Service Bulletin

DriveTools32™ Downloads to Bulletin


3500-TBX Interfaces

Precautions

ATTENTION: Risk of injury or equipment damage exists.


! Unintended motion may be caused by DriveTools32™
downloads to the Bulletin 3500-TBX interface, over-writing the
Status Command parameter. This risk exists for the equipment
listed in the table below. Follow this procedure to avoid the risk.

Important: This procedure is not required if the DriveManager32 Version


2.50.01 patch is downloaded, installed and verified. Refer to
publication 9303-RN001A-EN-P, Release Note -
DriveTools32™ Version 2.50 Software Updates.
Table A Affected Products
Product Family Products Description
Bulletin 1352 Bulletin 1352 AC Scalar Drives
Bulletin 1352 Bulletin 1352 AC Vector Drives
Bulletin 3400 Bulletin 3450 DC Drives
Bulletin 3460 DC Drives
Bulletin 3500 Bulletin 1352 AC Scalar System Drives
Bulletin 1352 AC Vector System Drives
Bulletin 3502 Bulletin 3502 LGU

Procedure 1. Verify that the drive has been stopped and is at zero speed with power on.

2. Disconnect the Drive Enable input by removing connector X3 from the


TBX board.

3. Open the offline parameter file to be downloaded.

4. Check STATUS_CMD (parm 13) or LGU_CONTROL (parm 13) and


change to a value that will stop the drive (4 for 1352 and 3400 drives, 1
for 3502 LGU). Note the parameter view will be different for each type
of product.

Publication 9303-SB001A-EN-P - May 2002


2 DriveTools32™ Downloads to Bulletin 3500-TBX Interfaces

Figure 1 Off-line View of STATUS_CMD (parm 13) for 1352 AC Scalar Drives and 1352
AC Vector Drives

Enter a value of 4 in
the Internal Units box.

This will set


COAST_STOP (bit 2)

Figure 2 Off-line View of STATUS_CMD (parm 13) for 3400 DC Drives

Enter a value of 4 in
the Internal Units box.

This will set


COAST_STOP (bit 2)

Publication 9303-SB001A-EN-P - May 2002


DriveTools32™ Downloads to Bulletin 3500-TBX Interfaces 3

Figure 3 Off-line View of LGU_CONTROL (parm 13) for 3502 LGU

Enter a value of 1 in
the Internal Units box.

This will set


STOP (bit 0)

5. Save the parameter file.

6. Verify the value of STATUS_CMD (parm 13) or LGU_CONTROL


(parm 13) is still correct (4 for 1352 and 3400 drives, 1 for 3502 LGU).

Publication 9303-SB001A-EN-P - May 2002


4 DriveTools32™ Downloads to Bulletin 3500-TBX Interfaces

7. Download parameter file to the drive or LGU.


Figure 4 Downloading to a Drive or LGU

Click the Download icon

Enter the DH+ station number of


the drive or LGU

Click the OK button

This window will vary slightly


from product to product because
of varying product names,
versions and configurations.

Note: If the TBX has not


requested this information from Click the OK button
the drive since the last power
cycle, it may take more than one
attempt to connect to the drive
or LGU.

DriveTools should then begin


downloading the parameters

Publication 9303-SB001A-EN-P - May 2002


DriveTools32™ Downloads to Bulletin 3500-TBX Interfaces 5

8. After the download is complete, connect and go on-line with the drive or
LGU.
Figure 5 Connecting with the Drive or LGU and Going On-line
Click the Connect icon

Enter the DH+ station number of


the drive or LGU

Click the OK button

This window will vary slightly


from product to product because
of varying product names,
versions and configurations.

Note: If the TBX has not


requested this information from Click the OK button
the drive since the last power
cycle, it may take more than one
attempt to connect to the drive
or LGU.

Publication 9303-SB001A-EN-P - May 2002


6 DriveTools32™ Downloads to Bulletin 3500-TBX Interfaces

9. Examine STATUS_CMD (parm 13) or LGU_CONTROL (parm 13) and


verify that the start bits are off. Note the parameter view will be different
for each type of product.
Figure 6 On-line View of STATUS_CMD (parm 13) for 1352 AC Scalar Drives and 1352
AC Vector Drives

Verify that the following bits are off:


• START @ 27/29 (bit 6)
• START @ 161/167 (bit 7)
• START @ 162/168 (bit 8)

Figure 7 On-line View of STATUS_CMD (parm 13) for 3400 DC Drives

Verify that the following bits are off:


• bit 6
• bit 7
• bit 8

Publication 9303-SB001A-EN-P - May 2002


DriveTools32™ Downloads to Bulletin 3500-TBX Interfaces 7

Figure 8 On-line View of LGU_CONTROL (parm 13) for 3502 LGU

Verify that START (bit 1) is off

10.Re-connect the Drive Enable input by re-connecting connector X3 to the


TBX board.

Publication 9303-SB001A-EN-P - May 2002


www.rockwellautomation.com

Corporate Headquarters
Rockwell Automation, 777 East Wisconsin Avenue, Suite 1400, Milwaukee, WI, 53202-5302 USA, Tel: (1) 414.212.5200, Fax: (1) 414.212.5201

Headquarters for Allen-Bradley Products, Rockwell Software Products and Global Manufacturing Solutions
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe: Rockwell Automation SA/NV, Vorstlaan/Boulevard du Souverain 36-BP 3A/B, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, 27/F Citicorp Centre, 18 Whitfield Road, Causeway Bay, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846

Headquarters for Dodge and Reliance Electric Products


Americas: Rockwell Automation, 6040 Ponders Court, Greenville, SC 29615-4617 USA, Tel: (1) 864.297.4800, Fax: (1) 864.281.2433
Europe: Rockwell Automation, Brühlstraße 22, D-74834 Elztal-Dallau, Germany, Tel: (49) 6261 9410, Fax: (49) 6261 17741
Asia Pacific: Rockwell Automation, 55 Newton Road, #11-01/02 Revenue House, Singapore 307987, Tel: (65) 351 6723, Fax: (65) 355 1733

U.S. Allen-Bradley Drives Technical Support


Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives

Publication 9303-SB001A-EN-P - May 2002 P/N 313999


Copyright © 2002 Rockwell Automation. All rights reserved. Printed in USA.