emfis Plus

Operation and instruction manual for emfis Plus series

emfis Plus

R 240.0
Y 240.0 V

B 240.0
T

CAL

Scroll Scroll Prog


Up Down

GCPK6EMFISPLUS-R2

HPL Electric & Power Pvt. Ltd.


1/21, Atma Ram Mansion, Asaf Ali Road, New Delhi-110002
Phone : 23234411, 23234811, 23236811; Fax : 23232639
E-Mail : hpl@hplindia.com, Website : www.hplindia.com
This document is not contractual, HPL Electric & Power Pvt. Ltd. reserves the
right to modify features without prior notice in view of continued improvements. HPL Electric & Power Pvt. Ltd.
emfis Plus emfis Plus

HPL ELECTRIC & POWER PVT. LTD. Contents

TEST CERTIFICATE 1. Preliminary Operations ........................................ 2

2. General Information............................................. 2
ITEM : LT ac, Three Phase, Four Wire Panel Mounted Static 3. Installation............................................................ 3
kWh Meter with LCD Display (96mm x 96mm)
4. Operations ........................................................... 5
METER SL. No. : 5. Programming Parameters ................................. 18

RATING : -/5A, 3x240V, 50Hz 6. Programming Mode ........................................... 18

7. Technical Specifications .................................... 43


METER : 16000 Impulses per kWh for -/5A
CONSTANT 8. Test Certificate................................................... 44

MODEL :

The Meter tested as per IEC 62053-21 & has passed following tests at
reference conditions: This instruction manual is applicable for the following models:

TEST RESULT S.No. Type Model Number


01 No-Load Conditions Passed
1 emfis Plus Basic NEMFPCT2EMFA1
02 AC Voltage Test Passed
2 emfis Plus Basic + RS485* NEMFPCT2EMFA2
03 Insulation Resistance Test Passed
3 emfis Plus Basic + Control NEMFPCT2EMFA3
04 Starting Test Passed 4 emfis Plus Basic + Control + RS485* NEMFPCT2EMFA4
05 Meter Accuracy Test Passed
Note: 1. Please check the correct reference number with the order.
2. MODBUS Address mapping given in separate manual.
3. * Please Refer separate manual for RS485 Models.

CERTIFIED BY:
Signature:
Dated:

Operation and Instruction Manual 44 Operation and Instruction Manual 1


emfis Plus emfis Plus

Caution ! Technical Specifications


This equipment must be mounted only by professional. The manufacturer shall not
be held responsible for failure to comply with the instructions in this manual. Enclosure:
Dimensions 96mm x 96mm x 86mm
Preliminary Operations Weight < 400gms.

For personal & product safety please read the contents of these operation instructions
Front Panel:
carefully before connecting.
Display Three Line Backlit LCD
Check the following after receipt of package:
Digit Height 8mm x 5mm
a. The Packing is in good condition.
Protection Index IP 54
b. The product has not been damaged during transit.
c. The Product reference number confirms to the order placed. Inputs Current:
l Via Current Transformer From 5A to 6000A in multiple of 5 for
General Information with primary -/5A meter or 1A to 1200A in multiple of 1 for
-/1A meter
The emfis Plus is an instrument for measuring and metering electrical values for Three
Phase, LV Electrical Network. It consists of 3 push buttons on the front panel and a l Insulated secondary 5A / 1A (selectable)
bright LCD display. l Current circuit burden < 0.25VA

Please refer to Table 1.0 on page 6 for the parameter details of the model being used. l Starting Current 5 mA (Secondary)
l Overload without CT 7A
The emfis Plus series meter provides optional two relay outputs available for control
l Overload with CT 6500A
function and programming of Upper/Lower Thresholds, Hysteresis, Time Delay and
NO/NC contacts for Voltage, Total Current, Frequency, Power & Demands.
Inputs Voltage:
The emfis Plus series meter provides an optional RS485 serial link.
l Measurement range 120V AC to 300V AC Phase to Neutral
The emfis Plus series meter provides last 6 months billing history. This includes Energy
Parameters (kWh, kVAh, kVArh lag, kVArh lead), Maximum Demand (kW, kVA) with Auxiliary Supply: 240V AC, +30%, 50Hz
date & time stamping, Maximum Parameters (Voltage, Current, Power) and Hour (Run l Burden < 2.5 VA
hours, Power On hours).
Pulse Output:
The emfis Plus series meter provides last 30 days load profile. This includes Energy
Parameters (kWh, kVAh, kVArh lag, kVArh lead) with date stamping l Duration 100ms
l Width 1 Pulse = 1kWh
The emfis Plus series meter provides last 10 event occurrence/restoration for each
Relay 1 and for Relay 2.

The emfis Plus series meter provides data values for Energy, Hour and Maximum
Parameters with date & time stamping for the last reset event.

Operation and Instruction Manual 2 Operation and Instruction Manual 43


emfis Plus emfis Plus

The Range and Default Value for the Programming Parameter: Installation
PARAMETER RANGE DEFAULT VALUE The emfis Plus can be fitted on the Panel by means of supplied four clips in a 96x96mm
CT Ratio flush mounted case.
Primary 5-6000 in step of 5 for -/5 500
1-1200 in step of 1 for -/1
Secondary -/1A or -/5A -/5A
Relay 1
emfis Plus

Mode Disable,Enable Disable R 240.0


Parameter Current
Voltage
Current Y 240.0 V

Total KW
Total KVA
B 240.0
T
Frequency
KW MD
KVA MD CAL

Upper Threshold (I, V, kW, kVA, MD) 0-9999, F,0-999.9 0


Scroll Scroll Prog
Lower Threshold (I, V, kW, kVA, MD) 0-9999, F,0-999.9 0 Up Down

Delay 0-9999 0 Sec


Hysteresis 0-99 5%
Status NO or NC NO
Relay 2
1. Mechanical Dimension : To install the device properly the cutout diagram
Mode Disable, Enable Disable
given below must be followed.
Parameter Current Total KVA
Voltage
Total KW +0.8mm
92mm -0.0mm
Total KVA
Frequency
KW MD

92mm +0.8mm
-0.0mm
KVA MD
Upper Threshold (I, V, kW, kVA, MD) 0-9999, F,0-999.9 0
86mm
Lower Threshold (I, V, kW, kVA, MD) 0-9999, F,0-999.9 0
Delay 0-9999 0 Sec
emfis Plus

Hysteresis 0-99 5%
96mm
Status NO or NC NO
CAL

Scroll Scroll Prog


Up Down

96mm

Operation and Instruction Manual 42 Operation and Instruction Manual 3


emfis Plus emfis Plus

2. Climatic Environment : For optimum operation, it is recommended to use Keys Instruction Display Comment
o o
this equipment between -10 C to +55 C with relative humidity between 20 to 95%.
Scroll up Press Once Digit increment by 1
ps4321
3. Connections:
Unbalanced 3 Phase, 4 Wire Network:
N Prog Press Once To confirm setting
230V ± 30%
P
N
P1 P2 Please remember the password after changing it. In case user forget the password, the user must
L1 S1 S2 send the meter to the factory for factory settings, which can not be done at site.
P1 P2
L2 S1 S2
P1 P2
L3 S2
REAR VIEW
S1 13. Meter Software Version Number:
Fuse
0.5A C NO C NO +RX -RX Keys Instruction Display Comment
P A
N
U
X
hPl Meter Software Version
RLY-1 RLY-2 RS 485
11.xx Number
L1 S1
AUX SUPPLY I1
L2 =230V+30% AC S2

S1
L3 I2
S2
14. Exit from Programming Mode:
N

G I3
S1 Keys Instruction Display Comment
PULSE
OUTPUT S2
S

Prog Press Once Exit from programming


4. Pulse Output: Mode
(+) DC Supply (5V-24V)

External Resistance (For 24V Supply use resistance of 6.8KΩ) To exit from programming mode press the programming button once. The meter will exit from the
programming mode only by coming to exit and pressing the button.
Enlarged view s Out Put
of meter back * Note:
plate
1. If new parameter values are not accepted,"Fail" icon will be displayed and the old parameter
G
(-)
values are retained.

FAIL
1. Pulse output is Open Collector Type.
2. External Resistance is to be used between DC Supply point & 'S' for Pulse
Output. 2. If meter is in the programming mode and no scroll button is pressed for 1 minute the meter
3. For 24V DC use an external resistance of 6.8KΩ. automatically comes out of programming mode.
4. The External resistance value will vary depending upon the external voltage
(5-24V) being given by the user.

Operation and Instruction Manual 4 Operation and Instruction Manual 41


emfis Plus emfis Plus

Scroll down Press Once Moves cursor right Operations


ps10--
1. Front Panel View:
Scroll up Press Twice Digit increment by 2
ps12-- emfis Plus

R - 5.001 Values
Scroll down Press Once Moves Cursor right
Y 5.002 A Measurement Parameter

Scroll up Press Thrice Digit increment by 3 B 4.999


AMP

ps123- Reverse Indication

Phase Indication
Scroll down Press Once Moves Cursor right
CAL

ps1230 Scroll
UP
Scroll
down
Prog

Scroll up Press Four times Digit increment by 4


ps1234 2. Display Parameter:
Display parameters for the emfis Plus type panel meters are given below. There
Prog Press Once Old password is accepted. are two modes of display:
ps0---
Enter new password
Auto Scroll Mode: The parameters in this mode will scroll automatically one after
the other.
Scroll up Press Four times Digit increment by 4
ps4---
Push Button Mode: The parameters in this mode will be displayed by pressing '▲'
or '▼' key once. The parameters can be viewed in the following modes:
Scroll down Press Once ps40-- Moves Cursor right
a. Forward fast select mode: Press '▲' to move to next parameter immediately.
b. Backward fast select mode: Press '▼' to move to previous parameter
immediately.
Scroll up Press thrice ps43-- Digit increment by 3
c. Scroll Mode: The parameter in this mode will auto scroll one after the other
without pressing any push button.
Scroll down Press Once ps430- Moves Cursor right

Scroll up Press twice ps432- Digit increment by 2

Scroll down Press Once ps4320 Moves Cursor right

Operation and Instruction Manual 40 Operation and Instruction Manual 5


emfis Plus emfis Plus
The screen shots for auto scroll/push button mode are same for all emfis Plus
series. The display parameters for the emfis Plus series are given below: Now enter new password, for example if the new energy password to be set is
S.No. DISPLAY PARAMETERS "1000", then proceed as follows:
AUTO SCROLL MODE
1 Inst. Phase wise Phase – Neutral Voltage Scroll up Press Once Digit increments by1
2 Inst. Phase wise Current (Amp)
3 Inst. Phase wise Active Power (kW)
4 Inst. Phase wise Apparent Power (kVA) Scroll down Press Once Moves cursor right
5 Inst. Phase wise Reactive Power (kVAr)
6 Inst. Phase wise Power Factor (PF)
7 Inst. Frequency (Hz), System PF, Real Date & Time
8 Active, Apparent, Reactive Lag Energy
9 Reactive Lead Energy
Scroll down Press Once Moves cursor right
PUSH BUTTON MODE
1 Inst. Phase wise Phase – Neutral Voltage
2 Inst. Phase wise Current (Amp)
3 Inst. Phase wise Active Power (kW)
Scroll down Press Once Moves cursor right
4 Inst. Phase wise Apparent Power (kVA)
5 Inst. Phase wise Reactive Power (kVAr)
6 Inst. Phase wise Power Factor (PF)
Prog Press Once To confirm setting
7 Inst. Frequency (Hz), System PF, Real Date & Time
8 Active, Apparent, Reactive Lag Energy
9 Reactive Lead Energy Please remember the password after changing it. In case user forget the password, the user must
10 Inst. line Voltage (volts) send the meter to the factory for factory settings, which can not be done at site.
11 Total Active, Apparent & Reactive Power
12 Avg. Active, Apparent & Reactive Power
12. Change Programming Mode Password:
13 Max. Active, Apparent & Reactive Power
14 Phase wise Average Voltage (Volts) Keys Instruction Display Comment
15 Phase wise Maximum Voltage (Volts)
16 Phase wise Average Current (Amp) To change programming
17 Phase wise Maximum Current (Amp)
mode password
18 Total Current (Amp)
19 Meter Run Hour(Hr) The password to enter into the programming mode can be changed. The default
20 Meter Power On Hour (Hr) password to enter into the programming mode is "1234". Typical example showing
21 kW MD with Date & Time how to change the default password to "4321" is shown below.
22 kVA MD with Date & Time
To change the default password first the factory set default password has to be
23 R Phase – kW, Current, Voltage & PF entered (i.e.1234)
24 Y Phase – kW, Current, Voltage & PF
25 B Phase – kW, Current, Voltage & PF
Prog Press Once Enter old password.
26 Total Harmonic Distortion in Phase Voltage (%)
27 Total Harmonic Distortion in Phase Current (%)
28 Total Harmonic Distortion in Line Voltage (%)
29 CT Ratio Scroll up Press Once Digit Increment by 1
Table 1.0

Operation and Instruction Manual 6 Operation and Instruction Manual 39


emfis Plus emfis Plus

Typical Screen shots for emfis Plus Series:


Scroll down Press Once Moves cursor right and year The sequence of display parameters for emfis plus series are as follows:
12:04:13 Date digit start blinking
Time17:05
emfis Plus Screen Shots:
Prog Press Once To confirm setting a. Auto Scroll Mode:
1. Instantaneous Phase wise Phase-Neutral Voltage

11. Change Energy Reset Password:


R 240.0
Keys Instruction Display Comment
Y 240.0 V

B 240.0
To change energy reset
password

The password to reset the energies can be user defined. The default Energy reset 2. Instantaneous Phase Wise Current
password is "8000" typical example showing how to change the default password to
"1000" is shown below. R 500.0
To change the default password first the factory set default password has to be
entered (i.e.8000).
Y 500.0 A
B 500.0
Prog Press Once To enter old password amp

3. Instantaneous Phase Wise Active Power


Scroll up Press eight times Digit increments by 8
R 119.9 kW
Y 119.8
119.9
Scroll down Press Once Moves cursor right
B

Scroll down Press Once Moves cursor right


4. Instantaneous Phase wise Apparent Power

Scroll down Press Once Moves cursor right R 120.0


Y 120.0 kVA

Prog Press Once Old password is accepted B 120.0


Enter new password

Operation and Instruction Manual 38 Operation and Instruction Manual 7


emfis Plus emfis Plus

5. Instantaneous Phase Wise Reactive Power 10. Date & Time Setting:

R -0.1 Keys Instruction Display Comment


Date & Time is displayed in
Y 0.2 the following format
02:03:13
0.1
Date: DD:MM:YY
B kVAr 10:00
Date
Time Time: HH:MM
(-) Sign indicates Leading Power
To change date & time press "Prog" button once. The default date & time will be
shown as set from the factory. Typical example showing how to set the date to 12th
6. Instantaneous Phase Wise Power Factor April 2013 and time to 17.05 Hours is shown below.

R 0.99 Prog Press Once Hour digit start blinking


02:03:13
Y -0.99 PF Time10:00
Date

B 0.99
(-) Sign indicates Leading PF Scroll up Press Seven times Hour digit increments to
02:03:13 Date seventeen
Time17:00

7. Instantaneous Frequency, System PF, Date & Time


Scroll down Press Once Minute digit start blinking
02:03:13
50.00
Date
HZ Time17:00

1.00 PF
Scroll up Press Five times Minute digit increments by
29:03:13 Date 02:03:13
Time17:05
Date five

Time 10:30
Scroll down Press Once Day digit start blinking
02:03:13 Date
8. Active, Apparent, Reactive Lag Energy Time17:05

18.2 kWh Scroll up Press ten times Date digit increments to


12:03:13
18.3 twelve
Date
kVAh Time17:05

0.1 kVArh
Scroll down Press Once Month digit start blinking
12:03:13 Date
Time17:05

Scroll up Press Once Month digit increments to


12:04:13 Date four
Time17:05

Operation and Instruction Manual 8 Operation and Instruction Manual 37


emfis Plus emfis Plus

Keys Instruction Display Comment 9. Reactive Lead Energy

Prog Press Once To set value


0-

Scroll down Press Once Move cursor right


0.1 kVArh
00 LEAD

Scroll up Press Six times Digit increment by 6


06 b. Push Button Mode:

1. Instantaneous Phase Wise Phase - Neutral Voltage


Prog Press Once To confirm setting
R 240.0
Y 240.0 V
g). NO & NC Setting:
B 240.0
Keys Instruction Display Comment

To set NO & NC
2. Instantaneous Phase Wise Current

Press "Prog" key once to change the initial mode as normally connected or normally R 500.0
open.
Y 500.0 A
Prog Press Once To set No
B 500.0
amp
Scroll up Press Once To set NC
3. Instantaneous Phase Wise Active Power

Prog Press Once To confirm setting


R 119.9 kW
Y 119.8
B 119.9

Operation and Instruction Manual 36 Operation and Instruction Manual 9


emfis Plus emfis Plus

4. Instantaneous Phase wise Phase Apparent Power e). Delay Time Setting:
R 120.0 Keys Instruction Display Comment

Y 120.0 kVA
To set Delay Time
B 120.0
Press "Prog" key once to change the delay for the relay 2. The time is in seconds,
Example of setting the delay of 10 seconds is as follows:

5. Instantaneous Phase Wise Reactive Power Prog Press Once To enter time
0---
R -0.1
Y 0.2 Scroll down Press Once Move cursor right
00--
B 0.1 kVAr
(-) Sign indicates Leading Power
Scroll down Press Once Move cursor right

000-
6. Instantaneous Phase Wise Power Factor
Scroll up Press Once Digit increment by 1

R 0.99 001-
Y -0.99 PF
Scroll down Press Once Move cursor right to right
B 0.99 0010
(-) Sign indicates Leading PF

Prog Press Once To confirm setting

7. Instantaneous Frequency, System PF, Date & Time

50.00 HZ f). Hysteresis Setting:


1.00 PF Keys Instruction Display Comment

29:03:13 Date
To Set Relay 2 hysteresis
Time
10:30
Press "Prog" key once to change the Hysteresis. The Hysteresis can be from 0 to 99.
Example of setting Hysteresis of 6% is as follows:

Operation and Instruction Manual 10 Operation and Instruction Manual 35


emfis Plus emfis Plus

d). Lower Limit Setting: 8. Active, Apparent, Reactive Lag Energy

Keys Instruction Display Comment


18.2 kWh

V
To Set Lower Limit for 18.3 kVAh
Voltage Parameter 0.1 kVArh

Press "Prog" key once to change the lower limit of the parameter shown by the
example of voltage parameter.
9. Reactive Lead Energy
Prog Press Once V To enter Voltage limit
0---

V
Scroll down Press Once 00-- Move cursor right
0.1 kVArh
LEAD
Scroll up Press Once V Digit increment by 1
01--
10. Instantaneous Line Voltage
V
Scroll down Press Once
415.0
Move Cursor Right
010- RY

YB 415.0 V

415.0
Scroll up Press eight times V Digit increment by 8
018- BR

V
Scroll down Press Once 0180 Move Cursor Right
11. Total Active, Apparent & Reactive Power

Prog Press Once To confirm setting 359.8 kW


359.9 kVA
Note: The upper limit can not be less than the lower limit except the case when upper limit is 0. 0.1 kVAr
Total

Operation and Instruction Manual 34 Operation and Instruction Manual 11


emfis Plus emfis Plus

12. Average Active, Apparent & Reactive Power c). Upper Limit Setting:

350 kW
Keys Instruction Display Comment

350 kVA
To set Upper Limit for
0
V Voltage Parameter
kVAr

AVG Press "Prog" key once to change the upper limit of the parameter is shown by the
example of voltage parameter.
13. Maximum Active, Apparent & Reactive Power
Prog Press Once V To enter Voltage Limit
0---
350 kW
350 kVA
Scroll down Press Once V Move cursor right
0 kVAr 00--
MAX
Scroll up Press twice V Digit increment by 2
02--
14. Phase Wise Average Voltage
Scroll down Press Once Move cursor right
R 240 020-
V

Y 240 V
B 240 Scroll up Press five times
025-
V Digit increment by 5

AVG

Scroll down Press Once V Move cursor right


15. Phase Wise Maximum Voltage 0250

R 240 Prog Press Once To confirm setting


Y 240 V
B 240
MAX

Operation and Instruction Manual 12 Operation and Instruction Manual 33


emfis Plus emfis Plus

b). Parameter Setting: 16. Phase Wise Average Current


The Parameters are Frequency, Active Power MD, Apparent Power MD, Current,
Voltage, Active Power, Apparent Power. R 500
*Note: The Frequency is in Hz, Current in Amp, Voltage in Volt, Active Power & Y 500 A
Active Power MD in kW, Apparent Power & Apparent Power MD in kVA.
B 500
Keys Instruction Display Comment
AVG
To set Relay 2 Parameter
17. Phase Wise Maximum Current

Press "Prog" key once to change the parameters. R 500


Prog Press Once To set Frequency Y 500 A
Parameter
B 500
MAX
MD
Scroll up Press Once To set Active Power MD
Parameter
18. Total Current
MD
Scroll up Press Once To set Apparent Power MD
Parameter
1500 A
Scroll up Press Once To set Current Parameter
Total

Scroll up Press Once To set Voltage Parameter


19. Meter Run Hours

Scroll up Press Once To set Active Power


Parameter
0.5
Prog Press Once To confirm setting
Hr

Note: Whenever we select the new relay parameter the other relay parameters get their default value.

Operation and Instruction Manual 32 Operation and Instruction Manual 13


emfis Plus emfis plus

20. Meter Power on Hours


Prog Press Once To confirm setting

5.1 g). NO & NC Setting:


Keys Instruction Display Comment

Hr
To set NO & NC

21. Maximum Demand in kW with Date & Time Press "Prog" key once to change the initial mode as normally connected or normally
open.
350.2 kW
MD
Prog Press Once To set NO

25:03:13 Date
Scroll up Press Once To set NC
Time 10:30

22. Maximum Demand in kVA with Date & Time Prog Press Once To confirm setting

MD
350.5 kVA 9. Relay 2 Parameter Setting:
a). Mode Setting:
25:03:13 Date Keys Instruction Display Comment

Time 10:30 Relay 2 Default Mode

23. R Phase Active Power, Current, Voltage & Power Factor


Press "Prog" key once to change the mode of the relay. The mode can enable or disable.
R 120.0 kW
Prog Press Once Relay 2 default Mode
500.0 A

240.0 V
Scroll up Press Once Relay 2 mode setting
0.99

Prog Press Once To confirm setting

Operation and Instruction Manual 14 Operation and Instruction Manual 31


emfis Plus emfis Plus

24. Y Phase Active Power, Current, Voltage & Power Factor


Prog Press Once To enter time
0---
120.0 kW

Scroll down Press Once Move cursor right


Y 500.0 A
00-- 240.0 V
0.99
Scroll down Press Once Move cursor right
000-
25. B Phase Active Power, Current, Voltage & Power Factor
Scroll up Press Once
120.0
Digit increment by 1
kW
001-
500.0 A
Scroll down Press Once Move cursor to the Right
B 240.0 V
0010
0.99

Prog Press Once To confirm setting


26. Total Harmonic Distortion in Phase - Neutral Voltage

f). Hysteresis Setting:


R 10.2
Keys Instruction Display Comment
Y 10.2
B 10.2
To set Relay 1 hysteresis THD %

Press "Prog" key once to change the Hysteresis. The Hysteresis can be from 0 to 99.
27. Total Harmonic Distortion in Phase Current
Example of setting Hysteresis of 6% is as follows:

Prog Press Once To set value R 11.2


0- Y 11.3
B 11.1
Scroll down Press Once Move cursor right
THD
00 amp %

Scroll up Press Six times Digit increment by 6


06

Operation and Instruction Manual 30 Operation and Instruction Manual 15


emfis Plus emfis Plus

28. Total Harmonic Distortion in Line Voltage Press "Prog" key once to change the lower limit of the parameter shown by the
example of voltage parameter.
RY 17.3
Prog Press Once To enter Voltage Limit
17.2
V
YB 0---
BR 17.5
THD Scroll down Press Once V Move cursor right
%
00--

29. CT Ratio Scroll up Press Once Digit increment by 1


V
01--

0500-5 Scroll down Press Once V Move Cursor Right


010-

V
Scroll up Press eight times Digit increment by 8
018-
Display LCD Check at Power 'ON' :

Scroll down Press Once V Move cursor right


0180

Prog Press Once To confirm setting

*Note: The upper limit can not be less than the lower limit except the case when
upper limit is 0.

Scroll Lock / Unlock Feature :


e). Delay Time Setting:
For some application where you require monitoring a particular parameter, scroll lock function
has been provided. Keys Instruction Display Comment
To activate the “Scroll Lock” function, press & hold any of the scroll keys for 5 seconds, the
scroll is now locked and the display shows: To set Delay Time

Press "Prog" key once to change the delay for the relay 1. The time is in seconds
example of setting the delay of 10 seconds is as follows:

Operation and Instruction Manual 16 Operation and Instruction Manual 29


emfis Plus emfis Plus

Press "Prog" key once to change the upper limit of the parameter is shown by the Even during power Off / On condition this scroll Lock will be enabled.
example of voltage parameter.
To disable the scroll lock, press any of the scroll keys for 5 second, the scroll is now unlocked and the
display shows:
Prog Press Once V
To enter Voltage limit
0---

V
Scroll down Press Once 00-- Move cursor right

Scroll up Press twice V Digit increment by 2


02-- If the secondary current exceeds 6500A in any phase, the meter displays overload as shown below:

R
Scroll down Press Once V Move cursor right
020- Y A

B
Scroll up Press five times Digit increment by 5
V amp
025-

Scroll down Press Once V Move cursor right Note:


0250
This Model of Emfis Plus has been provided with
1. Run Hours
Prog Press Once To confirm setting
2. Power ON Hours

Run Hours is the Cumulative time the meter has run on load (the least count is 10
minutes). The Threshold for Run Hour is when the secondary current in any of the
d). Lower Limit Setting: phase is greater than 10mA.
Keys Instruction Display Comment
Power ON Hours is the cumulative time the meter is powered up using the auxiliary
supply (The least count is 10 minutes).
To Set Lower Limit for
Voltage Parameter

Operation and Instruction Manual 28 Operation and Instruction Manual 17


emfis Plus emfis Plus

Programming Parameters: Press "Prog" key once to change the parameters.


The programming parameters for emfis Plus are given below:

S.No. Programming Parameters Basic* Control* Prog Press Once To set current parameter

1 CT Ratio (Primary & Secondary)


2 Integration Time for Average parameters
(Average Time) Scroll up Press Once To set voltage parameter

3 MD Integration Time
4 Reset Maximum Parameters
5 Hour-Reset Scroll up Press Once To set Active Power
6 Energy Reset Parameter
7 Relay 1 Parameter Setting
8 Relay 2 Parameter Setting Scroll up Press Once To set Apparent Power
Parameter
9 Date & Time Setting
10 Change Energy Reset Password
11 Change Programming Password Scroll up Press Once To set Frequency
Parameter
Table 1.1
* Separate manual for RS485 Models.
MD
Scroll up Press Once To set Active Power MD
Programming Mode: Parameter
To access/view the programming mode:

Keys Instruction Display Comment Scroll up Press Once MD To set Apparent Power MD
parameter

Prog Press once PS Enter programming


0--- mode password
Prog Press Once To confirm setting

Enter the password (default password is 1234) to access the programming


parameters. A typical example of how to enter the default password is given below. Note: Whenever we select the new relay parameter the other relay parameters get their default value.
Keys Instruction Display Comment
PS c). Upper Limit Setting:
Scroll up Press Once 1--- Digit increment by 1
Keys Instruction Display Comment

PS
Scroll down Press Once Moves cursor right
10-- V To set Upper Limit for
Voltage Parameter
PS
Scroll up Press Twice Digit increment by 2
12--

Operation and Instruction Manual 18 Operation and Instruction Manual 27


emfis Plus emfis Plus

Keys Instruction Display Comment


Scroll down Press Once Moves cursor right
PS8000 PS
Scroll down Press Once 120- Moves cursor right

Prog Press Once Energy reset successfully


PS
Scroll up Press Thrice 123- Digit increment by 3

8. Relay 1 Parameter Setting:


a). Mode Setting: PS
Keys Instruction Display Comment
Scroll down Press Once 1230 Moves cursor right

The Default Mode


PS
Scroll up Press Four Times 1234 Digit increment by 4

Press "Prog" key once to change the mode of the relay. The mode can enable or Finally press 'Prog' key user will enter into the programming mode. Please refer to
disable. table 1.1 to match the programming parameters. The typical screen shots of
programming parameters are shown below.
Prog Press Once Relay 1 mode setting

Prog Press Once Sn Meter Serial No.


12
040074
Scroll up Press Once Relay 1 mode setting
Scroll down Press Once CT Primary and Secondary
0500-5 Setting

Prog Press Once To confirm setting


Scroll down Press Once To Change Integration Time
for average parameters
AVG (Average Time)
b). Parameter Setting:
Scroll down Press Once MD To Change the MD
The Parameters are Frequency, Active Power MD, Apparent Power MD, Current, 30 Integration Time
Voltage, Active Power, Apparent Power. (Maximum Demand)
*Note: The Frequency is in Hz, Current in Amp, Voltage in Volt, Active Power &
Active Power MD in kW, Apparent Power & Apparent Power MD in kVA. Scroll down Press Once To reset all Maximum
Parameters
Keys Instruction Display Comment

Scroll down Press Once To reset meter run hours &


To set Relay 1 parameter Power on Hours
Hr

Operation and Instruction Manual 26 Operation and Instruction Manual 19


emfis Plus emfis Plus

Keys Instruction Display Comment 6. Hour Reset:


Keys Instruction Display Comment
Scroll down Press Once To reset energies
To reset Meter Run Hours &
Power on Hours
Hr

Scroll down Press Once To set slave address

To reset the meter run hours & Power on hours values press "Prog" Button once.

Scroll down Press Once To set baud rate Prog Press Once Meter Run Hours & Power
on hour reset successfully

Scroll down Press Once To set Relay 1 Mode


7. Energy Reset:
Keys Instruction Display Comment
Scroll down Press Once To set Relay 1 Parameters
To reset all Energies

Scroll down Press Once A To set Relay 1 Upper Limit


Press "Prog" key once to reset the energies. This operation is password protected.
The default password is 8000. To reset the energies, enter the default password as
given below.
Scroll down Press Once To set Relay 1 Lower Limit
Keys Instruction Display Comment

Scroll down Press Once To set Relay 1 delay in Scroll down Press Once Enter the Password
seconds

Scroll down Press Once To set Relay 1 Hysteresis Scroll up Press eight times Digit increments by 8
in % PS8---

Scroll down Press Once To select Relay 1 NO & NC Scroll down Press Once Moves cursor right
PS80--

Scroll down Press Once To select Relay 2 Mode Scroll down Press Once Moves cursor right
PS800-

Operation and Instruction Manual 20 Operation and Instruction Manual 25


emfis Plus emfis Plus

4. To Change MD Integration Time for MD Parameters (Maximum Keys Instruction Display Comment
Demand Time):
Keys Instruction Display Comment Scroll down Press Once To select Relay
2 Parameters
MD To change MD Integration
30 Time for MD Parameters
kVA
Scroll down Press Once To set Relay 2 Upper Limit

The Default MD Integration Time is 30 Min. To Change the MD Integration press


"Prog" button once to enter into the programming mode. The MD Integration can be Scroll down Press Once kVA To set Relay 2 Lower Limit
15 & 30 only.
MD
Prog Press Once Set MD Integration Time
30 Scroll down Press Once To set Relay 2 Delay in
Seconds

MD
Scroll Up Press Once Change MD Integration
15 Scroll down Press Once To set Relay 2 Hysteresis
Time in %

Prog Press Once To confirm Setting Scroll down Press Once To select Relay 2 NO & NC

5. Reset MD Parameter: Scroll down Press Once To set RTC


Keys Instruction Display Comment
02:07:12 Date
Time 10:00
To reset all Maximum
Parameters & Maximum Scroll down Press Once To change Energy Reset
Demand Password

To reset the all Maximum Parameters & Maximum Demand values press "Prog" Scroll down Press Once To change Programming
Mode Password
Button.

Prog Press Once To confirm setting hPl


Scroll down Press Once 11.xx To see Version Number

Scroll down Press Once To exit from Programming


Mode

Operation and Instruction Manual 24 Operation and Instruction Manual 21


emfis Plus emfis Plus

Programming Parameter: Keys Instruction Display Comment


1. Serial Number:
Scroll down Press Once Moves cursor right
Keys Instruction Display Comment 5000-5

Sn
12 Displays the Serial Number
Prog Press Once To confirm setting
040080 of the Meter

2. Set CT Ratio:
The default CT ratio is 500/5. To change the CT ratio press the “Prog” key once to 3. To change Integration Time for Average Parameters
enter into the programming mode. The CT secondary can be selected as 5 or 1 & the (Average Time):
CT primary can be programmed from 5 to 6000 in multiples of 5 if the CT secondary
Keys Instruction Display Comment
is 5A and 1 to 1200 in multiples of 1 if the CT secondary is 1A.
Typical example showing how to change the CT ratio to 5000/5. To change Integration Time
for Average Parameters
(Average Time)
Keys Instruction Display Comment AVG

Setting CT Ratio The default average integration time is 5 minutes. To change the average integration
time press "Prog" button once to enter into the programming mode. The average
integration time can be set between 1 to 60 minutes in interval of 1 minute. Typical
Press "Prog" button to set secondary. example showing how to change the average time to 15 minutes.

Prog Press Once CT Secondary Start Blinking


Prog Press Once Set Avg. Time
AVG

Press "Prog" button to confirm secondary & to set Primary.


Scroll up Press Once Digit increment by 1
Prog Press Once 0----5 Set CT Primary AVG

Scroll down Press Once Moves cursor right


Scroll up Press Five Times Digit increments to 5
5----5 AVG

Scroll up Press five times 15 Digit increment by 5


Scroll down Press Once Moves cursor right
50---5 AVG

Prog Press Once To confirm setting


Scroll down Press Once Moves cursor right
500--5

Operation and Instruction Manual 22 Operation and Instruction Manual 23