P/No. : MFL69982107
Single CAC
FDF
Heat Pump
General information
Product data
Indoor Units
Outdoor Units
Installation of Outdoor Units
FDF
Heat Pump
General information
Single CAC
1.Model Line Up
2.Nomenclature
Single CAC Heat Pump General information
1. Model line up
1.1 Indoor Units
Model Name
Category Type Chassis Capacity class, kBtu/h
18 24 36 48 60
VM1 AVNW36GM1P0
Ceiling
Suspended Unit
VM2 AVNW48GM2P0 AVNW60GM2P0
Chassis
ATUW48GMLP0 ATUW60GMLP0
Model Name
AVUW48GM2P0 AVUW60GM2P0
No. of connectable Indoor units 1
Capacity class kBtu/h 48 60
ATNW48GMLP0 ATNW60GMLP0
Connectable indoor unit model name
AVNW48GM2P0 AVNW60GM2P0
220-240V, 1Ø, 50 Hz
Power supply
220,1Ø, 60 Hz
Chassis
2
Single CAC Heat Pump General information
2. Nomenclature
Model Name A T N W 24 G P L P0
No. 1 2 3 4 5 6 7 8 9
No. Signification
Refrigerant Type
1
A : Using R410A
Product Type
2
T : Ceiling Mounted Cassette
V : Ceiling Suspended Unit
Unit Type
3
N : Indoor Unit
U : Outdoor Unit
Model type
4
W : Heat Pump
Nominal Capacity
5
Ex) 24,000 Btu/h Class ˧ '24'
Electrical rating
6
G: 1Ø, 220-240V, 50 Hz / 1Ø, 220V, 60 Hz
7 Chassis Name of indoor unit
Ceiling Mounted Cassette
L : Basic
8
Ceiling Suspended Unit
1, 2 : Chassis Name
9 Serial number
3
FDF
Heat Pump
Product data
Single CAC
Indoor units
Outdoor units
FDF
Heat Pump
Indoor units
Single CAC
1.List of Functions
2.Specifications
3.Dimensions
4.Piping diagrams
5.Wiring diagrams
6.Air flow and temperature distribution
7.Sound levels
8.Installation
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
1. List of functions
ATNW18GPLP0 / ATNW24GPLP0 / ATNW36GMLP0
Category Functions
ATNW48GMLP0 / ATNW60GMLP0
Air supply outlet 4
Airflow direction control (left & right) X
Airflow direction control (up & down) Auto
Auto swing (left & right) X
Air flow Auto swing (up & down) O
Airflow steps (fan/cool/heat) 4/5/4
Chaos wind(auto wind) X
Jet cool/heat O/X
Swirl wind O
Triple filter (Deodorizing) X
Plasma air purifier PTPKM0 O
Air purifying
Allergy Safe filter X
Long-life prefilter (washable / anti-fungus) O
Drain pump O
E.S.P. control* X
Installation
Electric heater X
High ceiling operation* O
Hot start O
Reliability
Self diagnosis O
Auto changeover O
Auto cleaning X
Auto operation(artificial intelligence) X
Auto Restart O
Child lock* O
Forced operation O
Convenience
Group control* O
Sleep mode O
Timer(on/off) O
Timer(weekly)* O
Two thermistor control* O
Auto Elevation Grille PTEGM0 O
Network Solution(LGAP) O
PQWRHQ0FDB O
Wireless Remote Controller**
PQWRCQ0FDB X
PQRCVCL0Q(W) O
Simple
PQRCHCA0Q(W) O
Wired remote PREMTB001 O
controller Standard PREMTBB01 O
PREMTB100 O
Premium PREMTA000(A/B) O
Simple Contact PDRYCB000 O
PDRYCB400 X
Dry Contact
Communication type PDRYCB300 X
PDRYCB500 X
PHNFP14A0 X
Gateway IDU PI485
PSNFP14A0 X
Note
1. O : Applied, X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
2. Some functions can be limited by remote controller.
3. In case of ducted type indoor units using the wireless remote controller, it needs to connect the wired remote controller for received the signal of that.
4. In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
5. * : These functions need to connect the wired remote controller.
6. ** : It is included by default when the product is manufactured.
2
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
1. List of functions
ATNW18GPLP0 / ATNW24GPLP0 / ATNW36GMLP0
Category Functions
ATNW48GMLP0 / ATNW60GMLP0
Remote temperature sensor PQRSTA0 O
Zone controller ABZCA X
Electronic thermostat AQETC X
CTI(Communication transfer PKFC0 X
interface)
ETC CO2 Sensor PES-C0RV0 X
Group control wire PZCWRCG3 O
2-Remo Control wire PZCWRC2 X
Extension Wire PZCWRC1 X
Wi-Fi Controller LG-IR-WF-1 X
Telecom shelter controller PQCSA001T0 X
Note
1. O : Applied, X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
2. Some functions can be limited by remote controller.
3. In case of ducted type indoor units using the wireless remote controller, it needs to connect the wired remote controller for received the signal of that.
4. In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
5. * : These functions need to connect the wired remote controller.
6. ** : It is included by default when the product is manufactured.
3
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
2. Specifications
Model Name ATNW18GPLP0 ATNW24GPLP0
220-240, 1, 50/60 220-240, 1, 50/60
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input Min./Nom./Max. W 20 / 50 / 60 20 / 50 / 60
Running Current A 0.60 0.60
Exterior Color - - -
WxHxD mm 840 x 204 x 840 840 x 204 x 840
Dimensions Body
WxHxD inch 33-1/16 x 8-1/32 x 33-1/16 33-1/16 x 8-1/32 x 33-1/16
Net kg (lbs) 21 (46.3) 21 (46.3)
Weight
Shipping kg (lbs) 27 (59.5) 27 (59.5)
(Row x Column x FPI) x No. - (2 x 8 x 19) x 1 (2 x 8 x 19) x 1
Heat Exchanger
Face Area m2 (ft2) 0.35 (3.77) 0.35 (3.77)
Type - Turbo Fan Turbo Fan
Fan H/M/L m3/min 16.5 / 14.5 / 13.0 17.0 / 15.0 / 13.0
Air Flow Rate
H/M/L ft3/min 583 / 512 / 459 600 / 530 / 459
Type - BLDC BLDC
Fan Motor
Output W x No. 60 x 1 60 x 1
Dehumidification Rate l /h (pts/h) 1.3 (2.7) 2.4 (5.1)
Sound Pressure Cooling H/M/L dB(A) 38 / 36 / 34 40 / 38 / 36
Level Heating H/M/L dB(A) 38 / 36 / 34 40 / 38 / 36
Sound Power Level Cooling Max. dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 9.52 (3/8)
Piping Connections Gas mm(inch) Ø 12.7 (1/2) Ø 15.88 (5/8)
Drain (O.D. / I.D.) mm Ø 32.0 / 25.0 Ø 32.0 / 25.0
- Fuse
Safety Devices
- Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 4C x 0.75 4C x 0.75
Model Name - PT-UMC1 PT-UMC1
Exterior Color - Morning Fog Morning Fog
WxHxD mm 950 x 25 x 950 950 x 25 x 950
Decoration Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32
Net weight kg (lbs) 5.0 (11.0) 5.0 (11.0)
Shipping weight kg (lbs) 8.8 (19.4) 8.8 (19.4)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound Level Values are measured at Anechoic chamber. Therefore, these values depend on the ambient conditions and values are normally higher
in actual operation.
4. Capacities are net capacities and based on the following conditions. Refer to the Outdoor Unit Specifications for calculating the real capacity.
• Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
4
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
2. Specifications
5
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
2. Specifications
6
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
3. Dimensions
[TP Chassis] ATNW18GPLP0 / ATNW24GPLP0
7
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
3. Dimensions
[TM Chassis] ATNW36GMLP0 / ATNW48GMLP0 / ATNW60GMLP0
8
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
4. Piping diagrams
Gas pipe connection port
Heat exchanger
(flare connection)
Heating
Thermistor for
Evaporator inlet
temperature
9
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
5. Wiring Diagrams
̰ ATNW18GPLP0 / ATNW36GMLP0 / ATNW48GMLP0 / ATNW60GMLP0
jGGG
OXGÞGYZWG}G]WGo¡P
XGÞGYYWTY[WG}G\WGo¡
̰ ATNW24GPLP0
8 7 6 5 4 3 2 1
SW01
10
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
Cooling Heating
Discharge angle: 40° Discharge angle: 50°
2.7m 2.7m
1.5 1.5 2m
1.5 1.5 2m
1.0 1.0
0.5 0.5 1m
1m
1.0 1.0
0.5 0.5
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
2.7m 2.7m
22 22
22 24 24 22 2m
22 22 2m
20 28 28 20
26 26
23 23
1m 1m
24 24
52 52
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
̰ Model : ATNW36GMLP0
Cooling Heating
Discharge angle: 40° Discharge angle: 50°
3.2m 3.2m
3m 3m
2.5 2.5
2.5 2.5
2.0 2.0 2m 2.0 2.0 2m
1.5 1.5
1.0 1.0
1.5 1.5 1m 1m
0.5 0.5
0.5 1.0 1.0 0.5
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
3.2m 3.2m
3m 24 26 24 3m
34 34 26
21 21
2m 28 2m
22 22
32 32 28
23 23 22 22
1m 30 30 1m
24 24
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
11
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
Cooling Heating
Discharge angle: 40° Discharge angle: 50°
2m 26 26 2m
22 22 24 28 28 24
32 32
23 23 1m 1m
22 22
24
24 30 30
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
12
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
7. Sound levels
7.1 Sound pressure level
̰ Overall
Note
1.Sound measured at some distance away from the center
of the unit.
2.Data is valid at free field condition.
3.Reference accoustic pressure 0dB = 20μPa.
4.Data is valid at nominal operation condition.
Ceiling
Refer to the Model Specifications for nominal
1.5m conditions(Power source and Ambient temperature, etc)
5.Sound levels can be increased in accordance with
installation and operating conditions. (Static pressure
mode, used air guide, Room target temperature setting,
* Measuring place : Anechoic chamber etc)
6.Sound level will vary depending on a range of factors such
as the construction(acoustic absorption coefficient) of
particular room in which the equipment in installed.
70 70 70
Sound Pressure Level (dB re 20uPa)
60 60
NC-60 NC-60 NC-60
13
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
7. Sound levels
ATNW48GMLP0 / ATNW60GMLP0
80
70
Sound Pressure Level (dB re 20Pa )
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
20 NC-25
Approximate
NC-20
Hearing
Threshold NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
14
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
8. Installation
• Please read the instruction sheets completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards.
• Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning,
temperature control, etc.)
Anti-bacteria filter
Air
Intake
Wired Remote Controller
Air Outlet * In accordance with each model,
remote controller could have different
external figures and be an accessory part.
15
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
8. Installation
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.
※ According to type of indoor unit, external appearance
or installed structure could be different.
Air conditioner or
Ducted air diffuser
Take enough
distance
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
2. Avoid installing air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
CAUTION
• If the temperature rise above 30 or the humidity rise above RH 80%, the dew-protective kit should be equipped
or use additional insulation to the indoor unit body.
– "Dew Protective kit" is sold separately.
– Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least.
TQ/TR Chassis
* According to product type,
model line up, sales
region..etc, applicability of
each chassis could be
different. 10(13/32)
or more
Ceiling Ceiling Board
Ceiling Board
300(11-13/16) or less
3600(141-23/32) or less
1000(39-3/8)
500(19-11/16)
At least 1800(70-7/8)
or more
Unit:mm(inch)
Floor
16
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
8. Installation
TP Chassis
* According to product type,
model line up, sales
region..etc, applicability of
each chassis could be
different. 10(13/32)
or more
Ceiling Ceiling Board
Ceiling Board
300(11-13/16) or less
1000(39-3/8)
3600(141-23/32) or less
500(19-11/16)
At least 1800(70-7/8)
or more
15(19/32) 500(19-11/16) or more
or more
±3(1/8)
Unit:mm(inch)
Floor
TM/TN Chassis
* According to product type,
model line up, sales
region..etc, applicability of
each chassis could be
different. 10(13/32)
or more
Ceiling Ceiling Board
Ceiling Board
300(11-13/16) or less
4200(165-11/32) or less
1000(39-3/8)
500(19-11/16)
At least 1800(70-7/8)
or more
Unit:mm(inch)
Floor
17
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
8. Installation
Indoor
Low temperature
Discharge of the floor
Suction
In case the floor or surfaces is contact with the outdoor air directly
• If the floor of air conditioned room contact with the outside air, like the store room or garage, the floor
temperature will be decreased and users can have a cold feeling in the feet.
• In such places where the feet comes in direct contact with floors will give a cold feeling to the foot.
CAUTION
– In case there is a cold air intake,
» The duct surface may have some dew drops. So a insulation on the duct is a must.(Insulation material: a
glass wool of thickness 25 mm will be appropriate.)
• Countermeasure method
1. Use the carpet on the floor.
(compared to the tiles the carpet over it will have a 3 degree rise in temperature)
2. Insulating the floor.
3. Floor heating.
In case of high temperature or humidity between the false ceiling and ceiling slab
• In case of places having the temperature and humidity of the Psychrometric chart
surrounding water sources(sea, river etc.)
Enhance additional
• In case the steam is generated between the false ceiling and
insulation required area
the ceiling slab due to some nearby by steam source.
• In case of temperature of 30 degree and humidity above
80%, the units body as well as the piping insulation should
be strengthened. Refer to the psychrometric chart.
• Countermeasure method
– Indoor unit: Insulate the unit body with some insulation like glass wool at least 10 mm in thickness.
– Refrigerant piping: Increase the piping insulation thickness with thickness above 20 mm.
– Others: Inside the ceiling near th air tight seal places. (To escape of the humidity inside false ceiling)
18
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
8. Installation
In case of multiple indoor cassette units (recommended)
Indoor unit Indoor unit
Ventilator
Lighting
1,500mm or more
2,000mm or more
3,000mm or more
CAUTION
• During the installation, care should be taken not to damage electric wires.
• In case of using a drain pump, install the unit horizontally using a level gauge.
Ceiling
Level gauge
1. The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.
2. Select and mark the position for fixing bolts and piping hole.
3. Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
4. Drill the hole for anchor bolt on the wall or ceiling.
• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
• Mount the suspension bolts to the set anchor firmly.
• Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring
washers.
5. In case of ducted type unit, apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
19
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
8. Installation
a Set anchor
b Plate washer
c Spring washer
d Nut
e Suspension
bolts
Ceiling
875(Ceiling opening)
684(Hanging bolt)
570
523
517
671
461
Unit:mm Unit:mm
20
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
8. Installation
Remote
controller cord
Transmission cord
Remote controller cord
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
– Never fail to have separate power specially for the air conditioner.
– Provide a circuit breaker switch between power source and the unit.
– Confirm the Specification of power source.
– Confirm that electrical capacity is sufficient.
– Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
– Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
– Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
– The following troubles would be caused by voltage drop-down.
» Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the
normal function of a overload protection device.
» Proper starting power is not given to the compressor.
21
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
8. Installation
8.4.2 Wiring connection
• Connect the wires to the terminals on the control board ind vidually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit
respectively.
• In case of the system with multiple indoor units, mark each indoor unit as unit A, unit B, etc and be sure the
terminal board wiring to the outdoor unit and indoor units are properly matched. If wiring and piping between the
outdoor unit and an indoor unit are mismatched, the system may cause a malfunction.
WARNING
• Make sure that the screws of the terminal are fixed tightly.
• The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to
which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly
fastened. (If they are loose, it could give rise to burn-out of the wires.)
• Make sure to attach the sealing material or (field supplied) to hole of wiring to prevent the infiltration of foreign
particle from outside. Otherwise a short-circuit may occur inside the electric parts box.
• When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping
material to make appropriate clamps. Also, when wiring, make sure the cover on the electric parts box fits snugly
by arranging the wires neatly and attaching the electric parts box cover firmly. When attaching the electric parts
box cover, make sure no wires get caught in the edges. Pass wiring through the wiring through holes to prevent
damage to them.
• Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass
through the same locations outside of the unit, separating them properly, otherwise electrical noise (external
static) could cause product malfunction.
22
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
8. Installation
Display
Lead wire for
louver motor and
display
Inlet
InletGrille
Grill
CAUTION
• Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
23
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
8. Installation
Upward
Pipe clamp Hanger
routing
not allowed Max 300mm distance Hanger bracket
1~15m 1/50~1/100 slope
Indoor unit
Metal
Max 700mm
clamp
Maintenance
Flexible drain hose
drain port
Insulation
※ According to type of indoor unit, external appearance could be different. ※ According to type of indoor unit, external appearance could be different.
• Possible drain head height is upto 700 mm (27-6/19 inch). So the drain head should be installed below 700 mm
(27-6/19 inch).
• Be sure to install heat insulation on the drain piping.
– Heat insulation material: Polyethylene foam with thickness more than 8 mm (5/16 inch).
Thermal insulation
1/50~1/100 (Local supply)
Drain pipe
Drain Pipe Unit (Local supply)
Maximum 700mm
(27-9/16 inch)
Elbow
Drain pump
Drain Pump
※ According to type of indoor unit, external appearance could be different.
24
Single CAC Heat Pump Ceiling Mounted Cassette 4-way
8. Installation
Indoor Unit
Metal clamp
Thermal insulation(bend area)
※ According to type of indoor unit,
Drain pan external appearance could be different.
CAUTION
– The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may
cause a leakage of water.
– It is need to insulate the auxiliary drain hose with thermal insulation material.
Face piping
downward
Vent pipe
25
FDF
Heat Pump
1.List of Functions
2.Specifications
3.Dimensions
4.Piping diagrams
5.Wiring diagrams
6.Air flow and temperature distribution
7.Sound levels
8.Installation
Single CAC Heat Pump Ceiling Suspended Unit
1. List of functions
Category Functions AVNW36GM1P0 / AVNW48GM2P0 / AVNW60GM2P0
Air supply outlet 1
Airflow direction control (left & right) X
Airflow direction control (up & down) Auto
Auto swing (left & right) X
Air flow Auto swing (up & down) O
Airflow steps (fan/cool/heat) 4/5/4
Chaos wind(auto wind) X
Jet cool/heat O/X
Swirl wind* X
Triple filter (Deodorizing) X
Plasma air purifier PTPKM0 X
Air purifying
Allergy Safe filter X
Long-life prefilter (washable / anti-fungus) O
Drain pump X
E.S.P. control* X
Installation
Electric heater X
High ceiling operation* X
Hot start O
Reliability Self diagnosis O
Soft dry operation O
Auto changeover O
Auto cleaning X
Auto operation(artificial intelligence) O
Auto Restart O
Child lock* O
Forced operation O
Convenience
Group control* O
Sleep mode O
Timer(on/off) O
Timer(weekly)* O
Two thermistor control* O
Auto Elevation Grille PTEGM0 X
Network Solution(LGAP) O
PQWRHQ0FDB X
Wireless Remote Controller**
PQWRCQ0FDB O
PQRCVCL0Q(W) O
Simple
PQRCHCA0Q(W) O
Wired remote PREMTB001 O
controller Standard PREMTBB01 O
PREMTB100 O
Premium PREMTA000(A/B) O
Simple Contact PDRYCB000 O
PDRYCB400 X
Dry Contact
Communication type PDRYCB300 X
PDRYCB500 X
PHNFP14A0 X
Gateway IDU PI485
PSNFP14A0 X
Note
1. O : Applied, X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
2. Some functions can be limited by remote controller.
3. In case of ducted type indoor units using the wireless remote controller, it needs to connect the wired remote controller for received the signal of that.
4. In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
5. * : These functions need to connect the wired remote controller.
6. ** : It is included by default when the product is manufactured.
2
Single CAC Heat Pump Ceiling Suspended Unit
1. List of functions
Category Functions AVNW36GM1P0 / AVNW48GM2P0 / AVNW60GM2P0
Remote temperature sensor PQRSTA0 X
Zone controller ABZCA X
Electronic thermostat AQETC X
CTI(Communication transfer PKFC0 X
interface)
ETC CO2 Sensor PES-C0RV0 X
Group control wire PZCWRCG3 O
2-Remo Control wire PZCWRC2 X
Extension Wire PZCWRC1 X
Wi-Fi Controller* LG-IR-WF-1 X
Telecom shelter controller PQCSA001T0 X
Note
1. O : Applied, X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
2. Some functions can be limited by remote controller.
3. In case of ducted type indoor units using the wireless remote controller, it needs to connect the wired remote controller for received the signal of that.
4. In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
5. * : These functions need to connect the wired remote controller.
6. ** : It is included by default when the product is manufactured.
3
Single CAC Heat Pump Ceiling Suspended Unit
2. Specifications
AVNW48GM2P0
Model Name AVNW36GM1P0
AVNW60GM2P0
220-240, 1, 50/60 220-240, 1, 50/60
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input Nom. W 105.4 145.7
Running Current A 0.34 0.47
Exterior Color - Morning Fog Morning Fog
WxHxD mm 1,200 x 235 x 690 1,600 x 235 x 690
Dimensions Body
WxHxD inch 47-1/4 x 9-1/4 x 27-5/32 63 x 9-1/4 x 27-5/32
Net kg (lbs) 28.0 (61.7) 35.0 (77.2)
Weight
Shipping kg (lbs) 34.5 (76.1) 43.0 (94.8)
(Row x Column x FPI) x No. - (3 x 18 x 18) x 1 (3 x 18 x 18) x 1
Heat Exchanger
Face Area m2 (ft2) 0.31 (3.34) 0.46 (4.95)
Type - Cross Flow Fan Cross Flow Fan
Fan H/M/L m3/min 20.0 / 18.0 / 16.0 30.0 / 25.0 / 20.0
Air Flow Rate
H/M/L ft3/min 706 / 636 / 565 1,059 / 882.5 / 706
Type - BLDC BLDC
Fan Motor
Output W x No. 85.9 x 1 125.0 x 1
Dehumidification Rate l /h (pts/h) 3.8 (8.1) 6.5 (13.8)
Sound Pressure Cooling H/M/L dB(A) 47 / 45 / 42 50 / 46 / 42
Level Heating H/M/L dB(A) 47 / 45 / 42 50 / 46 / 42
Sound Power Level Cooling Max. dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping Connections Gas mm(inch) Ø 15.88 (5/8) Ø 19.05 (3/4)
Drain (O.D. / I.D.) mm Ø 21.5 / 16.0 Ø 21.5 / 16.0
- Fuse
Safety Devices
- Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 4C x 0.75 4C x 0.75
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound Level Values are measured at Anechoic chamber. Therefore, these values depend on the ambient conditions and values are normally higher
in actual operation.
4. Capacities are net capacities and based on the following conditions. Refer to the Outdoor Unit Specifications for calculating the real capacity.
• Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
4
Single CAC Heat Pump Ceiling Suspended Unit
3. Dimensions
[VM1 Chassis] AVNW36GM1P0
5
Single CAC Heat Pump Ceiling Suspended Unit
3. Dimensions
[VM2 Chassis] AVNW48GM2P0 / AVNW60GM2P0
6
Single CAC Heat Pump Ceiling Suspended Unit
4. Piping diagrams
Heating
Th3
Cooling Cross Flow Fan
M Th1
Th2
Strainer
7
Single CAC Heat Pump Ceiling Suspended Unit
5. Wiring Diagrams
̰ AVNW36GM1P0 / AVNW48GM2P0 / AVNW60GM2P0
SW01
OFF
ON
8 7 6 5 4 3 2 1
MEZ65001211
8
Single CAC Heat Pump Ceiling Suspended Unit
Cooling Heating
Discharge angle: 0° Discharge angle: 0°
Y YU^ YU^
XU\ XU\
XUW
X Y WU\ Y
WU\
X
X
W
_ ^ ] \ [ Z Y X W W
_ ^ ] \ [ Z Y X W
YU^ Z_ [W [Y YU^
YY X[ Z]
Z[
YW ZY
X] Y
Y
ZW
X_
X X
W W
_ ^ ] \ [ Z Y X W
_ ^ ] \ [ Z Y X W
Cooling Heating
Discharge angle: 0° Discharge angle: 0°
YU^ YU^
XU\ XUW XU\
XUW Y WU\ Y
WU\
X X
W W
_ ^ ] \ [ Z Y X W _ ^ ] \ [ Z Y X W
YU^ YU^
[Y [[
Z_ Z] [W
X_ XY
Z[
Y Y
X[
ZY
X] X_ ZW ZY
Y_
X X
X_
W W
_ ^ ] \ [ Z Y X W _ ^ ] \ [ Z Y X W
9
Single CAC Heat Pump Ceiling Suspended Unit
7. Sound levels
7.1 Sound pressure level
̰ Overall
Note
1.Sound measured at some distance away from the center
of the unit.
2.Data is valid at free field condition.
3.Reference accoustic pressure 0dB = 20μPa.
4.Data is valid at nominal operation condition.
1m Refer to the Model Specifications for nominal
conditions(Power source and Ambient temperature, etc)
1m
AVNW48GM2P0
AVNW36GM1P0 AVNW60GM2P0
_WG _WG
o o
̵ t ̵ t
vGiGzGwGsGOWiGdGYWɆwPG
vGiGzGwGsGOWiGdGYWɆwPG
ujT]\G ujT]\G
]WG ]WG
ujT]WG ujT]WG
ujT\\G ujT\\G
\WG \WG
ujT\WG ujT\WG
ujT[\G ujT[\G
[WG [WG
ujT[WG ujT[WG
ujTZ\G ujTZ\G
ZWG ZWG
ujTZWG ujTZWG
hG hG
ujTYWG ujTYWG
oGG oGG
{G {G
ujTX\G ujTX\G
XWG XWG
]ZG XY\G Y\WG \WWG XWWWG YWWWG [WWWG _WWWG ]ZG XY\G Y\WG \WWG XWWWG YWWWG [WWWG _WWWG
vGiGjGm GOo¡PG vGiGjGm GOo¡PG
10
Single CAC Heat Pump Ceiling Suspended Unit
8. Installation
• Please read the instruction sheets completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards.
• Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning,
temperature control, etc.)
Signal Receiver
Air Intake (Wireless remote controller)
11
Single CAC Heat Pump Ceiling Suspended Unit
8. Installation
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.
※ According to type of indoor unit, external appearance
or installed structure could be different.
Air conditioner or
Ducted air diffuser
Take enough
distance
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
2. Avoid installing air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
CAUTION
• If the temperature rise above 30 or the humidity rise above RH 80%, the dew-protective kit should be equipped
or use additional insulation to the indoor unit body.
– "Dew Protective kit" is sold separately.
– Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least.
[Unit: mm(inch)]
10 (13/32)
or more
300 (11-13/16)
or more
2500 (98-3/7)
or more
Floor
12
Single CAC Heat Pump Ceiling Suspended Unit
8. Installation
CAUTION
• During the installation, care should be taken not to damage electric wires.
• In case of using a drain pump, install the unit horizontally using a level gauge.
Ceiling
Level gauge
1. The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.
2. Select and mark the position for fixing bolts and piping hole.
3. Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
4. Drill the hole for anchor bolt on the wall or ceiling.
• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
• Mount the suspension bolts to the set anchor firmly.
• Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring
washers.
5. In case of ducted type unit, apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
13
Single CAC Heat Pump Ceiling Suspended Unit
8. Installation
a Set anchor
b Plate washer
c Spring washer
d Nut
e Suspension
bolts
14
Single CAC Heat Pump Ceiling Suspended Unit
8. Installation
8.2.2 Preparing work for Installation
Left side
Backside cover
Backside
Important
• It is recommended to select the left side for drain to have common hole in the side-cover along with pipe and
wiring.
• Knock hole on right side-cover only if right side is selected for water drain.
CAUTION
• Hold the side-cover with other hand while tapping to prevent it to fall down.
15
Single CAC Heat Pump Ceiling Suspended Unit
8. Installation
̰ Drill a hole in the wall
5~7mm
8.2.3 Indoor unit installation
Hang the Indoor unit on suspension bolt as per following guidelines:
1) Lift the indoor unit to sufficient height.
2) Insert the suspended part of four suspension bolt in the four hangers provided on the side of main body one
by one.
3) Lower the indoor unit till the hangers rest on their respective flat washer.
4) Adjust the level in the top down direction by adjusting the suspension bolts. Inclined the indoor unit as per
direction provided in the figures.
CAUTION
• Installation with declination of the indoor unit is very important for the drain of air conditioner.
• Minimum thickness of the insulation for the connecting pipe shall be 10mm.
• If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the
bottomside.
[ Front of view ]
• The unit must be horizontal or inclined at angle.
• The inclination should be less than or equal to 1° or in between 10 to 20mm inclined in drain direction as shown
in fig.
Ceiling
10~20 mm
[ Side of view ]
• The unit must be declined to the bottomside of the unit when finished installation.
j
\¥XWG
16
Single CAC Heat Pump Ceiling Suspended Unit
8. Installation
8.3 Indoor Unit Drain Piping
Pipe clamp
Upward Thermal insulator
routing (Local supply)
not allowed
Important
i
kG
• The drain hose should point downward for easy drain flow. Downward slope
Water Water
leakage leakage Ditch
Accumulated
drain water
Air Less than
50mm gap
Water
Waving
leakage
17
Single CAC Heat Pump Ceiling Suspended Unit
8. Installation
8.3.2 Drain test
Drainage test of indoor unit
Use the following procedure to test the drainage.
1.In case that there are air filter, remove the air filter first.
2.Spray one or two glasses of water on the evaporator.
3.Check the drainage. Ensure that water flows through drain
hose of indoor unit without any leakage.
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
– Never fail to have separate power specially for the air conditioner.
– Provide a circuit breaker switch between power source and the unit.
– Confirm the Specification of power source.
– Confirm that electrical capacity is sufficient.
– Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
– Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
– Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
– The following troubles would be caused by voltage drop-down.
» Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the
normal function of a overload protection device.
» Proper starting power is not given to the compressor.
18
Single CAC Heat Pump Ceiling Suspended Unit
8. Installation
8.4.2 Wiring connection
• Connect the wires to the terminals on the control board ind vidually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit
respectively.
• In case of the system with multiple indoor units, mark each indoor unit as unit A, unit B, etc and be sure the
terminal board wiring to the outdoor unit and indoor units are properly matched. If wiring and piping between the
outdoor unit and an indoor unit are mismatched, the system may cause a malfunction.
WARNING
• Make sure that the screws of the terminal are fixed tightly.
• The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to
which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly
fastened. (If they are loose, it could give rise to burn-out of the wires.)
• Make sure to attach the sealing material or (field supplied) to hole of wiring to prevent the infiltration of foreign
particle from outside. Otherwise a short-circuit may occur inside the electric parts box.
• When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping
material to make appropriate clamps. Also, when wiring, make sure the cover on the electric parts box fits snugly
by arranging the wires neatly and attaching the electric parts box cover firmly. When attaching the electric parts
box cover, make sure no wires get caught in the edges. Pass wiring through the wiring through holes to prevent
damage to them.
• Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass
through the same locations outside of the unit, separating them properly, otherwise electrical noise (external
static) could cause product malfunction.
19
FDF
Heat Pump
Outdoor units
Single CAC
1.List of Functions
2.Specifications
3.Dimensions
4.Piping diagrams
5.Wiring diagrams
6.Capacity tables
7.Capacity Correction Factor
8.Operation range
9.Electric characteristics
10.Sound levels
Single CAC Heat Pump Outdoor units
1. List of functions
ATUW36GMLP0 / AVUW36GM1P0
Category Functions ATUW18GPLP0 / ATUW24GPLP0 ATUW48GMLP0 / AVUW48GM2P0
ATUW60GMLP0 / AVUW60GM2P0
Defrost / Deicing O O
High pressure switch X X
Low pressure switch X X
Reliability Phase protection X X
Restart delay (3-minutes) O O
Self diagnosis O O
Soft start O O
Test function O O
Night Silent Operation X X
Wiring Error Check X X
Convenience Peak Control X X
Mode Lock X X
Forced Cooling Operation(Outdoor Unit) O O
SLC (Smart Load Control) X X
Network function Network solution(LGAP) X O
ATUW36GMLP0 / AVUW36GM1P0
Device ATUW18GPLP0 / ATUW24GPLP0 ATUW48GMLP0 / AVUW48GM2P0
ATUW60GMLP0 / AVUW60GM2P0
AC Ez (Simple Controller) X PQCSZ250S0
AC Ez Touch X PACEZA000
AC Smart IV X PACS4B000
Central Controller
ACP IV X PACP4B000
AC Manager IV X PACM4B000
PI485 X PMNFP14A1
BNU (Building LONWORKS Gateway X PLNWKB000
Network Unit) BACnet Gateway X PQNFB17C0
Low Ambient Kit O (Logical operation*) O (Logical operation*)
Note
1. O : Applied, X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
2
Single CAC Heat Pump Outdoor units
2. Specifications
̰ Ceiling Cassette 4-way
Outdoor unit ATUW18GPLP0 ATUW24GPLP0
Combination
Indoor unit ATNW18GPLP0 ATNW24GPLP0
Min. ~ Rated ~ Max. kW 1.80 ~ 5.28 ~ 5.60 2.80 ~ 7.03 ~ 8.20
Cooling*
Min. ~ Rated ~ Max. Btu/h 6,100 ~ 18,000 ~ 19,000 9,600 ~ 24,000 ~ 28,000
Capacity
Min. ~ Rated ~ Max. kW 1.90 ~ 5.20 ~ 5.80 3.00 ~ 7.60 ~ 8.60
Heating*
Min. ~ Rated ~ Max. Btu/h 6,500 ~ 17,740 ~ 19,800 10,200 ~ 25,930 ~ 29,300
Cooling* Rated W 1,630 2,170
Power Input
Heating* Rated W 1,525 2,235
Cooling* Rated A 7.4 9.9
Running Current
Heating* Rated A 6.9 10.2
EER / COP Cooling* / Heating* W/W 3.24 / 3.41 3.24 / 3.40
3
Single CAC Heat Pump Outdoor units
2. Specifications
4
Single CAC Heat Pump Outdoor units
2. Specifications
5
Single CAC Heat Pump Outdoor units
2. Specifications
ATUW36GMLP0 ATUW48GMLP0
Outdoor unit
AVUW36GM1P0 AVUW48GM2P0
220-240, 1, 50 220-240, 1, 50
Power Supply V , Ø , Hz
220, 1, 60 220, 1, 60
Power Factor Rated - 0.98 0.98
Power Supply Cable
Wiring Connections (included Earth) No. x mm2 3C x 2.5 3C x 6.0
6
Single CAC Heat Pump Outdoor units
2. Specifications
ATUW60GMLP0
Outdoor unit
AVUW60GM2P0
220-240, 1, 50
Power Supply V , Ø , Hz
220, 1, 60
Power Factor Rated - 0.98
Power Supply Cable
Wiring Connections (included Earth) No. x mm2 3C x 6.0
7
Single CAC Heat Pump Outdoor units
3. Dimensions
[UL2 Chassis] ATUW18GPLP0
8
Single CAC Heat Pump Outdoor units
3. Dimensions
[U24A Chassis] ATUW24GPLP0
9
Single CAC Heat Pump Outdoor units
3. Dimensions
[U4 Chassis] ATUW36GMLP0 / AVUW36GM1P0
10
Single CAC Heat Pump Outdoor units
3. Dimensions
[U3 Chassis] ATUW48GMLP0 / AVUW48GM2P0 / ATUW60GMLP0 / AVUW60GM2P0
11
Single CAC Heat Pump Outdoor units
4. Piping diagrams
̰ ATUW18GPLP0
Outdoor Unit
Inlet Air
Temperature
Refrigerant Flow Condenser Out Thermistor
Temperature
Thermistor
Cooling
Heating
Condensing
Temperature
Thermistor
Flare Connection
M
Electronic
Strainer Expansion
Valve
Pressure
Sensor
4 way
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator
Suction
Temperature
Thermistor
Inverter
Compressor
12
Single CAC Heat Pump Outdoor units
4. Piping diagrams
̰ ATUW24GPLP0 / ATUW36GMLP0 / AVUW36GM1P0
Condensing
Temperature
Thermistor
Flare Connection
M
Strainer Strainer
Electronic
Expansion Valve
Pressure
Sensor
4 way
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator
Suction
Temperature
Thermistor Inverter
Compressor
13
Single CAC Heat Pump Outdoor units
4. Piping diagrams
̰ ATUW48GMLP0 / AVUW48GM2P0 / ATUW60GMLP0 / AVUW60GM2P0
Outdoor Unit Inlet Air
Refrigerant Flow Condenser Out Temperature
Temperature Thermistor
Cooling Thermistor
Heating
Condensing
Temperature
Thermistor
Flare Connection
M
Strainer Strainer
Electronic
Expansion Valve
Pressure
Sensor
4 way
Valve
Flare Connection
Discharge
Temperature
Accumulator Thermistor
Suction
Temperature
Thermistor Inverter
Compressor
14
Single CAC Heat Pump Outdoor units
5. Wiring diagrams
̰ ATUW18GPLP0
MEZ66178908
̰ ATUW24GPLP0
NOTE:
BK BR
WH RD
GN WH
YL BL
VI
FAN
MOTOR
BR
220-240 V~ 50 Hz
BL
RD BL
COMPRESSOR
FUSE
YL
BR
RD
BL
RD
BK
BL
BL
MEZ66178913
15
Single CAC Heat Pump Outdoor units
5. Wiring diagrams
̰ ATUW36GMLP0 / AVUW36GM1P0
F01Q 250V,3.15A
FUSE01M 250V,3.15A
FUSE1K 250V, 25A
ON
OFF
12 34 5
FUSE1K
F01Q
FUSE01M
CN_LGMV_BL
MEZ66178914
16
Single CAC Heat Pump Outdoor units
5. Wiring diagrams
̰ ATUW48GMLP0 / AVUW48GM2P0 / ATUW60GMLP0 / AVUW60GM2P0
DIP_SW01D
1 2 3 4 5 6 7 8 9 10
ON
OFF
MEZ66178916
17
Single CAC Heat Pump Outdoor units
6. Capacity tables
6.1 Cooling Capacity
̰ Ceiling Cassette 4-way
ATUW18GPLP0 + ATNW18GPLP0
Outdoor Indoor Air Temperature : °CDB / °CWB
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 30.0 / 22.0 32.0 / 24.0
°CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
20.0 5.18 4.39 0.91 5.50 4.45 1.19 5.81 4.48 1.29 5.97 4.52 1.30 6.45 4.61 1.30 6.77 4.70 1.33
25.0 4.95 4.25 1.10 5.27 4.31 1.26 5.59 4.36 1.29 5.75 4.40 1.31 6.22 4.50 1.34 6.54 4.59 1.35
32.0 4.65 4.08 1.26 4.97 4.15 1.45 5.28 4.21 1.52 5.44 4.26 1.54 5.91 4.37 1.58 6.23 4.47 1.61
35.0 4.51 3.94 1.37 4.82 4.02 1.56 5.14 4.08 1.62 5.28 4.12 1.63 5.76 4.25 1.67 6.08 4.35 1.70
40.0 4.31 3.82 1.51 4.62 3.91 1.63 4.94 3.98 1.65 5.10 4.03 1.65 5.57 4.16 1.68 5.88 4.26 1.71
43.0 3.95 3.47 1.50 4.23 3.55 1.65 4.51 3.61 1.70 4.65 3.65 1.71 5.08 3.76 1.74 5.36 3.86 1.78
46.0 3.59 3.14 1.48 3.84 3.21 1.68 4.09 3.26 1.75 4.20 3.29 1.76 4.59 3.39 1.80 4.84 3.47 1.84
48.0 3.35 2.97 1.32 3.58 3.02 1.51 3.81 3.07 1.56 3.91 3.09 1.57 4.26 3.18 1.59 4.49 3.26 1.61
ATUW24GPLP0 + ATNW24GPLP0
Outdoor Indoor Air Temperature : °CDB / °CWB
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 30.0 / 22.0 32.0 / 24.0
°CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
20.0 6.89 5.84 1.21 7.32 5.91 1.58 7.74 5.96 1.71 7.95 6.02 1.73 8.59 6.14 1.73 9.02 6.25 1.77
25.0 6.59 5.65 1.47 7.02 5.74 1.68 7.44 5.80 1.72 7.65 5.85 1.75 8.28 5.99 1.78 8.70 6.11 1.79
32.0 6.19 5.42 1.68 6.61 5.52 1.93 7.03 5.60 2.03 7.24 5.66 2.05 7.87 5.81 2.10 8.29 5.94 2.14
35.0 6.00 5.24 1.83 6.42 5.35 2.08 6.84 5.43 2.15 7.03 5.48 2.17 7.67 5.65 2.22 8.09 5.78 2.26
40.0 5.74 5.08 2.01 6.16 5.20 2.16 6.58 5.29 2.19 6.78 5.36 2.20 7.41 5.53 2.23 7.83 5.67 2.28
43.0 5.30 4.65 2.02 5.67 4.75 2.24 6.05 4.83 2.30 6.23 4.89 2.31 6.81 5.04 2.35 7.19 5.17 2.40
46.0 4.85 4.25 2.04 5.19 4.34 2.32 5.53 4.40 2.40 5.68 4.44 2.42 6.21 4.58 2.47 6.54 4.69 2.52
48.0 4.56 4.03 1.83 4.87 4.11 2.09 5.18 4.17 2.16 5.32 4.20 2.18 5.80 4.33 2.21 6.11 4.43 2.24
ATUW36GMLP0 + ATNW36GMLP0
Outdoor Indoor Air Temperature : °CDB / °CWB
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 30.0 / 22.0 32.0 / 24.0
°CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
20.0 8.90 8.07 1.56 9.45 8.18 2.04 10.00 8.25 2.21 10.27 8.32 2.24 11.10 8.49 2.24 11.64 8.65 2.28
25.0 8.52 7.81 1.90 9.06 7.93 2.17 9.61 8.02 2.22 9.88 8.10 2.26 10.70 8.28 2.29 11.24 8.45 2.31
32.0 8.00 7.50 2.17 8.54 7.64 2.49 9.08 7.75 2.62 9.35 7.83 2.65 10.17 8.04 2.71 10.71 8.22 2.76
35.0 7.75 7.24 2.36 8.29 7.40 2.68 8.83 7.51 2.78 9.08 7.58 2.80 9.91 7.81 2.86 10.45 8.00 2.92
40.0 7.41 7.02 2.59 7.95 7.19 2.79 8.49 7.32 2.83 8.76 7.42 2.84 9.57 7.65 2.88 10.11 7.85 2.95
43.0 6.87 6.46 2.48 7.36 6.60 2.74 7.85 6.71 2.81 8.09 6.79 2.82 8.83 7.00 2.88 9.32 7.18 2.94
46.0 6.33 5.93 2.37 6.77 6.05 2.69 7.21 6.15 2.78 7.41 6.21 2.81 8.09 6.40 2.87 8.53 6.55 2.93
48.0 5.97 5.65 2.11 6.37 5.76 2.41 6.78 5.85 2.49 6.96 5.89 2.50 7.60 6.07 2.54 8.00 6.21 2.58
ATUW48GMLP0 + ATNW48GMLP0
Outdoor Indoor Air Temperature : °CDB / °CWB
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 30.0 / 22.0 32.0 / 24.0
°CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
20.0 13.51 10.42 2.37 14.34 10.56 3.10 15.18 10.65 3.35 15.59 10.74 3.39 16.84 10.96 3.39 17.67 11.16 3.46
25.0 12.92 10.09 2.88 13.75 10.24 3.29 14.58 10.35 3.37 14.99 10.45 3.42 16.24 10.69 3.48 17.06 10.90 3.51
32.0 12.13 9.68 3.29 12.96 9.86 3.79 13.78 10.00 3.97 14.19 10.11 4.02 15.43 10.38 4.11 16.25 10.62 4.19
35.0 11.76 9.35 3.58 12.58 9.55 4.07 13.40 9.69 4.21 13.78 9.79 4.25 15.04 10.09 4.34 15.86 10.33 4.43
40.0 11.25 9.07 3.93 12.07 9.28 4.24 12.89 9.45 4.30 13.30 9.58 4.31 14.53 9.88 4.38 15.35 10.13 4.47
43.0 10.63 8.50 4.07 11.39 8.69 4.50 12.15 8.84 4.62 12.52 8.94 4.65 13.67 9.22 4.74 14.43 9.45 4.83
46.0 10.02 7.99 4.20 10.71 8.15 4.77 11.41 8.28 4.95 11.73 8.36 4.99 12.81 8.62 5.10 13.51 8.82 5.20
48.0 9.61 7.74 3.89 10.26 7.89 4.43 10.92 8.01 4.58 11.21 8.07 4.62 12.24 8.32 4.69 12.89 8.51 4.77
Note
1. DB : Dry bulb temperature(), WB : Wet bulb temperature()
2. TC : Total capacity(kW), SHC : Sensible Heating Capacity(kW)
3. PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
4. All capacities are net. A deduction (cooling mode) or an addition (heating mode) of Capacity due to operating heat of indoor unit motor is reflected.
5. Direct interpolation is permissible. Do not extrapolate.
6. Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table. Except for
rated value, the performance is not guaranteed.
7. In accordance with the test standard(or nations), the rating will vary slightly.
18
Single CAC Heat Pump Outdoor units
6. Capacity tables
ATUW60GMLP0 + ATNW60GMLP0
Outdoor Indoor Air Temperature : °CDB / °CWB
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 30.0 / 22.0 32.0 / 24.0
°CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
20.0 14.36 10.86 2.69 15.25 11.01 3.53 16.13 11.10 3.81 16.58 11.20 3.86 17.90 11.42 3.86 18.79 11.64 3.93
25.0 13.74 10.51 3.27 14.62 10.68 3.73 15.50 10.79 3.83 15.94 10.90 3.89 17.26 11.14 3.96 18.14 11.37 3.99
32.0 12.90 10.09 3.74 13.78 10.28 4.30 14.65 10.43 4.52 15.09 10.54 4.57 16.40 10.82 4.67 17.28 11.07 4.76
35.0 12.51 9.75 4.07 13.38 9.95 4.62 14.25 10.10 4.79 14.65 10.20 4.83 15.99 10.52 4.94 16.86 10.76 5.04
40.0 11.96 9.45 4.47 12.83 9.68 4.82 13.70 9.85 4.88 14.14 9.98 4.90 15.44 10.30 4.97 16.32 10.56 5.08
43.0 11.07 8.68 4.39 11.86 8.88 4.86 12.65 9.02 4.98 13.03 9.13 5.01 14.23 9.41 5.10 15.02 9.64 5.21
46.0 10.18 7.96 4.32 10.89 8.13 4.90 11.60 8.25 5.08 11.93 8.33 5.12 13.02 8.59 5.23 13.73 8.79 5.34
48.0 9.59 7.58 3.89 10.24 7.72 4.45 10.90 7.84 4.60 11.19 7.90 4.63 12.21 8.14 4.69 12.86 8.32 4.77
Note
1. DB : Dry bulb temperature(), WB : Wet bulb temperature()
2. TC : Total capacity(kW), SHC : Sensible Heating Capacity(kW)
3. PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
4. All capacities are net. A deduction (cooling mode) or an addition (heating mode) of Capacity due to operating heat of indoor unit motor is reflected.
5. Direct interpolation is permissible. Do not extrapolate.
6. Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table. Except for
rated value, the performance is not guaranteed.
7. In accordance with the test standard(or nations), the rating will vary slightly.
19
Single CAC Heat Pump Outdoor units
6. Capacity tables
̰ Ceiling Suspended Unit
AVUW36GM1P0 + AVNW36GM1P0
Outdoor Indoor Air Temperature : °CDB / °CWB
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 30.0 / 22.0 32.0 / 24.0
°CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
20.0 8.33 6.80 1.46 8.85 6.88 1.91 9.36 6.94 2.07 9.62 7.01 2.09 10.39 7.14 2.09 10.90 7.28 2.13
25.0 7.97 6.58 1.77 8.48 6.68 2.03 8.99 6.75 2.08 9.25 6.81 2.11 10.01 6.97 2.15 10.53 7.11 2.17
32.0 7.49 6.31 2.03 7.99 6.43 2.33 8.50 6.52 2.45 8.76 6.59 2.48 9.52 6.77 2.54 10.03 6.92 2.58
35.0 7.26 6.10 2.21 7.76 6.22 2.51 8.27 6.32 2.60 8.50 6.38 2.62 9.28 6.58 2.68 9.78 6.73 2.73
40.0 6.94 5.91 2.42 7.44 6.05 2.61 7.95 6.16 2.65 8.20 6.24 2.66 8.96 6.44 2.70 9.47 6.60 2.76
43.0 6.81 5.75 2.11 7.29 5.88 2.33 7.78 5.98 2.38 8.01 6.05 2.40 8.75 6.24 2.44 9.23 6.39 2.49
46.0 6.68 5.63 1.80 7.14 5.74 2.04 7.61 5.83 2.12 7.82 5.89 2.14 8.54 6.07 2.18 9.00 6.21 2.23
48.0 6.59 5.61 1.70 7.04 5.72 1.93 7.49 5.81 2.00 7.69 5.85 2.01 8.40 6.03 2.05 8.85 6.17 2.09
AVUW48GM2P0 + AVNW48GM2P0
Outdoor Indoor Air Temperature : °CDB / °CWB
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 30.0 / 22.0 32.0 / 24.0
°CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
20.0 13.51 10.51 2.37 14.34 10.65 3.10 15.18 10.74 3.35 15.59 10.84 3.39 16.84 11.05 3.39 17.67 11.26 3.46
25.0 12.92 10.17 2.88 13.75 10.33 3.29 14.58 10.44 3.37 14.99 10.54 3.42 16.24 10.78 3.48 17.06 11.00 3.51
32.0 12.13 9.76 3.29 12.96 9.95 3.79 13.78 10.09 3.97 14.19 10.20 4.02 15.43 10.47 4.11 16.25 10.71 4.19
35.0 11.76 9.43 3.58 12.58 9.63 4.07 13.40 9.78 4.21 13.78 9.87 4.25 15.04 10.17 4.34 15.86 10.41 4.43
40.0 11.25 9.15 3.93 12.07 9.36 4.24 12.89 9.53 4.30 13.30 9.66 4.31 14.53 9.96 4.38 15.35 10.22 4.47
43.0 11.04 8.90 3.43 11.82 9.10 3.78 12.61 9.25 3.87 12.99 9.36 3.89 14.18 9.65 3.96 14.97 9.89 4.04
46.0 10.82 8.71 2.92 11.58 8.89 3.32 12.33 9.02 3.44 12.68 9.11 3.47 13.84 9.39 3.54 14.59 9.61 3.61
48.0 10.68 8.68 2.75 11.41 8.85 3.13 12.15 8.98 3.24 12.47 9.06 3.27 13.61 9.33 3.32 14.34 9.55 3.38
AVUW60GM2P0 + AVNW60GM2P0
Outdoor Indoor Air Temperature : °CDB / °CWB
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 30.0 / 22.0 32.0 / 24.0
°CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
20.0 14.90 11.17 2.79 15.82 11.32 3.66 16.74 11.42 3.95 17.20 11.52 4.00 18.57 11.75 4.00 19.49 11.97 4.08
25.0 14.26 10.81 3.39 15.17 10.98 3.87 16.08 11.10 3.98 16.54 11.20 4.04 17.91 11.46 4.10 18.82 11.69 4.14
32.0 13.38 10.38 3.88 14.29 10.57 4.46 15.20 10.72 4.69 15.66 10.84 4.74 17.02 11.13 4.85 17.93 11.38 4.94
35.0 12.98 10.03 4.22 13.88 10.23 4.79 14.79 10.39 4.97 15.20 10.49 5.01 16.59 10.81 5.12 17.50 11.07 5.22
40.0 12.41 9.72 4.64 13.31 9.95 5.00 14.22 10.13 5.07 14.67 10.26 5.08 16.02 10.59 5.16 16.93 10.86 5.27
43.0 12.17 9.46 4.04 13.04 9.67 4.45 13.91 9.84 4.56 14.33 9.95 4.58 15.65 10.26 4.67 16.51 10.51 4.77
46.0 11.94 9.25 3.44 12.77 9.44 3.91 13.60 9.59 4.05 13.98 9.68 4.09 15.27 9.98 4.18 16.10 10.22 4.26
48.0 11.78 9.23 3.26 12.59 9.41 3.71 13.40 9.55 3.84 13.76 9.62 3.87 15.01 9.92 3.93 15.82 10.15 4.01
Note
1. DB : Dry bulb temperature(), WB : Wet bulb temperature()
2. TC : Total capacity(kW), SHC : Sensible Heating Capacity(kW)
3. PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
4. All capacities are net. A deduction (cooling mode) or an addition (heating mode) of Capacity due to operating heat of indoor unit motor is reflected.
5. Direct interpolation is permissible. Do not extrapolate.
6. Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table. Except for
rated value, the performance is not guaranteed.
7. In accordance with the test standard(or nations), the rating will vary slightly.
20
Single CAC Heat Pump Outdoor units
6. Capacity tables
ATUW24GPLP0 + ATNW24GPLP0
Outdoor Air Indoor Air Temperature : °CDB
Temp. 16.0 18.0 20.0 21.0 22.0 24.0
°CWB TC PI TC PI TC PI TC PI TC PI TC PI
-10.0 6.01 1.78 6.00 1.82 6.00 1.87 6.00 1.89 6.00 1.92 5.94 1.98
-5.0 6.52 1.86 6.52 1.91 6.53 1.97 6.53 2.00 6.52 2.02 6.45 2.08
0.0 6.96 2.00 6.96 2.06 6.94 2.11 6.92 2.14 6.90 2.16 6.85 2.22
6.0 7.73 2.14 7.68 2.19 7.60 2.24 7.55 2.26 7.50 2.28 7.44 2.31
10.0 8.16 2.23 8.06 2.27 8.01 2.30 8.01 2.32 8.00 2.33 7.86 2.35
15.0 8.86 2.37 8.83 2.40 8.85 2.41 8.79 2.42 8.72 2.42 8.62 2.43
18.0 9.27 2.45 9.16 2.46 9.07 2.46 8.95 2.45 8.82 2.44 8.58 2.43
ATUW36GMLP0 + ATNW36GMLP0
Outdoor Air Indoor Air Temperature : °CDB
Temp. 16.0 18.0 20.0 21.0 22.0 24.0
°CWB TC PI TC PI TC PI TC PI TC PI TC PI
-10.0 8.86 2.54 8.85 2.60 8.84 2.67 8.84 2.70 8.85 2.74 8.76 2.82
-5.0 9.60 2.66 9.61 2.73 9.62 2.81 9.62 2.85 9.62 2.89 9.50 2.97
0.0 10.26 2.85 10.25 2.93 10.23 3.01 10.20 3.05 10.17 3.09 10.09 3.16
6.0 11.38 3.05 11.31 3.12 11.20 3.19 11.13 3.22 11.05 3.25 10.96 3.30
10.0 12.03 3.18 11.88 3.24 11.80 3.29 11.80 3.31 11.79 3.33 11.59 3.36
15.0 13.06 3.38 13.01 3.42 13.04 3.44 12.95 3.45 12.84 3.45 12.70 3.47
18.0 13.66 3.50 13.49 3.51 13.37 3.51 13.19 3.49 12.99 3.48 12.64 3.47
ATUW48GMLP0 + ATNW48GMLP0
Outdoor Air Indoor Air Temperature : °CDB
Temp. 16.0 18.0 20.0 21.0 22.0 24.0
°CWB TC PI TC PI TC PI TC PI TC PI TC PI
-10.0 12.10 3.57 12.08 3.66 12.08 3.76 12.08 3.81 12.08 3.86 11.97 3.97
-5.0 13.12 3.74 13.13 3.85 13.14 3.96 13.14 4.01 13.14 4.07 12.98 4.18
0.0 14.01 4.02 14.00 4.13 13.97 4.24 13.94 4.29 13.90 4.35 13.79 4.45
6.0 15.55 4.30 15.45 4.40 15.30 4.49 15.20 4.53 15.09 4.57 14.97 4.65
10.0 16.43 4.47 16.23 4.56 16.12 4.63 16.12 4.66 16.10 4.68 15.83 4.73
15.0 17.83 4.76 17.78 4.82 17.81 4.85 17.69 4.85 17.55 4.85 17.35 4.89
18.0 18.66 4.92 18.43 4.94 18.26 4.93 18.02 4.92 17.75 4.90 17.27 4.88
Note
1. DB : Dry bulb temperature(), WB : Wet bulb temperature()
2. TC : Total capacity(kW), SHC : Sensible Heating Capacity(kW)
3. PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
4. All capacities are net. A deduction (cooling mode) or an addition (heating mode) of Capacity due to operating heat of indoor unit motor is reflected.
5. Direct interpolation is permissible. Do not extrapolate.
6. Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table. Except for
rated value, the performance is not guaranteed.
7. In accordance with the test standard(or nations), the rating will vary slightly.
21
Single CAC Heat Pump Outdoor units
6. Capacity tables
ATUW60GMLP0 + ATNW60GMLP0
Outdoor Air Indoor Air Temperature : °CDB
Temp. 16.0 18.0 20.0 21.0 22.0 24.0
°CWB TC PI TC PI TC PI TC PI TC PI TC PI
-10.0 13.37 4.34 13.35 4.44 13.34 4.56 13.35 4.62 13.35 4.68 13.22 4.82
-5.0 14.49 4.54 14.51 4.67 14.52 4.80 14.52 4.87 14.51 4.94 14.33 5.08
0.0 15.48 4.87 15.47 5.01 15.43 5.15 15.40 5.21 15.35 5.28 15.23 5.40
6.0 17.18 5.22 17.07 5.34 16.90 5.45 16.79 5.50 16.67 5.55 16.54 5.64
10.0 18.15 5.43 17.93 5.53 17.81 5.62 17.81 5.65 17.78 5.68 17.49 5.74
15.0 19.70 5.78 19.64 5.85 19.67 5.88 19.54 5.89 19.38 5.89 19.16 5.93
18.0 20.62 5.97 20.36 6.00 20.17 5.99 19.91 5.97 19.60 5.94 19.07 5.92
Note
1. DB : Dry bulb temperature(), WB : Wet bulb temperature()
2. TC : Total capacity(kW), SHC : Sensible Heating Capacity(kW)
3. PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
4. All capacities are net. A deduction (cooling mode) or an addition (heating mode) of Capacity due to operating heat of indoor unit motor is reflected.
5. Direct interpolation is permissible. Do not extrapolate.
6. Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table. Except for
rated value, the performance is not guaranteed.
7. In accordance with the test standard(or nations), the rating will vary slightly.
22
Single CAC Heat Pump Outdoor units
6. Capacity tables
̰ Ceiling Suspended Unit
AVUW36GM1P0 + AVNW36GM1P0
Outdoor Air Indoor Air Temperature : °CDB
Temp. 16.0 18.0 20.0 21.0 22.0 24.0
°CWB TC PI TC PI TC PI TC PI TC PI TC PI
-10.0 7.91 2.43 7.90 2.49 7.90 2.55 7.90 2.59 7.90 2.62 7.82 2.70
-5.0 8.57 2.54 8.58 2.61 8.59 2.69 8.59 2.72 8.59 2.76 8.48 2.84
0.0 9.16 2.73 9.15 2.81 9.13 2.88 9.11 2.92 9.08 2.95 9.01 3.02
6.0 10.16 2.92 10.10 2.99 10.00 3.05 9.94 3.08 9.86 3.11 9.79 3.16
10.0 10.74 3.04 10.61 3.10 10.54 3.14 10.54 3.16 10.52 3.18 10.35 3.21
15.0 11.66 3.24 11.62 3.27 11.64 3.29 11.56 3.30 11.47 3.30 11.34 3.32
18.0 12.20 3.34 12.05 3.36 11.93 3.35 11.78 3.34 11.60 3.33 11.28 3.31
AVUW48GM2P0 + AVNW48GM2P0
Outdoor Air Indoor Air Temperature : °CDB
Temp. 16.0 18.0 20.0 21.0 22.0 24.0
°CWB TC PI TC PI TC PI TC PI TC PI TC PI
-10.0 12.10 3.57 12.08 3.66 12.08 3.76 12.08 3.81 12.08 3.86 11.97 3.97
-5.0 13.12 3.74 13.13 3.85 13.14 3.96 13.14 4.01 13.14 4.07 12.98 4.18
0.0 14.01 4.02 14.00 4.13 13.97 4.24 13.94 4.29 13.90 4.35 13.79 4.45
6.0 15.55 4.30 15.45 4.40 15.30 4.49 15.20 4.53 15.09 4.57 14.97 4.65
10.0 16.43 4.47 16.23 4.56 16.12 4.63 16.12 4.66 16.10 4.68 15.83 4.73
15.0 17.83 4.76 17.78 4.82 17.81 4.85 17.69 4.85 17.55 4.85 17.35 4.89
18.0 18.66 4.92 18.43 4.94 18.26 4.93 18.02 4.92 17.75 4.90 17.27 4.88
AVUW60GM2P0 + AVNW60GM2P0
Outdoor Air Indoor Air Temperature : °CDB
Temp. 16.0 18.0 20.0 21.0 22.0 24.0
°CWB TC PI TC PI TC PI TC PI TC PI TC PI
-10.0 13.45 4.10 13.43 4.20 13.42 4.31 13.42 4.37 13.43 4.43 13.30 4.55
-5.0 14.58 4.29 14.59 4.41 14.60 4.54 14.60 4.60 14.59 4.67 14.42 4.80
0.0 15.57 4.61 15.56 4.74 15.52 4.86 15.49 4.92 15.44 4.99 15.32 5.11
6.0 17.28 4.93 17.17 5.05 17.00 5.15 16.89 5.20 16.77 5.24 16.64 5.33
10.0 18.26 5.13 18.03 5.23 17.91 5.31 17.91 5.34 17.89 5.37 17.59 5.42
15.0 19.82 5.46 19.75 5.52 19.79 5.56 19.66 5.57 19.50 5.57 19.27 5.61
18.0 20.74 5.64 20.48 5.67 20.29 5.66 20.03 5.64 19.72 5.62 19.18 5.60
Note
1. DB : Dry bulb temperature(), WB : Wet bulb temperature()
2. TC : Total capacity(kW), SHC : Sensible Heating Capacity(kW)
3. PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
4. All capacities are net. A deduction (cooling mode) or an addition (heating mode) of Capacity due to operating heat of indoor unit motor is reflected.
5. Direct interpolation is permissible. Do not extrapolate.
6. Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table. Except for
rated value, the performance is not guaranteed.
7. In accordance with the test standard(or nations), the rating will vary slightly.
23
Single CAC Heat Pump Outdoor units
24
Single CAC Heat Pump Outdoor units
8. Operation range
Cooling Heating
55
54
50
45
40
35
Outdoor Temperature [℃ DB]
30
25
25
Continuous
20 18
Operation
Warming up
10
Operation
Continuous
5 Operation
0
-5 -10
-10
-15
-25
-20 10 16 30 33
-20 10 12 15 20 23 25 28
Indoor Temp. [°C DB]
Indoor Temperature [℃ WB]
25
Single CAC Heat Pump Outdoor units
9. Electric characteristics
Outdoor Unit Combined Indoor Unit Unit Power Comp OFM IFM
No. of Phase Voltage
Model names Model Name MCA MFA MSC RLA kW FLA kW FLA
Unit Hz Volts range
ATUW18GPLP0 ATNW18GPLP0 12.7 15 - 9.5 0.043 0.25 0.06 0.60
ATUW24GPLP0 ATNW24GPLP0 20.3 25 - 15.5 0.085 0.33 0.06 0.60
ATUW36GMLP0 ATNW36GMLP0 22.7 25 - 17.0 0.124 0.48 0.124 1.00
AVUW36GM1P0 AVNW36GM1P0 1 22.2 25 - 17.0 0.124 0.48 0.086 0.50
Min. : 198
1 50
ATUW48GMLP0 ATNW48GMLP0 Max. : 264 33.2 40 - 25.0 0.124 x 2 0.48 x 2 0.124 1.00
220-240
AVUW48GM2P0 AVNW48GM2P0 32.8 40 - 25.0 0.124 x 2 0.48 x 2 0.125 0.60
ATUW60GMLP0 ATNW60GMLP0 34.5 40 - 26.0 0.124 x 2 0.48 x 2 0.124 1.00
AVUW60GM2P0 AVNW60GM2P0 34.1 40 - 26.0 0.124 x 2 0.48 x 2 0.125 0.60
Note
1. Voltage supplied to the unit terminals should be within the minimum MCA : Minimum Circuit Amperes (A)
and maximum range. MFA : Maximum Fuse Amperes (A)
2. Maximum allowable voltage unbalance between phase is 2%. MSC : Maximum Starting Current
3. MSC means the Max. current during the starting of compressor.
RLA : Rated Load Amperes (A)
4. MSC and RLA are measured as the compressor only test condition.
OFM : Outdoor Fan Motor
5. OFM and IFM are measured as the outdoor unit test condition.
IFM : Indoor Fan Motor
6. Select the wire size based on the MCA.
7. MFA is used to select the circuit breaker and ground fault circuit kW : Fan Motor rated output (kW)
interrupter, and recommended circuit breaker type is ELCB(Earth FLA : Full Load Amperes (A)
Leakage Circuit Breaker).
26
Single CAC Heat Pump Outdoor units
Note
1.Data is valid at free field condition.
2.Reference accoustic pressure 0dB = 20μPa.
3.Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal
conditions(Power source and Ambient temperature,
etc)
1.5m
4.Sound levels can be increased in accordance with
installation and operating conditions. (Operating
conditions include some functional condition like Static
pressure mode, air guide use, Room target
temperature setting, etc and these functions are
1m different in accordance with each model.)
5.Sound level will vary depending on a range of factors
such as the construction(acoustic absorption
coefficient) of particular room in which the equipment
in installed.
ATUW36GMLP0
ATUW18GPLP0 ATUW24GPLP0 AVUW36GM1P0
_WG _WG 80
̵ j j ̵ j
o ̵Go
vGiGzGwGsGOWiGdGYWɆwP
vGiGzGwGsGOWiGdGYWɆwP
^WG ^WG 70
Octave Band Sound Pressure Level (0dB = 20μPa)
27
Single CAC Heat Pump Outdoor units
̵ j
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
28
MULTI/SINGLE CAC
2
MULTI/SINGLE CAC Installation of Outdoor Units
2. Installation Space
2.1 Clearance around outdoor units
• Ensure that the space around the back is 300 mm or more
300 mm or more Su
300 mm nro
or more more than 300 mm on the or more of
opposite to the PCB side and secure 600
mm space near the compressor and PCB 300
100 mm
side of the air conditioner for service. Fe
ob nce o
or more
sta r
cle
s
600 mm or more
(Service space)
700 mm
or more
Turn the air outlet side toward the build- Set the outlet side at a right angle
ing's wall, fence or windbreak screen. to the direction of the wind.
Outdoor unit is representative. Actual appearance of outdoor unit may be
different but clearances will stay the same.
3
MULTI/SINGLE CAC Installation of Outdoor Units
2. Installation Space
̰ Where there is an obstacle on the air intake side:
No obstacle above
[Unit : mm(inch)]
• Obstacle on the suction side only • Obstacle on the both sides
300
or m(11-13
ore /16)
16) /16
)
13/ 600 -13
0 ( 11- e or m (23-19 0 (11 more
30 mor 0
3 or
ore /32)
or
1000(39-3/8) or more
less
) or
1000(39-3/8) or more
s /16
r les -11
o (19
/16) 500
19 -11
5 00(
300
or m(11-1
ore 3/16)
/16 )
/16) 60 0 -13
-13 (2 (11 re
(11 ore or m 3-19/3 300 or mo
0 0
3 or m ore 2)
1/1 6) o
(1 9-1
500
ore
6) or m
-1 1/1
(19 ore
500 rm
1/1 6) o
(1 9-1
500
4
MULTI/SINGLE CAC Installation of Outdoor Units
2. Installation Space
̰ Where there are obstacles on both suction and discharge sides:
Where the obstacles on the discharge side is higher than the unit:
[Unit : mm(inch)]
• No obstacle above • Obstacle above, too
ss
or le
1000(39-3/8) or more
11 /16)
( 19-
500
H
LD
LD
/16 )
LS
-1 3
0 (11 re /16)
0
3 rm o -13
e o 0 (11 re
mor 0
e 3 or mo
H
r
6) o mor
9- 11/1 / 8 ) or
500(1 39 -
3
0(
100
L A[mm(inch)]
0 < L ˺ 1/2H 750(29 1/32)
L˺H
1/2H < L 1 000(39 3/8)
H<L Set the stand as: L ˺ H
Close the bottom of the installation frame to prevent the discharged air from being bypassed.
Where the obstacles on the discharge side is lower than the unit:
[Unit : mm(inch)]
• No obstacle above • Obstacle above, too
‘L’ should be lower than ‘H’.
Close the bottom of the installation frame to prevent
the discharged air from being bypassed.
ss
or le
1000(39-3/8) or more
11 /16)
( 19-
500
H
LD
6)
13/1
0 (11 ore 6)
0
3 or m 13/1
6) ( 11- ore
11/1 0
30 or m
( 19- ore
0
50 or m 3/8)
39- e
LD
0 (
100 r mor
o
5
MULTI/SINGLE CAC Installation of Outdoor Units
2. Installation Space
̰ Series installation
[Unit : mm(inch)]
• One row of stand alone installation • Rows of collective installation (2 or more)
• L should be smaller than H
:L≤H
L
300(11-13/16) 300(11-13/16)
or more or more
H
600(23-19/32) or more 600(23-19/32) or more
1.5m
Ground
1. To protect outdoor unit from lightning, it should be placed within lightning safety zone.
Safety zone
Building Height [m] 20 30 45 60
Protection Angle [ȋ] 55 45 35 25
2. Power cable and communication cable should be 1.5m away from lightning rod.
3. High resistance grounded system should be performed against induced lightning or indirect stroke.
4. If the building has no lightning protection, outdoor may be damage from lightning. This should be informed to
customer or building owner in advance.
6
MULTI/SINGLE CAC Installation of Outdoor Units
c
a
d
b
e
f
ⓐ The corner part must be fixed firmly. Otherwise, the
Unit : mm support for the installation may be bent.
ⓑ Get and use M10 Anchor bolt.
ⓒ Put Cushion Pad between the outdoor unit and ground
support for the vibration protection in wide area.
ⓓ Space for pipes and wiring (Pipes and wirings for bot-
75
tom side)
75
200
200
ⓔ H-beam support
100
ⓕ Concrete support
Outdoor unit is representative. Actual appearance of
outdoor unit may be different but clearances will stay the
same.
WARNING
• Install where it can sufficiently support the weight of the outdoor unit.
If the support strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or earthquake.
If there is a fault in the supporting conditions, the outdoor unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the ground, water outlet treatment(treatment
of the water flowing out of the outdoor unit in operation) of heat pump unit, and the passages of the pipe
and wiring, when making the ground support.
• Do not use tube or pipe for water outlet in the Base pan. Use drainage instead for water outlet.
The tube or pipe may freeze and the water may not be drained. (Heat pump model)
WARNING
7
MULTI/SINGLE CAC Installation of Outdoor Units
20
CAUTION
• The ingredients of foundation : Cement : Sand : Gravel for the concrete should 1 : 2 : 4 ratio
• The foundation surface should be finished with mortar.
• The edges of foundation should be rounded.
• A drain passage should be made around the foundation to thoroughly drain water away from the equipment
installation area. (Heat pump model)
• If installing the outdoor units on the roof, the roof's strength have to be checked.
• Care should be taken for weather - proofing
• Blocking all gaps of outdoor unit, for passing piping and wiring, using sealing material (Field supply)
(Animals and bugs might enter in the machine.)
8
MULTI/SINGLE CAC Installation of Outdoor Units
CAUTION
• Please check the product type. Piping installation and refrigerant charge varies depending on the type of
product.
For more information, please refer to the installation manual.
L
Indoor Unit
H
H
Indoor Unit
Notes
L (m) : Piping Length (Outdoor Unit ~ Indoor Unit) Refer to the specifications of Outdoor Unit for Maximum limit.
H (m) : Height Difference (Outdoor Unit ~ Indoor Unit)
CAUTION
• Capacity is based on standard length and maximum allowance length is on the basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
9
MULTI/SINGLE CAC Installation of Outdoor Units
CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas,
are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result
corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause
product malfunctionor inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind.
Otherwise itneeds additional anticorrosion treatment on the heat exchanger.
2. In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Note
Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
10
MULTI/SINGLE CAC Installation of Outdoor Units
Note
1. The height of H frame must be more than 2 times the snowfall and its width shall not exceed the width of the
product. (If width of the frame is wider than that of the product, snow may accumulate)
2. Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.
11
Air Solution