Você está na página 1de 1

ALN/AL2N SAFETY PRECAUTION This manual uses the following symbols to ensure safe operation of this product.

LEVEL CONTROL RELAY WARNING Warnings are indicated when mishandling this product might result in death or serious injury
to user.
User's Manual CAUTION Cautions are indicated when mishandling this product might result in minor injury to the user,
or only physical damage to the timer.

WARNING
RESTRICTIONS ON USE
ΘNote this incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has
When using this product in applications been correctly wired before turning the power ON.
that require particular safety or when ΘBefore wiring, or removing / mounting the product, be sure to turn the power OFF. Failure to do so might cause
using this product in important facilities, electric shock.
please pay attention to the safety of the ΘDo not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
overall system and equipment. Install fail- ΘDo not disassemble the product. Doing so might cause electric shock or faulty operation.
safe mechanisms, perform redundancy
checks and periodic inspections and CAUTION
adopt other appropriate safety measures ΘUse the product within the operating ranges recommended in the specification (temperature, humidity, voltage,
when it is necessary. shock, mounting direction, atmosphere and etc.). Failure to do so might cause fire or faulty operation.
ΘMake sure the product is firmly connected to the socket. Failure to do so might cause electric shock or fire.

SPECIFICATIONS NAMES AND FUNCTIONS OF FACEPLATE


Operating voltage AC(V): 24, 110, 120, 220, 230, 240 Power indicator(Green)
Allowable operating
voltage range 85~110% of rated operating voltage

Rated frequency 50 / 60 Hz LEVEL CONTROL LEVEL CONTROL


REL AY REL AY
Contact rating 250VAC 5A (Resistive load) Sensitivity adjustment
Electrode voltage 20VAC

Sensitivity rang 5K ~ 100KӨ M in . Max. M in . Max.


NC.

Response time(water high) Approx. 300 ms Contact type setting NO .

5KħƝ100Kħ 5KħƝ100Kħ
Adjustable sensitivity Adjustable sensitivity
Response time(water low) Approx. 500 ms

Power consumption Approx. 3VA TYPE: TYPE:


ALN AL2N
Life Mechanical : 5,000,000 times / Electrical : 100,000 times
Contact type Contact indicator(Red)
Ambient temperature -10 ~ +50 °C
N.C. 1.Switch to N.O. , then contact (a) is for water-supply,
and contact (b) is for drainage.
Ambient humidity MAX 85% RH N.O. 2.Switch to N.C. , then contact (a) is for drainage, and
Weight Approx. 160g contact (b) is for water-supply.

CONNECTION
ALN-08 ALN-08A ALN-11

Water-supply running Water-supply running Water-supply running


Power source Power source Power source

6 5 4 3 6 5 4 3 9 8 7 5 3 4

Knife Knife Knife


switch 7 8 1 2 switch 7 8 1 2 switch 1011 6 1 2
Magnetic switch
Magnetic switch

Magnetic switch

˘ˆ ˘˅ ˘˄ ˘ˆ ˘˅ ˘˄ ˘ˆ ˘˅ ˘˄
Stop Stop Stop
Control range Control range Control range
Start Start Start
ˢ˟ ˢ˟ ˢ˟

ˠ ˣ ˠ ˣ ˠ ˣ

AL2N-11 DIMENSION(mm)

Water-supply running with prevention of idle running of pump.


Power source

9 8 7 5 3 4
Knife
switch Push-button switch
1011 6 1 2

34
80.5
75.3
Magnetic switch

E3 E2 E1

ӿ4 x 2
Control range
ˢ˟

E3 E2' E1' 30 4 73.3 16.1


35 93.4

M-ALN-E-A
ANLY ELECTRONICS CO., LTD.
Printed in Taiwan
http://www.anly.com.tw

Você também pode gostar