Você está na página 1de 8

028.P.

N:Layout 2 7/21/10 2:28 PM Page 1

PRESSURE

H.V.A.C. Differential Pressure Switch


Series
ADPS

With Dual Scale Field Adjustable Set Point Knob RoHS

2-17/64 2-9/16
[57.5] [65]
Ø11/64 7/8 1-31/32
[Ø4.5] [22] [50]
21/64
[8.5]
Differential Pressure Switches

2-21/64
[59]

19/64 Ø15/64
[7.5] [Ø6]
51/64
- [18] +
(P2) (P1)

The Series ADPS Adjustable Differential Pressure Switch is designed SPECIFICATIONS


for pressure, vacuum, and differential pressures. The dual scaled adjustment Service: Air and non-combustible, compatible gases.
knob in inches water column and pascals allows changes to the switching Wetted Materials:
pressure to be made without a pressure gage. The ADPS is available with Diaphragm material: silicone; Housing material: POM switch body: PA
settings from 0.08˝ w.c. (20 Pa) up to 16˝ w.c. (4000 Pa). The silicone diaphragm 6.6; Cover: Polystyrene.
and PA 6.6 body make the series ADPS ideal for use with air and other Temperature Limits: Process and ambient temperature from -4 to 185˚F
noncombustible gases. The compact size, adjustment knob and low cost make the (-20 to 85˚C).
ADPS the perfect choice for H.V.A.C. applications. Pressure Limits: Max. operating pressure: 40˝ w.c. (10 kPa) for all
pressure ranges.
APPLICATIONS Switch Type: Single-pole double-throw (SPDT).
• Monitoring air filters and ventilators Electrical Rating: Standard: max., 1.5A/250 VAC, max. switching rate: 6
• Monitoring industrial cooling-air circuits cycles/min.; Gold contact option: 0.4 A/ 250 VAC.
• Overheating protection for fan heaters Electrical Connections: Push-on screw terminals. M20x1.5 with cable
• Monitoring flows in ventilation ducts strain relief or optional 1/2˝ NPT connection.
• Controlling air and fire-protection dampers Process Connections: 5/16˝ (7.94 mm) outside diameter tubing, 1/4˝
• Frost protection for heat exchanges (6.0 mm) inside diameter tubing.
Mounting Orientation: Vertically, with pressure connections pointing
downwards.
Dual Scale Mechanical Working Life: Over 106 switching operations.
A-480
Field Adjustable
Weight: 5.6 oz (160 g).
Set Point Knob
Enclosure Rating: NEMA 13, IP54.
Agency Approvals: CE, RoHS.
A

Set Point Range Approx. Dead Band @ Min Approx. Dead Band @ Max
Model in w.c. (Pa) Set Point in w.c. (Pa) Set Point in w.c. (Pa)
ADPS-01-2-N 0.08 to 0.80 (20-200) 0.04 (10) 0.05 (12)
ADPS-04-2-N 0.12 to 1.60 (30-400) 0.06 (15) 0.09 (22)
ADPS-03-2-N 0.20 to 2.00 (50-500) 0.08 (20) 0.09 (23)
ADPS-05-2-N 0.80 to 4.00 (200-1000) 0.4 (100) 0.5 (130)
ADPS-06-2-N 2.00 to 10.00 (500-2500) 0.6 (150) 0.8 (200)
ADPS-07-2-N 4.00 to 16.00 (1000-4000) 1.0 (250) 1.4 (350)
Note: Models that include installer kit add -C to the end of the model number
Installer kit includes two static tips and 7 ft or PVC tubing.
For optional 1/2˝ NPT conduit connection, change -2-N to -1-N.

ACCESSORIES
A-288, “L” type metal mounting bracket with screws
A-289, “S” type metal mounting bracket with screws
A-480, Plastic static pressure tip
A-481, Installer kit. Includes 2 plastic static pressure tips
and 7 ft (2.1 m) of PVC tubing
DISTRIBUTOR IN VIETNAM: BACH KHOA EQUIPMENT AND ACCESSORIES CO.,LTD. Tel: 84-8-38636419 www.hvac.vn
28 VISIT OUR WEBSITES: www.dwyer-inst.com • www.dwyer-inst.co.uk • www.dwyer-inst.com.au
040.P.N:Layout 2 2/21/11 9:50 AM Page 1

®
Series
Magnesense Differential Pressure Transmitter
PRESSURE

MS

Monitors Pressure & Air Velocity

(3) 3/16 (4.76) HOLES


EQUALLY SPACED ON A
Differential Pressure Transmitters

4.115 (104.52) BC
21/32
Ø3-7/16 [16.67] 21/32 29/32
[Ø87.31] [16.67] [23.02] 2-11/64
[55.17]
1/2
2-41/64 [12.70]
[67.07]
1/2 NPT 57/64 2-9/16
Standard MS with optional LCD [22.62] [65.09]

Ø35/84 [13.87]

8-1/8
[206.38]

MS with optional LCD and static probe

The Series MS Magnesense® Differential Pressure Transmitter is an SPECIFICATIONS


extremely versatile transmitter for monitoring pressure and air velocity. This Service: Air and non-combustible, compatible gases.
compact package is loaded with features such as: Wetted Materials: Consult factory.
Accuracy: ±1% for 0.25˝ (50 Pa), 0.5˝ (100 Pa), 2˝ (500 Pa), 5˝ (1250
• Field selectable English or Metric ranges Pa), 10˝ (2 kPa), 15˝ (3 kPa), 25˝ (5 kPa) ±2% for 0.1˝ (25 Pa), 1˝ (250
• Field upgradeable LCD display Pa) and all bi-directional ranges.
• Adjustable damping of output signal (with optional display) Stability: ±1% / year F.S.O.
• Ability to select a square root output for use with pitot tubes and other Temperature Limits: 0 to 150°F (-18 to 66°C).
similar flow sensors Pressure Limits: 1 psi maximum, operation; 10 psi, burst.
Power Requirements: 10 to 35 VDC (2-wire); 17 to 36 VDC or isolated
Along with these features, the patented magnetic sensing technology provides 21.6 to 33 VAC (3-wire).
exceptional long term performance and enables the Magnesense® Differential Output Signals: 4 to 20 mA (2-wire); 0 to 5 V, 0 to 10 V (3-wire).
Pressure Transmitter to be the single solution for your pressure and flow Response Time: Adjustable 0.5 to 15 sec. time constant. Provides a
applications. 95% response time of 1.5 to 45 seconds.
Zero & Span Adjustments: Digital push button.
Loop Resistance: Current output: 0-1250 Ω max; Voltage output: min.
load resistance 1 kΩ.
Model Output Selectable Ranges Current Consumption: 40 mA max.
MS-121* 4-20 mA 0.1˝, 0.25˝, 0.5˝ w.c. (25, 50, 100 Pa) Display (optional): 4 digit LCD.
MS-321* 0-10 V 0.1˝, 0.25˝, 0.5˝ w.c. (25, 50, 100 Pa) Electrical Connections:
MS-111* 4-20 mA 1˝, 2˝, 5˝ w.c. (250, 500, 1250 Pa) 4-20 mA, 2-Wire: European style terminal block for 16 to 26 AWG.
MS-311* 0-10 V 1˝, 2˝, 5˝ w.c. (250, 500, 1250 Pa) 0-10 V, 3-Wire: European style terminal block for 16 to 22 AWG.
MS-131 4-20 mA 10˝ w.c. (2 kPa) Electrical Entry: 1/2˝ NPS thread
MS-141 4-20 mA 15˝ w.c. (3 kPa) Accessory (A-151): Cable gland for 5 to 10 mm diameter cable.
MS-151 4-20 mA 25˝ w.c. (5 kPa) Process Connections: 3/16˝ ID tubing (5 mm ID). Maximum OD 9 mm.
MS-721* 0-5 V 0.1˝, 0.25˝, 0.5˝ w.c. (25, 50, 100 Pa) Enclosure Rating: NEMA 4X (IP65).
MS-711* 0-5 V 1˝, 2˝, 5˝ w.c. (250, 500, 1250 Pa) Mounting Orientation: Diaphragm in vertical position.
MS-621 0-5 V ±0.1˝, 0.25˝,0.5˝ w.c. (±25, 50, 100 Pa) Weight: 8.0 oz (230 g).
MS-331 0-10 V 10˝ w.c. (2 kPa) Agency Approvals: CE.
MS-341 0-10 V 15˝ w.c. (3 kPa)
MS-351 0-10 V 25˝ w.c. (5 kPa)
MS-021 4-20 mA ±0.1˝, 0.25˝,0.5˝ w.c. (±25, 50, 100 Pa)
MS-221 0-10 V ±0.1˝, 0.25˝,0.5˝ w.c. (±25, 50, 100 Pa) ACCESSORIES
A-435, Field Upgradeable LCD
Note: Add -LCD to end of model for units with display. A-480, Plastic Static Pressure Tip
*Models available with duct mount static pressure probe. Change last A-481, Installer kit. Includes 2 plastic static pressure tips and 7 ft (2.1 m)
digit from 1 to 2. Ex. MS-122 of PVC tubing

DISTRIBUTOR IN VIETNAM: BACH KHOA EQUIPMENT AND ACCESSORIES CO.,LTD. Tel: 84-8-38636419 www.hvac.vn
40 VISIT OUR WEBSITES: www.dwyer-inst.com • www.dwyer-inst.co.uk • www.dwyer-inst.com.au
309.P.N:Layout 2 7/23/10 11:43 AM Page 1

Series
S
Surface Mount Temperature Sensor
RTD and Thermistor, 304 SS Probe, Waterproof
2.000˝
[50]
CABLE LENGTH
6FT [1.8]

ø1/4˝
[6.3]

The Series S Surface Mount Temperature Sensors provide a cost effective and SPECIFICATIONS
reliable solution for surface contact temperature measurement of conditioned water pipes, Accuracy:
low pressure steam or refrigerant lines. The sensors are ideal for applications where Platinum RTD: ±0.1% @ 32°F (0°C), alpha 385 per DIN 43760.
immersion wells are not practical to install. Models are constructed with a 2˝ (50 mm) 304 Nickel RTD: ±0.5°F @ 70°F (21.1°C).
SS probe and a 6 ft (1.8 m) plenum rated cable. Nylon ties are included to secure the sensor Balco: ±0.5°F @ 70°F (21.1°C).
to the pipe. Thermistor: ±0.2°C interchangeable @ 77°F (25°C).
Operating Temperature: -40 to 250°F (-40 to 125°C).
Model Sensor Type
Probe Diameter: 1/4˝ (6.3 mm).
S-11 Pt 100Ω RTD
Probe Length: 2˝ (50 mm).
S-12 Pt 1000Ω RTD
Probe Material: 304 SS.
S-13 Ni 1000Ω RTD
S-14 1000Ω Balco RTD
S-15 10 kΩ NTC Thermistor
S-16 3 kΩ NTC Thermistor
S-17 5 kΩ NTC Thermistor
S-18 100 kΩ NTC Thermistor
S-19 20 kΩ NTC Thermistor
S-1A 2252Ω NTC Thermistor

Series
I2-1 Immersion Temperature Probes
RTD & Thermistor Outputs, 304 SS Probes

TEMPERATURE
1-27/32
1/2˝ INTERNAL NPT [46.99] 1/2˝ EXTERNAL NPT
1-1/8 [28.19] 6˝ THERMOWELL: L = 6.250˝
3/8 [9.53] 4˝ THERMOWELL: L = 4.000˝
L
1W2-2X2 THERMOWELL
1-5/16
[33.31] 1/2˝ NPT
31/32 [24.87]
L = 7.000˝ FOR 6˝ THERMOWELL
1/4 [6.37] L = 5.000˝ FOR 4˝ THERMOWELL
L
12-1X0X2 SENSOR

The Series I2-1 Immersion Temperature Probes are designed to monitor the hot SPECIFICATIONS
and chilled water lines throughout a building’s water distribution loop. The multiple Accuracy: Platinum RTD: ±0.6% @ 32°F (0°C); Nickel RTD: ±0.5°F @ 32°F
temperature sensor outputs allow these sensors to connect to virtually any digital building (0°C); Balco RTD: ±0.1% @ 32°F (0°C); Thermistors: ±0.36°F from 32 to 158°F (0
controller. The Series IW2 stainless steel thermowells allow the temperature sensors to to 70°C).
be replaced without draining the water line. The temperature sensors are available in 4˝ Operating Temperature: -32 to 240°F (-35.5 to 115.5 °C).

Temperature Sensors
and 6˝ insertion lengths. Probe Diameter: 1/4˝ (6.3 mm).
Cable Length: 6 ft (1.8 m).
Note: A Series IW2 Thermowell must be used on pressurized air and water lines to Probe Material: 304 SS.
prevent leakage around the probe. Mounting: 1/2˝ threaded connection to fit Series IW2 thermowell.

Model Sensor Type Insertion Length Model Sensor Type Insertion Length
I2-11062 Pt 100 Ohm RTD 6˝ I2-11042 Pt 100 Ohm RTD 4˝
I2-12062 PT 1000 Ohm RTD 6˝ I2-12042 PT 1000 Ohm RTD 4˝
I2-13062 Ni 1000 Ohm RTD 6˝ I2-13042 Ni 1000 Ohm RTD 4˝
I2-14062 Balco 1000 Ohm RTD 6˝ I2-14042 Balco 1000 Ohm RTD 4˝
I2-15062 10K Ohm Type 2 Thermistor 6˝ I2-15042 10K Ohm Type 2 Thermistor 4˝
I2-16062 3K Ohm Thermistor 6˝ I2-16042 3K Ohm Thermistor 4˝
I2-17062 5K Ohm Thermistor 6˝ I2-17042 5K Ohm Thermistor 4˝
I2-18062 100K Ohm Thermistor 6˝ I2-18042 100K Ohm Thermistor 4˝
I2-19062 20K Ohm Thermistor 6˝ I2-19042 20K Ohm Thermistor 4˝
I2-1A062 2252 Ohm Thermistor 6˝ I2-1A042 2252 Ohm Thermistor 4˝
I2-1B062 10K Ohm Type 3 Thermistor 6˝ I2-1B042 10K Ohm Type 3 Thermistor 4˝

Thermowells
Model Material Insertion Length ACCESSORY
IW2-262 304 SS 6˝ IW-C, Thermowell Compound
IW2-242 304 SS 4˝

DISTRIBUTOR IN VIETNAM: BACH KHOA EQUIPMENT AND ACCESSORIES CO.,LTD. Tel: 84-8-38636419 www.hvac.vn
CALL TO ORDER: U.S. Phone 219 879-8000 • U.K. Phone (+44) (0)1494-461707 • Australia Phone (+61) (0) 2 4272 2055 309
132_Layout 2 7/18/13 3:44 PM Page 132

Series
RHP
Humidity/Temperature Transmitter
Passive Temperature Outputs, Sintered Filter Options
Duct Mount OSA (Outside Air)
5-1/8
4-17/32 2-15/64 4-17/32 [130.18]
[115.09] [56.75] [115.09]

3-1/8
3-1/8 [79.38]
[79.38]
1-13/64
[30.56]
AIR QUALITY

6-25/32
Ø3/16 [172.09]
[4.76]
MOUNTING
2-11/64 HOLES
[55.17] TYP 4 PLCS 55/64
[21.83]
1/2 NPT
2-33/64
2-9/64 9
[63.90]
[228.60] Sintered Filter Version 5-1/8
[54.37] [130.18] 2-1/4
ø35/64 55/64 [57.15]
ø3-7/16 [21.83]
[ø87.31] [ø13.89]
3-45/64
[94.06]
Humidity/Temperature

(3) 3/16 (4.76) HOLES


EQUALLY SPACED ON A
Transmitters

ø3-11/64 4 115 (104.52) BC 6-25/32


[ø80.57] 2- 9/16 [172.16]
[64.96]

2-11/64 2-41/64
[55.12] [67.07]

The Series RHP Temperature and Humidity Transmitter combine the voltage or SPECIFICATIONS
current humidity transmitter output with a passive temperature thermistor or RTD output. Relative Humidity Range: 0 to 100% RH.
The polymer capacitance humidity sensor is not affected by condensation, fog, high Temperature Range: -40 to 140°F (-40 to 60°C).
humidity, or contaminants. The humidity sensors are available with 2%, 3% or 5% accuracies. Accuracy, RH:
Duct mounted transmitters are available with an optional two-line alpha numeric LCD RHP-2XXX ±2% 10-90% RH @ 25°C;
display. The Series RHP is available with interchangeable filter options as well as RHP-3XXX ±3% 20-80% RH @ 25°C;
replaceable sensors. RHP-5XXX ±5% 20-80% RH @ 25°C.
Accuracy, Thermistor Temp Sensor: ±0.2°C @ 25°C (±0.36°F @ 77°F).
Example RHP 2 D 1 A LCD RHP-2D1A-LCD Accuracy, RTD Temp Sensor: DIN Class B; ±0.3°C @ 0°C (±0.54°F @ 32°F).
Series RHP RH/Passive Temperature Hysteresis: ±1%.
Sensor Transmitter Repeatability: ±0.1% typical.
Accuracy 2 2% Accuracy Temperature Limits: -40 to 140°F (-40 to 60°C).
3 3% Accuracy Storage Temperature: -40 to 176°F (-40 to 80°C).
5 5% Accuracy Compensated Temperature Range: -4 to 140°F (-20 to 60°C).
Housing D Duct Mount 4 to 20 mA Loop Powered Models:
Type w/Membrane Filter Power requirements: 10 to 35 VDC;
F Duct Mount Output signal: 4 to 20 mA.
w/Sintered Filter 0-5/10V Output Models:
O OSA (Outside Air) Power requirements: 15 to 35 VDC or 15 to 29 VAC;
S OSA w/Sintered Filter* Output signal: 0 to 10V @ 5 mA max.
R Radiation Shield Response Time: 15 seconds.
RH Output 1 4 to 20mA Electrical Connections: Removable screw terminal block.
2 0 to 10V Conduit Connection:
3 0-5V Duct mount: 1/2˝ NPS;
Temperature 0 None OSA: 1/2˝ (22.3 mm).
Sensor 1 4 to 20mA Drift: <1% RH/year.
2 0 to 10 VDC RH Sensor: Capacitance polymer.
3 0-5V Temperature Sensor:
A 10K @ 25°C Thermistor Types 1, 2, 3: Solid state band gap;
Type III Curves A, B, C: Thermistor;
B 10K @ 25°C Thermistor Curves D, E: Platinum RTD DIN 385.
Type II Enclosure:
C 3K @ 25°C Thermistor Duct mount: PBT;
D 100Ω RTD DIN 385 OSA: Polycarbonate.
E 1KΩ RTD DIN 385 Enclosure Rating: NEMA 4X (IP66) for OSA mount only.
F 20KΩ @ 25°C Thermistor Display: Duct mount only, optional 2-line alpha numeric, 8 characters/line.
Option LCD LCD Display Display Resolution: RH: 0.1%; 0.1°F (0.1°C).
NIST NIST traceable calibration Weight:
certificate (Humidity) Duct mount: .616 lb (.3 kg);
*Model RHRS Radiation Shield is required for sintered filter OSA models. OSA: 1 lb (.45 kg).
Agency Approvals: CE.

132 DWYER INSTRUMENTS, INC. | www.dwyer-inst.com


203.P.N:Layout 2 7/23/10 10:49 AM Page 1

Vane Flow Switch


Series
FS-2

Low Cost, Field Adjustable Set Point


2-13/32 5
[61.1] [127]
4-17/64
[108.3]

3-1/32
[77]

5-49/64
[146.5]

5-1/8 Shown with conduit


[130.2] connection option

The Series FS-2 Vane Flow Switch offers an economical flow proving solution. SPECIFICATIONS
Custom set points tailored for the application are enabled by field adjustable vane layers Service: Compatible liquids.

FLOW
and a set point adjustment screw. The FS-2 features an aluminum weatherproof housing Wetted Materials:
for outdoor installation. Paddles are adjustable to fit 1˝ to 8˝ size pipe. FS-2 is ideal for Bellow: Tin-bronze.
use in “flow or no flow” applications in cold and hot water systems. Perfect for proving flow Vane: Stainless Steel.
in boilers, hot water heaters, and chillers. Body: Forged brass.
Temperature Limit: 230ºF (110ºC).
APPLICATION Pressure Limit: 145 psig (10 bar).
• Perfect for proving flow in boilers, hot water heaters, and chillers Enclosure Rating: NEMA 4 (IP64).
Switch Type: SPDT snap switch.
FEATURES Electrical Rating: 10A res, 3A ind @ 250 VAC.
• Field adjustable paddle Electrical Connection: Cable gland with attached wire leads or optional conduit
• Field adjustable set point connection.

Flow Switches, Paddle


• Weatherproof construction Process Connection: 1˝ male NPT or BSPT.
Mounting Orientation: Switch must be installed vertically on horizontal pipe runs.
Set Point Adjustment: Four vane combinations and an adjustment screw.
Enclosure: Die-cast aluminum alloy.
Flow Rate Chart
Weight: 28.22 oz (0.8 kg).
Approximate Actuation and Deactuation Agency Approvals: CE.
Blade Vane Flow Rates for Water
Pipe Length Minimum Setting Maximum Setting
Diameter in (mm) GPM (LPM) GPM (LPM)
(inch) Dim. X Actuate Deactuate Actuate Deactuate
Series FS-2, Paddle Flow Switch
1 1.34 (34) 4.0 (15.0) 1.8 (6.7) 8.8 (33.3) 6.6 (25.0)
1-1/4 1.34 (34) 5.3 (20.0) 2.6 (10.0) 11.4 (43.3) 8.4 (31.7)
1-1/2 2.24 (57) 7.0 (26.7) 4.0 (15.0) 14.5 (55.0) 11.4 (43.3) OPTIONS
2 2.24 (57) 14.1 (53.3) 9.7 (36.7) 31.3 (118.3) 22.5 (85.0) BSPT Process Connection,
2-1/2 3.46 (88) 18.5 (70.0) 15.4 (58.3) 35.2 (133.3) 30.8 (116.7) To order add suffix -BSPT.
3 3.46 (88) 27.7 (105.0) 25.1 (95.0) 52.8 (200.0) 46.2 (175.0) Example: FS-2-BSPT
4 3.46 (88) 59.4 (225.0) 52.8 (200.0) 123.3 (466.7) 114.5 (433.3)
5 6.57 (167) 52.8 (200.0) 39.6 (150.0) 132.1 (500.0) 123.3 (466.7) Conduit Connection, 1˝ NPT female conduit connection with no wire leads.
6 6.57 (167) 75.7 (286.7) 52.8 (200.0) 154.1 (583.3) 140.9 (533.3) To order add suffix -CND.
8 6.57 (167) 184.9 (700.0) 158.5 (600.0) 396.3 (1500.0) 374.2 (1416.7) Example: FS-2-CND

DISTRIBUTOR IN VIETNAM: BACH KHOA EQUIPMENT AND ACCESSORIES CO.,LTD. Tel: 84-8-38636419 www.hvac.vn
CALL TO ORDER: U.S. Phone 219 879-8000 • U.K. Phone (+44) (0)1494-461707 • Australia Phone (+61) (0) 2 4272 2055 203
Series
626 Industrial Pressure Transmitter
PRESSURE

&
628 Complete Offering of Ranges, Connections and Outputs
Single Pressure Transmitters

General Purpose Housing (-GH) General Purpose Housing (-GH) with DIN C

626 with LED Display (CH housing only) Conduit Housing (-CH)

*Please see our website for dimensional drawings.

The Series 626 Pressure Transmitters possess a highly precise 0.25% piezo-resistive SPECIFICATIONS
Service: Compatible gases and liquids.
Wetted Materials: Type 316L SS.
sensor contained in a compact, rugged, NEMA 4X stainless steel general purpose housing

Accuracy: 626: 0.25% full scale; 626 absolute ranges: 0.5% full scale; 628: 1%
or cast aluminum conduit housing.

The Series 628 Pressure Transmitters are ideal for OEMs with 1% full scale accuracy full scale. (Includes linearity, hysteresis, and repeatability.)
Temperature Limit: 0 to 200°F (-18 to 93°C).
Compensated Temperature Range: 0 to 175°F (-18 to 79°C).
sensors. The transmitter is also available in the general purpose stainless steel housing

Thermal Effect: 626: ±0.02% FS/°F. 628: ±0.04% FS/°F (includes zero and span).
and the cast aluminum conduit housing.

Pressure Limits: See table.


The corrosion resistant 316L stainless steel wetted parts allow the Series 626 and 628

Power Requirements: 13 to 30 VDC.


transmitters to measure the pressure in a multitude of processes from hydraulic oils to

Output Signal: 4 to 20 mA. Optional 0-5,1-5 or 0-10.


chemicals. The Series 626 and 628 are available in ranges of vacuum, compound to 5000

Response Time: 50 msec.


psi with a variety of optional outputs, process connections and electrical terminations to

Loop Resistance: 0 - 1300 ohms maximum for current. For voltage outputs,
allow you to select the right transmitter for your application.

APPLICATIONS minimum load resistance: 2000 ohms.


• Compressors Current Consumption: 38 mA (maximum).
• Pumping systems Electrical Connections: Conduit Housing (-CH): terminal block, 1/2˝ female NPT
• Irrigation equipment conduit; General Purpose Housing (-GH): cable DIN EN 175801-803-C.
• Hydraulic Process Connection: 1/4˝ male or female NPT and BSPT.
• Industrial process monitoring Enclosure Rating: NEMA 4X (IP66).
Mounting Orientation: Mount in any position.
FEATURES Weight: 10 oz (283 g).
• Metal conduit housing option Agency Approvals: CE.
• Robust 316 SS oil filled sensor
• Compact design

102
DISTRIBUTOR IN VIETNAM: BACH KHOA EQUIPMENT AND ACCESSORIES CO.,LTD. Tel: 84-8-38636419 www.hvac.vn
VISIT OUR WEBSITES: www.dwyer-inst.com • www.dwyer-inst.co.uk • www.dwyer-inst.com.au
103.qxd:Layout 2 4/13/11 8:19 AM Page 1

Pressure Limits
Range Pressure Maximum Over Range Pressure Maximum Over

PRESSURE
Number Range Pressure (psig) Pressure (psig) Number Range (psig) Pressure (psig) Pressure (psig)
00 0-15 psia 30 45 11 0-150 300 750
30 15-0 psia 30 45 12 0-200 400 1000
06 0-5 psig 10 50 13 0-300 600 1500
07 0-15 psig 30 150 14 0-500 1000 2500
08 0-30 psig 60 300 15 0-1000 2000 5000
09 0-50 psig 100 300 16 0-1500 3000 5000
10 0-100 psig 200 500 18 0-3000 6000 7500
19 0-5000 7500 10000
26 0-8000 10000 12000

Single Pressure Transmitters


Ordering Chart
Accuracy
626 0.25% Full Scale Accuracy
628 1.0% Full Scale Accuracy
Range -00 0-15 psia
-06 0-5 psi
-07 0-15 psi
-08 0-30 psi
-09 0-50 psi
-10 0-100 psi
-11 0-150 psi
-12 0-200 psi
-13 0-300 psi
-14 0-500 psi
-15 0-1000 psi
-16 0-1500 psi
-18 0-3000 psi
-19 0-5000 psi
-26 0-8000 psi
-67 0-0.5 bar
-71 0-2.5 bar
-75 0-10 bar
-81 0-40 bar
Housing -CH Conduit Housing
-GH General Purpose Housing
Process -P1 1/4˝ male NPT
Connection -P2 1/4˝ female NPT
-P3 1/4˝ male BSPT
-P5 1/4˝ female SAE with Refrigerant Valve Depressor 1
-P9 1/2˝ male NPT1
Electrical -E1 Cable Gland with 3’ of Prewired Cable
Connection -E3 Cable Gland with 9’ of Prewired Cable
-E4 DIN EN 175801-803-L 1
-E5 1/2˝ female NPT Conduit 2
-E6 M-12 4 Pin Connector
Signal Output -S1 4-20 mA
-S2 1-5 Volt
-S4 0-5 Volt
-S5 0-10 Volt
Options -AT Aluminum Tag
-NIST NIST Traceable Certificate
-LED Bright Red LED display23

1 Available with -GH Housing only


2 Available with -CH Housing only
3 LED option is not NEMA 4X

CALL TO ORDER: U.S. Phone 219 879-8000 • U.K. Phone (+44) (0)1494-461707 • Australia Phone (+61) (0) 2 4272 2055 103

DISTRIBUTOR IN VIETNAM: BACH KHOA EQUIPMENT AND ACCESSORIES CO.,LTD. Tel: 84-8-38636419 www.hvac.vn
310.P.N:Layout 2 7/23/10 11:42 AM Page 1

DISTRIBUTOR IN VIETNAM: BACH KHOA EQUIPMENT AND ACCESSORIES CO.,LTD. Tel: 84-8-38636419 www.hvac.vn
Series
I2-2 General Purpose Immersion Temperature Sensor
Locking Screw Cover, Multiple Conduit Holes
2-3/16 2
[55.88] [50.80] 4X ø0.896˝ [22.76 MM]
1/2˝ NPT CONDUIT KNOCKOUTS

FOR 1/2˝ NPT THERMOWELL CONNECTION


4-1/16
[103.12]
L
L = 7.000˝ FOR 6˝ THERMOWELL
L = 5.000˝ FOR 4˝ THERMOWELL
2X ø0.743˝ [18.87 MM]
3/8˝ NPT CONDUIT KNOCKOUTS

The Series I2-2 General Purpose Immersion Temperature Sensor is ideal for SPECIFICATIONS Operating Temperature: -32 to 240°F
monitoring hot and chilled water lines throughout a building or mechanical room. The Accuracy: (-35.5 to 115.5 °C).
plastic housing is in the shape of a standard junction box with multiple knockouts for easy Platinum RTD: ±0.6% @ 32°F Probe Diameter: 1/4˝ (6.3 mm).
conduit access. The locking cover prevents unauthorized occupants from tampering with (0°C); Cable Length: 8˝.
the temperature sensor. The Sensor I2-2 can be ordered with a choice of 11 output options Nickel RTD: ±0.5°F @ 32°F (0°C); Probe Material: 304 SS.
that allow it to communicate to any standard building control system. Balco RTD: ±0.1% @ 32°F (0°C); Mounting: 1/2˝ threaded connection to
Thermistors: ±0.36°F from 32 to fit Series IW2 thermowell.
Note: A Series IW2 Thermowell must be used on pressurized air and water lines to 158°F (0 to 70°C).
prevent leakage around the probe.

Model Sensor Type Insertion Length Model Sensor Type Insertion Length
I2-21062 Pt 100 Ohm RTD 6˝ I2-21042 Pt 100 Ohm RTD 4˝
I2-22062 PT 1000 Ohm RTD 6˝ I2-22042 PT 1000 Ohm RTD 4˝
I2-23062 Ni 1000 Ohm RTD 6˝ I2-23042 Ni 1000 Ohm RTD 4˝
I2-24062 Balco 1000 Ohm RTD 6˝ I2-24042 Balco 1000 Ohm RTD 4˝
I2-25062 10K Ohm Type 2 Thermistor 6˝ I2-25042 10K Ohm Type 2 Thermistor 4˝
I2-26062 3K Ohm Thermistor 6˝ I2-26042 3K Ohm Thermistor 4˝
I2-27062 5K Ohm Thermistor 6˝ I2-27042 5K Ohm Thermistor 4˝
I2-28062 100K Ohm Thermistor 6˝ I2-28042 100K Ohm Thermistor 4˝
I2-29062 20K Ohm Thermistor 6˝ I2-29042 20K Ohm Thermistor 4˝
I2-2A062 2252 Ohm Thermistor 6˝ I2-2A042 2252 Ohm Thermistor 4˝
I2-2B062 10K Ohm Type 3 Thermistor 6˝ I2-2B042 10K Ohm Type 3 Thermistor 4˝
Thermowells ACCESSORY
Model Material Insertion Length IW-C, Thermowell Compound
IW2-262 304 SS 6˝
IW2-242 304 SS 4˝

Series
I2-4 Weather-Proof Immersion Temperature Sensor
TEMPERATURE

Twist Off Cover, Multiple Conduit Holes


2-7/32 4X ø0.896˝ [22.76 MM]
[56.16] 1/2˝ NPT CONDUIT KNOCKOUTS
3-31/32
[101.00] FOR 1/2˝ NPT THERMOWELL CONNECTION
3-3/32 [78.74]

1/4
[6.35]
L
L = 7.000˝ FOR 6˝ THERMOWELL
L= 5.000˝ FOR 4˝ THERMOWELL

The Series I2-4 Weather-Proof Immersion Temperature Sensor is ideal for SPECIFICATIONS Operating Temperature: -32 to 240°F
monitoring hot and chilled water lines feeding Air Handlers and Cooling Towers. The Accuracy: (-35.5 to 115.5 °C).
Temperature Sensors

plastic housing has a 1/4 turn twist off cover to reduce installation time. The multiple Platinum RTD: ±0.6% @ 32°F Probe Diameter: 1/4˝ (6.3 mm).
knockouts allow for easy conduit access to any side of the housing. The Series I2-4 can be (0°C); Cable Length: 8˝.
ordered with a choice of 11 output options that allow it to communicate to any standard Nickel RTD: ±0.5°F @ 32°F (0°C); Probe Material: 304 SS.
building control system. Balco RTD: ±0.1% @ 32°F (0°C); Mounting: 1/2˝ threaded connection to
Thermistors: ±0.36°F from 32 to fit Series IW2 thermowell.
Note: A Series IW2 Thermowell must be used on pressurized air and water lines to 158°F (0 to 70°C).
prevent leakage around the probe.
Model Sensor Type Insertion Length Model Sensor Type Insertion Length
I2-41062 Pt 100 Ohm RTD 6˝ I2-41042 Pt 100 Ohm RTD 4˝
I2-42062 PT 1000 Ohm RTD 6˝ I2-42042 PT 1000 Ohm RTD 4˝
I2-43062 Ni 1000 Ohm RTD 6˝ I2-43042 Ni 1000 Ohm RTD 4˝
I2-44062 Balco 1000 Ohm RTD 6˝ I2-44042 Balco 1000 Ohm RTD 4˝
I2-45062 10K Ohm Type 2 Thermistor 6˝ I2-45042 10K Ohm Type 2 Thermistor 4˝
I2-46062 3K Ohm Thermistor 6˝ I2-46042 3K Ohm Thermistor 4˝
I2-47062 5K Ohm Thermistor 6˝ I2-47042 5K Ohm Thermistor 4˝
I2-48062 100K Ohm Thermistor 6˝ I2-48042 100K Ohm Thermistor 4˝
I2-49062 20K Ohm Thermistor 6˝ I2-49042 20K Ohm Thermistor 4˝
I2-4A062 2252 Ohm Thermistor 6˝ I2-4A042 2252 Ohm Thermistor 4˝
I2-4B062 10K Ohm Type 3 Thermistor 6˝ I2-4B042 10K Ohm Type 3 Thermistor 4˝
Thermowells
Model Material ACCESSORY
Insertion Length
IW2-262 304 SS 6˝ IW-C, Thermowell Compound
IW2-242 304 SS 4˝

310 VISIT OUR WEBSITES: www.dwyer-inst.com • www.dwyer-inst.co.uk • www.dwyer-inst.com.au