This is PLC Program for automatic mixing controlling in a tank.

Automatic Mixing Controlling in a Tank


Material A and material B are collected in a tank. These materials will be mixed for
particular time and then mixed product drained out through outlet valve. Implement
ladder program for this application in PLC.
Problem Diagram
Problem Solution

 In this example, we use PLC programming of Siemens S7-300 PLC. We can use
other PLC also for this application.
 Two level sensors are used for detecting the level of material A and material B.
Also one bottom level sensor used for detecting the bottom level.
 To control level of this system, single acting valve is used which has two states,
either fully opened or fully closed.
 Particular is provided to mix the material A and material B in a tank. We can use
on delay timer this function.
 After successfully completion of mixing, outlet valve is operated to drain the
mixed material.
 When mixing process is completed, buzzer will be activated and it will remain ON
and after 5sec it will be automatically OFF.
List of inputs/outputs

Digital Inputs
 Cycle START :- I0.0
 Cycle STOP :- I0.1
 Low level switch :- I0.2
 Level material A :- I1.0
 Level material B :- I1.1
Digital outputs
 Cycle ON :- Q0.0
 Inlet valve 1 :- Q0.1
 Inlet valve 2 :- Q0.2
 Agitator motor :- Q0.3
 Outlet valve :- Q0.4
 Buzzer :- Q0.5
PLC Logic for Automatic mixing controlling in a tank
Program Description

For this application we used S7-300 PLC and TIA portal software for programming.
Network 1 :-
In network 1 latching circuit is used for latching the cycle. When START PB (I0.0) is
pressed, cycle ON (Q0.0) output will be ON and it can be STOP by pressing STOP
PB (I0.1).
Network 2 :-
When bottom level switch (I0.2) is detected and level material A (I1.0) is not detected,
inlet valve 1 will be ON (Q0.1).
Network 3 :-
When level material A (I1.0) is detected and level material B (I01.1) is not detected,
inlet valve 1 will be ON (Q0.1).
Network 4 :-
When the tank is full of material A and material B, level material B s detected. This
detection energizes the agitator motor and we need mixing for 20 s, so timer
instruction will be ON with agitator motor (Q0.3).
Network 5 :-
Timer instruction will be executed when agitator motor (Q0.3) is activated.
Network 6 :-
When mixing process is completed, Outlet valve (Q0.4) will be ON for draining the
mixed material.
Network 7 :-
When mixing process completed successfully, buzzer (alarm) will be ON (Q0.5).
Network 8 :-
Buzzer will remain ON for 5 second after 5sec it will be OFF. Here timer instruction is
executed.
Network 9 :-
When Buzzer ON delay completed, buzzer output will be OFF automatically.
Note:- Above application may be different from actual application. This example is
only for explanation purpose only. We can implement this logic in other PLC also. All
parameters are considered here for explanation.
Runtime Test Cases