Você está na página 1de 9

Combox-S Modbus address mapping for Mk5 controll

ZT22_08 gen. 6 , API793343 Mk5 controller must be in Mk4 CAN profile !


1900525614 - FS GraphicPlus 2.0.22.0
02/10/2018 14:13:12

Coils
Name Coil
Stopped/Running 1
Unload/Load 2
General Warning 3
General ShutdownWarning 4
General Shutdown 5
General Service 6
General StartFailure 7
Emergency Stop 8
Manual/Automatic 9
Local/Remote 10

Analog Inputs Registers


Name Type Unit Status
Saída do Compressor Pressure (mB mBar 1
DP Filtro de Ar Pressure (mB mBar 3
Pressão de Oleo Pressure (mB mBar 5
Resfriador Intermediário Pressure (mB mBar 7
Saída do Compressor Temperature 0.1 °C 9
Saída do Elemento 1 Temperature 0.1 °C 11
Entrada do Elemento 2 Temperature 0.1 °C 13
Saída do Elemento 2 Temperature 0.1 °C 15
Injeção de Oleo Temperature 0.1 °C 17

Digital Inputs Registers


Name Status
Parada de Emergência 201
Sobrecarga Motor/Ventilador 203
Sinal de Pressão Remoto 205
Dreno de Condensado IC 207
Dreno de Condensado AC 209
Seleção do ajuste de pressão 211
Bit
0
1
2
3
4
5
6
7
8
13

Counters Registers
Value = (65536 x W2) + W1
Name Unit
Value W2
Horas em Funcionamento s 301
Horas em Carga s 303
Núm. Partidas do Motor Count 305
Ciclos Carga/Alívio Count 311
Horas do Modulo s 307

Special Alarms Registers


Name Status
Controle de Pressão Inválido 605
Comunicação - Módulo de Expansão 606
Bit
2
6
10

Machine Control Mode


Register 402 , LO byte
Name Value
2a - Local Start/Stop & Pressure Sensing 0
3a - Remote Start/Stop, Local Pressure 1
4a - Communication Start/stop, Local Pr 2
2b - Local Start/Stop, Digital Contact Pr 16
3b - Remote Start/Stop, Digital Contact 17
4b - Communication Start/Stop & SPS Co 18
4c - Communication Start/Stop & Speed 34
4d - ES Controlled 50
2e - Local Start/Stop & 4-20mA Speed Co 64
3e - Remote Start/Stop & 4-20mA Speed 65
4e - Communication Start/Stop & 4-20m 66

Machine Mechanical State


Register 401 , HI byte
Name Value
Stop 1
Unload 2
Loaded 4

General Status
Register 403
Name Bit
PreWarning 0
General Warning 1
General Shutdown Warning 2
General Shutdown 3
General Service 4
General Start Failure 5
Emergency Stop 6
Manual/Automatic 7
Local/Remote 8
Week Timer 9
PreWarning Service Running Hours 10
- 11
PreWarning Service Analog Input 12
PrePermissive 13
Test Mode 14

ESi Status
Register 404 , HI byte
Name Value
PowerUp ES 22
Local Operation ES 1
Central Stop ES 3
Shutdown ES 14
Automatic Operation ES 2

Regulation Parameters
Name Register Value Read Value Write
Use Pressure Band 1 1061 1 1
Use Pressure Band 2 1061 2 2
Pressure Band 1 - Load 1062 mBar n/a
Pressure Band 1 - Unload 1063 mBar n/a
Pressure Band 2 - Load 1064 mBar n/a
Pressure Band 2 - Unload 1065 mBar n/a

Use ES(i) Pressure Band 1 1081 0 0


Use ES(i) Pressure Band 2 1081 1 1
ES(i) Pressure Band 1 - Load 1082 mBar n/a
ES(i) Pressure Band 1 - Unload 1083 mBar n/a
ES(i) Pressure Band 2 - Load 1084 mBar n/a
ES(i) Pressure Band 2 - Unload 1085 mBar n/a

Commands
Name Register Value Read Value Write
Start 2001 n/a 1
Stop 2001 n/a 2
Load 2001 n/a 3
Unload 2001 n/a 4
StartES 2001 n/a 5
StopES 2001 n/a 6
LocalES 2001 n/a 7
Load50 2001 n/a 8

Switch to 4B (Integrate) 2002 n/a 1


Switch to 4A (Isolate) 2002 n/a 2
-S Modbus address mapping for Mk5 controller
k4 CAN profile !

Registers
Value
2
4
6
8
10
12
14
16
18

Registers
Value
202
204
206
208
210
212
Description
PreWarning
Warning
ShutdownWarning
Shutdown
Service
Permissive
Sensor Error
Set/Not set
SPM valid measurement
PrePermissive

Registers
Value = (65536 x W2) + W1
Value W1
302
304
306
312
308

Description
Warning
Shutdown
Permissive
Commands
Info
Start the main machine
stop the main machine

CCM must be in 4A, command to be repeated at least every 20s (typ. 10s), if not compressor will isolate automatically
If compressor is integrated, it will isolate (go from 4B to 4A). Use of this command is not mandatory (auto isolation after 20s)
Value Interpretation

Values are S16. 32767 = Sensor error.

0/1
Aberto / Fechado
Aberto / Fechado
Aberto / Fechado
Aberto / Fechado
Aberto / Fechado
Banda de Pressão 1 / Banda de Pressão 2
Reference counters for % calculation

Você também pode gostar