Escolar Documentos
Profissional Documentos
Cultura Documentos
emfis Plus
R 240.0
Y 240.0 V
B 240.0
T
CAL
GCPK6EMFISPLUS-R2
2. General Information............................................. 2
ITEM : LT ac, Three Phase, Four Wire Panel Mounted Static 3. Installation............................................................ 3
kWh Meter with LCD Display (96mm x 96mm)
4. Operations ........................................................... 5
METER SL. No. : 5. Programming Parameters ................................. 18
MODEL :
The Meter tested as per IEC 62053-21 & has passed following tests at
reference conditions: This instruction manual is applicable for the following models:
CERTIFIED BY:
Signature:
Dated:
For personal & product safety please read the contents of these operation instructions
Front Panel:
carefully before connecting.
Display Three Line Backlit LCD
Check the following after receipt of package:
Digit Height 8mm x 5mm
a. The Packing is in good condition.
Protection Index IP 54
b. The product has not been damaged during transit.
c. The Product reference number confirms to the order placed. Inputs Current:
l Via Current Transformer From 5A to 6000A in multiple of 5 for
General Information with primary -/5A meter or 1A to 1200A in multiple of 1 for
-/1A meter
The emfis Plus is an instrument for measuring and metering electrical values for Three
Phase, LV Electrical Network. It consists of 3 push buttons on the front panel and a l Insulated secondary 5A / 1A (selectable)
bright LCD display. l Current circuit burden < 0.25VA
Please refer to Table 1.0 on page 6 for the parameter details of the model being used. l Starting Current 5 mA (Secondary)
l Overload without CT 7A
The emfis Plus series meter provides optional two relay outputs available for control
l Overload with CT 6500A
function and programming of Upper/Lower Thresholds, Hysteresis, Time Delay and
NO/NC contacts for Voltage, Total Current, Frequency, Power & Demands.
Inputs Voltage:
The emfis Plus series meter provides an optional RS485 serial link.
l Measurement range 120V AC to 300V AC Phase to Neutral
The emfis Plus series meter provides last 6 months billing history. This includes Energy
Parameters (kWh, kVAh, kVArh lag, kVArh lead), Maximum Demand (kW, kVA) with Auxiliary Supply: 240V AC, +30%, 50Hz
date & time stamping, Maximum Parameters (Voltage, Current, Power) and Hour (Run l Burden < 2.5 VA
hours, Power On hours).
Pulse Output:
The emfis Plus series meter provides last 30 days load profile. This includes Energy
Parameters (kWh, kVAh, kVArh lag, kVArh lead) with date stamping l Duration 100ms
l Width 1 Pulse = 1kWh
The emfis Plus series meter provides last 10 event occurrence/restoration for each
Relay 1 and for Relay 2.
The emfis Plus series meter provides data values for Energy, Hour and Maximum
Parameters with date & time stamping for the last reset event.
The Range and Default Value for the Programming Parameter: Installation
PARAMETER RANGE DEFAULT VALUE The emfis Plus can be fitted on the Panel by means of supplied four clips in a 96x96mm
CT Ratio flush mounted case.
Primary 5-6000 in step of 5 for -/5 500
1-1200 in step of 1 for -/1
Secondary -/1A or -/5A -/5A
Relay 1
emfis Plus
Total KW
Total KVA
B 240.0
T
Frequency
KW MD
KVA MD CAL
92mm +0.8mm
-0.0mm
KVA MD
Upper Threshold (I, V, kW, kVA, MD) 0-9999, F,0-999.9 0
86mm
Lower Threshold (I, V, kW, kVA, MD) 0-9999, F,0-999.9 0
Delay 0-9999 0 Sec
emfis Plus
Hysteresis 0-99 5%
96mm
Status NO or NC NO
CAL
96mm
2. Climatic Environment : For optimum operation, it is recommended to use Keys Instruction Display Comment
o o
this equipment between -10 C to +55 C with relative humidity between 20 to 95%.
Scroll up Press Once Digit increment by 1
ps4321
3. Connections:
Unbalanced 3 Phase, 4 Wire Network:
N Prog Press Once To confirm setting
230V ± 30%
P
N
P1 P2 Please remember the password after changing it. In case user forget the password, the user must
L1 S1 S2 send the meter to the factory for factory settings, which can not be done at site.
P1 P2
L2 S1 S2
P1 P2
L3 S2
REAR VIEW
S1 13. Meter Software Version Number:
Fuse
0.5A C NO C NO +RX -RX Keys Instruction Display Comment
P A
N
U
X
hPl Meter Software Version
RLY-1 RLY-2 RS 485
11.xx Number
L1 S1
AUX SUPPLY I1
L2 =230V+30% AC S2
S1
L3 I2
S2
14. Exit from Programming Mode:
N
G I3
S1 Keys Instruction Display Comment
PULSE
OUTPUT S2
S
External Resistance (For 24V Supply use resistance of 6.8KΩ) To exit from programming mode press the programming button once. The meter will exit from the
programming mode only by coming to exit and pressing the button.
Enlarged view s Out Put
of meter back * Note:
plate
1. If new parameter values are not accepted,"Fail" icon will be displayed and the old parameter
G
(-)
values are retained.
FAIL
1. Pulse output is Open Collector Type.
2. External Resistance is to be used between DC Supply point & 'S' for Pulse
Output. 2. If meter is in the programming mode and no scroll button is pressed for 1 minute the meter
3. For 24V DC use an external resistance of 6.8KΩ. automatically comes out of programming mode.
4. The External resistance value will vary depending upon the external voltage
(5-24V) being given by the user.
R - 5.001 Values
Scroll down Press Once Moves Cursor right
Y 5.002 A Measurement Parameter
Phase Indication
Scroll down Press Once Moves Cursor right
CAL
ps1230 Scroll
UP
Scroll
down
Prog
B 240.0
To change energy reset
password
The password to reset the energies can be user defined. The default Energy reset 2. Instantaneous Phase Wise Current
password is "8000" typical example showing how to change the default password to
"1000" is shown below. R 500.0
To change the default password first the factory set default password has to be
entered (i.e.8000).
Y 500.0 A
B 500.0
Prog Press Once To enter old password amp
5. Instantaneous Phase Wise Reactive Power 10. Date & Time Setting:
B 0.99
(-) Sign indicates Leading PF Scroll up Press Seven times Hour digit increments to
02:03:13 Date seventeen
Time17:00
1.00 PF
Scroll up Press Five times Minute digit increments by
29:03:13 Date 02:03:13
Time17:05
Date five
Time 10:30
Scroll down Press Once Day digit start blinking
02:03:13 Date
8. Active, Apparent, Reactive Lag Energy Time17:05
0.1 kVArh
Scroll down Press Once Month digit start blinking
12:03:13 Date
Time17:05
To set NO & NC
2. Instantaneous Phase Wise Current
Press "Prog" key once to change the initial mode as normally connected or normally R 500.0
open.
Y 500.0 A
Prog Press Once To set No
B 500.0
amp
Scroll up Press Once To set NC
3. Instantaneous Phase Wise Active Power
4. Instantaneous Phase wise Phase Apparent Power e). Delay Time Setting:
R 120.0 Keys Instruction Display Comment
Y 120.0 kVA
To set Delay Time
B 120.0
Press "Prog" key once to change the delay for the relay 2. The time is in seconds,
Example of setting the delay of 10 seconds is as follows:
5. Instantaneous Phase Wise Reactive Power Prog Press Once To enter time
0---
R -0.1
Y 0.2 Scroll down Press Once Move cursor right
00--
B 0.1 kVAr
(-) Sign indicates Leading Power
Scroll down Press Once Move cursor right
000-
6. Instantaneous Phase Wise Power Factor
Scroll up Press Once Digit increment by 1
R 0.99 001-
Y -0.99 PF
Scroll down Press Once Move cursor right to right
B 0.99 0010
(-) Sign indicates Leading PF
29:03:13 Date
To Set Relay 2 hysteresis
Time
10:30
Press "Prog" key once to change the Hysteresis. The Hysteresis can be from 0 to 99.
Example of setting Hysteresis of 6% is as follows:
V
To Set Lower Limit for 18.3 kVAh
Voltage Parameter 0.1 kVArh
Press "Prog" key once to change the lower limit of the parameter shown by the
example of voltage parameter.
9. Reactive Lead Energy
Prog Press Once V To enter Voltage limit
0---
V
Scroll down Press Once 00-- Move cursor right
0.1 kVArh
LEAD
Scroll up Press Once V Digit increment by 1
01--
10. Instantaneous Line Voltage
V
Scroll down Press Once
415.0
Move Cursor Right
010- RY
YB 415.0 V
415.0
Scroll up Press eight times V Digit increment by 8
018- BR
V
Scroll down Press Once 0180 Move Cursor Right
11. Total Active, Apparent & Reactive Power
12. Average Active, Apparent & Reactive Power c). Upper Limit Setting:
350 kW
Keys Instruction Display Comment
350 kVA
To set Upper Limit for
0
V Voltage Parameter
kVAr
AVG Press "Prog" key once to change the upper limit of the parameter is shown by the
example of voltage parameter.
13. Maximum Active, Apparent & Reactive Power
Prog Press Once V To enter Voltage Limit
0---
350 kW
350 kVA
Scroll down Press Once V Move cursor right
0 kVAr 00--
MAX
Scroll up Press twice V Digit increment by 2
02--
14. Phase Wise Average Voltage
Scroll down Press Once Move cursor right
R 240 020-
V
Y 240 V
B 240 Scroll up Press five times
025-
V Digit increment by 5
AVG
Note: Whenever we select the new relay parameter the other relay parameters get their default value.
Hr
To set NO & NC
21. Maximum Demand in kW with Date & Time Press "Prog" key once to change the initial mode as normally connected or normally
open.
350.2 kW
MD
Prog Press Once To set NO
25:03:13 Date
Scroll up Press Once To set NC
Time 10:30
22. Maximum Demand in kVA with Date & Time Prog Press Once To confirm setting
MD
350.5 kVA 9. Relay 2 Parameter Setting:
a). Mode Setting:
25:03:13 Date Keys Instruction Display Comment
240.0 V
Scroll up Press Once Relay 2 mode setting
0.99
Press "Prog" key once to change the Hysteresis. The Hysteresis can be from 0 to 99.
27. Total Harmonic Distortion in Phase Current
Example of setting Hysteresis of 6% is as follows:
28. Total Harmonic Distortion in Line Voltage Press "Prog" key once to change the lower limit of the parameter shown by the
example of voltage parameter.
RY 17.3
Prog Press Once To enter Voltage Limit
17.2
V
YB 0---
BR 17.5
THD Scroll down Press Once V Move cursor right
%
00--
V
Scroll up Press eight times Digit increment by 8
018-
Display LCD Check at Power 'ON' :
*Note: The upper limit can not be less than the lower limit except the case when
upper limit is 0.
Press "Prog" key once to change the delay for the relay 1. The time is in seconds
example of setting the delay of 10 seconds is as follows:
Press "Prog" key once to change the upper limit of the parameter is shown by the Even during power Off / On condition this scroll Lock will be enabled.
example of voltage parameter.
To disable the scroll lock, press any of the scroll keys for 5 second, the scroll is now unlocked and the
display shows:
Prog Press Once V
To enter Voltage limit
0---
V
Scroll down Press Once 00-- Move cursor right
R
Scroll down Press Once V Move cursor right
020- Y A
B
Scroll up Press five times Digit increment by 5
V amp
025-
Run Hours is the Cumulative time the meter has run on load (the least count is 10
minutes). The Threshold for Run Hour is when the secondary current in any of the
d). Lower Limit Setting: phase is greater than 10mA.
Keys Instruction Display Comment
Power ON Hours is the cumulative time the meter is powered up using the auxiliary
supply (The least count is 10 minutes).
To Set Lower Limit for
Voltage Parameter
S.No. Programming Parameters Basic* Control* Prog Press Once To set current parameter
3 MD Integration Time
4 Reset Maximum Parameters
5 Hour-Reset Scroll up Press Once To set Active Power
6 Energy Reset Parameter
7 Relay 1 Parameter Setting
8 Relay 2 Parameter Setting Scroll up Press Once To set Apparent Power
Parameter
9 Date & Time Setting
10 Change Energy Reset Password
11 Change Programming Password Scroll up Press Once To set Frequency
Parameter
Table 1.1
* Separate manual for RS485 Models.
MD
Scroll up Press Once To set Active Power MD
Programming Mode: Parameter
To access/view the programming mode:
Keys Instruction Display Comment Scroll up Press Once MD To set Apparent Power MD
parameter
PS
Scroll down Press Once Moves cursor right
10-- V To set Upper Limit for
Voltage Parameter
PS
Scroll up Press Twice Digit increment by 2
12--
Press "Prog" key once to change the mode of the relay. The mode can enable or Finally press 'Prog' key user will enter into the programming mode. Please refer to
disable. table 1.1 to match the programming parameters. The typical screen shots of
programming parameters are shown below.
Prog Press Once Relay 1 mode setting
To reset the meter run hours & Power on hours values press "Prog" Button once.
Scroll down Press Once To set baud rate Prog Press Once Meter Run Hours & Power
on hour reset successfully
Scroll down Press Once To set Relay 1 delay in Scroll down Press Once Enter the Password
seconds
Scroll down Press Once To set Relay 1 Hysteresis Scroll up Press eight times Digit increments by 8
in % PS8---
Scroll down Press Once To select Relay 1 NO & NC Scroll down Press Once Moves cursor right
PS80--
Scroll down Press Once To select Relay 2 Mode Scroll down Press Once Moves cursor right
PS800-
4. To Change MD Integration Time for MD Parameters (Maximum Keys Instruction Display Comment
Demand Time):
Keys Instruction Display Comment Scroll down Press Once To select Relay
2 Parameters
MD To change MD Integration
30 Time for MD Parameters
kVA
Scroll down Press Once To set Relay 2 Upper Limit
MD
Scroll Up Press Once Change MD Integration
15 Scroll down Press Once To set Relay 2 Hysteresis
Time in %
Prog Press Once To confirm Setting Scroll down Press Once To select Relay 2 NO & NC
To reset the all Maximum Parameters & Maximum Demand values press "Prog" Scroll down Press Once To change Programming
Mode Password
Button.
Sn
12 Displays the Serial Number
Prog Press Once To confirm setting
040080 of the Meter
2. Set CT Ratio:
The default CT ratio is 500/5. To change the CT ratio press the “Prog” key once to 3. To change Integration Time for Average Parameters
enter into the programming mode. The CT secondary can be selected as 5 or 1 & the (Average Time):
CT primary can be programmed from 5 to 6000 in multiples of 5 if the CT secondary
Keys Instruction Display Comment
is 5A and 1 to 1200 in multiples of 1 if the CT secondary is 1A.
Typical example showing how to change the CT ratio to 5000/5. To change Integration Time
for Average Parameters
(Average Time)
Keys Instruction Display Comment AVG
Setting CT Ratio The default average integration time is 5 minutes. To change the average integration
time press "Prog" button once to enter into the programming mode. The average
integration time can be set between 1 to 60 minutes in interval of 1 minute. Typical
Press "Prog" button to set secondary. example showing how to change the average time to 15 minutes.