Você está na página 1de 2

abcd CLIENT : uvws

DATE:24-01-2019
BASIS OF DESIGN PROJECT:
LOCATON:xytz
Room No.

DEHUMID
IFIED AIR
Room Name TONNAGE SUPPLY AIR FLOW RATE
FLOW
RATE

flow rate SELECTED

Min. Air Flow rate as

Supply Air flow rate


Clean Classification

Min. Air changes as

per air changes per


DESIGN TONNAGE

(Max. of D.Hum air


Fresh Air flow rate
as per min FACPH
Relative Humidity

(AS PER CALCS)

as per calcs. and


Dehumidified Air

Dehumidified Air
flow rate (As per

AHU Capacity
Room Length

rounded off)
Room Width

Occupancy

Reheat KW
Eqpt load

per Class

selected
Volume

Calcs.)
Height

at rest
Area

hour
m m m m² m³ % # KW # cfm TR cfm # # cfm cfm KW
AHU-01

1 Reator Room 3.24 4.07 2.50 13.17 32.92 55+5 IS0 - 8 1 1 1.3 746 45 390 746

TOTAL 13 33 1 1 ### 1 746 ### 390 746 1000

AHU-02
1 Drier Room
2 Miller Room 3.24 4.07 2.50 13.17 32.92 55+5 IS0 - 8 2 1 ### 1.6 972 45 390 972
3 packing Quarintine Room 2.86 4.07 2.50 11.64 29.10 55+5 IS0 - 7 0 1 ### 0.40 181 45 384 384
2.86 2.32 2.50 6.64 16.59 55+5 IS0 - 7 0 0 0.20 118 45 210 210
2.50
2.86 1.70 2.50 4.86 12.16 55+5 IS0 - 7 0 0 0.20 118 45 210 210
TOTAL 31 79 2 2 ### 2 1271 ### 984 1566 2500

AHU-03
1 Change Room-1 1.66 1.78 2.50 2.95 7.39 55+5 IS0 - 8 2 2 ### 1.80 985 25 280 985
2 Change Room-2 1.78 3.80 2.50 6.76 16.91 55+5 IS0 - 8 3 2 ### 2.10 1227 25 410 1227
3 Air lock 1.66 1.78 2.50 2.95 7.39 55+5 IS0 - 8 2 2 ### 1.80 985 25 280 985

Carridor 1.78 3.80 2.50 6.76 16.91 55+5 IS0 - 8 3 2 ### 2.10 1227 25 410 1227
4

TOTAL 39 0 0 0 ### 4 2374 ### 0 2761 4000

1 Wash Room 2.30 2.00 2.50 4.60 11.50 UNCL UNCL


### 400 400 400
TOTAL 0 12 ### ### 400 400 500

1) AHU : Air Handling Unit; NC : Not Controlled; UNCL : Unclassified; NMT : Not More Than.

2) Grade - C : Clean Class 10000 [(At Rest) ISO-7]

3) Grade - D : Clean Class 100000 [(At Rest) ISO-8]


4) Grade – E : UN CLASSIFIED