The document provides specifications for 600/1000V copper conductor cables including:
1) Current carrying capacities and resistance/reactance/impedance values for different cross-sectional areas of 4-core cables.
2) Factors for adjusting current ratings based on ambient temperature, ground temperature, and number of cables in trays.
3) Diameters and weights of 4-core and single-core cables with different cross-sectional areas.
The document provides specifications for 600/1000V copper conductor cables including:
1) Current carrying capacities and resistance/reactance/impedance values for different cross-sectional areas of 4-core cables.
2) Factors for adjusting current ratings based on ambient temperature, ground temperature, and number of cables in trays.
3) Diameters and weights of 4-core and single-core cables with different cross-sectional areas.
The document provides specifications for 600/1000V copper conductor cables including:
1) Current carrying capacities and resistance/reactance/impedance values for different cross-sectional areas of 4-core cables.
2) Factors for adjusting current ratings based on ambient temperature, ground temperature, and number of cables in trays.
3) Diameters and weights of 4-core and single-core cables with different cross-sectional areas.
Current Carrying Capacity in Air Resistance/Reactance/Impedance
Conductor Cross- Sectional area Current Rating Type of R X Z (sq.mm) in Air (Amp) Conductor (ohm/Km) (ohm/Km) (ohm/Km) 4C x 2.0 Sqmm 25 Cu 10.1639 0.2393 10.1668 4C x 3.5 Sqmm 30 Cu 6.5574 0.2230 6.5612 4C x 5.5 Sqmm 40 Cu 3.9344 0.2066 3.9398 4C x 8 Sqmm 55 Cu 2.5574 0.2131 2.5662 4C x 14 Sqmm 75 Cu 1.6066 0.2098 1.6202 4C x 22 Sqmm 95 Cu 1.0164 0.1967 1.0353 4C x 30 Sqmm 115 Cu 0.6557 0.1869 0.6818 4C x 38 Sqmm 130 Cu 0.5246 0.1869 0.5569 4C x 50 Sqmm 150 Cu 0.3934 0.1803 0.4328 4C x 60 Sqmm 170 Cu 0.3279 0.1770 0.3726 4C x 80 Sqmm 205 Cu 0.2590 0.1705 0.3101 4C x 100 Sqmm 240 Cu 0.2066 0.1672 0.2658 4C x 125 Sqmm 285 Cu 0.1770 0.1705 0.2458 4C x 150 Sqmm 320 Cu 0.1475 0.1672 0.2230 4C x 175 Sqmm 345 Cu 0.1279 0.1639 0.2079 4C x 200 Sqmm 360 Cu 0.1148 0.1607 0.1974 4C x 250 Sqmm 425 Cu 0.0951 0.1574 0.1839 4C x 325 Sqmm 490 Cu 0.0820 0.1574 0.1774 4C x 375 Sqmm 530 Cu 0.0689 0.1574 0.1718 4C x 400 Sqmm 535 Cu 0.0689 0.1574 0.1718 Note: Ambient Temp 50 (ºC) Power Factor 0.80
Rating Factors (Ca) for variation in Rating Factors for variation in
Cables laid on cable trays exposed to air, the cable touching and trays are in tiers spaced by 30 cm. No.of Cable trays No .of cables per Tray in tier 0 1 2 3 6 9 1 1.00 0.84 0.80 0.75 0.73 2 1.00 0.80 0.76 0.71 0.69 3 1.00 0.78 0.74 0.70 0.68 6 1.00 0.76 0.72 0.68 0.66
Ca:Rating Factor for variation in ambient air temperature
Cg:Rating Factor for cables laid on cable trays exposed to air,the cables spaced by one cable
CABLE DIAMETER 600/1100V, XHHW INSULATED
4C XHHW INSULATED 1C XHHW INSULATED Conductor Cross- Overall Dia. of Conductor Cross- Overall Dia. of Weight of Cable Weight of Cable Sectional area (sq. Cable Sectional area (sq. Cable (kg/Km) (kg/Km) mm) (mm) mm) (mm) 4C x 2 Sqmm 15.0 385 1C x 2 Sqmm 10.0 150 4C x 3.5 Sqmm 15.5 400 1C x 3.5 Sqmm 10.0 150 4C x 5.5 Sqmm 16.0 455 1C x 5.5 Sqmm 11.0 170 4C x 8 Sqmm 16.5 475 1C x 8 Sqmm 12.0 220 4C x 14 Sqmm 17.0 550 1C x 14 Sqmm 12.0 300 4C x 22 Sqmm 18.0 575 1C x 22 Sqmm 14.0 400 4C x 30 Sqmm 19.0 755 1C x 30 Sqmm 15.0 500 4C x 38 Sqmm 19.5 795 1C x 38 Sqmm 16.0 650 4C x 50 Sqmm 22.0 1040 1C x 50 Sqmm 17.0 750 4C x 60 Sqmm 23.5 1295 1C x 60 Sqmm 18.0 850 4C x 80 Sqmm 28.5 1955 1C x 80 Sqmm 19.0 1000 4C x 100 Sqmm 31.5 2440 1C x 100 Sqmm 21.0 1150 4C x 125 Sqmm 34.5 3040 1C x 125 Sqmm 22.0 1400 4C x 150 Sqmm 40.5 4345 1C x 150 Sqmm 24.0 1650 4C x 175 Sqmm 45.0 5580 1C x 175 Sqmm 26.0 2050 4C x 200 Sqmm 50.0 7195 1C x 200 Sqmm 29.0 2600 4C x 250 Sqmm 55.0 8600 1C x 250 Sqmm 30.0 2800 4C x 325 Sqmm 60.5 10390 1C x 325 Sqmm 32.0 3200 4C x 375 Sqmm 67.5 13060 1C x 375 Sqmm 33.0 3700 4C x 400 Sqmm 74.0 15810 1C x 400 Sqmm 36.0 4100