Escolar Documentos
Profissional Documentos
Cultura Documentos
CHAPTER-I
CHAPTER –II
“Why to Automate”
• Reduces workload
• Can reduce cost
• Human can not perform to the precision
• Time delay
• Power consumption minimum
• Best way to use the latest technology
Water-tube boilers require accurate control of water level in the steam drum to be
maintained at all steaming rates.
For large capacity steam drums, not subject to very large and rapid load changes, a
simple level control system is adequate. However, where large load changes are
experienced it may be necessary to fit what is known as a two-element control system,
which provides anticipatory action actuated from steam flow measurement. Where
extremely large and rapid load changes will be experienced then a three-element system
balancing steam flow against water flow should be considered.
Soot Blowing
Soot blowing, a necessary function in marine boilers, can easily be carried out by
automatic sequence control system operating the valves to the soot blowing nozzles.
Changing the sequence pattern is usually a simple task and the whole system can be
started by the operation of one push button.
Other than the few sections of the ship described above in this chapter, there are many
more examples of implementation of control on a ship. Some of these systems are
explained in detail later on in this course.
Sensing Element:
Sensing Element is having direct contact with process. These are sensors , Diaphragms
and bellows. They have tendency to cause mechanical movement as process value
changes.
The sensing elements are normally connected to device which converts the mechanical
movement into suitable pneumatic/electrical signal.
These Signals are very small in magnitude normally 3PSI to 15 PSI or 4MA to 20 MA
These elements are termed as Transmitters / Tranducer
Comparing Element:
This element is used for detecting the error or deviation. The process value is compared
with set value and deviation is directed to the controller. Based 9nthe controller
configuration and error the controller generates an output.
Amplifier:
The deviation at the controller is not very large in magnitude, therefore controller
amplifies the error or deviation . Every controller has pilot valve amplifier, which
amplifies the error suitably so that final controlling element can be operated.
CHAPTER-III
Control is a function, which is not possible with a single element. It is only applicable to
International Maritime Training Centre 5
AUTOMATION & CONTROLS
Some systems are almost self-regulating. For example, the temperature of mixture of ice
and water is completely so. If the ambient temperature rises, some ice melts; if it falls,
some water freezes, the temperature remains at zero degree Celsius. Note that it is only
the temperature that has this property. The mass of ice, the mass of water, or the ratio of
these two quantities will all vary. Other systems are partly self-regulating. A furnace or
oven is such. If the fuel supply increases, the temperature rises, but so do losses by
radiation, convection, and through the stack; and a new, higher, temperature is reached
and held. Nearly all-engineering processes have an inherent tendency to self-regulation.
There are also essentially non-self-regulating processes, such as the explosion of
gunpowder, or the operation of a nuclear reactor.
Ease of control depends upon two things: the response of a system to a disturbance—
whether stable or unstable (self-regulating or non-self-regulating) and the time constant
of the system. This is the basis of Plant Analysis. The process under investigation,
International Maritime Training Centre 6
AUTOMATION & CONTROLS
steam boiler, furnace, pump, lift, liquid level, or whatever it may be, is given a little
disturbance or experiences a disturbance, usually a Step-change, and the nature of the
response observed.
(a) Step
Level
Of
Process
(b) Ramp
Level
Of
Process
(c) Sinusoidal
Time Constants
Response of process with smaller time constant is faster than with larger time
constant. Particular system having some time constant if given different step
changes the rate of response in each case will be different. However the time taken
for 63.2% of change to take place will be same.
PROCESS
International Maritime Training Centre 10
AUTOMATION & CONTROLS
MEASUREMENT
• To control a dynamic variable in a process it is important to have information
about the variable itself.
• This information is obtained by measuring the variable.
• Measurement refers to the conversion of process variable into an analog or digital
signal that can be used by the control system.
• The device that performs the initial measurement is called SENSOR or
INSTRUMENT.
• The result of measurement is the conversion of dynamic variable into some
proportional information that is required by other elements in the process control
loop.
EVALUATION
• In the evaluation step of process control sequence, the MEASURED VALUE is
examined, compared with the DESIRED VALUE or the SET POINT and the
amount of corrective action needed to maintain proper control is determined.
• A device known, as CONTROLLER can be pneumatic, electronic, electrical or a
combination of any of them.
CONTROL
• The control element in a control loop is a device that exerts a direct influence on
the process.
• This final control element accepts an input from the controller and transforms into
proportional operation that is performed on the process.
• In most of the cases final control element is the CONTROL VALVE that adjusts
the flow of fluid in a process.
In Summary,
- Poor repeatability means poor accuracy
- Good accuracy means good repeatability
- Good repeatability does not necessarily means good accuracy.
Calibration Adjustments
Zero adjustment
100 %
Measured
International Maritime Training Centre 12
AUTOMATION & CONTROLS
Value
b) In this adjustment the instrument reading moves up and down by equal amount at
every point of measurement. Hence error remains constant through out the entire
range.
Span Adjustment
100%
Measured
International Maritime Training Centre 13
AUTOMATION & CONTROLS
Value
a) The span means the response of measuring instrument when the process variable
value changes from minimum to maximum.
c) Changing the mechanical advantages of the lever system that relates the output
response to and input response usually makes the span adjustment.
d) The span adjustment is likely to affect the zero reading. Hence the zero
adjustment should always be followed by span adjustment.
e) Interaction between span and zero adjustment can complicate calibration unless
special attention is paid i.e. after zero adjustment if a span correction is made then
when input is returned to zero it might appear that instrument reading is not zero.
Therefore an over compensation in span adjustment can be made in order to
correct the value by zero adjustment
Sensor Characteristics
Sensitivity
4) In case of an ideal sensor the output signal is only affected by input signal
however no pratical sensor is ideal. Therefore the output of sensor is
affected by temperature, humidity, vibration
INPUT
• INPUT is the stimulus or excitation applied to a control system from an external
energy source usually in order to produce a specified response from the control
system.
OUTPUT
• OUTPUT is the actual response obtained from the control system. It may or may
not be equal to the desired response implied by the input. The purpose of the
control system usually identifies or defines the inputs or outputs. Once inputs and
outputs are defined, it becomes possible to specify the nature of the system’s
components.
order to adjust the controlled condition without human intervention in the closed
loop formed by the comparing and correcting chains of the elements and the
process.
CONTROL SYSTEMS
Definition – A control system is a group of components that maintains a desired result by
manipulating the value of another variable in the system.
In any control system once inputs and outputs are known then it is easier to determine the
type of control action required to achieve the desired output for given input
ENERGY
SOURCE
The controller always knows the effect of its action on the process.
EXAMPLE: A man steering a ship. Measurement is his view of landmarks or buoys,
Controller is his brain, course is the Desired Value, helm is the Regulating or
Controlling Element, and rudder is the Final control Element.
International Maritime Training Centre 17
AUTOMATION & CONTROLS
In a closed loop system process variable measured value is sent to the comparing element
via transmitter, where measured value is compared with set point or desired value and
difference in computed, which is termed as Deviation or Error. Based on the deviation
controller sends an amplified output signal to the final controlling element i.e Control
Valve
There are four modes of closed loop control system commonly used.
Two Position/ On-Off Control
With such systems a desired value is selected and the automatic controller adjusted so
that the correcting unit (a valve, pump or compressor) has only two positions or 2
conditions—open / shut, running or stopped. The automatic controller switches the
correcting unit from one extreme to the other as the controlled condition passes the set
point.
EXAMPLES: Electric thermostat, controlling immersion heaters, room heating, etc.
In systems such as steam hot water heaters, there is a time lag between the valve
operating and the heat passing from the steam to the water due to the heat transfer delay
by the tube mat
serial; this is known as a Transfer Lag and due to this the water temperature may take
time to rise or fall, as shown in the figure. This tends to prevent oscillation.
However, in domestic fresh water pressure or level control, the operation of the automatic
controller, the valve or pump and associated water flow can be very quick and oscillation
can occur. Such systems may be given overlap by the use of limit switches or adjusting
the controller.
All on-off devices have a Dead Zone or a zone of indeterminacy—a form of
Hystersis.Two Step systems are suitable for processes with High Demand Side capacity
and a Low Supply Side capacity, i.e., a large capacity of hot water tank with a small
supply of heat, the reverse would cause oscillations, which can cause rapid wear and tear
on the components and increased maintenance.
Floating Control
It is the same as two-position control except that the operation of the regulating element
International Maritime Training Centre 20
AUTOMATION & CONTROLS
Proportional Control
This is the basic form of modulating control in which the controller is set up so that
any change in output is directly proportional to the deviation between the controlled
condition and the desired value.
The corrective action of the controller C bears a constant ratio to the error.
ERROR = +(M.V-D.V)
C = -K x ERROR
K = Constant Of Proportionality Or Gain Of the Controller—infact –K is the transfer
function of the controller:
K = output /input
Where Gain can be defined as output divided by input or ratio of output to input
and Error is the difference between Process value to Set value and constant is
nothing but a Bias.
PROPORTIONAL BAND
Proportional Band is defined as percentage change in the input signal that will allow
out put to change by hundred percent. If we say proportional band of a controller is
50 percent i.e. in irder to get 100% change in the controller output one need to
change the input by 50%..
0.2-0.6 0.2-1.0
0.2-0.4 0.2-1.0
0.2-0.3 0.2-1.0
0.2-0.25 0.2-1.0
When proportional Band is narrow or Gain is high what would happen to the
control system?
Should we go for wide proportional band or narrow proportional band and why?
Higher the controller gain, narrower will be the proportional band. If the
proportional bandwidth is too narrow then a very small deviation between the
measured value and the desired value can cause a very large change in the output
signal. It can also cause instability and hunting. If too wide then the process will be
sluggish. The practical result is a comprise and the set value must be offcourse
within the band.
3
INPUT
OUTPUT
E Input
r
r
o
r
Output
Time
Integral Action
Since the proportional controller can not eliminate the offset
International Maritime Training Centre 29
AUTOMATION & CONTROLS
Note-
It is clearly evident that after time t the output due to integral action
equals the output due to proportional action if a constant deviation
exists.
Plants having inherent characteristics such that when a disturbance occurs, because
International Maritime Training Centre 33
AUTOMATION & CONTROLS
of large volumes / or masses or long distances involved, there are time delays before
equilibrium is restored. A long reset time may be necessary and if there is a
tendency to hunting, a wide proportional band will be required. To improve
recovery from a disturbance in a plant with such problems, Derivative or Rate action
may be applied by adding a further term to the automatic controller output, in
addition to proportional and reset. Such action tends to stabilize the control system
and allows either the proportional band to be narrowed, or a shorter integral action
time to be used, or a combination of both.
With derivative action, the output signal change due to this action is proportional to the
rate of change of error.
It is measured in terms of the Derivative Action Time—the time taken for the
proportional component to become equal to the derivative component under ramp
conditions. Figures below show this effect.
NOTE— the rate of action is dependant upon the rate of change in error, or the rate
at which it is developing, and not upon the amount of error. Thus, a considerable
corrective action is possible for a small error or deviation if it takes place rapidly.
Also, a long derivative action time means that the proportional action takes longer
to repeat the derivative action, and assuming the gain or proportional band
constant, the derivative action is therefore greater than with the shorter derivative
action time. This is the reverse to integral time, where the shorter the time, the
International Maritime Training Centre 34
AUTOMATION & CONTROLS
If rate of change of error remains constant for a period of time td, then output due
to derivative action remains steady for time td. Time td is derivative action time and
is decided by controller setting.
However due to varying error contribution due to proportional controller also
changes as indicated in graph.
While selecting the values on controller it is desired to keep a moderate proportional
band value so that system stabilizes with moderate offset. Then a moderate Integral
action is supplemented in parallel with proportional action so that offset can be
eliminated and system stabilizes without any offset.
Derivative action would bring the system in control condition at a faster rate as it is
anticipatory action.
controller output.
CHAPTER IV
This chapter explains some of the devices used to produce signals suited to long
distance signal transmission for control, alarm and recording purposes. The process
may generally be named telemetering and the devices are often called transducers.
Flapper Nozzle
Air is fed to the nozzle at a constant pressure via a restricter (to limit airflow so that P is
approximately atmospheric pressure when the nozzle / flapper gap is maximum).
The air leaks to the atmosphere at a rate depending upon the clearance between the
flapper and the nozzle tip and follows the curve as shown in the figure.
Nozzle / Flapper
With the flapper hard on the nozzle P (the back pressure) would be 1.4 bar (20 psi) while
if it is moved away approximately 0.03 mm, P is then slightly above atmospheric. As the
curve shows the back pressure P flapper movement relationship is only approximately
linear over the signal range, but if the curve is taken between the P pressures of 0.2 bar
and 0.5 bar, approximately 0.015 mm flapper travel, then the curve is much closer to the
International Maritime Training Centre 42
AUTOMATION & CONTROLS
linear requirement (i.e. P varies an equal amount, each time the flapper moves an equal
amount).
Considering the same temperature change where Negative Feedback is applied, the
flapper initially moves the same amount and the backpressure P increases to 0.5 bars, but
in doing so, it causes the bellows to expand, pivoting the flapper about point 1. The
nozzle/flapper gap then increases, moving it back towards, but not exactly to, its original
position until a position of equilibrium is reached. The actual resultant movement of the
flapper from its position may then be only 0.00025 mm and output (back pressure) will
have increased by a very small amount, say 0.05 bar so that the output is now 0.25 bar.
International Maritime Training Centre 43
AUTOMATION & CONTROLS
Thus with 2 degree Celsius giving a pressure change of 0.05 bar, the temperature range
that can be measured and transmitted has been increased to 0.5- 0.2 x 2 = 12
0.05
NOTE--- The reason the feedback is given a negative notation is that it moves the
flapper back towards its original position.
If it moved the flapper further away from its original position it would be called
Positive Feedback.
Also note that any variable such as level, pressure, flow, etc. could be used to move the
flapper, the position of point 1 being adjustable to suit the input movement available to
give the flapper/nozzle the necessary gap variation for correct operation.
Relay Valve
Provides pneumatic amplification, proportional movement, and reduced time lag.
Equivalent in action to an electronic amplifier.
If P increases then the bellows act to close the bleed port and the supply air passes, to the
controlling unit, conversely if P decreases a continuous bleed to the atmosphere occurs.
Amplification by a factor of 16 can easily be arranged, for example a flapper travel of
0.01 mm causing a change of P on the bellows of 0.05 bars could give an output from 1.2
to 2 bars.
Booster or Pilot Valve Relay or Pilot Valve Amplifier
The nozzle/flapper described above may be considered as an amplifier, as a small input
movement is converted in a measurable pneumatic signal, but the increments of pressure
change are still too small to be transmitted over long distance or operate large equipment,
and there is therefore a second stage amplifier called a Booster or Pilot Valve Relay as
shown in the figures given below.
International Maritime Training Centre 44
AUTOMATION & CONTROLS
Here, the nozzle backpressure acts on a diaphragm attached to a spindle with a valve on
the opposite end. The leaf spring can be adjusted to give the correct operating range and
balance the load on the diaphragm. Consider that air at input pressure, say 1.4 bar, is
supplied to the underside of the ball valve.
If the backpressure P increases as the flapper approaches the nozzle, the diaphragm
pressure increases and the conical exhaust valve moves towards its seat, thus reducing the
air bleeding off to atmosphere and at the same time opening the ball valve so that output
pressure increases. If the exhaust valve is shut in completely, the output pressure
increases to 1.4 bars.
If P decreases, the spring moves the spindle to open the exhaust valve and shut in the ball
valve reducing the output pressure to the extent that it drops to just above atmospheric if
International Maritime Training Centre 45
AUTOMATION & CONTROLS
the ball valve shuts completely. Intermediate positions of the valves give output pressures
from 0 to 1.4 bars.
The nozzle backpressure relationship with the pilot valve is not linear over the full range
and usually pilot valves are adjusted to accommodate a nozzle backpressure range of
approximately 0.2 to 0.5 bars, which gives reasonable linearity for the nozzle/flapper
behaviour. This gives an output range for the ball valve between 0.2 to 1.0 bar ~ linear.
Self-Balancing Device
diaphragm etc., acts on the end of a beam as shown in the figure given below. The beam
is pivoted, and at the opposite end to the applied force acts against a nozzle. Air is
supplied through a restriction to a nozzle whence it bleeds to atmosphere.
Any change in the measured condition of the system being monitored, alters the
measured value signal and the difference between this and the set point signal pivots the
right hand side altering the nozzle/flapper gap. Suppose the beam approaches the nozzle,
then the air escape is restricted and the back pressure builds up, increasing the output
pressure and also the force on the feedback diaphragm which in turn produces an
opposing torque on the beam, tending to move it away from the flapper—having negative
feedback effect.
NOTE—On instruments of this type, in practice the position of the pivot is variable to
alter the operating range and a zero adjusting spring is also fitted to create a force against
the beam to pre-load it to give an output of 0.2 bar at the lowest value of the range over
which the system is being monitored.
follow up bellows move to position the detector nozzle in line with the tapered step of the
wire pilot.
Process pressure acts on measuring diaphragm. An increase in process pressure moves
the diaphragm upward, which via U-Shaped linkage moves the wire pilot upward. The
wire pilot restricts the annular orifice and the backpressure increases. The two bellows
that make up the follow up bellows system have the same area and are connected rigidly
The main function of the pilot valve is used to deliver or exhaust a large volume of
air per unit time. It also acts as a pressure amplifier. The pilot valve may be adjusted so
that a change of nozzle back pressure of between about 0.15 bar and 0.3 bar will give the
full range of change in the output pressure.
This valve consists of double-seated pilot valve where the nozzle flapper
backpressure operates from the top of the diaphragm and regulates the relay output
pressure. This is a direct acting pilot relay valve where the increasing in the nozzle
back pressure causes increase in the relay output pressure. The air to the nozzle and
flapper unit is routed via very fine restriction consisting of a filtering unit. This type
of pilot relay valve is capable of giving amplification of 5 to 6 times.
Pilot relay valve unit is prone to malfunction since it consists of diaphragm and Teflon
valve seats if air quality is not good then it may hamper smooth functioning of pilot relay
unit. This is suggested that the air supplied to the pilot relay assembly should be clean
and dry. The maximum number of problems in a controller system is associated with
pilot valve assembly. The pilot valve is not designed for the changes in the output for a
given input.
MULTI-FUNCTIONAL RELAY
International Maritime Training Centre 51
AUTOMATION & CONTROLS
A multi functional relay combines the requirement for adding, averaging, subtracting and
rationing in one relay.
The relay contains four bellows and a movable fulcrum, which can be accurately
positioned and clamped in the central position for all cases, except when it is sued as a
ratio relay.
The bellows required are connected to the input signals; any bellows not required being
vented to atmosphere.
Smart Transmitters
Until recently, measuring technology lagged behind the developments in controllers and
control systems. The development of smart transmitters has enabled measurement quality
to now be commensurate with control.
A smart transmitter is a microprocessor-based measuring instrument that provides two
major features: improved performance and two-way digital communications between the
control station and the field. These features have resulted in increased process
profitability by providing improved accuracy, remote communication, configuration for
application, diagnostics, greater reliability, reduced maintenance, improved control
quality, and more efficient communication. The normal accuracy of process transmitters
was at one time considered to be ±1% of full-scale value. Measurement precision has
always been important, because the emphasis generally was on control of a variable
rather than measurement for absolute accuracy. When measurement accuracy can be
improved to ±O..l % or even ±O.05%, tighter control around a desired point can
be achieved. This improved accuracy can translate to substantial improvement in product
quality, reduction in raw materials, and increased profits. With increasing emphasis on
product purity and improved efficiency, the retrofitting of production units often is
justified by increased accuracy of measurement and improved control quality.
A later version of a smart transmitter is shown in Figure . The sensor is isolated from
electrical and temperature disturbances of the process fluid. This enables operation in
temperature environments up to 175°C, with process temperature measurement to
compensate for temperature effects. During cell characterization at the factory, all cells
are run through temperature and pressure cycles. Data from these tests are stored in each
transmitter's characterization PROM to ensure precise signal correction during operation.
The PROM represents a personality circuitry to convert the sensor response to a digital
signal for further processing and refinement by the microprocessor. The EEPROM
(electrically erasable and programmable read-only memory) is a nonvolatile memory
module that stores the characterization data and is an integral part of the sensor module.
Digital trim data that can be changed by the transmitter software are also included in the
EEPROM. The digital trim data are cell dependent and should be retrimmed when an
associated component is replaced or exchanged. The RAM (random access memory) is a
temporary workspace used by the microprocessor for calculations and cannot be
addressed by the user.
International Maritime Training Centre 57
AUTOMATION & CONTROLS
Configuration and sensor linearization data stored in the nonvolatile EEPROM are
retained in the transmitter when power is interrupted. The measurement data are stored
digitally to enable precise connections and engineering conversion before being
converted to a corresponding current value for analog transmission. Remote testing and
configuration of the transmitter are accomplished from the control station or from a
remote hand-held communicator (HHC).
The information in the Transmitter Memory may be different from that in the Working
Register, since the Working Register may contain changed data that have not yet been
sent to the transmitter. Therefore, the HHC will warn that reviewing this location will
erase the information currently held in the Working Register.
The HHC can interface with the transmitter from the control room, the transmitter site, or
any other wiring termination point in the loop. To communicate, it must be connected in
parallel with the transmitter; the connections are nonpolarized.
To function properly, there must be a minimum of 250 .Q resistance in the loop between
the power supply and the HHC. Capacitance across the load resistor should be less than
0.1 pF .
Configuration
The transmitter is programmed or configured for modification of several kinds of specific
information divided into two categories: that which affects the transmitter output and that
which supplies information
about the transmitter or loop. The various configure modes are discussed below.
OFLN DATA can be used to store transmitter configuration or to provide access to off-
line-entered data. Duplication of configuration data from one transmitter to another is
possible, so manually entering data each time is not required. Figure 5-4 shows where
data are stored and how they are transferred between the transmitter and the remote
transmitter interface.
CHNG OPUT can be used to configure parameters that affect transmitter output. The
following functions are affected:
• Units: se~ects engineering units
Range: can be selected for rerange (1) from the HHC, (2) by reference to an externally
applied pressure source using the HHC to confirm the 4- and 20-mA points, and (3) by
reference to an externally applied pressure source using span and zero push buttons
without connection to the HHC
• Output: selects linear or square root output
• Dampening: selects dampening values from 0 to 16 s
SEND DATA allows the transfer of all information from the Working Register of the
HHC to the transmitter. All data are sent at once and the user knows whether the
transmitter data have actually been changed.
The format functions are used during the initial setup of a transmitter and for
maintenance of the digital electronics. The top-level format menu offers two functions:
CHARIZ allows for retrofitting of analog transmitters to digital using the same sensor
module.
DGTL TRIM allows adjustment of the transmitter characterization for purposes of
calibration. Two separate options are provided:
Sensor trim, to adjust the digital output signal to a precise pressure input
• 4- to 20-mA trim, to adjust the output electronics
Some information such as sensor limits and transmitter / communications software
revision levels are not user changeable.
Special Features and Advantages of Smart Transmitters
The many advantages and features of digital transmitters are listed below. Improved
performance and functional specifications
• Reduced ertor of temperature effects for wide range:
process, -40 to 175°C
ambient, -40 to 85°C
• Failure alarm: high or low limit, user selectable
Damping: 0- to 16-s output response to step input
• Accuracy to include hysteresis, linearity, repeatability, and drift:
±0.1 % of calibrated span for analog transmission
±0.07% of calibrated span for digital transmission
• Static pressure effect:
zero error,
±0.1 % to ±0.2% depending on range and static pressure
span error,
±0.2% of reading per 1000 psi
Power supply effect:
0.0005% of calibrated span
FI effect: 0.1% of calibrated span
Overrange effect: 0.05% of reference span to maximum pressure rating
Special features
Execute complex calculations
International Maritime Training Centre 62
AUTOMATION & CONTROLS
Configurable
• Dampening setting
• Calibrated range
Diagnostics: automatic with no prompt required
Input range
• 0 or full vacuum to 6000 psi gage or 51 and metric equivalent for pressure
reranging
diagnostics
Communication
Many protocols are now in use, each with its own advantages and limitations. In one,
alternating 4- and 20-mA signals is used to represent data information in l's and D's
format. This makes it fairly easy to distinguish between information and noise. An
obvious disadvantage is that communication to the transmitter interrupts the information
from the process even if the operator simply asks for a tag number. For more involved
communication to the transmitter, the controller would be transferred to manual so that
momentary loss of information from
the transmitter would be acceptable. Figure 5-7 shows data exchange with a digital
transmitter by shifting the signal level between 4 and 20mA.
The l's and D's can also be represented by modulating the loop current 0.5 mA above and
below the transmitter's output signal. This modulation is accomplished by transformer-
coupling a signal generator to the loop. A message consisting of l's would shift the
intelligent signal from the transmitter 0.5 mA above its normal signal. This 3.125%
change in signal is no doubt more susceptible to noise corruption.
Another approach uses the Bell 202 frequency-shift keying standard to impose a high-
frequency signal riding on the 4- to 20-mA signal. The l's and O's are represented by
different frequencies. This format allows digital communication with the transmitter's 4-
to 20-mA uninterrupted. Communication is in parallel with the field instrument and can
be initiated at any point on the loop.
A fourth scheme devised to communicate with field smart transmitters is to separate the
communication link from the 4- to 20-mA loop. The field communicator is connected
directly to the transmitter, and repeaters are used to transmit the data.
Applications
Committees such as ISA SP-50 are working to set standard methods of communication
protocol. Like most such standards, however, progress has been slow. Presently, the
entire control package-transmitter and control systems-must be purchased from the same
vendor unless special consideration is given to mix and match applications. If a
commonly accepted standard is not soon established by a central organization, one will
soon be set and adopted by users.
Smart transmitters can be linked to personal computers that provide a special interface
between the transmitter and the receiver. The control system then operates with the 4- to
20-mA signal from the transmitter, while the PC (using software provided by the
transmitter's manufacturer) utilizes the digital signal to perform other functions, such as
diagnostics, configuration, and recordkeeping. The effectiveness of this scheme depends
on the ability of the 4- to 20-mA and digital signals to coexist simultaneously. If they can,
a PC interface with smart transmitters can be advantageous.
Eventually total digital instrumentation will develop to a point where all communication
between field instruments and receivers will be on a communications highway. This will
eliminate the need for cable pairs, perhaps a favorable economic situation. Information
will be transmitted digitally over local area networks that employ many devices
addressable so that total communication among all instruments will be possible. For
maximum advantage, such a system must accommodate existing two-wire instruments
and support all other field instruments, such as transmitters, valves, composition
transmitters, and contact inputs/outputs (I/Os). This development will, however, wait for
a standard.
Some applications and functions of smart transmitters include
calibration by remote communications, complex calculations, versatile configurations,
diagnostics, new maintenance structure, built-in control capability, and added control
efficiency by true distributed control. The fact that true digital transmitters do not have
physical adjustments knobs to twist or switches to throw for calibration purposes-makes
them ideal for operation in remote and inaccessible locations. Calibration adjustments are
International Maritime Training Centre 67
AUTOMATION & CONTROLS
Smart transmitters were field tested by a power-generating company that switched to the
devices because of remote ranging capability and immunity to error caused by process
and ambient-temperature variations. Prior to the conversion to digital transmitters,
conventional analog types were used with temperature-controlled enclosures.
The company realized the need to upgrade to more versatile equipment and conducted
tests with several different types of smart pressure transmitters to determine accuracy and
repeatability. Test pressures were produced with a highly accurate and precise
deadweight tester, and the output was read with a highly accurate and precise
milliampmeter multiplexed to a computer. The test instruments were energized for 24 h,
with 30 readings taken at five different pressures. Some of the transmitters were placed in
plant vehicles and subjected to handling that would be encountered during transportation
and moving. Others were placed in storage for several weeks, and others remained on the
calibration stand and were recalibrated. The devices were rechecked by comparing the
first calibration result against a known pressure that consisted of 30 data points at the
same pressures as the calibration check.
The transmitters were checked at 400,100, and 50 in. The accuracy was well within
±0.05% until the range was reduced to 50 in., in which case the error became significant.
The instruments under evaluation performed as well as analog types in enclosures. The
power company, like the chemical company, concluded that smart transmitters are the
best choice for use in all critical pressure and differential-pressure applications [Ref. 6].
CHAPTER V
If the pivot is moved towards the right hand side so that X = 1.5 and Y= 0.5 for the same
temperature change and signal error (assume 0.1 bar)
Thus by moving the pivot on R.H.S, for the same deviation the gain has been increased
three times and proportional band narrowed to 331/3 %
In general
Po= [ ( P2-P1 ) X / Y ] + P3
Since P3 is open to atmosphere and thus is zero, as all the pressure involved use
atmospheric pressure as datum.
Moving the pivot to left reduces the gain and widens the proportional Band
As this is proportional controller the V/V controlling the L.O by pass at cooler would
move an amount proportion to the error and depending upon the gain or proportional
band setting, there would be some degree of “OFFSET”
While using the integral control instead of venting bellow 3 the controller output is
brought to bellow 3 via adjustable resistance valve. By throttling the opening of the
adjustable valve the integral action is increased and decreased larger opening of valve
will result in higher integral action as bellow 3 will expand more and further move the
balance beam clockwise if there is increase in the deviation hence there will be higher
controller output for given deviation.
While using this controller as P-I-D in addition to above the measured value is feed to
another controller in parallel to the bellow no 6 via a adjustable valve. When the valve is
fully open the pressure applied on both bellow no 5& 6 remains same hence the derivate
action remains zero. As we start throttling the adjustable valve derivate action comes into
the picture and larger the throttling the more effective is the derivate action.
When we throttle the derivate action valve after some period of time the pressure on both
the below 5&6 will equalize and derivate action will seize. Hence derivate action is
depended upon Rate of Deviation and Derivate action time
The nakakita controller is typical P-I-D controller with pilot relay unit as integral part of
the controller. Supply air is connected at the pilot relay unit and with a very small orifice
air is allowed to enter the nozzle assembly. The leak of between nozzle and flapper is
determined by the distance between the nozzle and flapper and hence the backpressure on
top of the top diaphragm of pilot relay unit is varied. The variation in back pressure alters
the opening of the pilot relay valve hence the controller output is also varied in an
amplified manner. The relay output is subjected to negative feed back bellow via derivate
action valve. The negative feed back bellow movement is just opposite of the process
variable change i.e. if controller output increase the effect of negative feed back bellow
will be to move the gap between the nozzle flapper and thus reduce the output pressure.
Any alteration in the derivate action in the valve setting will change the negative feed
back effect hence the output is varied.
It is also equipped with integral action unit valve. By regulating that valve the output is
varied for given deviation. Therefore the controller sends a different output signal for the
same amount of deviation with different P,I,D settings. Proportional band is varied by
using the dial which alters the gap between nozzle and flapper and hence the controller
output. To change over from direct to reverse the proportional band dial is turned by 270O
and vice versa.
Like nakakita controller Yamatake honey well is also P-I-D controller. Which is also
equipped with pilot relay unit, negative feed back bellow and reset bellow
(Integral bellow). The gap between the nozzle and flapper is altered by deviation and
proportional band setting.
Finally controller output is affected by proportional band value, integral setting, derivate
setting and deviation.
control VIV. To change the set up from reverse to direct turn the P.B Dial to the
right by ¾ turns & from direct to reverse turn the dial by ¾ th turn to left.
MAINTENANCE OF CONTROLLER
1) Remove the drain deposited in air supply by loosening the drain plug
2) Supply air pressure should be maintained at 1.4 bar
3) Regularly inspect and clean the pilot relay valve orifice holes and nozzles.
4) Orifice can be cleaned by using push button
5) To remove orifice out of relay disassemble it after shutting of air supply
6) Clean the orifice in gas oil and blow air to clean
7) Increase the deviation and confirm following for controller
- At zero deviation – controller output pressure = 0.6 bar
- Measured value is less than set value with max deviation = controller
output Pr = 0.2 bar
- Measured value is more than set value with max deviation. Controller
output = 1.0 bar
8) Regularly check the supply Pr, output Pr on dual gauge.
The jacket cooling water outlet temperature sensor monitors the cooling water at the
outlet from the cylinder head (resistance thermometer, thermocouple or thermistor for
electrical control circuits, filled system type for a pneumatic control system and possibly
SPLIT RANGE CONTROL APPLICATION
for an electrical system via a transducer), and feeds a signal to the automatic controller
where the comparing element checks for any deviation or error. The automatic controller
output usually ranges from 0.2 bars to 1,0 bars and this is fed to both the valve
positioners. These are adjusted so that when the jacket cooling water temperature is low,
International Maritime Training Centre 76
AUTOMATION & CONTROLS
the low air signal 0.2 bars—0.4 bars operates the steam supply valve to raise the
temperature of the water. When the pressure is above 0.4 bars this valve is shut, and 0.4
bars—1.0 bars range, the cooling water valve, is open. Below 0.4 bars this valve is shut,
so that there is only one valve open at any time.
In some cases where there would be problems with two valves opening at the same
time, a dead band is used, one valve closing at 0.4 bar for instance and the other
opening at 0.5 bars. This would be used when using exhaust steam and bled steam for
deaerating feed water for boilers. Excess exhaust steam may be dumped to a condenser,
but to prevent this happening to steam bled from the turbines, the dead band ensures
that the dump valve is shut before the bled steam valve opens.
This dead band is not required in the cooling water system.
Cascade Control
By suitable adjustment of proportional band, integral action time, and possibly the
rate action time, an automatic control system can deal with the time lag between a
deviation or error arising and equilibrium being restored, introduced by a large
capacitor, whether it is a large volume of water or a large thermal storage capacity.
But, when two such capacitors are involved control can become difficult and it may
be necessary to use cascade control.
This involves two automatic controllers in series, the output signal of one, the master,
being used as the set point of the second, the slave. The output signal from this is
then being used to adjust the correcting unit. Each automatic controller has a sensor
providing a measured value signal of the system under control from a different
position in the plant. In this way the two capacitors are split into two single
capacitor systems making control easier.
Maintaining a constant cooling water outlet temperature from the cylinder jackets
of a diesel engine presents problems due to thermal inertias of the large mass of
water flowing, variations in engine loading and sea water temperature and possibly
pressure while maneuvering. In this application, therefore, the master controller
responds to the sensor at the jacket outlet, compares it with a set point signal
introduced by the plant operator and if there is a deviation or error, produces a
resetting signal, which is taken to the set point bellows of the slave controller. The
slave controller then transmits a signal to the correcting unit or final control
element (valve), which adjusts the seawater flow.
Thus the effect of any change in engine loading on jacket cooling water outlet
temperature is sensed by the master controller, which operates the seawater control
valve at the cooler via the set point of the slave controller.
If there is a change in the seawater temperature or pressure, this will immediately
affect the water in the cooler and a sensor monitors the outlet temperature here, to
which the slave controller responds. Any change in this temperature operates the
slave controller that acts as a self-contained control loop to readjust the seawater
control valve.
Thus any temperature change at the cooler due to seawater temperature or pressure
fluctuation is prevented from reaching the engine and causing a temperature change
in the whole system that would take a long time to sense and correct.
VISCOMETER
In laminar flow the fluid flow rate is proportional to applied stress or applied stress is
proportional to velocity gradient
F == η dv
A dx
International Maritime Training Centre 78
AUTOMATION & CONTROLS
Also η == Kd4∆P
VL
K= Constant, d= Inside diameter of cap. V= Flow rate, L = length of cap.
Viscosity of the fluid to be measured is passed through a fine capillary tube fixed
dimension and Pressure drop across the capillary tube is measured.
Pressure drop across the capil lary is proportional to the viscosity of fluid if the
dimensions of capillary is fixed.
The pressure drop across the capillary is sent across the oil separating chambers which is
filled up with Ethylene Glycol. Ethylene Glycol has specific Gravity less than Diesel oil
and Heavy oil and also it is not miscible with oil. In addition to this it has very good
pressure transmitting property. Output of oil separating chamber is passed to Differential
pressure transmitter, where measured DP is converted into pneumatic signal.
Since fuel oil pressure on board the ship is having slight fluctuation even engine is
running at fixed RPM, this differential pressure signal is passed through the needle valve
where hunting is reduced to minimum. This measured differential pressure acts as
measured value signal and passed to a P-I-D Controller which is equipped with set point
value and based on the difference in set value and measured value controller sends output
signal which operates the steam valve to the heater.
Maintenance
a) Normally the oil separating chamber oil leaks out and cylinder get filled
up with Heavy Oil, which latter passed on to Pneumatic Differential
pressure transmitter. The capsule of differential pressure transmitter
becomes sluggish and hampers the movement. It is always suggested to
keep the oil separating chamber full of Ethylene Glycol.
b) Before stopping the system it needs to be changed over to diesel oil and
also flushed thoroughly.
c) Any fluctuation in fuel oil system should be eliminated using the needle
valve as it would lead to the hunting of controller.
d) The differential pressure transmitter should be calibrated regularly. At
zero differential the output should be 3PSI or 0.2 Bar.
VISCOTHERM
Operating Principle
side.
a) The Driver Piezos
b) Receiver Piezos
ADVANTAGES
CHAPTER VI
Under steady condition the temperature will be controlled in the normal closed loop and
feed back manner, but as soon as there is change in demand there would be an immediate
corrective action by opening or closing the steam control valve accordingly.
The immediate corrective action i.e. the feed forward action need only be approximate as
it is subsequently trimmed by the action of controller.
In general terms, with the feed forward control it is implicit that knowledge of the effect
of a disturbance and the required corrective action is known.
In a feed forward control system information concerning on oncoming disturbances is fed
forward to the regulating before disturbance reaches the system under control, hence
effects of disturbances are reduced Combined with cascade and feed back feed forward
can give a 100 to 1 improvement in difficult control condition.
Any change in flow in the pipe line causes variation in the pressure drop across the
orifice which is picked up by DP Cell Bellows and thus a pneumatic transmitter is
operated to produce a non linear out put signal related to the fluid flow change. This
signal is then fed to bellow A. Assume it to increase, thus expanding the bellows and
pivoting the force arm on diaphragm B towards the nozzle. Airflow from the nozzle is
restricted and build up in backpressure operates the direct acting relay to increase the
pressure on bellows c making angle a greater. The increase in pressure on diaphragm B
and the force arm causes this to pivot around the pivot point, thus moving the force arm
away from the nozzle. Equilibrium is thus restored to give a linear output signal, which is
square root of the input signal.
The triangle shows the relationship of forces, with R the longitudinal restraining force on
the flexure arm. Force A is directly proportional to the input pressure on bellows A.
Force B is directly proportional to the output pressure.
Tan α =A/B or B Tan α =A
Therefore if angle α is restricted to be very small ( α is less than 0.5 degree)
Bα= A
Position of flexure arm creating angle α is directly proportional to the pressure in bellows
C and this bellow is also connected to Bellow B
Therefore BxB =A Or B= √ A
Output pressure is square root of input pressure
In general an overall error of one percent of the maximum scale reading occurs with DP
Instruments.
Out put at the DP cell.
S
I
G
N
A
L
Flow Quantity: - F α√∆ P Therefore D.P cell output must be added with square root
extractor, for the signal becomes linear to flow rate
A - signal for the three term controller which protects the feed water flow and hence the
drum level against changes in feed water pressure .The set point of this controller is
cascaded from the summing relay whose output is input-1 minus input-2 plus the bias
(I1-I2+Bias). The output of the steam outflow flow-meter with square root extraction
and suitably scaled is sent via the summing relay direct to the set point of the feed water
flow controller so that inflow constantly matches outflow with minimal effect on boiler
water level .A level transmitter and a controller on the level drum provides a feedback
path to make small corrections to the set point of the feed water flow controller for losses
and gains to the drum level from other parts of the plant.
1) Cannot cope up with shrink and swell factor.
2) Also not suitable for high load changes.
Boilers where the steam release water storage ratio is low, i.e. where the amount of water
contained in the boiler relative to the steam output is reasonably high and also where load
variations are of limited magnitude. The level of the water in the boiler drum is referred
to a constant head with the resulting differential being applied to a differential
transmitter, which converts the measurement to a proportional pneumatic signal. This
signal is passed to a controller as a measured variable signal where it is compared with a
desired value and any deviation or error between the two causes the controller output to
change and pass the changed signal, via an auto/manual station, to the feed water control
valve.
In the two element boiler control water system another variable i.e. Is the steam flow is
being measured across the orifice plate using the differential pressure transmitter. The
differential pressure transmitter is been set across the square root extractor which makes
The signal liner to the flow and this signal is being used as measured value signal to the
controller.
The square root extractor output and PI controller output is passed through a summation
relay where both the signals are added up and this combine signal is being sent across the
final controlling element i.e. is feed check valve.
In two-element boiler water control any change in the steam demand is immediately
picked up by the differential pressure transmitter, which is mounted at the orifice plate.
Hence the output of the DP cell will indicate of variation in steam demand and will alter
the signal to the feed check valve considerably to negate the effect the shrink and swell
phenomenon.
pressure will affect the drum level and this control will then try to adjust the regulating
valve to restore the desired level condition.
NOTE—It will be seen that square root extractors have been incorporated on both steam
flow and feed flow signals to linearize them, as flow measurements by flow nozzle and
orifice plate have a square root function of the pressure drop across these.
This could cause cyclic conditions in the system, over working components and
compounding the trouble. A third element is therefore introduced, namely feed water
Based on the operation upon the fact that for equilibrium, steam flow must equal feed
water flow both of these conditions are monitored and signals compared in a differential
relay, and provided they are equal, then the output of this is added to the desired value of
the water level in the drum. This signal is then compared with the drum level measured
value signal in the two-term controller and any deviation or error between the measured
value and the desired value plus the difference between the steam and the feed flows will
cause the controller to reposition the feed water control valve to restore the level.
When there is an increase in the steam demand, the differential relay is unbalanced and
demands a higher drum level, counterbalancing the swell effect and trying to close the
feed water control valve. When the steam flow falls, the differential relay is again
International Maritime Training Centre 90
AUTOMATION & CONTROLS
unbalanced and demands a low level and alters the shrinkage effect.
Any variation in the feed water flow due to pressure fluctuation will be detected by the
flow meter, repositioning the valve before the drum level is affected. With this system it
is also possible to provide a variable level set point depending upon the load—higher
level as load increases and also high and low signal limits to optimize the setting of the
system to account for boiler dynamics under arduous maneuvering conditions.