Sr. No.

Calculation
1 INPUT DATA

Load Case Px Py Pz Mx My Mz *Notation


DL 0 2000 0 150 0 90 Px = Reaction in X-Direction
LL 0 0 0 0 0 0 Py = Vertical Reaction\
EQX 60 80 0 0 0 120 Pz = Reaction in Z- Direction
EQZ 0 100 80 160 0 0 Mx = Moment about X-Axis
My = Moment about Y-axis
Mz = Moment about Z-axis

Diameter of Pile to be used = 450 mm Spacing b/w Pile = 1000 mm Cover = 50 mm


Number of Pile to be used = 2 Projection from the face of outer most pile = 450 mm Dia of Bar = 16 mm
Width of Column = 230 mm Grade of Concrete = 30 N/mm^2
Depth of Column = 600 mm Grade of Steel = 500 N/mm^2
Trial Thickness of Plie Cap = 1000 mm Pile Capacity = 1200 kN From Soil Report

Load Combination Px (kN) Py (kN) Pz (kN) Mx (kN m) My (kN m) Mz (kN m)

1.0 (DL+LL) 0 2000 0 150 0 90


1.0 (DL+0.8LL+0.8EQX) 48 2064 0 150 0 186
1.0 (DL+0.8LL-0.8EQX) -48 1936 0 150 0 -6
1.0 (DL+0.8LL+0.8EQZ) 0 2080 64 278 0 90
1.0 (DL+0.8LL-0.8EQZ) 0 1920 -64 22 0 90
1.0 (DL+EQX) 60 2080 0 150 0 210
1.0 (DL-EQX) -60 1920 0 150 0 -30
1.0 (DL+EQZ) 0 2100 80 310 0 90
1.0 (DL-EQX) 0 1900 -80 -10 0 90

2350

My

1000
230
1350

Mx

450 450 600

Fig.1 Arrangement of Piles in Plan

Fmax/min = P/n ± Mx *x/Ix ± My *y/Iy

∑x2 = 2 ∑y2 = 0

Load on Capacity
Load Combination Px (kN) Py (kN) Pz (kN) Mx (kN m) My (kN m) Mz (kN m)
Each Pile Check
1.0 (DL+LL) 0 2000 0 150 0 90 1037.50 OK
1.0 (DL+0.8LL+0.8EQX) 48 2064 0 150 0 186 1069.50 OK
1.0 (DL+0.8LL-0.8EQX) -48 1936 0 150 0 -6 1005.50 OK
1.0 (DL+0.8LL+0.8EQZ) 0 2080 64 278 0 90 1109.50 OK
1.0 (DL+0.8LL-0.8EQZ) 0 1920 -64 22 0 90 965.50 OK
Sr. No. Calculation
1.0 (DL+EQX) 60 2080 0 150 0 210 1077.50 OK
1.0 (DL-EQX) -60 1920 0 150 0 -30 997.50 OK
1.0 (DL+EQZ) 0 2100 80 310 0 90 1127.50 OK
1.0 (DL-EQX) 0 1900 -80 -10 0 90 947.50 OK

Design Load Load on


Py (kN) My (kN m) Mz (kN m)
Combination Each Pile
1.5(DL+LL) 3000 225 135 1556.25
1.2(DL+LL+EQX) 2496 180 252 1293.00
1.2(DL+LL-EQX) 2304 180 -36 1197.00
1.2(DL+LL+EQZ) 2520 372 108 1353.00
1.2(DL+LL-EQZ) 2280 -12 108 1137.00
1.5(DL+EQX) 3120 225 315 1616.25
1.5(DL-EQX) 2880 225 -45 1496.25
1.5(DL+EQZ) 3150 465 135 1691.25
1.5(DL-EQZ) 2850 -15 135 1421.25
0.9DL+EQX 1920 135 261 993.75
0.9DL-EQX 1680 135 -99 873.75
0.9DL+EQZ 1950 375 81 1068.75
0.9DL-EQZ 1650 -105 81 798.75
Maximum Load on Pile 1691.25

Governing Load Combination = 1.5(DL+EQZ) = 1691.25 kN

Moment at the face of column = 1691.25 X (0.5 - 0.3) = 338.25 kN m


Effective depth of pile cap = 942 mm
Required depth d = 291.16 mm OK
Minimum % of steel = 0.12 %
Minimum Area of Steel Required = 1526.04 mm^2
Required Area of Steel = 1526.04 mm^2
Diameter of Bar = 16 mm
Required no. of bar = 7.6
Provided No. of Bar in each Direction = 10
Pt provided = 0.1 %

Check For Shear


Distance of pile center from face of the column = 0.20 m
x-d/2 = -271.00 mm
Pile load causing shear = -682.14 kN
τv = -0.31 N/mm^2
τc = 0.23 N/mm^2
Design shear = OK

Dia of shear Steel = 16 mm


Spacing of Shear Reinforcement = 218.65 mm
Spacing provided = 200.00 mm

Side Face Reinforcement


Ast required Along X- Direction = 2213.7 mm^2 on each Face
Diameter of Bar = 16
No. of Bar Required = 11.01
No. of Bar Provided = 12