Escolar Documentos
Profissional Documentos
Cultura Documentos
but would complicate the calculations. at the fault point can be expressed as
For the base case, incoming line short-circuit duties (at the −1
⎡ 1 1 1 ⎤
, Radial = ⎢ + +
F
primary side of distribution substations) are assumed to be MVASC ⎥ (6)
5000 MVA. They are normally given by a power company. ⎢⎣ MVAsa MVAT1 MVA(1− K ) L1 ⎥⎦
The lengths of the feeder cables are all assumed to be 10 km, Where
and the per unit reactances of the three main transformers are MVAsa is the incoming line short-circuit duty at the
assumed 0.1672 pu. In the following subsections, these
primary side of the substation transformer A.
parameters will be changed in a reasonable ranges to examine
MVAT1 is the corresponding short-circuit MVA of the main
the effects of each parameter under various feeder
arrangements. transformer #1.
As conversion was made, Table II and an MVA diagram MVA(1− K ) L1 is the short-circuit MVA of the feeder segment
were developed. Referred to the MVA diagram, the Short- between the fault point (any location on the main feeder) and
circuit MVA’s of all equipments were combined. The series feed point (the secondary busbar of the main transformer)
MVA’s were combined as resistances in parallel, and the K: variable from 1 to 0, for indicating the fault location
parallel MVA’s were added arithmetically. Finally, the short- Substituting (1) and (2) into (6), the SCC of the fault point
circuit MVA’ of the fault point was found. The short-circuit on the radial feeder can be formulated as
MVA method do make the calculation of short-circuit current −1
more straightforward and easy. ⎡ 1 ZT ( pu ) (1 − K ) L1Z Ω ⎤
F
MVASC , Radial =⎢ + 1 + ⎥ (7)
For comparison, the SCC’s along the primary feeders for ⎢⎣ MVAsa ST1 KVL2 ⎥⎦
various network arrangements, such as radial and three types
Based on (7), the SCC curves were developed as shown in
of normally closed loops, were evaluated. Finally, the
Fig. 5. The SCC curves relate the incoming line short-circuit
increments of the SCC’s along a feeder due to network
duty, transformer impedance and the fault location. There are
upgrading were compared by the SCC curves. These curves
five curves in Fig. 5. The solid curve show the SCC’s along
make the impacts of system upgrading from original radial to
the feeder F#1 under the conditions of base case. The other
normally closed-loop arrangement with different connection
four curves show the deviations of the corresponding SCC’s
schemes more clear.
from the base case for two values of the incoming line short-
circuit duties and two values of the transformer impedances.
TABLE I
PARAMETERS OF THE SAMPLE DISTRIBUTION SYSTEM The smaller the incoming line short-circuit duty or the greater
the transformer impedance is, the smaller the corresponding
Parameters Variables Base Case Ranges SCC’s obtain, as shown in Fig. 5. These two factors
Incoming line short- MVAsa, predominantly affect the SCC’s along the feeder. As usual,
5000 MVA 20%~200%
circuit duties MVAsb
the farther the fault point at the primary feeder is, the smaller
Transformer capacities ST1, ST2, ST3 60 MVA 100%
Transformer
the corresponding SCC obtain. Fig. 5 also shows that the
ZT1, ZT2, ZT3 0.1672 pu 90%~110% farther the fault point at the primary feeder is, the smaller the
impedances
Feeder lengths L1, L2 10 km 20%~200% deviations of corresponding SCC obtain. That means the
Tie line length LTL 0.3 km 100% effect of the incoming line short-circuit duty and the
Feeder impedances ZΩ 0.1795 Ω/km 100% transformer impedance on the SCC’s along a feeder is the
largest in the feed point and the smallest in the end of the
TABLE II feeder. This is because of the MVA(1− K ) L1 is relative larger
CORRESPONDING SHORT-CIRCUIT MVA OF EACH EQUIPMENT
when the fault point is far away from the feed point.
Equipment Base Case Ranges
MVAsa, MVAsb 5000 MVA 1000 MVA~10000 MVA Infinite bus
MVAT1, MVAT2, MVAT3 359 MVA 326 MVA~399 MVA
MVAL1, MVAL2 290 MVA 145 MVA~1448 MVA MVAsa
MVATL 9653 MVA 9653 MVA ⎧ generator ,
⎪
⎪motor ,
component z ⎪ MVAT1
⎨transformer ,
A. Radial Arrangement ⎪conductor ,
⎪
⎪⎩etc.
For the system shown in Fig. 2, if the feeder F#1 is MVA(1− K ) L1
connected to bus 1, and the two tie breakers, one located
between the secondary busbars of two main transformers and F F
the other at its end are open, then the feeder F#1 is radial. The Fig. 3. Scheme for calculating short- Fig. 4. MVA diagram of
MVA diagram of this radial arrangement was shown in Fig. 4. circuit MVA of individual elements radial arrangement
Assumed a three-phase fault occurs at a point on the main
feeder at a distance of (1-k)L1 m from the feed point, the SCC
4
400 MVAsa
350
90%*ZT1 MVAT1
200%*MVAsa
300
) MVAsa=5000 MVA
A ZT1=0.1672 pu
V
250 L1=10 km MVA(1− K ) L1
M(.
C.
C.
110%*ZT1 MVAL2
S 200 F
20%*MVAsa
MVAKL1
150
100
1 0.8 0.6 0.4 0.2 0
K MVALTL
Fig. 5. SCC versus fault location for radial arrangement
B. Closed Loop Arrangement Fig. 6. MVA diagram of a normally-closed feeder arrangement of type I
Type I: The MVA diagram of a normally closed loop The only difference between radial and Type I closed loop
arrangement of Type I was shown in Fig. 6. Assumed fault arrangement is the feeder structure. For the closed loop
occurs at a point on the main feeder at a distance of (1-k)L1 m arrangement, there are two sources contribute the fault
from the feed point, the SCC at the fault point can be current. However, there is only one source contributes the
expressed as fault current for the radial arrangement. For this reason, the
−1 SCC’s along the primary feeder get higher moderately when
⎧ 1 1 ⎫
⎪ MVA + MVA ⎪ the feeder arrangement was upgraded from radial to normally
⎪⎪ ⎪
sa T
−1 ⎪
1
F
MVASC =⎨ ⎡ −1 ⎤ ⎬
closed-loop. The increment of the SCC’s along the feeder F#1
,TypeI
⎪+ ⎢ MVA ⎛ ⎞ due to network upgrading mainly depend on the lengths of the
⎟ ⎥ ⎪
1 1 1
⎪ ⎢ (1− K ) L1 + ⎜ + +
⎜ MVAKL MVAL
⎝ MVAL2 ⎟⎠ ⎥ ⎪ two tied feeders F#1 and F#2. Generally, the shorter the
⎩⎪ ⎣⎢ 1 TL ⎥⎦ ⎭⎪
(8) length the feeder F#2 is, the more the increment of the SCC’s
Where along the feeder F#1 obtain.
F
MVASC ,TypeI is the SCC’s along the primary feeder of Type
380
I arrangement. 360
Similarly, Substituting (1) and (2) into (8), the SCC’s along 340 MVAsa=5000 MVA
the primary feeder of Type I arrangement can be formulated 320
ZT1=0.1672 pu
L1=L2=10 km
as: ) 300
−1 A 90%*ZT1
⎧ 1 ZT 1( pu ) ⎫ V
280
⎪ + ⎪
M(. 200%*MVAsa
⎪ MVA sa S T 1 ⎪ (9) C.
260 20%*L2
F
MVASC =⎨ −1 ⎬
C.
⎪+ ⎡ ⎤ ⎪
,TypeI S
KVL2 KVL2 240
+
⎪ ⎢⎢ (1 − K ) L Z ⎥
( KL1 + LTL + L2 ) Z Ω ⎦⎥ ⎪⎭
⎩ ⎣ 1 Ω 220 200%*L2
110%*ZT1
Based on (9), seven SCC curves, relating the incoming line 200
20%*MVAsa
short-circuit duty, transformer impedance, the length of feeder 180
1 0.8 0.6 0.4 0.2 0
F#2 and the fault location, have been developed, as shown in K
Fig. 7. The solid curve show the SCC’s along the feeder F#1 Fig. 7. SCC’s versus fault location for a normally-closed feeder arrangement of
Type I
under the conditions of base case. The other six curves show
the deviations of the corresponding SCC’s from the base case
Type II.1: The MVA diagram of a normally closed loop
for two values of the incoming line short-circuit duties, two
arrangement of Type II.1 was shown in Fig. 8. According to
values of the transformer impedances and two values of the
the system structure, the SCC’s along the Feeder #1 can be
lengths of feeder F#2. The effects of the incoming line short-
represented as
circuit duty and the transformer impedance are the same as
that of the feeder with radial arrangement. The effects of the
incoming line short-circuit duty and the transformer
impedance on the SCC’s along the feeder F#1 is the largest in
the feed point and the smallest in the end of the feeder. On the
contrary, the effects of the length of feeder F#2 on the SCC’s
along the feeder F#1 is the smallest in the feed point and the
largest in the end of the feeder.
5
( )
−1
⎪ ⎢⎝ 1 1 ⎠
⎥ ⎪ ⎪ MVA + MVAT1 + MVAT2 ⎪
⎪ 1 ⎢ −1 ⎪ ⎪ ⎪
⎞ ⎥ ⎬
sa
MVASC ,TypeII .1 = ⎨
F
+ ⎛ 1
+
1
⎪ ⎡ −1
⎪
⎞ ⎤ ⎪
−1
⎢ ⎥
⎪ MVAsa ⎢ ⎜⎜ MVAT2 MVAL2 ⎟ ⎪ ⎛ 1 (12)
⎟ ⎥ ⎪⎪ =⎨ ⎢ + ⎟ ⎥ ⎬
F
MVASC ⎜
⎪ + ,TypeII .2
⎢
⎪+ MVA ⎜ MVAL2 ⎟ ⎥ ⎪
⎢ ⎜ 1 1 ⎟ ⎥ ⎪ +
⎪ ⎢ ⎜⎜ + + ⎥ ⎪ ⎢ (1− K ) L1
⎜ 1 1 ⎟ ⎥ ⎪
⎪ ⎢ ⎝ MVALTL MVAKL1 ⎟⎟⎠ ⎥ ⎪ ⎪ ⎢ ⎜⎜ MVA + MVA ⎥
⎟⎟ ⎥ ⎪
⎩⎪ ⎣ ⎦ ⎪⎭ ⎪ ⎢ ⎝ L KL1 ⎠ ⎦ ⎪
⎩ ⎣ TL
⎭
(10) Equation (12) can be rewritten as
Substituting (1) and (2) into (10) yields ⎧ −1 ⎫
−1
⎛ S ST2 ⎞
⎧
−1
−1 ⎫ ⎪ 1 + ⎜ T1 + ⎟ ⎪
⎡⎛ Z −1
⎞ ⎤ ⎪ ⎪⎪ MVAsa ⎜ ZT ( pu ) ZT ( pu ) ⎟ ⎪⎪
⎪ ⎢⎜ (1 − K ) L Z ⎝ ⎠ (13)
⎟ ⎥ ⎪ =⎨
T ( pu ) Ω F
+ −1 ⎬
1 2
1 1 MVASC
⎪ ⎢⎜ ST ⎟ ⎥
,TypeII .2
⎪ ⎡ ⎤ ⎪
⎪ ⎝ KVL2 ⎠ ⎥ ⎪ KVL2 KVL2
⎢ 1
⎪+ ⎢ + ⎥ ⎪
⎪⎪ 1 ⎢ ⎛ ZT ( pu ) −1
⎞ ⎥ ⎪ (11)
⎪ ⎪⎩ ⎢⎣ (1 − K ) L1Z Ω ( L2 + LTL + KL1 ) Z Ω ⎥⎦ ⎪⎭
F
MVASC =⎨ +⎢ + ⎥ ⎬
⎜ ⎟
2
,TypeII .1
⎪ MVAsa ⎢ ⎜ ST2 ⎟ ⎥ ⎪ Based on (13), seven SCC curves were developed as shown
⎪ ⎢ + ⎜ ( L + L + KL ) Z ⎟ ⎥ ⎪ in Fig. 11. The curves in Fig. 11 are similar to the
⎪ ⎢ ⎜ 2 TL 1 Ω
⎟ ⎥ ⎪ corresponding curves shown in Fig. 9. However, the levels of
⎪ ⎢ ⎜⎝ KV 2 ⎟ ⎥ ⎪
⎪⎩ ⎣ L ⎠ ⎦ ⎪⎭ the SCC’s are all going up because the two transformers were
Based on (11), seven SCC curves were developed as shown operated parallel in this arrangement.
in Fig. 9. The curves in Fig. 9 are similar to the corresponding
curves shown in Fig.7. However, the levels of the SCC’s are MVAsa
all going up and the effects of the factors are enlarged.
MVAsa MVAT1 MVAT2
MVAL2
MVA(1− K ) L1 F
MVAKL1
MVAL2
F
MVAKL1
MVALTL
MVALTL Fig. 10. MVA diagram of a normally-closed feeder arrangement of type II.2
700
Fig. 8. MVA diagram of a normally-closed feeder arrangement of type II.1 650
90%*ZT1 & 90%*ZT2
500 600
200%*MVAsa
550
110%*ZT1 & 110%*ZT2
20%*L2 MVAsa=5000 MVA
450 ) 500
90%*ZT1 & 90%*ZT2 ZT1=ZT2=0.1672 pu MVAsa=5000 MVA
A
L1=L2=10 km V ZT1=ZT2=0.1672 pu
200%*MVAsa M(. 450
L1=L2=10 km
400 C.
) C. 400
A S
V 350 20%*L2
M(. 350
C. 300
C.
S 300 20%*MVAsa
250
200%*L2
200
250 110%*ZT1 & 110%*ZT2 1 0.8 0.6 0.4 0.2 0
200%*L2 K
20%*MVAsa Fig. 11. SCC’s versus fault location for a normally-closed feeder arrangement of
200
1 0.8 0.6 0.4 0.2 0 Type II.2
K
Fig. 9. SCC’s versus fault location for a normally-closed feeder arrangement of
Type II.1 Type III: The MVA diagram of a normally closed loop
arrangement of Type III was shown in Fig. 12. According to
Type II.2: The MVA diagram of a normally closed loop the system structure, the SCC’s along the Feeder #1 can be
arrangement of Type II.2 was shown in Fig. 10. According to represented as
6
MVALTL BIOGRAPHIES
250
Wei-Tzer Huang was born in Taiwan, R.O.C., on
1 0.8 0.6 0.4 0.2 0 August 15, 1971. He received his B.S. and M.S.
K
degree in electrical engineering from National Taiwan
Fig. 13. SCC’s versus fault location for a normally-closed feeder arrangement of University of Science and Technology, Taipei,
Type III Taiwan, the Republic of China, in 1997 and 1999,
respectively. Presently, he is a graduate student at
5 CONCLUSIONS National Taiwan University of Science and
Technology, and he is a lecturer of Chienkuo
Technology University, too. His research interests
In this paper, a simple, straightforward and planning- include modeling and simulation of power systems,
oriented method, the short-circuit MVA method, was applied electric power distribution system planning, and
to evaluate the increments of SCC’s along primary feeders unbalanced problem studies.