchors and installation


Anchor size M10x80 M10 M12 M16
Pre-setting / Through-fastening HDA- P T P(R) T(R) P(R) T(R) T(R)

Nominal diameter of drill bit d0 [mm] 20 20 22 30


Cutting diameter of drill bit dcut  [mm] 20,55 20,55 22,55 30,55
Depth of drill hole h1 [mm] 87  87 107  1072) 133  1333)  2034)
Diameter of clearance hole
df  [mm] 12 21 12 21 14 23 32
in the fixture
Installation torque Tinst [Nm] 50 50 80 120
Tension loads
Minimum thickness of fixture min tfix [mm] - 10 - 10 - 10 15
hS  [mm]
1)
Minimum sleeve recess 2 2 2 2
hS  [mm]
1)
Maximum sleeve recess 6 6 7 8
Shear loads and combined tension and shear loads
Minimum thickness of fixture min tfix [mm] - 15 - 15 - 20 20
Minimum sleeve recess 1) hS  [mm] 2 2 2 2
Maximum sleeve recess 1) hS  [mm] 6 6 7 8
1)
Sleeve recess hS after setting of the anchor (Installed condition)
a) Pre-setting anchor HDA-P(R): Distance from surface of concrete
to top edge of the expansion sleeve, see Figure 2
b) Through-fastening anchor HDA-T(R): Distance from surface of the fixture
to top edge of the expansion sleeve, see Figure 4
for HDA-T M10x160/20: h1  167mm
2)

for HDA-T M12x185/30: h1  193 mm


3)

for HDA-T M16x250/40: h1  263 mm and accordingly


4)

for HDA-T M16x270/40: h1  283 mm

Hilti Undercut Anchor HDA KKW


Annex 7
Characteristic values of anchors and installation

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Table 6: Minimum thickness of concrete member


Anchor size HDA-P M10x80 M10x100 M12x125
HDA-PR - M10x100 M12x125
Minimum
thickness of hmin [mm] 150 180 200
concrete member

Anchor size HDA-T M10x80 M10x100 3) M12x125 4) M16x190 5)


HDA-TR - M10x100 M12x125 M16x190
Maximum
thickness tfix,max1) [mm] 20 20 30 50 40 60
of fixture
Minimum
thickness of hmin2) [mm] 170-tfix 200-tfix 230-tfix 250-tfix 310-tfix 330-tfix
concrete member
1)
tfix,max see Table 3, column 2, Annex 5 (Thickness of fixture incl. thickness of mortar layer if existing)
2)
hmin is dependent on the existing thickness of fixture tfix (use a stop drill bit)
e.g. HDA-T M12x125/50: tfix = 20 mm  hmin = 250 mm - 20 mm = 230 mm
tfix = 50 mm  hmin = 250 mm - 50 mm = 200 mm
3)
for HDA-T M10x160/20: hmin = 260 mm - tfix
4)
for HDA-T M12x185/30: hmin = 290 mm - tfix
5)
for HDA-T M16x250/40: hmin = 370 mm - tfix
for HDA-T M16x270/40: hmin = 390 mm - tfix

Table 7: Minimum spacing and edge distances


Anchor size HDA-P / HDA-T M10x80 M10 M12 M16
HDA-PR / HDA-TR - M10 M12 M16
Cracked concrete
Minimum spacing 1) smin [mm] 80 100 125 190
2)
Minimum edge distance cmin [mm] 70 80 100 150
Non-cracked concrete
Minimum spacing 1) smin [mm] 80 100 125 190
2)
Minimum edge distance cmin [mm] 70 80 100 150
1)
Relation smin / hef = 1,0
2)
Relation cmin / hef = 0,8

Hilti Undercut Anchor HDA KKW

Minimum thickness of concrete member, Annex 8


Minimum spacing and edge distances

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Table 8: Design method A:


Characteristic values of resistance to tension loads
Anchor size HDA-P / HDA-T / HDA-PR / HDA-TR M10x80 2) M10 M12 M16
Steel failure
Characteristic tension resistance NRk,s [kN] 46 46 67 126
Partial HDA-P, HDA-T Ms 1,50
safety factor HDA-PR, HDA-TR Ms 1,60
Pull-out failure

Characteristic B25
Category A1 20 25 35 75
resistance C20/25
NRk,p [kN]
in cracked Category A2 B25
concrete 18,5 24,7 35 70,6
Category A3 C20/25
B35 1,18
C30/37 1,22
Increasing factors B45 1,34
for NRk,p c
for cracked concrete C40/50 1,41
B55 1,48
C50/60 1,55
Mp Category A1 1,50
Partial safety factor Mp Category A2 1,50
Mp Category A3 1,50
1)
Concrete cone failure
Effective anchorage depth hef [mm] 80 100 125 190
Spacing scr,N [mm] 3  hef
Edge distance ccr,N [mm] 1,5  hef
Mc Category A1 1,50
Partial safety factor Mc Category A2 1,50
Mc Category A3 1,50
1)
Splitting failure
Spacing scr,sp [mm] 3  hef
Edge distance ccr,sp [mm] 1,5  hef
1)
For concrete cone failure, the initial value of the characteristic resistance in cracked concrete shall be designed
using the following equations instead of Equation (5.2a) in Annex C, Section 5.2.2.4
for Requirement Category A1
N0Rk,c (A1) = 8,3  fck,cube0,5  hef1,5 and
for Requirement Categories A2 and A3 to take into account big cracks (w > 0,3mm)
N0Rk,c (A2, A3) = 0,75  8,3  fck,cube0,5  hef1,5
2)
M10x80: only HDA-P / HDA-T

Hilti Undercut Anchor HDA KKW

Characteristic values of resistance to tension loads. Annex 9


Requirement Categories A1, A2 and A3

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Table 9: Displacements under tension loads 1)


Anchor size HDA-P(R) /HDA-T(R) M10x80 M10 M12 M16
Requirement Category A1
Tension load N [kN] 11,9 11,9 16,7 35,7
Displacement N0 [mm] 0,8 0,8 0,9 2,1
Displacement N [mm] 1,3 1,3 1,3 2,1
Requirement Categories A2 and A3
Tension load N1 [kN] 12 16 23 37
Displacement N1 [mm] 2,4 2,7 2,5 3,0
Tension load N2 [kN] - - - 47
Displacement N2 [mm] - - - 4,3
1)
The displacement can be reduced linearly depending on the applied load.

Hilti Undercut Anchor HDA KKW

Displacement under tension load, Annex 10


Requirement Categories A1, A2 and A3

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Table 10: Design method A:


Characteristic values of resistance to shear loads
HDA-P, HDA-T (galvanised), filling of the annular gap optional
Pre-setting anchor HDA-P M10x80 M10 M12
Steel failure without lever arm
Characteristic Category A1 VRk,s [kN] 22 22 30
shear resistance Categories A2, A3 VRk,s [kN] 21 21 28
Partial safety factor Ms 1,25
Steel failure with lever arm
Lever arm according to
a3 [mm] 8 8 10
ETAG 001, Annnex C, 4.2.2.4
Characteristic bending moment MRk,s [Nm] 60 60 105
Partial safety factor Ms 1,25

Through-fastening anchor HDA-T M10x80 M10 M12 M16


1)
Steel failure without lever arm
Characteristic Category A1 VRk,s [kN] 65 65 80 140
shear resistance Categories A2, A3 VRk,s [kN] 50 50 62 120
Partial safety factor Ms 1,5
Steel failure with lever arm
Characteristic bending moment MRk,s [Nm] 60 60 105 266
Partial safety factor Ms 1,25

Anchor size HDA-P / HDA-T M10x80 M10 M12 M16


2)
Concrete pryout failure
Factor in Equation (5.6) in Annex C
k 2
of the Guideline, Section 5.2.3.3
Mc Category A1 1,50
Partial safety factor Mc Category A2 1,50
Mc Category A3 1,50
3)
Concrete edge failure
Effective length of anchor
lf [mm] 56 70 88 90
in shear loading
External diameter of anchor dnom [mm] 19 19 21 29
Mc Category A1 1,50
Partial safety factor Mc Category A2 1,50
Mc Category A3 1,50
1)
Minimum thickness of fixture for through-fastening, see Table 5, Annex 7
2)
For Categories A2 and A3 to take into account big cracks (w > 0,3 mm):
VRk,cp (A2, A3) = 0,75 · VRk,cp (ETAG 001, Annex C)
3)
For Categories A2 and A3 to take into account big cracks (w > 0,3 mm):
VRk,c (A2, A3) = 0,75 · VRk,c (ETAG 001, Annex C)

Hilti Undercut Anchor HDA KKW

Characteristic values of resistance to shear loads HDA-P / HDA-T Annex 11


Requirement Categories A1, A2 and A3

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Table 11: Design method A:


Characteristic values of resistance to shear loads
HDA-PR, HDA-TR (stainless steel), filling of the annular gap optional
Pre-setting anchor HDA-PR M10 M12
Steel failure without lever arm
Characteristic Category A1 VRk,s [kN] 23 34
shear resistance Categories A2, A3 VRk,s [kN] 20 25
Partial safety factor Ms 1,33
Steel failure with lever arm
Lever arm according
a3 [mm] 8 10
to ETAG 001, Annex C, 4.2.2.4
Characteristic bending moment MRk,s [Nm] 60 105
Partial safety factor Ms 1,33

Through-fastening anchor HDA-TR M10 M12 M16


1)
Steel failure without lever arm
Characteristic Category A1 VRk,s [kN] 71 87 152
shear resistance Categories A2, A3 VRk,s [kN] 50 70 115
Partial safety factor Ms 1,33
Steel failure with lever arm
Characteristic bending moment MRk,s [Nm] 60 105 266
Partial safety factor Ms 1,33

Anchor size HDA-PR / HDA-TR M10 M12 M16


2)
Concrete pryout failure
Factor in Equation (5.6) in Annex C
k 2
of the Guideline, Section 5.2.3.3
Mc Category A1 1,50
Partial safety factor Mc Category A2 1,50
Mc Category A3 1,50
3)
Concrete edge failure
Effective length of anchor
lf [mm] 70 88 90
in shear loading
External diameter of anchor dnom [mm] 19 21 29
Mc Category A1 1,50
Partial safety factor Mc Category A2 1,50
Mc Category A3 1,50
1)
Minimum thickness of fixture for through-fastening, see Table 5, Annex 7
2)
For categories A2 and A3 to take into account big cracks (w > 0,3 mm):
VRk,cp (A2, A3) = 0,75 · VRk,cp (ETAG 001, Annex C)
3)
For categories A2 and A3 to take into account big cracks (w > 0,3 mm):
VRk,c (A2, A3) = 0,75 · VRk,c (ETAG 001, Annex C)

Hilti Undercut Anchor HDA KKW

Characteristic values of resistance to shear loads HDA-PR / HDA-TR Annex 12


Requirement Categories A1, A2 and A3

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Table 12: Displacement under shear load HDA-P(R), HDA-T(R) 1)


Anchor size HDA-P / HDA-PR M10x80 M10 M12
Requirement Category A1
Shear load, annular gap not filled V1 [kN] 11,4 11,4 17,1
Displacement V01 [mm] 3,6 3,6 2,7
Displacement V1 [mm] 5,4 5,4 4,0

Shear load, annular gap filled V2 [kN] 11,4 11,4 17,1


Displacement V02 [mm] 1,2 1,2 1,4
Displacement V2 [mm] 1,8 1,8 2,1
Requirement Categories A2, A3
Shear load, annular gap not filled V1 [kN] 17 17 22
Displacement V1 [mm] 7,1 7,1 6,5

Shear load, annular gap not filled V2 [kN] 7,5 7,5 11


Displacement V2 [mm] 3 3 3

Shear load, annular gap filled V3 [kN] 17 17 22,4


Displacement V3 [mm] 2,5 2,5 2,3

Anchor size HDA-T / HDA-TR M10x80 M10 M12 M16


Requirement Category A1
Shear load, annular gap not filled V1 [kN] 33,3 33,3 42,8 95,2
Displacement V01 [mm] 6,2 6,2 6,9 10,1
Displacement V1 [mm] 9,3 9,3 10,3 15,1

Shear load, annular gap filled V2 [kN] 33,3 33,3 42,8 95,2
Displacement V02 [mm] 2,5 2,5 2,5 4,0
Displacement V2 [mm] 3,8 3,8 3,8 6,0
Requirement Categories A2, A3
Shear load, annular gap not filled V1 [kN] 33 33 41 80
Displacement V1 [mm] 7,0 7,0 8,2 9,7

Shear load, annular gap not filled V2 [kN] 15 15 16 30


Displacement V2 [mm] 3 3 3 3

Shear load, annular gap filled V3 [kN] 28 28 37 59


Displacement V3 [mm] 3 3 3 3
1)
The displacement can be reduced linearly depending on the applied load.

Hilti Undercut Anchor HDA KKW

Displacement under shear loads HDA-P(R) / HDA-T(R) Annex 13


Requirement Categories A1, A2 and A3

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Figure 11: Stop drill bit HDA-B

Table 13: Required stop drill bits HDA-B for HDA and HDA-R
Nominal
Anchor Stop drill bit with working Diameter
length
TE-C TE-Y
connection end connection end t d0
[mm] [mm]
HDA-P M10x80/20 TE-C-HDA-B 20x80 - 87 20
HDA-T M10x80/20
TE-C-HDA-B 20x100 TE-Y-HDA-B 20x100 107 20
HDA-P(R) M10x100/20
HDA-T(R) M10x100/20 TE-C-HDA-B 20x120 TE-Y-HDA-B 20x120 127 20
HDA-T(R) M10x160/20 TE-C-HDA-B 20x180 TE-Y-HDA-B 20x180 187 20
HDA-P(R) M12x125/30
TE-C HDA-B 22x125 TE-Y HDA-B 22x125 133 22
HDA-P(R) M12x125/50
HDA-T(R) M12x125/30 TE-C HDA-B 22x155 TE-Y HDA-B 22x155 163 22
HDA-T(R) M12x125/50 TE-C HDA-B 22x175 TE-Y HDA-B 22x175 183 22
HDA-T M12x185/30 - TE-Y HDA-B 22x215 223 22
HDA-T(R) M16x190/40 - TE-Y HDA-B 30x230 243 30
HDA-T(R) M16x190/60 - TE-Y HDA-B 30x250 263 30
HDA-T M16x250/40 - TE-Y HDA-B 30x290 303 30
HDA-T M16x270/40 - TE-Y HDA-B 30x310 323 30

Hilti Undercut Anchor HDA KKW


Annex 14
Stop drill bit

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Figure 12: Setting tool HDA-ST

Table 14: Required setting tools and hammer drills


Anchor Setting tool Hammer drill

TE 80 (-ATC AVR)
TE 76 (P/-ATC) 2)
3)
Connection end

Hammer drill 4)
TE 70 (-ATC) 2)
TE 56 (-ATC) 2)
TE 40 (-AVR)

TE 60 (-ATC)
TE 30-A36
d [mm]

TE 251)
TE 24

TE 35

TE 75
HDA-P/T M10x80/20 TE-C-HDA-ST 20-M10 20 TE-C  
TE-C-HDA-ST 20-M10 20 TE-C    
HDA-P/T M10x100/20
TE-Y-HDA-ST 20-M10 20 TE-Y  
HDA-T M10x160/20 TE-Y-HDA-ST 20-M10 20 TE-Y 
HDA-P/T M12x125/30 TE-C-HDA-ST 22-M12 22 TE-C    
HDA-P/T M12x125/50 TE-Y-HDA-ST 22-M12 22 TE-Y  
HDA-T M12x185/30 TE-Y-HDA-ST 22-M12 22 TE-Y 
HDA-P/T M16x190/40
TE-Y-HDA-ST 30-M16 30 TE-Y    
HDA-P/T M16x190/60
HDA-T M16x250/40
TE-Y-HDA-ST 30-M16 30 TE-Y 
HDA-T M16x270/40

TE-C-HDA-ST 20-M10 20 TE-C     


HDA-PR/TR M10x100/20
TE-Y-HDA-ST 20-M10 20 TE-Y  

HDA-PR/TR M12x125/30 TE-C-HDA-ST 22-M12 22 TE-C     


HDA-PR/TR M12x125/50 TE-Y-HDA-ST 22-M12 22 TE-Y  
HDA-TR M16x190/40
TE-Y-HDA-ST 30-M16 30 TE-Y    
HDA-TR M16x190/60
1)
Use only 1st gear
2)
Use with maximum impact energy
3)
Use only with TE-Y connection end
4)
Hammer drill with impact energy 16 to 20J and rotation speed 200 to 250 1/min (on-load operation).

Hilti Undercut Anchor HDA KKW


Annex 15
Setting tools and hammer drills

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Figure 13: Installation instruction HDA-P / HDA-PR

Figure 14: Installation instruction HDA-T / HDA-TR

Hilti Undercut Anchor HDA KKW


Annex 16
Installation instruction I

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Figure 15: Installation instruction:


Filling the annular gap with injection mortar Hilti HIT-HY 200-A
(optional)

Hilti Undercut Anchor HDA KKW


Annex 17
Installation instruction II

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Example: Setting and installation protocol (to be amended with respect to the facility)

Hilti Undercut Anchor HDA KKW


Annex 18
Setting and installation protocol I

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Example: Setting and installation protocol (continuation)

Hilti Undercut Anchor HDA KKW


Annex 19
Setting and installation protocol II

Z50587.14_1 1.21.1-14/15
Allgemeine bauaufsichtliche Zulassung
No. Z-21.1-1987 of 2 March 2015

Content of the Setting and installation protocol (continuation)

Post-installation check possibility:


A) Without filling the annular gap
Rectangularity of the anchor with respect to the concrete surface
Diameter and length of the anchor (length code)
Installation torque applied
Cracks / damages in the base material which can be recognized

HDA-T and HDA-TR (after unscrewing the nut and washer):


- Sleeve recess
- Position of red ring

HDA-P und HDA-PR (after disassembly the fixture):


- Sleeve recess
- Position of red ring

B) After filling the annular gap with injection mortar


Diameter and length of the anchor (length code)
Filling of the annular gap executed
Cracks / damages in the base material which can be recognized

Hilti Undercut Anchor HDA KKW


Annex 20
Setting and installation protocol III

Z50587.14_1 1.21.1-14/15

Você também pode gostar