2015 ASHRAE DOMESTIC HOT WATER SIZING CALCULATIONS

Building System

Fixture - Quantity - GPH Load - Total

Sink - 24 - 20 - 480

Lav/Public - 4 - 15 - 60

Lav/Private - 26 - 2 - 52

Shower - 3 - *30 - 90

*Shower load factor adjusted per actual usage

1/2 Round Lav - 3 - 15 - 45

_____________

727 gph Possible Max Demand

727gph x .40 (Demand factor) = 290 gph Probable Max Demand

System provided = Two 100 gallon sealed direct vent water heaters with a recovery rate of 223 gph each
(1st hour storage availability of 80 gallons @140 degrees F + 223gph recovery @140 degrees F = 303 gph
available 1st hour usage with 223 gph thereafter per each heater)

Second heater is 100% redundancy in the event of heater failure.

Kitchen System

Fixture - Quantity - GPH Load - Total

2 Comp Sink - 1 - 10 - 10

3 Comp Sink - 1 - 105 - 105

Hand Sink - 3 - 5 - 15

Mop Sink - 1 - 15 - 15

Dishwasher - 1 - 50 - 50

Prerinse Sprayer - 1 - 45 - 45
_____________

240 gph Max Peak Demand

System provided = one 100 gallon sealed direct vent water heaters with a recovery rate of 223 gph each
(1st hour storage availability of 80 gallons @140 degrees F + 223gph recovery @140 degrees F = 303 gph
available 1st hour usage with 223 gph thereafter)

Kitchen heater could be installed with bypass line to Building System in the event of heater failure.