Você está na página 1de 8

Insulation Resistance

Testing
Application Note

Introduction detailed information on leakage tion of relative readings. It


Insulation resistance testers can currents and resistance tests see would be a waste of time to
be used to determine the integ- the following sections: What Is perform these tests on low-
rity of windings or cables in Insulation Resistance & Leak- capacitance equipment since
motors, transformers, switch- age Currents and Predictive the time-dependent currents
gear, and electrical installations. Maintenance Tests). diminish quickly, resulting in all
The test method is determined On the other hand, when the the measurements being the
by the type of equipment being equipment to be tested is a long same.
tested and the reason for test- run of cable, large motor, or
ing. For instance, when testing generator (high-capacitance Installation testing
electrical cabling or switchgear equipment) the time-dependent The most important reason for
(low-capacitance equipment) currents will last for hours. testing insulation is to insure
the time-dependent capacitive These currents will cause the public and personal safety. By
leakage and absorption leakage meter readings to change con- performing a high dc voltage
currents become insignificant stantly, making it impossible to test between de-energized cur-
and decrease to zero almost obtain an accurate steady read- rent-carrying (hot), grounded,
instantly. A steady conductive ing. This condition can be and grounding conductors, you
leakage current flow is reached overcome by using a test that can eliminate the possibility of
almost instantly (a minute or establishes a trend between having a life-threatening short
less) providing perfect condi- readings, such as the step volt- circuit or short to ground. This
tions for the spot-reading/short- age or dielectric-absorption test. test is usually performed after
time resistance test. (For more These tests do not depend on a the initial installation of the
single reading but on a collec- equipment. This process will
protect the system against
miswired and defective equip-
ment, and it will insure a high
quality installation, customer
satisfaction, and protect against
fire or shock.

Maintenance testing
The second most important
reason for insulation testing is
to protect and prolong the life
of electrical systems and motors.
Over the years, electrical sys-
tems are exposed to environ-
mental factors such as dirt,
grease, temperature, stress, and
vibration. These conditions can
lead to insulation failure, result-
ing in loss of production or even
fires. Periodic maintenance tests
can provide valuable informa-
tion about the state of deteriora-
tion and will help in predicting
possible failure of the system.
Correcting problems will result
not only in a trouble-free sys-
tem, but will also extend the
operating life for a variety of
equipment.
Before measuring the insulation surface, and, in ture (resistance goes down as
some cases will be absorbed temperature goes up), the
In order to obtain meaningful by the material. recorded readings are altered
insulation resistance measure- by changes in the temperature
ments, the electrician should 3. The surface of the conductor
is free of carbon and other of the insulating material. It is
carefully examine the system recommended that tests be
under test. The best results are foreign matter that can be-
come conductive in humid performed at a standard con-
achieved when: ductor temperature of 20°C
conditions.
1. The system or equipment is (68°F). As a rule of thumb,
taken out of service and 4. Applied voltage is not too when comparing readings to
disconnected from all other high. When testing low- 20°C base temperature,
circuits, switches, capacitors, voltage systems; too much double the resistance for ev-
brushes, lightning arrestors, voltage can overstress or ery 10°C (18°F) above 20°C or
and circuit breakers. Make damage insulation. halve the resistance for every
sure that the measurements 5. The system under test has 10°C below 20°C in tempera-
are not affected by leakage been completely discharged ture. For example, a one-me-
current through switches to the ground. The grounding gohm resistance at 40°C
and overcurrent protective discharge time should be (104°F) will translate to four-
devices. about five times the testing megohm resistance at 20°C
2. The temperature of the con- charge time. (68°). To measure the conduc-
ductor is above the dew 6. The effect of temperature is tor temperature, use a non-
point of the ambient air. considered. Since insulation contact infrared thermometer
When this is not the case, a resistance is inversely propor- such as the Fluke 65.
moisture coating will form on tional to insulation tempera-

Work safely
Safety is everyone’s responsi- • Hang or rest the meter if • Shut down the equipment
bility, but ultimately it is in your possible. Try to avoid hold- to be tested by opening
hands. No tool by itself can ing it in your hands to fuses, switches, and circuit
guarantee your safety. It is the minimize personal breakers.
combination of the instrument exposure to the effects of
and safe work practices that transients. • Disconnect the branch
circuit conductors,
gives you maximum protection. • Use the three-point test grounded conductors,
Here are a few safety tips you method, especially when grounding conductors, and
should follow: checking to see if a circuit all other equipment from
• Work on de-energized circuits is dead. First, test a known the unit under test.
whenever possible. live circuit. Second, test
Use proper lock-out/tag-out the target circuit. Third, • Discharge conductor
capacitance, both before
procedures. If these proce- test a live circuit again. and after the test. Some
dures are not in place or not This verifies that your instruments may have
enforced, assume the circuit meter worked properly automatic discharge
is live. before and after the mea- functions.
surement.
• On live circuits, use protective • Check for any leakage
gear: • Use the old electricians’ current through fuses,
trick of keeping one hand
• Use insulated tools in your pocket. This less-
switches, and breakers on
de-energized circuits.
• Wear flame resistant ens the chance of a closed Leakage current can cause
clothing, safety glasses, circuit across your chest
and insulation gloves inconsistent and incorrect
and through your heart. readings.
• Remove watches or other • Don’t use an insulation
jewelry • When performing insulation
tester in a dangerous or
and resistance tests:
• Stand on an insulation explosive atmosphere
mat • Never connect the insula- since the instrument can
tion tester to energized
generate arcing in dam-
• When making voltage mea- conductors or energized aged insulation.
surements on live circuits: equipment and always
• Hook on the ground clip follow the manufacturer’s • Use insulated rubber
recommendations. gloves when connecting
first, then make contact the test leads.
with the hot lead. Remove
the hot lead first and the
ground lead last.

2 Fluke Corporation Insulation Resistance Testing


What are insulation The value of insulation resis- Capacitive charging leakage
resistance and tance read on the meter will be current (IC )
leakage currents? a function of following three When two or more conductors
independent sub-currents. are run together in a raceway,
During the testing procedure, they act as a capacitor. Due to
the high dc voltage generated Conductive leakage
this capacitive effect, a leakage
by pressing the test button will current (IL ) current flows through conductor
cause a small (micro-amps) Conductive current is a small
(micro-amp) amount of current insulation. This current lasts
current flow through the con- only for a few seconds as the dc
ductor and the insulation. The that normally flows through
insulation, between conductors voltage is applied and drops out
amount of current depends on after the insulation has been
the amount of voltage applied, or from a conductor to ground.
This current increases as insula- charged to its full test voltage.
the system’s capacitance, the In low-capacitance equipment,
total resistance, and the tem- tion deteriorates and becomes
predominant after the absorp- the capacitive current is higher
perature of the material. For a than conductive leakage current,
fixed voltage, the higher the tion current (see Figure 1) van-
but usually disappears by the
current, the lower the resistance ishes. Because it is fairly steady time we start recording the data.
(E=IR, R=E/I). The total resis- and time independent, this is
Because of this, it is important
tance is the sum of the internal the most important current for to let the reading “settle out”
resistance of the conductor measuring insulation resistance.
before recording it. On the other
(small value) plus the insulation hand, when testing high capaci-
resistance in MΩs. tance equipment the capacitive
charging leakage current can
last for a very long time before
settling out.
Insulation
Resistance
Polarization absorption
(in Megohms)
leakage current (IA )
Total Current Absorption current is caused by
(IA + IC + IL ) the polarization of molecules
within dielectric material. In
low-capacitance equipment, the
current is high for the first few
seconds and decreases slowly
to nearly zero. When dealing
IL IC IA
with high capacitance equip-
ment or wet and contaminated
insulation, there will be no de-
Current crease in the absorption current
(in µA) for a long time.

0 Time ∞
(in seconds)

Figure 1. Current components


IL

IC

Dielectric
Insulation Dielectric
Insulation

Conductors Conductors

Figure 2. Conductive leakage current (IL) Figure 3. Capacitive charging leakage current (IC)

Insulation Resistance Testing Fluke Corporation 3


Applications facturer’s factory test voltage Proof test procedure
(higher than the rated voltage To conduct an installation proof
Installation test and is available from the cable test, use the following procedure:
Proof testing
manufacturer). If you don’t • Use a multimeter or the volt-
know the factory test voltage, age measurement function on
Electricians and engineers per- test using a voltage about twice the MegOhmMeter to make
form proof tests to insure proper the cable’s rated voltage plus sure there is no power applied
installation and integrity of 1000 volts. Rated voltage is the to the tested circuit.
conductors. The proof test is a maximum amount of voltage
simple, quick test used to indi- that the conductor can be ex- • Select the appropriate voltage
level.
cate the instantaneous condi- posed to for a prolonged amount
tion of insulation. It provides no of time, usually printed on the • Plug one end of the black test
diagnostic data and the test conductor. For single-phase, lead to the common terminal
voltages used are much higher two-phase, or three-phase sys- on the meter and touch the
than the voltages used in pre- tems, the cable is rated phase- test probe to a ground (earth)
dictive maintenance tests. The to-phase. or another conductor. Some-
proof test is sometimes called This previously mentioned times it is helpful to ground all
GO/NO GO TEST because it tests method should only be used for conductors that are not part of
cable systems for maintenance testing small and new appara- the test. Alligator clips can
errors, incorrect installation, tus because of its ability to make measurements easier
serious degradation, or contami- withstand higher stress voltages. and more accurate.
nation. The installation is For larger or older equipment or • Plug one end of the red test
declared acceptable if no break- wire use dc test voltages (see lead to the volt/ohm terminal
down occurs during testing. table 3). on the meter and connect the
Choosing the test voltage Common proof dc test volt- test probe to the conductor to
A proof test can be performed ages (not the manufacturer’s be tested.
on equipment of any capaci- test voltages) used for testing • Press the test button to apply
tance. It is performed with a rotating equipment are shown
single voltage, usually between in Table 1.
500 and 5000 V, for about one Rotating Equipment DC Test Voltages Formula Used
minute. It is common to stress
the insulation above normal Factory AC Test, VAC (only for reference) 2 x (VAC Nameplate Rating) + 1,000
working voltages in order to Maximum DC Installation Test, VDC 1.28 x (Factory AC Test)
detect subtle weaknesses in the Maximum DC After Service Test, VDC 0.96 x (Factory AC Test)
insulation. For new equipment, Table 1. Proof test voltage equations for rotating machines
the test should be done at about
60% to 80% of the manu-

Metal Conduit

Insulation

Figure 4. Conductor under test

4 Fluke Corporation Insulation Resistance Testing


the desired voltage and read should notice a steady increase shown in Figure 6. The down-
the resistance displayed on in insulation resistance due to ward slope is a normal sign of
the meter. It could take a few decrease in capacitive and ab- insulation aging. A sharp down-
seconds for the reading to sorption currents. Because tem- ward slope would indicate an
settle. The higher the resis- perature and humidity can af- insulation failure or a warning
tance is the better. fect the readings, the of troubles ahead.
• Test each conductor against measurements should prefer-
ground and against all the ably be made above the dew DC Test Voltages Formula Used

other conductors present in point at standard temperature, For phase-to-phase DCt = 0.8165 x Ep-p
about 20°C/68°F. voltage rating
the conduit. Keep a dated
record of the measured values For equipment rated at or For phase-to-ground DCt = 1.414 x Ep-n
voltage rating
in a safe place. below 1000 volts, the insulation
reading should be of a value of Table 3. DC test voltage equations
• If some of the conductors fail 1MΩ or greater. For equipment DCt - dc test voltage related to
the test, identify the problem rated above 1000 volts, the
or re-pull the conductors. the maximum insulation
expected resistance should in- stress during normal ac
Moisture, water, or dirt can crease to one megohm per 1000
create low resistance readings. operation
volts applied. Usually, the mea-
sured insulation resistance will Ep-p - Phase-to-phase voltage
Predictive maintenance be a bit less than the values rating
tests recorded previously, resulting in Ep-n - Phase-to-ground voltage
a gradual downward trend as rating
Maintenance tests can provide
important information about
the present and future state of
conductors, generators, trans-
formers, and motors. The key to
effective maintenance testing is
good data collection. Examining Recorded Value
the collected data will aid in (in Megohms)
scheduling diagnostic and
repair work, which will reduce Resistance
(in Megohms)
downtime from unexpected fail-
ures. The following are the
most commonly applied dc test
voltages and maintenance tests
performed:

Equipment DC Test Voltage


AC Rating (Volts) (Volts) 0 Time 60 sec
0 – 100 100 – 250 (in seconds)
440 – 560 500 – 1,000
Figure 5. Insulation resistance test
2,300 1,000 or higher
4,100 and above 1,000 or higher Initial Aging
Acceptance of After
Table 2. Maintenance test voltages versus Test Insulation Rewinding
equipment ratings
1000

Spot-reading/short-time 500
resistance test
During the short-time test, the
MegOhmMeter is connected 100
directly across the equipment
being tested and a test voltage Resistance 50
(in Megohms)
is applied for about 60 seconds.
In order to reach a stable insu-
lation reading in about one 10
minute, the test should only be Insulation
5
performed on low-capacitance Failure
equipment. The basic connec-
tion procedure is the same as
for a proof test and the voltage
applied is calculated from the dc 1995 1996 1997 1998 1999 2000
test voltage formulas. When Year
testing good equipment, you Figure 6. Insulation resistance over a period of time

Insulation Resistance Testing Fluke Corporation 5


Step voltage test
The step voltage test involves
resistance testing at various Test Made
with 250V
voltage settings. In this test, you
apply each test voltage for the Test Made
with 500V
same period of time (usually 60
seconds), graphing the recorded
insulation resistance. By apply- Direction of
ing increasing voltages in steps, Resistance Insulation
the insulation is exposed to in- (in Megohms) Failure
creased electrical stress that can Test Made
with 1000V
reveal information about flaws
in the insulation such as pin-
holes, physical damage, or
brittleness. Good insulation
should withstand an increase in
over-voltage stress and its resis-
tance should remain approxi- 0 Time 60 sec
(in seconds)
mately the same during testing
with different voltage levels. On
Figure 7. Step voltage test
the other hand, especially at
higher voltage levels, deterio-
rated, cracked or contaminated
insulation will experience an
increased current flow, resulting 1000
in a decrease in insulation resis-
tance. This test is independent 500
of insulation material, equipment
capacitance, and temperature Good
Insulation
effect. Because it takes a longer 100 Condition
time to run, it should be per- 50
formed only after an insulation Resistance Poor
(in Megohms) Insulation
spot test has been inconclusive. Condition
A spot test deals with absolute
10
resistance change (single read-
ing) with respect to time, while 5
the step voltage test looks for
trends in resistance, with re-
spect to varying test voltages.
Dielectric-absorption/ Voltage
(in kV)
time-resistance test
The time resistance test is Figure 8. Good and poor test curves
independent of equipment size
and temperature. It compares
the absorption characteristics of
contaminated insulation with the Good
absorption characteristics of good Insulation
insulation. The test voltage is
applied over a 10 minute period,
with the data recorded every 10
seconds for the first minute and
then every minute thereafter. Resistance
The interpretation of the slope of (in Megohms)
the plotted graph will determine
the condition of the insulation. A Cracked
continuous increase in graphed Insulation

resistance indicates good insula-


tion. A flat or downward curve
indicates cracked or contami-
nated insulation. 0 Time 10 min
(in minutes)

Figure 9. Dielectric absorption test for good and contaminated curves

6 Fluke Corporation Insulation Resistance Testing


Another method for deter- Insulation Resistance 60/30 Second Ratio 10/1 Minute Ratio
mining the quality of insulation Condition (Polarization Index)
is to use the polarization index Dangerous 0 -1.0 0-1
(PI) test. It is particularly valu- Poor 1.0 – 1.3 1–2
able for uncovering moisture
Good 1.3 – 1.6 2–4
and oil ingress that have a flat-
tening effect on the PI curve, Excellent 1.6 and above 4 and above
causing leakage current and Table 4. Approximate dielectric absorption ratios
eventually shorted windings.
The polarization index is the Proof Test Spot- Test Step Test Dielectric- Polarization
Reading Voltage Absorption Index Test
ratio of two time-resistance Test
readings: one is taken after 1
minute and the other is taken
Single reading • •
after 10 minutes. With good
High test voltage •
insulation, the insulation resis- Performed
periodically
• • • •
tance will start low and get
higher as the capacitive leakage Various
voltages
test •
current and absorption current Timed test
get smaller. Results are obtained intervals • •
by dividing the 10 minute test Diagnostic • • • •
value by the one-minute test information
value. A low polarization index Table 5. Various insulation tests
usually indicates problems with
the insulation. When test time is Rm - Minimum insulation resis- For a three phase system tested
constrained, a shortcut to the tance corrected to 40°C with the other two phases
polarization index test is the (104°F) in MΩ grounded, the resistance re-
dielectric absorption ratio corded for each phase should
(60/30) second test. Kt - Insulation resistance
temperature coefficient at be divided by two. Then, the
winding temperature, resulting value can be com-
Testing connections obtained from Figure 10 pared with the recommended
in generators, minimum insulation resistance
transformers, kV - Rated machine terminal (Rm).
to terminal voltage in
motors, and wiring kilovolts
To test the insulation resistance
in generators, transformers, 100

motors, and wiring installations,


we can employ any of the pre- 50

viously mentioned predictive


maintenance tests. Whether we
choose the spot-reading, step
voltage, or time-resistance tests
depends on the reason for test- 10
ing and the validity of the data
Insulation Resistance Temperature Coefficient, K t

obtained. When testing genera- 5


tors, motors, or transformers
each winding/phase should be
tested in sequence and sepa-
rately while all the other wind-
ings are grounded. In this way,
the insulation between phases 1.0

is also tested.
0.5
Temperature correction for
testing rotating machines
For testing armature and field
winding insulation resistance at
various temperatures, the IEEE
recommends the following insu- 0.1

lation resistance formula.


0.05

Rm = Kt x (kV + 1)

-10 0 10 20 30 40 50 60 70 80 90 100
Table 6. Insulation resistance equation for ac
and dc rotating machinery Winding Temperature, Degrees Celsius

Figure 10. Approximate temperature coefficient for rotating machines

Insulation Resistance Testing Fluke Corporation 7


Testing generators and
motors Transformer Type 60-Hertz
When testing the resistance of Tanked oil-filled type 1.5
the stator coils make sure the
stator winding and phases are Untanked oil-filled type 30.0
To Different
disconnected. Measure the insu- Dry or compound-filled type 30.0 Windings
lation resistance between Table 9. Constant C values at 20°C (68°)
windings and windings to
ground. Also, when dc genera- Testing wiring and cable
tors or motors are being tested
installations
the brushes should be raised so
the coils can be tested sepa- When testing wires or cables,
rately from the armature. The they should be disconnected
following table lists recom- from panels and machinery to
mended minimum resistance keep them isolated. The wires To Ground

readings for various motor volt- and cables should be tested


age ratings. against each other and against
ground (see Figure 4 on page Fluke 1520
MegOhmMeter
Motor Nameplate Minimum Acceptable 4). The Insulated Power Cable
Voltage Rating Resistance Engineers Association (IPCEA)
0-208 100,000 Ω provides the following formula
208-240 200,000 Ω that suggests minimum insula-
240-600 300,000 Ω
tion resistance values. Figure 11. Testing the insulation resistance of a motor
600-1000 1 MΩ
R = K x Log10 (D/d)
1000-2400 2 MΩ
2400-5000 3 MΩ Table 10. Cable insulation resistance

Table 7. Recommended minimum resistance at


40°C (104°F)
R - MΩs per 1000 feet (305
meters) of cable. Based on
Testing transformers dc test potential of 500
When testing single-phase volts, applied for one
transformers, test winding to minute at 15.6°C (60°F)
winding, winding to ground, or temperature)
test one winding at a time with K - Insulation material constant.
all others grounded. For three- (For example: Impregnated
phase transformers, substitute E Paper-2640, Varnished
with EP-P (for delta transformers) Cambric-2460, Thermoplas-
or Ep-n (for wye transformers) tic Polyethlene-50000,
and kVA with kVA3Ø rating of the Composite Polyethylene-
winding under test. 30000)
For determining minimum D - Outside diameter of conduc-
insulation resistance use the tor insulation for single
following formula. conductor wire and cable
D = d + 2c + 2b diameter
Transformer Type Formula Used of single conductor cable
Single phase R = C x E ÷ √kVA d - Diameter of conductor Fluke. Keeping your world
Three phase wye R = C x Ep-n ÷ √kVA up and running.
c - Thickness of conductor
Three phase delta R = C x Ep-p ÷ √kVA insulation
Table 8. Transformers insulation resistance
equations
b - Thickness of jacket Fluke Corporation
PO Box 9090, Everett, WA USA 98206
insulation
Fluke Europe B.V.
R- One minute 500 volt dc For example, one thousand PO Box 1186, 5602 BD
minimum insulation feet of number 6 A.W.G. Heat Eindhoven, The Netherlands
resistance in megohms Resistant Natural Rubber insula- For more information call:
C- Constant for 20°C (68°) tion type stranded conductor U.S.A. (800) 443-5853 or
with 0.125 insulation thickness Fax (425) 356-5116
measurements Europe/M-East/Africa (31 40) 2 675 200 or
(see below) will have K = 10,560 and Log10 Fax (31 40) 2 675 222
E- Winding voltage rating. (D/d) = 0.373 inches. According Canada (800) 36-FLUKE or
to the formula (R = K x Log10 Fax (905) 890-6866
KVA - Rated capacity of wind- (D/d), R = 10,560 x 0.373 = Other countries (425) 356-5500 or
ing under test. For three 3,939 MΩ per 1000 feet) the Fax (425) 356-5116
Web access: http://www.fluke.com
phase units kVA3Ø = expected minimum insulation
√3 x kVA1Ø resistance for single conductor ©2000 Fluke Corporation. All rights reserved.
Printed in U.S.A. 8/2000 1579160 A-ENG-N Rev A
per thousand feet at tempera- Microsoft and Windows are registered trademarks of
ture of 60°F will be 3,939 MΩ. Microsoft Corporation.
Printed on recycled paper.

Você também pode gostar