LT AC THREE PHASE, FOUR WIRE PANEL MOUNTED

STATIC KWH METER WITH COUNTER DISPLAY

INSTALLATION & OPERATION MANUAL

FRONT VIEW

1. kWh Counter Display

2. Phase Indication LED’s

3. Calibration LED : 15000 imp/kWh for -/5A

CUTOUT DETAILS WIRING DIAGRAM


The Panel Meter is installed on the cabinet’s
front panel and shall be secured firmly with The meter shall be wired as per the following wiring
cabinet using 4 transparent Clips. Diagram :
2
Use 0.5 to 2.5mm Cable for Voltage
2 2
terminals & 3mm to 6mm cable for Current
terminals.
+0.8 N
92 -0.0mm P1
S1
L1
P2
S2
L2
P3
92 -0.0mm

L3
FUSE S3
0 .5A
+0.8

90mm REAR VIEW


3Phase, 4Wire Electronic kWh Meter L1 S1
CT-2E I1
L2 S2
k wh 18 kWh
L3 S1
I2
96mm N S2
CAL
G S1
I3
S S2

1 PULSE = 1 kWh

HPL-SOCOMEC

96mm
Fig. 2 S, G = PULSE OUTPUT
Fig. 3

MULTIPLIFACTION FACTOR
Actual Reading = Meter Reading x M.F.

M.F. = CT Primary / CT Secondary (5A)

Example: If the reading on the meter is 37.5 kWh. CT’s connected are of the rating 100/5A.
M.F = 100 / 5 = 20
Actual reading = 37.5 x 20 = 75 kWh

Ref: HPL / CT - 2M / 1007


LT AC THREE PHASE, FOUR WIRE PANEL MOUNTED
STATIC KWH METER WITH COUNTER DISPLAY
TECHNICAL PARAMETER

ENCLOSURE
Compact : 96mm x 96mm x 90 mm
Weight : 300 gms.
FRONT PANEL
Display : COUNTER with 6 digits
Digit Height : 8mm x 4.8mm
Protection Index : IP 54

INPUTS
A. CURRENT :

Insulated secondary : -/5A


Current circuit burden : < 0.5VA
Starting current : 10ma (for 5A Secondary)
Overload : 7A

B. VOLTAGE :
Measurement range : 120V AC to 300V AC Phase to Neutral
Voltage circuit burden : <1 W per phase
AUXILIARY SUPPLY : Self Powered, No Auxiliary Supply required

ACCURACY
Active Energy : Class 1.0

PULSE OUTPUT
Pulse duration : 100 msec minimum
Pulse weight : 1 Pulse = 1 kWh
Potential free contact : interrogated with an external
(Open collector type) DC Voltage of 5V to 24V

OPERATING CONDITION
Operating temperature : -100C to +550C
Relative humidity : 95%

SPECIAL FEATURES
1. Records energy accurately under the following Tamper conditions :
a) One or Two phases are removed OR
b) Neutral is Removed OR
c) One Phase and neutral are removed OR
d) Reverse current condition
2. Phase available indication LED’s
3. Finger touch-proof terminals for CT & Voltage connections.

Ref: HPL / CT - 2M / 1007