Differential temperature controller with 4 relays and 4 inputs
General Data
The control unit ST501-LN1KV.04FS is designed for differential controll applications with special error inputs.
The unit works together with resistance sensors (PTC, PT100 or PT1000).
The unit offers beyond the temperature regulation a wide range of other functions.
The outputs can be programmed to different functions (Parameter A90-A93 ).
The inputs can be configured with the parameters A94-A97
°C
1
2
E1 E2 E3 E4
SET F1 F2
Description
key 1: UP
Pressing the the UP-key together with the SET-key invreases the Setpoint value.
key 2: DOWN
Pressing the the DOWN-key together with the SET-key devreases the Setpoint value.
With the DOWN key it is also possible to cancel the alarm buzzer.
key 3: SET
The display normally shows the actual value. When the SET button is pressed , the display changes
SET to show the Control Setpoint.
key 4:
Different functions for this key can be selected by parameters.(see Parameter A85)
F1
The selected value is shown as long as the key is pressed and additional 4seconds.
key 5:
Different functions for this key can be selected by parameters.(see Parameter A86)
F2
The selected value is shown as long as the key is pressed and additional 4seconds.
key 6:
The Stand-By function for this key can be selected by setting the parameter A82. The key has to be
pressed for at least half a second.
ST501-LN1KV.04FS 1
First level (Setpoint Adjustment)
Display of the Set Values
The display normally shows the actual value of the process temperature. When the SET button is pressed ,
SET the display changes to show the Control Setpoint (Desired temperature)
Simultaneously press the SET button with either the UP or DOWN button to increase or decrease
the Setpoint. Please release the UP or DOWN button before releasing the SET button and the new
value is loaded into the non-volatile memory.
LED's
"1" Status of pump contact
"2" Status of control output 1
"3" Status of control output 2
E1 Status of input E1
E2 Status of input E2
E3 Status of input E3
E4 Status of input E4
ST501-LN1KV.04FS 2
Second level (P-level)
Setting of control parameters
In order to prevent accidental or unauthorised changes to the pre-set parameter values, access to the P-
Level has been made difficult.
Simultaneously pressing the UP and DOWN button for about 3 seconds switches the controller to the P-
Level, and allows adjustment of the P parameters. The display now shows P1
To display and adjust the value of P1, press the SET button and the existing value of P1 is displayed.
By simultaneously pressing the SET button and either the UP or DOWN button this value can be increased or
decreased as required. Release the UP or DOWN button before releasing the SET button and the new value
is saved into the non-volatile memory.
Use the UP or DOWN button to select the remaining P-parameters, and these can be adjusted in a similar
manner.
To return to the operating mode: Simultaneously press the UP and DOWN button for aprox. 3 seconds and
the display will again show the process temperature. In any case if no adjustment of the parameters is made
for 30 seconds, the controller will automatically return to the operating mode.
P35 Lower value for fixed setpoint control on -99...999°C -99°C -10°C
following sensor
(only avtive if differential control)
P36 Upper value for fixed setpoint control on -99...999°C +999°C 99,9°C
following sensor
(only avtive if differential control)
ST501-LN1KV.04FS 3
Second level, P-Parameters
P1: Setpoint 2 or Delta W
Two types of output relay control are available (see A5 for selection method).
The first control variation :
Contacts K1 and K2 are linked together with an adjustable switch separation Delta W (operation with Delta W).
This separation can have either a positive or negative value to provide a leading or trailing second contact. In this
variation the controller can also be used as a three-point controller.
ST501-LN1KV.04FS 4
Third level (A-level)
Simultaneously press the UP and DOWN button for about 3 seconds and ‘P1’ appears in the display.
Press the UP button until the highest p number is displayed. Keep the UP button pressed for a further 15 seconds and
the display will change to ‘PA’. Simultaneously press the UP and DOWN button until ‘A1’ is displayed.
To return to the operating mode: Simultaneously press the UP and DOWN button for aprox. 3 seconds and the display
will again show the process temperature. In any case if no adjustment of the parameters is made for 30 seconds, the
controller will automatically return to the operating mode.
ST501-LN1KV.04FS 5
A50 Minimum ON Time control output 1 0…600 sec 0 sec
A51 Minimum OFF Time control output 1 0…600 sec 0 sec
A52 Minimum ON Time control output 2 0…600 sec 0 sec
A53 Minimum OFF Time control output 2 0…600 sec 0 sec
A54 Time Delay for control after Mains ON 0…999 sec 0 sec
A56 Alarm Signal Delay after Mains ON 0...60 min 20 min
A57 Low pressure alarm Delay after first 0…600 sec 0 sec
compressor start
A58 Low pressure alarm Delay after 0…120 sec 0 sec
"low pressure alarm"
A59 time for number of low pressure alarms 0...60 min 45 min
defined in parameter A60
A60 number of low pressure alarms 0....100 8
before compressor stop
A65 Sensor selection 11: PT100 2-wire Dependent
21: KTY81-121 2-wire on
22: PT1000 2-wire Hardware
A70 Software time constant 1: not active
2...31: average value of "n" values 2
A80 Temperature Scale and 0: Fahrenheit and "AUS"
Display at Stand-By 1: Celsius and "AUS" 1
2: Fahrenheit and "OFF"
3: Celsius and "OFF"
A85 Function key F1 0: No function
1: actual value of sensor F2(leading value)
2: display of control setpoint
3: display of actual differential value
A86 Function key F2 00: No function
1: actual value of sensor F2(leading value)
2: display of control setpoint
3: display of actual differential value
A87 Function key 6 (Stand-By) 0: Not activated
1: Controller ON/OFF (Stand-By)
A90 function K1 1: Connected to pump 1
A91 function K2 2: Connected to control output 1 2
A92 function K3 3: Connected to control output 2 3
A93 function K4 4: Connected to alarm function 4
A94 Switch mode control input E1 0: active when open
pump 1: active when closed
A95 Switch mode control input E2 0: active when open 0
High pressure alarm only 0 is possible
A96 Switch mode control input E3 0: active when open 0
Low pressure alarm 1: active when closed
A97 Switch mode control input E4 0: active when open 0
motor protection compressor, fan 1: active when closed
A98 Activation of bypass control 0: No bypass
1: controll with bypass
A99 Control characteristics 0: Normal temperature control
F2 is deactivated
1: Differential control
2: Normal temperature control
F2 is active for alarme values
Pro Program Version - -
ST501-LN1KV.04FS 6
Third level, A-Parameters
A1: Switch mode control output 1
A2: Switch mode control output 2
Contact direction, i.e. cooling or heating function, can be individually set for each output relay.
Heating function - The output relay contact opens when the Setpoint is reached to switch the heating OFF
Cooling function - The output relay contact closes when the temperature is higher than the Setpoint and
switches the cooling power ON.
ST501-LN1KV.04FS 7
A32: Setpoint display:
The standard setting displays the process temperature. Setpoint 1 can be displayed momentarily by pressing
the SET button.
If setting 1 is chosen then the display shows Setpoint 1 only. i.e. there is no facility for displaying the process
temperature.
K1
A50
Switching behaviour t
(relay ON)
A51
K1
Switching behaviour t
(relay OFF)
A54: Time delay relay control output 1/2 after "Mains ON"
This parameter enables the operation to be delayed for a given period after "Mains ON"
ST501-LN1KV.04FS 8
A56: Alarm delay after "Mains ON"
This time delay prevents alarms from sounding after supply voltage has been switched on
A59: time for number of low pressure alarms defined in parameter A60
With this parameter you define the time for the number of low pressure alarms set in parameter A60, before
the compressor is blocked
ST501-LN1KV.04FS 9
Error codes
Display error What to do
--- Keyboard lock active see Parameter P19 or A19
F1 sensor error sensor F1 new sensor
short circuit / open circuit
F2 sensor error sensor F1 new sensor
short circuit / open circuit
F3 input E1 activated (pump / niveau) Refill water and reset with DOWN-button
(if manual reset is activated) with
F4 input E2 activated (high pressure) maybee high ambient or water temperatur to high
reset with DOWN-button (if manual reset is activated)
F5 input E3 activated (low pressure) maybee low ambient or water temperatur to low
reset with DOWN-button (if manual reset is activated)
F5A compressor is blocked becaues the maybee low ambient or water temperatur to low
numberr of low pressure alarms was reset with DOWN-button
bigger than set in parameter A60
F6 input E4 activated (motor protection) check motor of compressor or fan.
reset with DOWN-button (if manual reset is activated)
F7 Temperature alarm sensor F1 cancel with ∇ button
F8 Temperature alarm sensor F2 cancel with ∇ button
EP lost of data in EE-Prom repair of controller
ST501-LN1KV.04FS 10
TECHNICAL DATA
Measuring Input
F1/F2: Resistance thermometer KTY 81-121
Measuring range: -50...150°C
Measuring accuray: +/- 1K or +/- 0,5%
of scale range, which ever is greater
or
Resistance thermometer Pt100
Measuring range: -80...400°C
Measuring accuray: +/- 1K or +/- 0,5%
of scale range, which ever is greater
switching input
E1: switching input for external potential free switch, function see Parameter A94
E2: switching input for external potential free switch, function see Parameter A95
E3: switching input for external potential free switch, function see Parameter A96
E4: switching input for external potential free switch, function see Parameter A97
Displays
One 3-digit, 13 mm high, red LED display
Three LED’s, diameter 3mm, for status display of the outputs K1, K2 and K3
Three LED’s, diameter 3mm, for status display of lower, upper fixed setpoint control and alarm
Foure LED’s, diameter 3mm, for status display of the inputs E1, E2, E3 and E4
Outputs
K1: Relay, 8(1,5) A, NO-contact, connected with supply voltage 12-24 AC/DC
K2: Relay, 8(1,5) A, NO-contact, connected with supply voltage 12-24 AC/DC
K3: Relay, 8(1,5) A, NO-contact, connected with supply voltage 12-24 AC/DC
K4: Relay, 8 A-contact (cosϕ=1), 250 V, changeover-contact, potential free
Power Supply
12...24 V=~, current consumption max. 20mA
Installation Data
Front panel: 106 x 68 mm
Panel cutout: 87,5mm x 56,5mm
Depth: approx. 85 mm incl. terminals
Mounting: 4 screws
Enclosure
Front IP65
Weight
approx. 160g
Ambient Conditions
Storage temperature: -20...+70 °C
Operating temperature: 0...+55 °C
Relative Humidity: max. 75% without dew
ST501-LN1KV.04FS 11
F1 F2 E1 E2 E3 E4
1 2 3 4 1 2 3 4 5 6 7 8
X8 X9
Spule K2
X5 X6 X7
1 2 1 2 3 4 1 2 3
K1 K2 K3 K4
je 8(1,5)A 250V~
12-24V =/~ 8(1,5)A
wiring diagramm
ST501-LN1KV.04FS 12