Você está na página 1de 2

TEST REPORT

1. RELAY DETAILS:

Make ALSTOM
Relay Model MiCOM P141316N6M0460J
Serial No 32405540/01/13
Aux Voltage 110-250VDC
CT Ratio 2000/1A
VT Ratio 66000/110V

2. MEASURMENTS(RATIO):

Phase Applied Voltage(V) Measured Voltage L-L(KV) Measured Voltage L-N(KV)


R 63.51 ∟0 65.93 ˪0 38.07 ˪0
Y 63.51 ˪-120 65.93 ˪-90 38.07 ˪-120
B 63.51 ˪120 65.95 ˪150 38.07 ˪120

Phase Applied Current(A) Measured Current(A)


R 1 ˪0 2.001 ˪0
Y 1˪-120 2.000 ˪-120
B 1˪120 2.000 ˪+120

3. OVER CURRENT I>1:

Phase Set Current (A) Set Time(ms) Operating Time(ms)


R 1.2 500 558.3
Y 1.2 500 558.3
B 1.2 500 558.3

4. OVER CURRENT I>2: RCA:45

Phase Set Current(A) TMS Calculated Operating Time(ms)


2x Iset 5x Iset 10x Iset
R 0.6 0.2 1.2 2.055 3 896.6 6 635.2
Y 0.6 0.2 1.2 2.055 3 896.6 6 635.2
B 0.6 0.2 1.2 2.055 3 896.6 6 635.2

Theoretical Operating angle (Deg) Actual Operating angle(Deg)


R 45-0-225 43-0-228
Y 105-(-120)-285 108-(-120)-283
B 165-(+120)-345 163-(120)-348

Testing Engineer Witnessed By Date


G.Ramanakumar 26.03.2019
5. OVER VOLTAGE V>1:

Phase Set Voltage(V) Set Time(sec) Operating Time(sec)


R 76 ˪0 5 5.051
Y 76 ˪-120 5 5.051
B 76 ˪120 5 5.051

6. UNDER VOLTAGE V<1:

Phase Set Voltage(V) Set Time(sec) Operating Time(sec)


R 45 ˪0 2 4.082
Y 45 ˪-120 2 4.082
B 45 ˪120 2 4.082

7. UNDER FREQUENCY: F< set frequency

Phase Set Frequency(Hz) Set Time(sec) Operating Time(sec)


R 49 4 4.082
Y 49 4 4.082
B 49 4 4.082

8. OVER FREQUENCY: F>Set frequency

Phase Set Frequency(Hz) Set Time(sec) Operating Time(sec)


R 50.50 2 2.075
Y 50.50 2 2.075
B 50.50 2 2.075

Testing Engineer Witnessed By Date


G.Ramanakumar 26.03.2019