Equipment effected by LGO(V-5109) thermal analysis 8Kw/m2 (41m radius)
Area of Protection Water application rate Total water Number Description Content Protection (sq.m) (l/min/mm2) demand (l/min) V-5117 A/B DESULFURING DRUM FUEL GAS WATER SPRAY 66 10.2 1346.4 V-5120 ALKALINE DRAINAGE DRUM ALKALINE P-5126 A/B BOOSTER PUMPS CRUDE WATER SPRAY 8.3 20.4 169.32 P-5110 A/B LIGHT DIESEL PA PUMPS LIGHT DIESEL WATER SPRAY 8.3 20.4 169.32 P-5114 A/B TEMPERED WATER PUMPS TEMPERED WATER TOTAL 1685.04
Hydrant Demand (l/min) Water Monitor demand (l/min) (Single activation)
Activation Single demand (l/min 3000 3 1362 Total 4086 1135m3/hr Existing Pump Capacity (Per pump) 18916 l/min Total Water Demand (l/min) Available Pump 2 Duty 1 Standby 37832 l/min 32Kw/m2 10983.36 10kw/m2 2116.5 8Kw/m2 1685.04