General information Assembly and operating personnel must have the appropriate skills and
training. The present assembly instructions, in particular the safety notes on
page 23, must be followed in all cases during assembly and operation.

02

de

fr

en

nl

Mühlerainstrasse 26
CH-4414 Füllinsdorf
Phone +41 61 906 26 26
Fax +41 61 906 26 27
info@pneumatex.com
www.pneumatex.com

pneumatex.com
P ComCube 0705
Table of contents

03 Table of contents
Scope of delivery
04 Factory fitting
04 Wall-mounting
Operation
05 Assembly | Function DCA | DCD
05 Assembly | Function DCA • Example of analogue outputs
06 – 10 Assembly | Function DCD • Examples of digital outputs
11 Configuration DCA • Follow the accompanying instructions
for DCA isolating amplifiers.
11 – 14 Configuration DCD • Keyboard and Display | Operating
indications | menu | check Outputs | info |
Programmable Outputs | Factory Settings
Assembly
15 Electrical connection DCA | DCD • Requirements | Mains supply
15 Electrical connection DCA • Connections | Analogue outputs
16 Electrical connection DCD • Software updates | 230 V | SELV | RS 485-1
17 Terminal plan DCD
Start-up (IBN)
18 Requirements DCA | DCD
18 ComCube DCA • Switching on | Outputs calculation
18 | 19 ComCube DCD • Switching on | BrainCube configuration |
Initial start-up Welcome
Operation
20 Basic principles DCA | DCD 03
20 Operating modes DCD • auto | standby | menu | check
21 Messages DCD • Indications, acknowledgement | de
Message list | Correcting faults fr
22 Inspection | Disassembly DCA | DCD • No inspection requirement
• ComCube to be placed off circuit en

nl
23 Safety
24 Technical data
26 CE conformity
27 Customer service

pneumatex.com
P ComCube 0705
Scope of delivery
The scope of delivery is indicated on the delivery note and may include other
products in addition to ComCube. Intermediate storage is required in a dry room
protected from frost. Various ComCube communication modules are available.

Factory-fitted in Transfero TI
ComCube DCA TI Analogue communication module,
fully wired on mounting rail in PowerCube
panel.
ComCube DCD TI Digital communication module,
all inputs and outputs fully wired to
terminal strips in the PowerCube panel.

Wall mounting
ComCube DCA Analogue communication module for BrainCube controls,
fixing elements for optimal cable management.
1
• ComCube DCA is fastened to the wall using the
mounting plates. 4 screws and wall plugs are provided.
• Set the wall plugs in the wall corresponding to the positions 4
of the holes in the mounting plates, hold ComCube DCA,
1.2
and fasten with the screws.

ComCube DCD Digital communication module for BrainCube controls, 3


fixing elements for optimal cable management. 4
1
• ComCube DCD is fastened horizontally to the
wall using the mounting plate (3). 2
• Fix 2 screws into the wall corresponding to the positions
1.2
of the mounting slots.
• Mount the ComCube DCD and fasten with screws.

04

de Legend
1 ComCube
fr 1.2 Mains plug
en 2 Fixing elements for customer cables
3 Base plate
nl 4 Documents map
– Assembly | Operating instructions
– Isolating amplifier SINEAX TV 808-12 operating instructions
(for ComCube DCA only)

pneumatex.com
P ComCube 0705
Operation Assembly | Function
ComCube is a communication module that extends the BrainCube control functiona-
lity, as applied in Compresso, Transfero, Pleno and Vento. There are two types: digital
ComCube DCD and analogue ComCube DCA. The two can also be used in combi-
nation.

ComCube DCA PIS pressure and LIS content frequently have to be sent in simple form to the buil-
ding management system. The ComCube DCA | DCA TI provides 2 galvanically iso-
lated 4-20 mA analogue outputs.

Compresso | Transfero

ComCube DCA
Final equipment |
Building management system

PIS
LIS

ComCube DCA is connected between the BrainCube and the LIS and PIS sensors.
The 2 outputs are connected to the building management system.

05

de

fr

en

nl

pneumatex.com
P ComCube 0705
Operation Assembly | Function

ComCube DCD ComCube DCD | DCD TI is an 11-language communication module. It has 6 digital
IP inputs for registering and displaying external volt-free signals and 9 volt-free, indi-
vidually configurable digital OP outputs. All outputs are individually reversible from
NO (normally open) to NC (normally closed). The graphical 8-line display and the
encoder with Scroll and Select functions make it simple to operate.
ComCube DCD has two main applications:
• Up to 6 programmable external IP inputs and up to 9 OP outputs. For example,
external signals can be set for temperatures as commands on the DCD outputs.
For individual solutions, please contact our professional advisers.
Parallel connection of • OP outputs of a DCD. This avoids the need for expensive software for the inter-
ComCube DCD face (Examples 1-7). If more than 9 outputs are required, more than one DCDs
and the BrainCube (up to 250!) can be connected to one BrainCube.
should consist of up to – Individual assignment of BrainCube and ComCube messages on the OP outputs.
4 BrainCube controls – Individual switching of the OP outputs of the connected BrainCube control depen-
and 250 ComCube DCD ding on PIS pressure and/or LIS content.
communication modules. – Status indication (on/off) of ComCube IP inputs and OP outputs.
– Indication of pressure and content, and switching of the pumps and valves of the
The total length of the
connected BrainCube control.
RS 485 data link should
– Monitoring of the connected BrainCube control type.
be no more than 300 m.
Installed between the RS 485 of the BrainCube and the building management
system (Examples 1-6) or the final equipment for remote monitoring of the BrainCube
controls (Example 7). There are many other possible applications, which cannot all
be described here.

06

de

fr

en

nl

pneumatex.com
P ComCube 0705
Operation Assembly | Function

Example 1 Visualisation and building management system


ComCube DCD No.1: RS 485 signals on 9 outputs to represent water level, for
example Min., 20%, 30%, 40%, 50%, 60%, 70%, 80%, Max.
ComCube DCD No.2: RS 485 signals on 9 outputs, for example representing
min./standard/max. water level, min./standard/max. pressure, compressor on, spill
valve open, water make-up on.

ComCube DCD
No.2
Final equipment |
Building manage-
Compresso | Transfero ment system
Lighting column

ComCube DCD
No.1
BrainCube
RS 485
cable

RS 485 cable

It is advisable to install ComCube DCD No. 2 directly in the building management


system, as this will greatly reduce the amount of wiring required for the 9 outputs.

07

de

fr

en

nl

pneumatex.com
P ComCube 0705
Operation Assembly | Function

Example 2 Connecting a system to the building management system


Direct wiring of the volt-free OP outputs of the ComCube DCD to the building
management system. If the 1 or 2 volt-free outputs of the BrainCube are not enough,
then 9 more outputs can be made available through the ComCube DCD.

Compresso | Transfero

ComCube DCD Cabling with OP outputs


BrainCube Final equipment |
RS 485
Building manage-
cable
ment system

Link-up information* B

Example 3 Connecting several systems in different buildings to the building management system
It is advisable to connect them through the ComCube DCD over separate RS 485
data links.

08
Transfero Vento
de BrainCube

fr Compresso
BrainCube
en

nl
BrainCube Final equipment |
B Building management system

B ComCube
DCD

RS 485 cable
Link-up information* B
RS 485 cable
RS 485 cable

* Information on the main menu of ComCube DCD | DCD TI  page 12

pneumatex.com
P ComCube 0705
Operation Assembly | Function

Example 4 Connecting several systems in one building to the building management system
It is advisable to connect them over an RS 485 data link. In any case, each system
can be assigned to a specific ComCube DCD.

Compresso Transfero

Vento
BrainCube BrainCube BrainCube Final equipment |
Building management system

ComCube
DCD

RS 485 cable
Link-up information* B B B

Example 5 Master-slave parallel operation + several ComCube DCDs


The master and each slave are assigned to one ComCube DCD. This arrangement
allows the maximum required monitoring of the entire system with a minimum amount
of cabling. It is also the ideal arrangement for master-slave parallel operation.

09

de

fr

BrainCube BrainCube BrainCube en


Final equipment |
Building management system nl

ComCube
DCD
Master Slave Slave
RS 485 cable
Link-up information* M S S

* Information on the main menu of ComCube DCD | DCD TI  page 12

pneumatex.com
P ComCube 0705
Operation Assembly | Function

Example 6 Master-slave parallel operation + one ComCube DCD


The ComCube DCD is assigned to the master. The volt-free outputs on the slave
BrainCube controls are connected directly to the building management system. This
arrangement is useful in «parallel operation» and provides optimum monitoring at
minimum cost.

Final equipment |
Building management system

BrainCube

ComCube
DCD
Master Slave Slave
RS 485 cable
Link-up information* M S S

Example 7 Remote monitoring with one ComCube DCD


A ComCube DCD can, of course, also be used as a terminal for the remote monito-
ring of one or more BrainCubes. The graphical display can display any desired data.

10

de

fr Transfero
Vento
BrainCube
en Compresso

nl BrainCube

BrainCube

B ComCube DCD

RS 485 cable
Link-up information* B

* Information on the main menu of ComCube DCD | DCD TI  page 12

pneumatex.com
P ComCube 0705
Operation Programmable

ComCube DCA To use and operate the integrated isolating amplifier, read the «Isolating amplifier
SINEAX TV 808-12 operating instructions».

ComCube DCD Keyboard and display

push – confirm, scroll – select, modify,


open Change view
escape
Back,
Key lock
Press key lock for 5 s
until « » appears.
Press again for 5 s
to release the key lock. menu
Main menu
auto standby
Automatic operation Display only
check
Function check

Operating displays

Message row 1
Illuminated display ComCube +
Light goes off 60 s equipment type
after last operator
Information row
action. Activated by
Inputs, Outputs,
the scroll or other key.
BrainCube No.
Message row 2 11
Operating mode,
Most recent message de

Change between fr
operating displays
en
using scroll.
nl

pneumatex.com
P ComCube 0705
Operation Programmable

ComCube DCD menu —Selected applications


BrainCube 1, in this case: M = Master*
BrainCube 2, in this case: S = Slave*
BrainCube 3, in this case: B = stand alone**
BrainCube 4, in this case: X = not connected
Main menu MSBX Link-up information
Check outputs * Master-slave parallel operation
Parameters ** Individual operation, for example Vento
Info

2.2 70
bar Back %
PIS pressure LIS content
max. PSV pressure max. content 100%
min. P0 pressure min. content 0%

Check outputs
Switch outputs manually Output OP1 
 on,  off ..
.
Output OP9 

Parameters
Language selection DE, EN, FR, NL, IT, CZ, PL, SE, ES, FI, DK
Date 12.05.2007
Time 15:38
BrainCube 1 Select the BrainCube with which
communications are to be set up.
Output OP1 
12 Output OP2 
Set outputs
 pages 13 | 14
..
de .
Output OP9 
fr
Input IP1 
en
Set inputs: Input IP2 
nl  NO (normally open) ..
 NC (normally closed) .
Input IP6 
Factory setting Load factory settings.
Contrast 120 All individual settings will be overwritten!

Info
Type ComCube DCD
Version V1.01
View messages The last 20 ComCube messages.

pneumatex.com
P ComCube 0705
Operation Programmable

ComCube DCD Programmable outputs, for example output OP1

Output OP1
Inputs  1)
 This output is not assigned,
Pumps/valves  2)
 Assignment of this output,
Switch-points BrainC 
Messages BrainCube  3) Note: Multiple assignments are
Messages ComCube  4) not useful (except invers = )
Invers  5)

1) Assign IP inputs of ComCube DCD to the output.


2) Assign BrainCube pumps/compressors and valves individually.
If the corresponding unit switches, the output closes.
3) Assign BrainCube message individually. Multiple assignments are possible.
4) Assign ComCube DCD messages individually. Multiple assignments are possible.
5) Switch output to inverse:  NO (normally open) |  NC (normally closed).

Set switching points, for example output OP1

OP1 Switch-points BrainC Switching points for pressure are inactive,


PIS on off if PIS on = off,
PIS off 2.0 bar switching points for content are inactive,
LIS on 10% if LIS on = off,
LIS off 20% Note: It is not useful to switch an output
according to content or pressure.

Mode of operation
If PIS | LIS on is lower than PIS | LIS off , the output is switched on if the value falls
below PIS | LIS on, and switches off if the value goes above PIS | LIS off.
If PIS | LIS on is higher than PIS | LIS off , the output is switched on if the value goes
13
above PIS | LIS on, and switches off if the value falls below PIS | LIS off.
de
Example A: OP1 Switch-points BrainC Switching points for pressure are inactive.
PIS on off Output closes if content > 90 % and opens if fr
PIS off 0.0 bar < 80 %. This arrangement can be used, for
LIS on 90% example, to actuate a valve in order to prevent en
overfilling (separate water meter and locking is
LIS off 80% recommended for when maximum quantity is nl
exceeded).

Example B: OP1 Switch-points BrainC Switching points for pressure are inactive.
PIS on off Output closes if content > 30 % and opens if
PIS off 0.0 bar < 29 %. This output could be coupled with an
LIS on 30% indicator lamp. If other outputs are program-
med for other levels, a lighting column can
LIS off 29% then be easily set up to display the different -
vessel contents (page 7, example 1).

pneumatex.com
P ComCube 0705
Operation Programmable

ComCube DCD Factory settings menu - Parameters

Parameters Factory setting

Language selection English


Date 00.00.2000
Time 00:00
BrainCube off

Output OP1 Messages BrainCube  M01 Min pressure PIS 


Output OP2 Messages BrainCube  M02 Max pressure PIS 
Output OP3 Messages BrainCube  M03 Min contents LIS 
Output OP4 Messages BrainCube  M04 Max contents LIS 
Output OP5 Messages BrainCube  M11 Runtime FIQ 
M12 Leakages FIQ 
M13 NS leaky FIQ 
M14 Max quantity FIQ 
M15 Water meter FIQ 
Output OP6 Switch-points BrainC  LIS on: 70 %
LIS off: 69 %
Output OP7 Switch-points BrainC  LIS on: 50 %
LIS off: 49 %
Output OP8 Switch-points BrainC  LIS on: 30 %
LIS off: 29 %
Output OP9 Switch-points BrainC  LIS on: 10 %
LIS off: 9 %

Input IP1
Input IP2 All inputs NO 
14 ..
. (normally open)
de Input IP6
fr

en

nl

pneumatex.com
P ComCube 0705
Assembly Electrical connection
The electrical connection work should be performed by a skilled person in accor-
dance with local regulations. Please also follow the BrainCube control Assembly I
! Operation instructions. Shut down the ComCube before starting work.

Requirements
! Do not connect Pull out mains plug (1.2) and, for ComCube DCD, switch off any external voltages on
ComCube to the outputs OP1-OP9.
heating emergency Mains power requirements:
off switch! • Connection voltage U : 230 V, 50 Hz
• Connected load PA : 0.1 kW
• Electrical protection provided by customer : 10 A, FI protection switch,
follow the regulations applicable at the location
• If installed in residential buildings, we recommend fitting a commercially available
mains filter in the junction box.
Mains power supply through mains plug (1.2)
1.2 • Pull out the mains plug (1.2) and unscrew.
• Connect PE, N, L to the corresponding terminals and screw the mains plug
back together.
• Connect the mains plug (1.2) only at the initial start-up.
After cabling is complete
When cabling is complete, close off all unused screw connections on the housing back
panel with suitable plugs, in order to ensure Protection Class IP 54.

ComCube DCA Connections


Example connections are shown in the following terminal plan:
Example: BrainCube terminal plan with ComCube DCA
E E
ComCube DCA
101IN

102IN

105IN

104IN

103IN

106IN
1Aff
101+

102+

105+

104+

103+

106+
GND

GND

GND

GND

GND

GND
PE
N
L

0,6 m
max. max. max. max.
E E 4,0 m 4,0 m 4,0 m 4,0 m 15
GND

GND

Mains
2

2
1

plug + OUT + OUT

Terminal box
1.2.1 *
PIS
IN +
PIS sensor
IN +
LIS sensor LIS
de
Open cover: Network supply Pressure sensor BrainCube Content sensor Analogue output Analogue output
loosen the 4 screws (E), 3x 1,0 mm2 (L+N+PE) TecBox PIS/4-20 mA LIS/4-20 mA fr
230 V AV / 50 Hz * Line protection max.10 AT min. 2x 0,5 mm shielded
pull cover forward.
Close cover:
en
place cover and fasten Analogue outputs
nl
with 4 screws (E). To connect and operate the integrated isolating amplifier, please read the accom-
panying «Isolating amplifier SINEAX TV 808-12 operating instructions».
For the building management system, PIS pressure and LIS content can be made
available in the form of galvanically isolated 4-20 mA signals through the ComCube
DCA. The existing PIS BrainCube and LIS BrainCube cable connections must be
removed and rewired to the ComCube DCA. The total length of the PIS/LIS
BrainCube and/or PIS/LIS ComCube DCA cable connections should be no more
than 4 m. A twisted pair shielded cable should be used (for example, Belden Type
9501). With the DCA TI, the above cabling is no longer required ( Transfero TI
Assembly | Operation).

pneumatex.com
P ComCube 0705
Assembly Electrical connection

ComCube DCD Connections


•  Terminal plan page 17
• The connections for the digital IP inputs, digital OP outputs and the RS 485
interface are made on the terminal rail of the PowerCube PC1 panel
( Transfero TI Assembly | Operation)
C C

B On the rear panel


B: Run the software updates using the special adapter.
C C
This is to be done by Pneumatex Customer Service only!
D D

Terminal box SELV - Cover 1


• Digital inputs IP1-IP6
• RS 485 interface
Open cover 1: Close cover 1:
1. Open cover 2. 1. Insert the plugs of the ribbon cables for the
2. Loosen the 4 torx screws (C). display and keyboard in the «20 Display»
3 Carefully pull the cover 1 forward a few and «14 Keyboard» slots and snap the
centimetres, until the ribbon cable plugs for fasteners in.
the display and keyboard become accessible. 2. Push the cover into the guiding slots in the
4. Snap the fastener for the «20 Display» and housing and fasten with the screws (C).
«14 Keyboard» plugs outwards.
5. Carefully pull cover 1 forward and remove.

Terminal box 230 V – Cover 2


• Digital outputs OP1-OP9
Open cover 2: Close cover 2:
Loosen the 2 torx screws (D), Cover 1 must be closed.
carefully pull the cover forward and remove. Push cover 2 into the guiding slots in the
housing and fasten with the screws (D).

RS 485-1 interface
To operate the ComCube DCD | DCD TI with up to four BrainCubes. The total length
16 of the data link should be no more than 300 m. A twisted pair shielded cable should
be used (for example, Belden Type 9501). The RS 485-1 jumper ( terminal plan
de page 17) in the final equipment on the data link must be set to «on», and the jumper
on intermediate equipment to «off».
fr
Example: Parallel connection with 2 BrainCube controls and 2 ComCube DCD
en
communication modules
nl A B A B A B

B A B A B A
SHIELD

SHIELD

SHIELD

SHIELD

SHIELD

SHIELD
A

A
B

RS 485-1 RS 485-1 RS 485-1 RS 485-1


A B A` B` A B A` B` A B A` B` A B A` B`

OFF ON OFF ON OFF ON OFF ON


Jumper ON Jumper OFF Jumper OFF Jumper ON

BrainCube 1 ComCube 1 BrainCube 2 ComCube 2

pneumatex.com
P ComCube 0705
Digital inputs IP Interface Digital inputs IP
(not connect voltage) RS 485-1 (not connect voltage)
Input 1 Input 2 Input 3 Input 4 Input 5 Input 6

A
B
A`
B`

SHIELD
SHIELD

pneumatex.com
1
2
1
2
1
2
1
2
1
2
1
2
IP1 IP2 IP3 RS 485-1 IP4 IP5 IP6
IN IN IN A B A` B` IN IN IN

P
OFF ON OFF ON
Jumper
2 RS 485-1
2 2
1
1 1
14 Keyboard Diagnostics plug
20 Display
Assembly

Terminal box SELV


lower cover

L1 N
MAINS OP1 OP2 OP3 OP4 OP5 OP6 OP7 OP8 OP9

L
N
2)

PE
Terminal plan

Mains plug
1.2

C
C
C
C
C
C
C
C
C

NO
NO
NO
NO
NO
NO
NO
NO
NC
NO

1)

Terminal box 230 V


Network supply Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 Outputg 9
3 x 1,0 mm2 (L+N+PE)
230 V AV/50 Hz Digital outputs OP
1)
Allocation acc. to menu *Parameter*
Line protection max. 10 AT
2)
Line protection max. 2 AT

ComCube 0705
17

fr

nl
en
de
Start-up
We recommend having the start-up carried out by the nearest Pneumatex Customer
Service. This must be ordered separately, and will be at the price specified in the Zoom
for the country concerned. The scope of service is as described in this chapter.

Requirements
• The services described in the «Assembly» section have been completed.
• The electrical power supply is available.
• The BrainCube control is switched on.

ComCube DCA BrainCube with ComCube DCA | DCA TI


Switching on: For ComCube DCA, connect the mains plug (1.2), or for ComCube DCA
TI, switch on the main switch on the Transfero TI,.if all requirements for start-up are ful-
filled, all settings have been made, and the ComCube DCA is to go into operation. No
other steps are required for start-up.
Output calculations: For the building management system, PIS pressure and LIS con-
tent can be made available as galvanically isolated 4-20 mA signals through ComCube
DCA | DCA TI ( Electrical connection page 15). Parameter settings must not be made
on the BrainCube. The PIS and LIS 4-20 mA signals are calculated by the customer.
Sensors used Measurement range Output
PIS pressure
Compresso CPV -1 – 10 bar → 4-20 mA
Compresso C 10 | 20 0 – 10 bar → 4-20 mA
Transfero T_ 4 | 6 | 8 | 10 0 – 10 bar → 4-20 mA
Transfero TI 100.2 | 61.2 | 91.2 | 62.2 | 82.2 | 53.2 | 93.2 0 – 10 bar → 4-20 mA
Transfero TI 120.2 | 150.2 | 111.2 | 141.2 | 112.2 | 152.2 | 113.2 | 143.2 0 – 16 bar → 4-20 mA
Transfero TI 190.2 | 230.2 | 181.2 | 241.2 | 152.2 | 192.2 | 173.2 0 – 25 bar → 4-20 mA
Pleno PI 6.1 | PI 6.2 | PI 9.1 0 – 10 bar → 4-20 mA
Vento (all types) -1 – 10 bar → 4-20 mA
LIS content
Expansion vessels up to 1,000 litre 0 – 500 kg → 4-20 mA
Expansion vessels from 1,000 to 5,000 litres 0 – 2,000 kg → 4-20 mA
Expansion vessels from 5,000 to 20,000 litres 0 – 8,000 kg → 4-20 mA
18
The LIS signal at 0% and 100% can be determined in the following ways:
de • Read off the mA values stored in the BrainCube for 0% or 100% (service level per-
fr
formed by Pneumatex Customer Service only, at a cost),
• Measure the mA signals when the primary vessel is empty (0%) and when full (100%),
en • Measure the mA signal with the primary vessel empty (0%), calculate the mA signal
for 100% according to the size of the primary vessel, and assuming that weight is
nl
distributed equally between the three feet of the vessel ( 1 litre ≈ 0.33 kg/foot).

ComCube DCD BrainCube with ComCube DCD | DCD TI


Switching on: For ComCube DCD, connect the mains plug (1.2) , or for ComCube
DCD TI, switch on the main switch on the Transfero TI. ComCube DCD | DCD TI is
ready for start-up. BrainCube Software Version V2.00 or higher is required. If necessa-
ry, have a software update performed by Pneumatex Customer Service (this service is
payable). At the initial start-up, it displays a «Welcome» message (if there is no opera-
tor action for 4 min., it automatically changes to standby with display function only, then
to the menu.

pneumatex.com
P ComCube 0705
Start-up

Programme the BrainCube to operate with ComCube DCD


One or more ComCubes (up to 250) can be operated with up to 4 BrainCube controls.
Besides the cabling work ( pages 15 | 16), the following parameter settings are requi-
red on the BrainCube.
• Open *ComCube* menu: press menu, then press esc + push at the same time.
• Make the settings in the *ComCube* menu:
ComCube
BrainCube off Show selected BrainCube No.
ComCube  push Enable BrainCube for ComCube operation
* If a BrainCube No. BrainCube 1

}
scroll

is already assigned, it BrainCube 2


push Select an available BrainCube No.*
no longer appears in BrainCube 3
the selection list. BrainCube 4
Back push Exit the *ComCube* menu

«Welcome» at initial start-up of ComCube DCD | DCD TI


You can now make the desired settings and function tests on ComCube DCD | DCD TI.
Welcome • Set language, date and time;
Standard languages: de, en, fr, nl,
other languages on request.
Main menu
Check outputs • Check signal transfer to building management
system.
Parameters • Set BrainCube No. This setting is required in
order to establish communications.
• Set IP inputs, OP outputs.
If no settings are made, the ComCube DCD |
DCD TI uses the factory settings.  page 14
19
** Example: Check the functional efficiency of the link-up de
BrainCube No. 1 is a Check the link-up information on the ComCube DCD | DCD TI  page 12. The links
Transfero. Other to all connected BrainCubes are displayed there.** fr
BrainCube controls
are not included in this Select operating mode en
arrangement. The • standby : select this if ComCube DCD | DCD TI is not to go into operation yet.
nl
message BXXX appears. • auto: select this if all requirements for start-up are fulfilled, all settings
If XXXX appears or the have been made, and ComCube DCD | DCD TI is to go into operation.
display switches between After auto operation begins, note that:
BXXX and XXXX, there is key lock can be activated if desired ( page 11).
probably a data link fault.
In this case, check the
data link.
Start-up is now complete. ComCube works automatically.

pneumatex.com
P ComCube 0705
Operation Operating modes

Basic principles
ComCube is maintenance-free. Before working on the electrical components, the
ComCube should be shut down and placed off circuit. Pull out mains plug (1.2), or
for Transfero TI, switch off the main switch or the integrated ComCube DCD TI safe-
ty cut-out.

ComCube DCD Operating modes


For ComCube DCD | DCD TI, operating states and deviations from normal operation
are indicated and can if necessary be signalled to the central monitoring station over
the digital OP outputs. In general, auto operating mode is distinguished from stand-
by mode. To ensure safety at work, the ComCube DCD | DCD TI should be assumed
to be in operation when in either mode.
auto
After start-up is completed successfully, ComCube DCD | DCD TI remains in auto
mode all year round. Before working on the connected BrainCube control, deactiva-
te auto mode  standby.
standby
This operating mode is particularly suitable for maintenance work.
Standby mode can be selected manually. When in standby mode, the OP outputs are
no longer actuated. However, communications are still active with the connected
BrainCube controls.
menu
All the ComCube DCD | DCD TI functions can be selected, tested and modified from
the main menu. Data link function can also be checked here ( page 19).
check
20 In the check menu, outputs can be switched manually and signal transfer to the buil-
ding management system can be tested.
de
Auto mode is deactivated in the check menu. Messages that occur during function
fr
tests are stored in the message list.
en
After work is completed in the check menu, auto mode must be activated again.
nl

pneumatex.com
P ComCube 0705
Operation Messages

ComCube DCD View/acknowledge messages

Deviations from the parameter settings and parameters calculated by ComCube


DCD | DCD TI, but operating information is also shown as codes on the bottom line
of the display. If a current message is present, you can open the message list imme-
diately by pressing push.
push Use push to open the message list.

The last 20 messages are displayed.


The message list can also be opened
from the menu - info. 21

de
scroll Use scroll to select messages. fr
Use push to open the Help text, and acknowledge with push if prompted.
en

If it is not possible to establish full functionality, please contact Pneumatex Customer nl


Service.

pneumatex.com
P ComCube 0705
Operation Inspection | Disassembly

Inspection
ComCube communication modules are not subject to any particular inspection
requirement.

Disassembly
Before disassembling, place the ComCube off circuit ( Electrical connection
page 15).

22

de

fr

en

nl

pneumatex.com
P ComCube 0705
Safety

Application
! ComCube is a communication module for BrainCube controls (Transfero,
Compresso, Vento, Pleno PI). Applications other than those described require prior
agreement with Pneumatex. A declaration of conformity is included and certifies
compliance with EU Directives.

Follow the instructions


! Assembly, operation, maintenance, and disassembly must be carried out as descri-
bed in these instructions and in accordance with best practice. For the ComCube
DCD TI and DCA TI, the Transfero TI instructions should also be followed. If anything
is unclear, please contact the Pneumatex Customer Service.

Staff
! Assembly and operating staff must possess the appropriate skills and training.

Place of installation
! Access to the place of installation must be restricted to trained and specialised
personnel. Electrical power connections must correspond to the requirements of the
equipment.

Observing the parameters


! Please refer to the type plate for technical specifications and details of manufacturer,
year of construction, and serial number. The regulations must be observed to ensu-
re temperature and pressure protection, so that the system does not exceed or fall
below the maximum and minimum operating parameters respectively.

Electrical connection
! Electrical wiring and connections must be carried out by a skilled professional in
accordance with current local regulations. The system must be shut down before
working on any of the electrical components. 23

de

fr

en

nl

Failure to follow these instructions, in particular the safety instructions, may


cause loss of functionality, faults or even serious damage to the ComCube and the
electrically connected BrainCube, and may also result in physical injury. If there has
been a failure to comply with these instructions, the manufacturer can no longer
accept liability or claims under warranty.

pneumatex.com
P ComCube 0705
Technical data
The data on the ComCube type plate and the data given below should be compa-
red with the design and system parameters. There should be no inadmissible devia-
tions. Full technical information is available in the Zoom (Print) and on the internet
at www.pneumatex.com.

Terms
TU: 40 °C Max. admissible ambient temperature
PA/U/F: ..... kW / 230 V / 50 Hz Connected load/voltage/frequency/
as indicated on type plate
IP : ..... EN 60529 protection class,
as indicated on type plate

24

de

fr

en

nl

pneumatex.com
P ComCube 0705
Konformität | Conformité | Conformity | Conformiteit

Hersteller: Pneumatex AG, Mühlerainstrasse 26, CH-4414 Füllinsdorf


erklärt hiermit, dass die Produkte
ComCube
mit den folgenden EG-Richtlinien, einschliesslich der letzten Änderungen sowie mit den entsprechenden
Rechtsakten zur Umsetzung der Richtlinien in nationales Recht übereinstimmen:
73/23/EWG Niederspannungsrichtlinie und
89/336/EWG Richtlinie über die elektromagnetische Verträglichkeit (EMV),
und dass folgende harmonisierten Normen zur Anwendung gelangten:
ComCube DCA | DCA TI: EN 61010-1:1993, EN 50081-2:2993, EN 50082-2:1994, EN 60335-1:2002
ComCube DCD | DCD TI: EN 61000-6-2:2001, EN 61000-3-2:2000, EN 61000-3-3:1995 + A 2001,
EN 55022:1998 + A1+ A2 2003, EN 60335-1:2002.
_________________________________________________________________________________________
Constructeur: Pneumatex AG, Mühlerainstrasse 26, CH-4414 Füllinsdorf
déclare par la présente que
ComCube
est conforme aux dispositions des directives CE sulvantes, y compris les dernières modifications, et à la
législation nationale appliquant ces directives:
73/23/CEE Directive basse tension et
89/336/CEE Directive compatibilité électromagnétique (CEM),
et que les normes harmonisées suivantes ont été appliquées:
ComCube DCA | DCA TI: EN 61010-1:1993, EN 50081-2:2993, EN 50082-2:1994, EN 60335-1:2002
ComCube DCD | DCD TI: EN 61000-6-2:2001, EN 61000-3-2:2000, EN 61000-3-3:1995 + A 2001,
EN 55022:1998 + A1+ A2 2003, EN 60335-1:2002.
__________________________________________________________________________________________
Manufacturer: Pneumatex AG, Mühlerainstrasse 26, CH-4414 Füllinsdorf
herewith declares that the products
ComCube
are in conformity with the provisions of the following EC directives, including the latest amendments, and
with national legislation implementing these directives:
73/23/EEC Low voltage guideline and
89/336/EEC Electromagnetic compatibility guideline,
and that the following harmonized standards have been applied:
ComCube DCA | DCA TI: EN 61010-1:1993, EN 50081-2:2993, EN 50082-2:1994, EN 60335-1:2002
ComCube DCD | DCD TI: EN 61000-6-2:2001, EN 61000-3-2:2000, EN 61000-3-3:1995 + A 2001,
EN 55022:1998 + A1+ A2 2003, EN 60335-1:2002.
__________________________________________________________________________________________
26 Fabrikant: Pneumatex AG, Mühlerainstrasse 26, CH-4414 Füllinsdorf
verklaart hiermede dat
de ComCube
fr voldoet aan de bepalingen van de volgende EG-richtlijnen, de laatste wijzigingen inbegrepen, en met de
nationale wetgeving die deze richtlijnen van toepassing stelt:
en 73/23/EWG Laagspanningsrichtlijn en
89/336/EWG Richtlijn electromagnetische compatibiliteit (EMC),
nl en dat de volgende geharmoniseerde normen zijn toegepast:
ComCube DCA | DCA TI: EN 61010-1:1993, EN 50081-2:2993, EN 50082-2:1994, EN 60335-1:2002
ComCube DCD | DCD TI: EN 61000-6-2:2001, EN 61000-3-2:2000, EN 61000-3-3:1995 + A 2001,
EN 55022:1998 + A1+ A2 2003, EN 60335-1:2002.

Christian Müller
Quality Manager

pneumatex.com
P ComCube 0705
Kundendienst | Service après-vente | Customer service | Servicedienst

Schweiz PNEUMATEX AG
Suisse CH-4414 Füllinsdorf
Switzerland Tel. +41(0)61 906 26 26
Zwitserland Tel. +41(0)61 906 26 00
Fax +41(0)61 906 26 27
info@pneumatex.com
www.pneumatex.com
Australien SWISSMECH EQUIPMENT PTY.LTD. Österreich PNEUMATEX
Australie Braeside, Victoria 3195 Autriche Repräsentanz Österreich
Australia Tel. (03) 9587 8870 | Fax (03) 9587 8871 Austria A-3340 Waidhofen/Ybbs
Australië info@swissmech.com.au Oostenrijk Tel. +43 7442 52251 | Fax +43 7442 52150
pat@pneumatex.com
Belgien PNEUMATEX & CIE NV/SA
Belgique B-2170 Merksem RÖHRICH Ges.m.b.H.
Belgium Tel. (03) 640 33 80 | Fax (03) 640 33 83 A-5020 Salzburg
België info@pneumatex.be Tel. (0662) 439541 | Fax (0662) 43954139
roehrich@roehrich.co.at
Dänemark ARMATEC A/S
Danemark DK-2600 Glostrup Vorarlberg + Tirol
Denmark Tel. (046) 96 00 00| Fax (046) 96 00 01 Inhaus Handels GmbH
Denemarken armatec@armatec.dk A-6845 Hohenems
Tel. (05576) 77877 | Fax (05576) 77877 201
Deutschland PNEUMATEX GmbH
office@inhaus.cc
Allemagne D-55511 Bad Kreuznach
Germany Tel. 06 71/8 90 10-0 | Fax 06 71/8 90 10-60 Polen PNEUMATEX sp. z o.o.
Duitsland info@pneumatex.de Pologne PL-60-479 Poznań
Poland Tel. +48 (0)603783151
Finnland TOUR & ANDERSSON OY
Polen ppl@pneumatex.com
Finlande FIN-01511 Vantaa
Finland Tel. +358 207 401616 | Fax +358 207 401601 Portugal BOMBAS WILO-SALMSON
Finland ta-fi@tourandersson.com Portugal P-4050-040 Porto
Portugal Tel. (022) 208 03 50 | Fax (022) 200 14 69
Frankreich PNEUMATEX SA
Portugal bombas@salmson.pt
France F-77290 Mitry-Mory
France Tel. (01) 64 67 82 82 | Fax (01) 64 67 94 49 GRAU DIA, LDA
Frankrijk info@pneumatex.fr P-1250-240 Lisboa
Tel. +351 91 8031079
Grossbritannien ENGINEERING APPLIANCES LIMITED
graudia@sapo.pt
Grande-Betagne UK-TW16 7DX Middlesex
United Kingdom Tel. (01932) 788 888 | Fax (01932) 761 263 Rumänien PRATCO S.R.L.
Groot-Brittannië info@engineering-appliances.com Roumanie RO-032265 Bucureşti
Romania Tel. +40 21/345 1725
Italien PNEUMATEX SA
Roemenië Fax +40 21/345 2019
Italie I-22070 Montano Lucino (CO)
office@pratco.ro | www.pratco.ro
Italy Tel. +39 (0)31 47 1764 | Fax +39 (0)31 472 1711
Italië pit@pneumatex.com DOSETIMPEX S.R.L.
RO-300085 Timişoara
Japan PS COMPANY LTD. 27
Tel. +40 256/200 368
Japon J-Tokyo 151-0063
Fax +40 256/437 644
Japan Tel. (03) 3469 7111 | Fax (03) 5478 7260 de
office@dosetimpex.ro
Japan hq-importdpt@psk.co.jp
Russland MANOMETER TERMA LTD.
Luxemburg PNEUMATEX SA fr
Russie RUS-105120 Moskau
Luxembourg L-8399 Windhof
Russia Tel. | Fax +7 495 916 79 91
Luxembourg Tel. 262 615-1 | Fax 262 615-50
Rusland info@manoterm.ru
en
Luxemburg pneumatex@pt.lu
Schweden ARMATEC AB nl
Neuseeland ENERGY PRODUCTS INTERNATIONAL
Suède S-40091 Göteborg
Nouvelle-Zélande NZ-Hamilton
Sweden Tel. (031) 89 01 00 | Fax (031) 45 36 00
New Zealand Tel. (07) 847 27 05 | Fax (07) 847 42 22
Zweden info@armatec.se
Nieuw-Zeeland sales@energy-products.co.nz
Serbien AIRTREND Ltd. – GOBRID Ltd.
Niederlande PNEUMATEX BV
Serbie 11000 Beograd
Pays-Bas NL-5260 CA Vught
Serbia Tel. +381 11 383 68 86
Netherlands Tel. (073) 657 90 21 | Fax (073) 656 16 84
Serviën Fax: +381 11 344 41 13
Nederland info@pneumatex.nl
airtrend@eunet.yu | gobrid@eunet.yu
Norwegen ARMATEC AS
Spanien INDELCASA ING. DEL CALOR S/A
Norvège N-0508 Oslo 5
Espagne E-48530 Ortuella-Bizkaia
Norway Tel. 23 24 55 00 | Fax 23 24 55 10
Spain Tel. (094) 413 2560 | Fax (094) 446 7076
Noorwegen firmapost@armatec.no
Spanje webmaster@indelcasa.es

pneumatex.com
P ComCube 0705
WDMOIN00030705
| swiss made | Pneumatex – Dynamic Watermanagement

Mühlerainstrasse 26
CH-4414 Füllinsdorf
Tel.+41 61 906 26 26
Fax+41 61 906 26 27
info@pneumatex.com

www.pneumatex.com