FRONT VIEW
L3
FUSE S3
0 .5A
+0.8
1 PULSE = 1 kWh
HPL-SOCOMEC
96mm
Fig. 2 S, G = PULSE OUTPUT
Fig. 3
MULTIPLIFACTION FACTOR
Actual Reading = Meter Reading x M.F.
Example: If the reading on the meter is 37.5 kWh. CT’s connected are of the rating 100/5A.
M.F = 100 / 5 = 20
Actual reading = 37.5 x 20 = 75 kWh
ENCLOSURE
Compact : 96mm x 96mm x 90 mm
Weight : 300 gms.
FRONT PANEL
Display : COUNTER with 6 digits
Digit Height : 8mm x 4.8mm
Protection Index : IP 54
INPUTS
A. CURRENT :
B. VOLTAGE :
Measurement range : 120V AC to 300V AC Phase to Neutral
Voltage circuit burden : <1 W per phase
AUXILIARY SUPPLY : Self Powered, No Auxiliary Supply required
ACCURACY
Active Energy : Class 1.0
PULSE OUTPUT
Pulse duration : 100 msec minimum
Pulse weight : 1 Pulse = 1 kWh
Potential free contact : interrogated with an external
(Open collector type) DC Voltage of 5V to 24V
OPERATING CONDITION
Operating temperature : -100C to +550C
Relative humidity : 95%
SPECIAL FEATURES
1. Records energy accurately under the following Tamper conditions :
a) One or Two phases are removed OR
b) Neutral is Removed OR
c) One Phase and neutral are removed OR
d) Reverse current condition
2. Phase available indication LED’s
3. Finger touch-proof terminals for CT & Voltage connections.