PERHITUNGAN BEBAN PENDINGIN PADA COLD STORAGE UNTUK

PENYIMPANAN IKAN TUNA PADA PT.X

Saut Siagian
Program Studi Teknik Mesin, UPN Veteran Jakarta, Jakarta Selatan
email 1 : sautsiagian100753@gmail.com

Abstract

One application is the refrigeration system to cool freshness of the fish so that the fish
can survive longer. An engine coolant is used to store and cool fish called cold storage.
While the special machine used to freeze fish quickly (1-2 hours) is called Air Blast
Freezer (ABF). The purpose of freezing the fish in the ABF is to inhibit the growth of
microorganisms that exist in fish that could not breed, then the fish is stored and further
chill in cold storage. Cold storage and ABF is in Cirebon spend huge electricity costs
when the number of fish average - average stored in cold storage is less than 1 ton per
day. To that through this thesis the author seeks to examine and find solutions to these
problems.
How that is done to be able to analyze the problems of the first was to measure and
quantify the performance of the existing cooling system. Then compare it with the cooling
load conditions as a result of the heat is transmitted to the evaporator. Because if t he
load is too large cooling will also result in a heavy compressor work and result in large
power consumption as well.
Keywords: Cool Storage ,the refrigeration system

PENDAHULUAN ikan hingga mencapai 60 ton. Namun dalam


1.1 Latar Belakang pengoperasiannya, massa ikan rata – rata yang
Indonesia nerupakan salah satu Negara masuk cold storage tersebut hanya beberapa ton
dengan wilayah laut yang cukup besar. Kondisi saja dengan konsumsi listrik yang relatif besar
geografis seperti ini menjadikan Indonesia
memiliki potensi yang cukup besar. Dalam makalah ini saya men coba untuk
Namun dalam beberapa tahun terakhir menganalisis perbandingan sejumlah energi kalor
banyak sekali ditemukan kasus overfishing yaitu yang diserap akibat proses pen dinginan,
bahwa terjadinya penangkapan ikan dalam dengan energi listrik yang terpakai per bulannya
jumlah yang sangat besat di daerah yang tidak untuk sistem pendinginan tersebut.
jauh dari pantai, Dugaan sementara yang mengakibatkan
Untuk menangan kasus tersebut maka perlu sistem pendingin tersebut meng habiskan
didirikan suatu lembaga untuk memantau dan biaya listrik yang cukup besar adalah kondisi
meneliti produk-produk hasil laut sehingga temperatur lingkungan yang cukup panas
memiliki kualitas dan kuantitas hasil perikanan sehingga kalor yang diserap oleh cold storage
tersebut selalu dalam kondisi yang sesuai dengan tersebut cukup besar yang pada akhirnya
syandar mutu yang ada. Oleh sebab itu lembaga mengakibatkan konsumsi listrik yang besar pula.
tersebut mendirikan sebuah unit pendingin ikan 1.2 Tujuan
sebagai sebagai wujud nyata dalam rangka Adapun tujuan penulis dalam membuat
penerapan rantai dingin pada produk perikanan. tugas akhir ini adalah sebagai berikut :
Sistem pendingin ikan (cold storage). ini 1. Menghitung laju perpindahan kalor yang
digunakan untuk menyimpan ikan dan terjadi melalui dinding, pintu dan atap cold
mendinginkannya pada temperature tertentu storage (konduksi).
sehingga ikan segar tersebut dapat bertahan lama 2. Menghitung laju perpindahan kalor dari
hingga beberapa minggu bahkan bisa ikan di dalam ruang cold storage
bertahan hingga beberapa bulan. Dimana cold
storage ini memiliki daya tampung penyimpanan

139 BINA TEKNIKA, Volume 13 Nomor 1, Edisi Juni 2017, 139-149


3. Menghitung kapasitas mesin pendingin cold Sistem Pendingin (Refrigeration system)
storage dan membandingkannya dengan atau sistem refrigerasi merupakan suatu sistem
beban pendinginan total yang ada pada yang
coldstorage tersebut. dapat menurunkan dan menjaga temperatur
4. Membandingkan biaya listrik yang ruanganatau material tertentu menjadi lebih
terhitung secara teori dengan biaya listrik rendah temperaturnya dari pada temperatur
yang terpakai sebenarnya. lingkungan. Yaitu dengan cara memindahkan
1.3 Metode Penelitian panas. kalor dari ruang / material tersebut ke luar
Metode yang diterapkan dalam melakukan sistem (ruangan yang lain).
penelitian tugas akhir ini adalah sebagai berikut 2.2 Sistem Pendingin Kompresi Uap
ini, yaitu : Pada dasarnya sistem pendingin ikan (cold
a. Studi literature, yaitu dengan cara mencari, storage / Air Blast Freezer) ini memiliki prinsip
mengumpulkan dan mem pelajari bahan – kerja yang sama dengan kulkas (freezer) yang
bahan referensi yang berkaitan materi tugas ada pada rumah – rumah. Hanya saja
akhir. kapasitasnya yang jauh lebih besar dari kulkas ini
b. Observasi, mangamati langsung proses yang mengakibatkan cold storage memiliki
pembekuan ikan dan penyimpanannya serta mekanisme mesin yang kompleks dan cukup
mem pelajari cara kerja sistem rumit. Cold storage / ABF ini terdiri dari sebuah
pendinginnya. wadah / tempat penyimpanan ikan yang besar
c. Pengujian sistem, mangukur dan mengambil yang didinginkan oleh sebuah unit pendingin.
data – data yang diperlukan dalam Adapun unit pendingin yang digunakan pada cold
penelitian ini seperti temperatur dan storage / ABF ini adalah jenis sistem refrigerasi
tekanan sistem. kompresi uap, dimana sebagai media
d. Mengolah data hasil pengujian dan pendinginnya masih menggunakan refrigerant
melakukan perhitungan performansi R22 (HCFC 22).
kemudian menganalisanya. Dinamakan sistem refrigerasi kompresi uap
1.4 Batasan Masalah karena pada unit pendingin ini menggunakan
Untuk mempermudah dalam meng analisis kompresor yang memompa uap refrigerant dari
sistem, maka dalam pembuatan tugas akhir ini sisi tekanan rendah hingga menjadi uap tekanan
terdapat batasan-batasan tertentu yang membatasi tinggi. Sehingga pada sistem refrigerasi kompresi
ruang lingkup yang akan dikaji dalam tugas akhir uap ini terdapat dua kondisi tekanan berbeda
ini. Adapun batasan-batasan masalah dalam tugas yaitu sisi tekanan tinggi dan sisi tekanan rendah.
akhir ini adalah sebagai berikut : Pada sisi tekanan rendah inilah yang digunakan
1. Analisis perhitungan beban pendinginan untuk proses pendinginan karena temperaturnya
melalui dinding hanya jenis kalor konduksi juga rendah hingga dapat menyerap panas dari
dan konveksi dari udara sekitar dalam dan lingkungan sekitarnya
luar ruangan. Secara umum sistem refrigerasi kompresi
2. Nilai koefisien perpindahan panas konveksi uap ini terdiri dari 4 (empat) komponen utama,
(h) didapat berdasarkan rekomendasi dari yaitu: kompresor, kondensor, alat ekspansi, dan
beberapa buku. evaporator. Keempat komponen utama tersebut
3. Kondisi udara lingkungan diasumsikan dihubungkan oleh pipa besi / tembaga hingga
tidak berubah untuk setiap waktunya menjadi satu rangkaian tertutup sehingga
4. Jenis ikan yang ada di ruang pendingin membentuk suatu siklus (proses yang berulang –
dianggap seragam dengan mengambil data ulang) transfer panas dari lingkungan ke sistem,
dari jenis ikan yang paling banyak ada di dan dari sistem ke lingkungan kembali. Sebagai
ruangan media transfer panas yang bersirkulasi di dalam
rangkaian tersebut digunakan refrigeran (biasa
II. LANDASAN TEORI disebut freon) yang dapat dikompresi maupun di
2.1 Pengertian Sistem Pendingin ekspansi untuk menaikkan dan menurunkan
(Refrigeration System) temperaturnya pada kondisi tertentu. Berikut
adalah diagram rangkaian pemipaan sederhana
dari sistem refrigerasi kompresi uap.

Perhitungan Beban Pendingin pada Cold Storage.... (Siagian) 138


terjadinya penguapan refrigeran cair
menjadi uap jenuh kembali akibat
penambahan panas dari beban yang ada di
evaporator untuk selanjutnya di kompresi
kembali di kompresor.
2.2.1 Proses kompresi di kompresor
Telah dijelaskan sebelumnya bahwa
kompresor pada sistem refrigerasi kompresi uap
berfungsi untuk memompa uap refrigeran dari
Gambar 2.1. Diagram pemipaan system tekanan rendah menjadi uap refrigeran
refrigerasi kompresi uap sederhana bertekanan tinggi (lihat proses 1 – 2 pada gambar
diatas). Uap refrigeran tersebut menjadi
Atau jika siklus refrigerasi tersebut bertekanan tinggi sebagai akibat dari kerja yang
digambarkan pada diagram Tekanan – Entalphy diberikan kompresor kepada refrigeran (W).
(diagram P-h) maka akan terlihat seperti pada Besarnya kerja kompresi tersebut dapat dihitung
gambar berikut ini. berdasarkan data dari siklus refrigerasi kompresi
uap tersebut pada diagram Tekanan – Entalphy
(P-h). Maka berdasarkan gambar 2.2 diatas kerja
kompresi oleh kompresor dapat dihitung dengan
rumus berikut:

W KOMPRESOR = m ( h 2 – h 1 ) ................ 2.1

Gambar 2.2 siklus refrigerasi pada diagram W Komp = kerja kompresor, kJ


tekanan – entalpi m = massa refrigeran yang melewati kompresor,
kg
Penjelasan proses dari kedua gambar h 2 = entalpi refrigerant keluaran kompresor,
tersebut diatas adalah sebagai berikut : kJ/kg
1. Proses 1 – 2 (kompresi), merupakan proses h 1 = entalpi refrigerant masukan kompresor,
kompresi uap refrigeran dari keadaan awal kJ/kg
tekanan dan temperatur rendah yang
dikompresi secara reversibel dan isentropik Atau dengan kata lain kerja kompresor
sehingga sehingga mengakibatkan tekanan
dihitung dari selisih antara entalpi refrigerant
dan temperaturnya menjadi lebih tinggi keluaran dan masukan kompresor dikalikan
daripada temperatur lingkungan. dengan massa refrigeran yang melewatinya.
2. Proses 2 – 3 (kondensasi), proses ini terjadi Karena refrigerant yang melewati kompresor
di kondensor dimana uap refrigeran dengan mengalir dengan kecepatan tertentu, akan sulit
tekanan dan temperatur tinggi tersebut sekali untuk menghitung sejumlah massa
kemudian masuk ke kondensor untuk refrigerant yang melewatinya. Maka akan lebih
melepas panas ke lingkungan hingga
efektif jika persamaan 2.1 dinyatakan dalam
berubah fasa menjadi refrigeran cair satuan energy per satuan waktu (daya) dengan
bertekanan tinggi. cara mengalikan selisih enthalpy keluar dan
3. Proses 3 – 4 (ekspansi), refrigeran cair yang masuk dengan laju aliran massa refrigerant yang
masih bertekanan tinggi kemudian masuk mengalir, yaitu
alat ekspansi untuk diturunkan tekanannya
sehingga temperaturnya pun turun (lebih P Kompr = m (h 2 – h1) ......................2.2 )
rendah daripada
temperatur lingkungan) dan sebagian Persamaan 2.2 diatas merupakan rumus
refrigerant cair tersebut berubah fasa untuk menghitung nilai daya mekanik dari
menjadi uap.
kompresor, yaitu kerja yang disebabkan oleh
4. Proses 4 – 1 (evaporasi), proses ini terjadi gerakan piston kompresor. Dalam istilah mesin
di evaporator yang merupakan proses daya ini sering disebut dengan daya output (P o ).

139 BINA TEKNIKA, Volume 13 Nomor 1, Edisi Juni 2017, 139-149


Sedangkan yang dinamakan daya inputnya 2.3 Beban Pendinginan
adalah merupakan supplai daya listrik yang Sumber panas (beban) yang diserap
menggerakkan motor pada kompresor tersebut dievaporator pada sistem refrigerasi tidak hanya
(P Listrik) . Hubungan antara keduanya dinyatakan dari satu jenis sumber saja, melainkan sejumlah
dalam rumus efisiensi berikut ini panas yang dihasilkan dari berbagai sumber yang
berbeda.
Pada sistem refrigerasi, khususnya cold
storage dalam penulisan ini hanya akan
...................2.3 ) dijelaskan metode perhitungan beban
pendinginan untuk panas yang melewati dinding
2.2.2 Laju penyerapan panas (kapasitas) (konduksi), panas dari produk yang ada (dalam
di evaporator hal ini produknya adalah ikan) dan beban listrik
Refrigeran yang mengalir di evaporator dari kipas yang ada di evaporator. Sedangkan
sebagian besar berfasa cair dan bertemperatur ketiga beban yang lain tidak diperhitungkan
lebih rendah dari temperature lingkungan. karena tidak terdapat pada system atau juga
Selanjutnya refrigerant tersebut menyerap kalor karena nilainya yang kecil sehingga dapat
dari lingkungan sekitar yang mengakibatkan diabaikan.
semua refrigerant cair pada evaporator tersebut 2.3.1 Perhitungan beban konduksi melewati
menguap kembali menjadi fasa gas. Sejumlah dinding
panas yang diserap di evaporator tersebut dapat Terjadinya perpindahan panas dari udara
dihitung juga berdasarkan data dari siklus luar kedalam ruangan dingin sebagai akibat
refrigerasi kompresi uap pada diagram Tekanan – adanya perbedaan temperature antara sisi luar
Entalphy (P-h diagram). Dan berdasarkan gambar dinding dengan sisi bagian
2.2 diatas besarnya laju panas yang diserap di QWall = A.U.ΔT ..............2.7 )
evaporator dapat dihitung dengan menggunakan Koefisien perpindahan panas menyeluruh
rumus berikut: (U) dapat diartikan sebagai jumlah energy panas
Qev = m (h 1 – h4) ........................ 2.4.) yang dapat berpindah melewati dinding
Selain kerja kompresor dan kapasitas seluas 1 m dalam setiap 1oC perbedaan
penyerapan panas di evaporator, pada system temperatur pada
refrigerasi kompresi uap juga dikenal istilah dinding. Dimana nilai ini tergantung dari
coeffisien of performance (COP) yang mana nilai ketebalan dinding dan material dinding yang
COP tersebut merupakan suatu nilai digunakan pada ruangan tersebut. Perhatikan
perbandingan antara kapasitas penyerapan panas gambar berikut:
yang terjadi dievaporator dengan sejumlah kerja
kompresi yang dilakukan di kompresor. Atau
dengan kata lain,

............2.5.)
Nilai COP tersebut merupakan nilai COP
aktual atau yang sebenarnya terjadi. Terdapat
juga istilah COP carnot, dimana merupakan nilai
COP yang ideal dengan menganggap bahwa kalor
yang dilepas di kondensor adalah sama dengan Gambar 2.3. Perpindahan panas pada dinding
kalor yang diambil di evaporator ditambah energi
yang dikeluarkan di kompresor. Sehingga rumus Udara luar pada posisi A temperaturnya
COP Carnot ini adalah : lebih tinggi daripada udara dalam (posisi B)
sehingga panas mengalir dari udara A ke B.
Udara pada posisi A dan B masing – masing
memiliki koefisien konveksi Ha dan h
....2.6 ) Sedangkan luas permukaan dinding A dan
panas yang melewati dinding Q, maka bentuk

Perhitungan Beban Pendingin pada Cold Storage.... (Siagian) 140


lain dari persamaan 2.3diatas adalah sebagai 2.3.3 Perhitungan beban penghuni dan motor
berikut: listrik
Jenis panas lain yang ada pada ruang
penyimpanan dingin adalah panas yang
dihasilkan dari penghuni / orang yang ada di
ruangan ketika sedang bongkar muat produk dan
2.3.2 Perhitungan beban produk
juga panas yang ditimbulkan oleh peralatan
Ketika produk (ikan, daging, buah, dll)
listrik penghasil panas yang ada di dalam
yang temperaturnya lebih tinggi disimpan pada
ruangan. Biasanya peralatan listrik yang ada di
temperature ruang penyimpanan dingin maka
dalam ruangan tersebut hanya berupa motor kipas
produk ini akan memberikan panas pada ruang
evaporator. Dimana besarnya panas yang
sampai produk tersebut memiliki temperature
dihasilkan oleh motor listrik tersebut dapat
yang sama dengan temperature ruangan. Panas
dilihat pada tabel Heat Gain From Typical
yang dihasilkan produk ini dapat berupa panas
Electric Motor . Sedangkan untuk panas yang
sensible dan atau panas laten tergantung dari
dihasilkan oleh penghuni dapat dilihat pada tabel
temperature penyimpanan apakah lebih rendah
beban penghuni.
dari temperature titik beku produk atau lebih
III. SPESIFIKASI UNIT PENDINGIN
tinggi. Dimana nilai temperatur titik beku dari 3.1 Data ruang pendingin
berbagai macam produk dapat dilihat pada tabel
Berikut ini data dimensi dari cold storage
properties of perishable product.
dan ABF yang ada di karangsong, yaitu :
Jika temperatur penyimpanan produk lebih
Dimensi cold storage : panjang = 10 m, lebar = 6
rendah dari temperatur titik bekunya, maka jenis
m, tinggi = 3 m Dimensi ABF : panjang = 4 m,
panas yang di keluarkan oleh produk tersebut
lebar = 3 m, tinggi = 3 m
terdiri dari tiga jenis yaitu :
Berikut adalah gambar sederhana dari unit
1. Panas sensibel sebelum pembekuan,
bangunan pendingin cold storage tersebut,
merupakan yang dikeluarkan oleh produk
sedangkan untuk gambar detail dari bangunan
penurunan
pendingin ini baik unit cold storage maupun ABF
temperatur produk tersebut sampai pada batas
dapat dilihat pada lampiran
temperatur titik bekunya.
2. Panas laten pembekuan, yaitu panas yang
dikeluarkan ketika terjadi perubahan wujud
produk dari cair menjadi padat (beku).
3. Panas sensibel setelah pembekuan,
merupakan panas yang dikeluarkan produk
akibat penurunan temperatur dari
temperatur titik beku hingga pada
temperatur yang lebih rendah lagi (minus).
Besarnya panas sensibel dari produk
tersebut dapat dihitung dengan menggunakan
rumus berikut ini, yaitu : Gambar 2.3 Gambar ruang pendingin ( Cold
Qs.prod = m. Cp ( ΔT ) ...................2.9 ) Storage )
Selain dari panas sensible yang dihasilkan
oleh produk, terdapat beban laten jika temperatur Untuk dinding, pintu dan atap dari ruang
penyimpanan produk lebih rendah dari titik pendingin ini memiliki lapisan material yang
beku produk itu sendiri. Beban laten ini disebut sama.
dengan panas laten pembekuan, yaitu sejumlah Konstruksi dari dinding, pintu dan atap
panas yang dikeluarkan oleh benda tertentu tersebut sama – sama terdiri dari 3 lapis material
ketika benda tersebut mangalami perubahan fasa seperti
dari cair menjadi padat. yang terlihat pada gambar berikut ini.
Dan besarnya panas laten pembekuan
produk tersebut dapat dihitung dengan
menggunakan rumus berikut ini.
QL.prod = m. h lf .............................................2.10)

141 BINA TEKNIKA, Volume 13 Nomor 1, Edisi Juni 2017, 139-149


QC = m ( h 1 - h 4 ) = 0,233 kg/s ( 400 -
245 ) kJ /kg
= 36,13 Kw

36,13
= 18,65
= 1,94

IV.PERHITUNGAN BEBAN
4.1 Pengambilan Data
( −29 + 273 )
Titik-titik pengukuran yang diperlukan = 42 − ( −29 )
dalam pengambilan data tersebut meliputi : = 3,3
1. Tekanan kondensasi
2. Tekanan evaporasi
3. Temperatur discharge kompresor
4. Temperatur suction kompresor 1,94
5. Temperatur masuk evaporator = 3,3
x 100%
6. Temperatur kabin = 58,8 %
4.2 Perhitungan COP, kapasitas pendinginan,
dan efisiensi refrigerasi Pada jam 13.00 tabel 2 Data Cold Storage 1
Untuk mempermudah perhitungan, maka Tekanan discharge : 15 Bar absolut
data yang sudah ditentukan diatas digambarkan Tekanan suction : 1.8Bar absolut
pada diagram tekanan-enthalpi (P-h) Temperatur Discharge : 120.5 °C
Berdasarkan pada data yang ada, kita Temperatur masuk evap : - 20 °C
dapat mengetahui kinerja sistem yang kemudian Temperatur keluar kondensor : 35.5 °C
dianalisis dan dibandingkan dengan kondisi Temperatur Suction : 2.2 °C
rancangan. Jika diplotkan ke diagram Ph R-22 maka dapat
Pada jam 16.00 tabel 3 Data Air Blast diperoleh harga-harga enthalpy sebagai
Freezer berikut:
Tekanan discharge : 17 Bar absolut h 1 : 410 kJ/kg
Tekanan suction :1.6 Bar absolut h 2 : 485 kJ/kg
Temperatur Discharge : 121.7 °C h 3 = h 4 = 242 kJ / kg
Temperatur masuk evap : - 29 °C P Komp = 15 pk = 11,19 Kw ( data
Temperatur keluar kondensor : 37.2 °C spesifikasi alat )
𝑃𝑘𝑜𝑚𝑝
Temperatur Suction : - 4.6 °C m =
( ℎ2 − ℎ1 )
Jika diplotkan ke diagram P- h R-22 maka 11,19
dapat diperoleh harga-harga enthalpy sebagai = ( 485 − 410 )
berikut : = 0,155 kg / s
Sehingga berdasarkan pada persamaan 2.4 Sehingga berdasarkan pada persamaan 2.4
h 1 = 400 kJ / kg kapasitas pendinginan di evaporator Qe dapat
h 2 = 480 kJ / kg dihitung, yaitu :
P Komp = 25 pk = 18,65 kW ( data Qe = m ( h 1 - h4 )
spesifikasi alat ) = 0,155 kg/s ( 410 - 242 ) kJ / kg
m = P komp / h2 - h 1 = 25,07 Kw
= 18,65 / 480 - 400
= 0,233 kg/s
Sehingga berdasarkan pada persamaan 2.4 25,07
kapasitas pendinginan di evaporator Qe dapat = 11,19
dihitung, yaitu :kapasitas pendinginan di = 2,24
evaporator :

Perhitungan Beban Pendingin pada Cold Storage.... (Siagian) 142


Sehingga besarnya perpindahan panasyang
melewati dinding tersebut dapat dihitung
dengan menggunakan persamaan 2.5 :
( −20,6 + 273 )
= 40 − ( −20,6 )
= 4,13

2,42
= 4,13
x 100%
= 54 % = 0,32 Kw
Dan melalui atap,
4.4 Beban pendinginan pada Air Blast Freezer
Karena Air Blast Freezer ini hanya
digunakan untuk proses precooling dan tidak
digunakan untuk menyimpan ikan yang beku,
maka jumlah beban yang harus diambil pada
evaporatornya lebih sedikit bila dibandingkan
dengan jumlah beban yang ada di cold storage.
Proses precooling ini sendiri biasanya = 0,09 kW
terjadi antara 1 jam sampai 4 jam tergantung dari
massa ikan yang didinginkan. Jenis beban 4.4.2 Panas dari produk
pendinginannya hanya terdiri dari tiga jenis, Jenis panas dari ikan yang akan
yaitu panas sensible sebelum pembekuan pada didinginkan pada ABF ini hanya panas sensible
ikan, panas yang melewati dinding dan panas dari sebelum pembekuan, yaitu panas sensible yang
motor kipas evaporator. dikeluarkan dari penurunan temperatur awal ikan
4.4.1 Panas yang melewati dinding 28 °C hingga temperatur beku -2 °C. Dan untuk
Berdasarkan dari data ruang pendingin jenis ikan yang didinginkan tersebut adalah dari
pada bab 3 diatas maka perhitungan jumlah panas berbagai jenis ikan laut seperti ikan kakap, ikan
yang melewati dinding ABF tersebut dapat pari, ikan bandeng dan berbagai jenis ikan laut
dihitung. Diketahui dari data spesifikasi : yang lain.
Luas dinding sebelah Utara (AU) = 12 m² Pada perhitungan panas yang dihasilkan
Luas dinding sebelah Selatan (AS) = 12 m² oleh ikan ini memerlukan data kalor sepesifik
Luas dinding sebelah Barat (AB) = 9 m² dari ikan itu sendiri. Oleh karena nilai kalor
Luas dinding sebelah Timur (AT) = 9 m² spesifik tersebut berbeda – beda untuk berbagai
Luas dinding total keseluruhan (A) = 42 m² jenis ikan, maka nilainya diambil dari ikan yang
Luas atap (Atap) = 12 m² paling sering dan paling banyak disimpan di
Koefisien perpindahan panas konveksi ruang pendingin, yaitu dipilih jenis ikan tuna
permukaan dinding = 8,3 W/m² °C (ikan manyung). Dari table data yang ada di
Koefisien perpindahan panas konveksi lampiran, didapat nilai – nilai kalor spesifik dan
permukaan atap = 6,1 W/m 2 °C laten dari jenis ikan tuna tersebut adalah sebagai
Material dinding : berikut :
* 0.5 mm baja jenis galvalum, dengan nilai k Kalor spesifik ikan tuna, c tuna = 3.43
=25 W/m.°C kJ/kg.°C
* 150 mm Polyurethane, dengan nilai k = Dan dari tabel data pengukuran 1 pada jam
0,023W/m.°C 12.00 WIB didapat :
* 0.5 mm baja jenis galvalum, dengan nilai k Massa ikan yang masuk, m = 3411 kg/hari
=25 W/m.°C Temperatur awal ikan, Tawal = 28 °C
Dan dari tabel 3 data pengukuran ABF Temperatur akhir ikan, Takhir = -2 °C
pada jam 16.00 WIB didapat : Perbedaan temperatur, ∆T = 30 °C
∆T = Temp. Lingkungan – Temp. ABF = Sehingga jumlah kalor yang diserap di
31,5 °C – (-20,6 °C) = 52,1 °C evaporator pada ABF ini berdasarkan persamaan

143 BINA TEKNIKA, Volume 13 Nomor 1, Edisi Juni 2017, 139-149


2.7 dan 2.8 tersebut adalah : diserap semu hingga temperatur ikan pun sesuai
Qs.produk = m.c ΔT dengan yang diinginkan.
= 3,411 x 3,43 x 30 4.5.1 Panas yang melewati dinding
= 35,992 kJ Berdasarkan dari data ruang pendingin,
Sejumlah kalor tersebut telah didinginkan maka perhitungan jumlah panas yang melewati
secara bertahap sebanyak 3 tahap. Tahap pertama dinding Cold storage tersebut dapat dihitung.
pendinginan sebanyak 700 kg dalam waktu 1 Diketahui dari data spesifikasi : Luas
jam, tahap kedua pendinginan sebanyak 1211 kg dinding sebelah Utara (AU) = 30 m²
juga dalam waktu 1,5 jam dan terakhir tahap tiga Luas dinding sebelah Selatan (AS) = 30 m²
sebanyak 1500 kg dengan waktu 2 jam. Sehingga Luas dinding sebelah Barat (AB) = 18 m²
total waktu yang diperlukan untuk mendinginkan Luas dinding sebelah Timur (AT) = 18 m²
produk sebanyak 3411 kg tersebut adalah selama Luas dinding total keseluruhan (A) = 96 m²
4,5 jam. Jadi beban produk yang tertera diatas Luas dinding Atas (Atap) Aatap = 60 m²
jika dikonversi dalam satuan kilowatt adalah Koefisien perpindahan panas konveksi
sebagai berikut : permukaan dinding = 8,3 W/m² °C
Qs.produk = 350,992 kJ / ( 4,5 jam x 3600 s Koefisien perpindahan panas konveksi
, jam ) permukaan atap = 6,1 W/m² °C
= 21,67 kW Material dinding & atap :
4.4.3 Panas dari motor kipas evaporator * 0.5 mm baja jenis galvalum, dengan nilai
Untuk mengetahui jumlah panas yang k = 25 W/m.°C
dikeluarkan motor kipas evaporator dapat dilihat * 100 mm Polyurethane, dengan nilai k =
pada tabel yang tertera di lampiran. Daya input 0,023 W/m. °C
motor yang digunakan adalah 460 W. Dan * 0.5 mm baja jenis galvalum, dengan nilai
berdasarkan pada tabel motor heat gain (Tabel 6 k = 25 W/m. °C
ASHRAE Refrigeration Load ) pada lampiran Dari data pengukuran cold storage 1 pada
didapat : jam 12.00 WIB didapat :
Motor heat gain : 694 W (untuk daya motor ∆T = Temp. Lingkungan – Temp. ruang =
460 W), ada 2 kipas, maka: 31,2 °C – (-12,7 °C) = 43,9 °C
Q motor = 0,694 kW x 2 = 1,38 kW Sehingga nilai jumlah perpindahan panas
Sehingga beban total keseluruhan yang yang
ditambahkan ke ruang ABF tersebut dapat melewati dinding vertikal dapat dihitung
dihitung dengan
dengan cara menjumlahkan sejumlah panas menggunakan persamaan 2.5 :
yang telah dihitung tersebut diatas.
QTotal ABF = Q wall + Q atap + Q Produk +
Q motor
= 0,32 + 0,09 + 21,67 + 1,38
= 23,46 kW
4.5 Beban pendinginan pada Cold storage
Berbeda dengan ABF, pada cold storage ini = 0,92 kW
terdapat sumber beban pendinginan yang lebih
banyak. Selain dari jenis panas seperti yang di Dan yang melalui atap :
ABF, juga terdapat panas tambahan dari
penghuni atau orang yang melekukan aktifitas di
ruangan cold storage ini ketika melakukan
aktifitas. Waktu pendinginannya pun lebih lama
disbanding dengan ABF yang hanya serkitar 1 –
2 jam, pada cold storage ini memiliki waktu
pendinginan selama 24 jam atau satu hari penuh. = 0,56 kW
Sehingga diharapkan dalam waktu satu hari 4.5.2 Panas dari produk
tersebut sejumlah beban pendingannya dapat Produk yang disimpan pada cold storage
tersebut adalah dari berbagai jenis ikan laut

Perhitungan Beban Pendingin pada Cold Storage.... (Siagian) 144


seperti ikan kakap, ikan pari, ikan bandeng dan panas laten pembekuan dan panas sensible
berbagai jenis ikan laut yang lain. Jenis panas setelah pembekuan (yaitu panas sensible dari
yang diserap pada cold storage ini merupakan penurunan temperatur -2 °C sampai -12 °C).
panas laten pembekuan dan panas sensible Sehingga pada perhitungan panas di cold storage
setelah pembekuan (yaitu panas sensible dari ini memerlukan data kalor sepesifik setelah
penurunan temperatur -2 °C sampai -12 °C). pembekuan dan kalor laten dari ikan itu sendiri.
Sehingga pada perhitungan panas di cold storage Dan karena nilai kalor spesifik dan laten tersebut
ini memerlukan data kalor sepesifik setelah berbeda – beda untuk berbagai ikan, maka
pembekuan dan kalor laten dari ikan itu sendiri. nilainya diambil dari jenis ikan yang paling
Dan karena nilai kalor spesifik dan laten tersebut sering dan paling banyak disimpan di ruang
berbeda – beda untuk berbagai ikan, maka pendingin, yaitu ikan tuna (ikan manyung). Dari
nilainya diambil dari jenis ikan yang paling tabel data yang ada di lampiran, didapat nilai –
sering dan paling banyak disimpan di ruang nilai kalor spesifik dan laten dari jenis ikan tuna
pendingin, yaitu ikan tuna (ikan manyung). Dari tersebut adalah sebagai berikut :
tabel data yang ada di lampiran, didapat nilai – Kalor spesifik setelah beku ikan tuna, C p
nilai kalor spesifik dan laten dari jenis ikan tuna tuna = 2,19 kJ/kg. °C
tersebut adalah sebagai berikut : Kalor laten pembekuan ikan tuna, h lf .tuna
Kalor spesifik setelah beku ikan tuna, c = 227 kJ/kg
tuna = 2,19 kJ/kg.°C Dan dari tabel 2 data pengukuran pada jam
Kalor laten pembekuan ikan tuna, hlf.tuna 13.00 WIB didapat :
= 227 kJ/kg * Massa ikan yang masuk, m = 3411
Dan dari tabel 2 data pengukuran pada jam kg/hari
13.00 WIB didapat : * Temperatur awal ikan, T awal = -2 °C
Massa ikan yang masuk, m = 3411 * Temperatur akhir ikan, T akhir = -12 °C
kg/hari * Perbedaan temperatur, ∆T = 10 °C
Temperatur awal ikan, Tawal = -2 °C Sehingga jumlah kalor yang ditambahkan
Temperatur akhir ikan, Takhir = -12 °C ke ruangan pada kondisi jam 13.00 WIB
Perbedaan temperatur, ∆T = 10 °C berdasarkan persamaan 2.7 dan 2.8 tersebut
Sehingga jumlah kalor yang ditambahkan adalah :
ke ruangan pada kondisi jam 13.00 WIB QL.prod = m . ℎ lf
berdasarkan persamaan 2.7 dan 2.8 tersebut = 3.411 x 227 = 774.297 kJ
adalah : Qs.prod = m.C p ( ΔT) = 3.411 x 2,19 x 10
QL.prod = m . ℎ lf = 74.701 kJ
= 3.411 x 227 = 774.297 kJ Qproduk = Qs.prod + QL.prod = 848.998
Qs.prod = m.c p = 3.411 x 2,19 x 10 = kJ
74.701 kJ Dan karena sejumlah panas dari produk
Qproduk = Q .prod + QL.prod = 848.998 tersebut akan didinginkan dalam waktu satu hari
kJ (24 jam), maka beban keseluruhan produk
Dan karena sejumlah panas dari produk tersebut jika dikonversi dalam satuan kilowatt
tersebut akan didinginkan dalam waktu satu hari adalah
(24 jam), maka beban keseluruhan produk
tersebut jika dikonversi dalam satuan kilowatt
adalah
Qproduk = 848,998 Kj / ( 24 jam x 3600 s 4.5.3 Panas dari penghuni dan motor kipas
/ jam ) evaporator
= 9,83 kW Untuk mengetahui jumlah panas yang
4.5.2 Panas dari produk dikeluarkan oleh penghuni (orang) dan motor
Produk yang disimpan pada cold storage kipas evaporator dapat dilihat pada tabel yang
tersebut adalah dari berbagai jenis ikan laut tertera di lampiran. Dan berdasarkan pada tabel
seperti ikan kakap, ikan pari, ikan bandeng dan beban penghuni yang ada di lampiran (tabel 1.
berbagai jenis ikan laut yang lain. Jenis panas ASHRAE Refrigeration Load) dan tabel heat gain
yang diserap pada cold storage ini merupakan

145 BINA TEKNIKA, Volume 13 Nomor 1, Edisi Juni 2017, 139-149


motor listrik pada lampiran (tabel 6. ASHRAE
Refrigeration Load) tersebut didapat :
Motor heat gain : 694 W (untuk daya motor
460W), ada 2 buah, maka :
Qmotor = 0,694 kW x 2 = 1,38 kW
Heat gain / person = 330 W / org (dari
table ASHRAE), ada 4 orang tiap bongkar muat
dan paling lama 2 jam sehari ada di ruangan
pendingin, Maka :
Qperson = (Heat gain / person) x jumlah
orang x (2 jam / 24 jam)
= 330 W/org x 4 org x (2 jam / 24
jam)
= 0.11 kW
Sehingga beban total keseluruhan yang
ditambahkan ke ruang pendingin tersebut dapat
dihitung dengan cara menjumlahkan sejumlah
panas yang telah dihitung tersebut diatas. 4.7 Analisa perhitungan
QTOTAL Cold storage = Qwall + Qatap + Dari hasil perhitungan diatas, didapat nilai
Qproduk + Qperson+Qmotor daya kompresor mekanik (Pkomp.) pada cold
= (0,92 + 0,56 + 9,83 + 0,11 + 1,38) storage dan ABF masing – masing adalah sebesar
11,19 kilowatt dan 18,65 kilowatt. Dan karena
kW
mesin pendingin tersebut dalam sehari dapat
= 12,81 kW beroperasi sebanyak 24 jam untuk cold storage
4.6 Perhitungan rata – rata per bulan dan 2 jam untuk ABF, maka jumlah energi listrik
Proses perhitungan yang dijelaskan pada yang terpakai pada mesin tersebut dalam satuan
subbab 4.4 dan 4.5 tersebut diatas merupakan kilowattjam (E, kWh) sebesar : E cold storage,
proses perhitungan beban pendinginan yang kWh = 11,19 kW x 24 jam/hari x 30 hari = 8.056
berdasarkan pada data selama satu hari saja dari kWh E ABF, kWh = 18,65 kW x 2 jam/hari x 30
waktu satu bulan yang ada. Sedangkan hari = 1.119 kWh
kenyataannya adalah bahwa ikan yang masuk Dengan menganggap biaya listrik per kWh
pada cold storage tersebut setiap harinya adalah adalah sebesar Rp 1000,- rupiah, maka biaya
berubah – ubah, kadang banyak dan kadang listrik yang harus dibayarkan untuk
pengoperasian dua buah mesin pendingin tersebut
sedikit atau malah tidak ada. Untuk itu perlu
selama satu bulan diperkirakan sebesar Rp
diadakan perhitungan rata – rata beban 9.175.000,- rupiah. Biaya sebesar 9,175 juta
pendinginan setiap harinya yang berdasarkan rupiah ini sedikit lebih besar nilainya bila
data ikan rata – rata yang masuk selama bulan dibandingkan dengan yang sebenarnya yang
November tersebut. Dimana agar dapat sebesar 9,166 juta rupiah. Padahal seharusnya
memperkirakan berapa kapasitas evaporator yang biaya listrik yang terhitung lebih kecil dari pada
seharusnya terpasang pada unitpendingin tersebut yang dibayarkan sebenarnya ke PLN, karena
dan membandingkannya dengan kapasitas biaya yang dibayarkan ke PLN merupakan biaya
evaporator yang ada saat ini. total keseluruhan selain dari unit pendingin saja.
Dari tabel 4 data ikan yang masuk selama Hal ini mungkin dikarenakan oleh perhitungan
satu bulan di bulan November, didapat massa yang menganggap bahwa unit pendingin
beroperasi selama 24 jam penuh dalam sehari,
ikan rata – rata per harinya tersebut adalah
padahal sebenarnya unit beroperasi kurang dari
sekitar 853 kg. Maka selanjutnya dengan cara 24 jam karena adanya defrost dan pada saat
yang sama seperti pada subbab 4.4 dan 4.5 diatas defrost ini kompresor tidak beroperasi.
didapat nilai – nilai berikut ini: Selanjutnya dari data biaya listrik yang
Beban rata – rata perhari pada Cold terhitung ini, kita bisa menghitung berapa biaya
storage) : sewa minimal yang harus dibayar untuk setiap
massa ikannya agar dapat mengetahui berapa
keuntungan yang ingin diperoleh dari sewa
pendinginan ikan ini, yaitu dengan menggunakan
cara berikut :

Perhitungan Beban Pendingin pada Cold Storage.... (Siagian) 146


Biaya Sewa minimal = Total biaya listrik / 2,24 lebihkecil dari COP Carnot-nya yang
total massa ikan selama sebulan= Rp 9.175.000,- sebesar 4,13.
/ 25587 kg = Rp 358,- / kg ikan
Dari perhitungan tersebut juga didapat nilai DAFTAR PUSTAKA
kapasitas pendinginan evaporator yang relative Althouse, Andrew. D, Carl H. Turguisht dan
lebih besar dari beban pendinginan yang ada Alfred F. Bracciano. 1992. “Modern
pada cold storage baik pada beban dalam 1 hari Refrigeration and Air Conditioning”. South
tertentu maupun pada perhitungan beban rata – Holland, Illionis: The good heart – Wilcox
rata perharinya. Dimana pada cold storage Company, Inc. ASHRAE Refrigeration
didapat nilai kapasitas pendinginan sebesar 25,07 Handbook 2006, American Society of
kW. Heating, Refrigerating and Air-Conditiong
Sedangkan beban pendinginan pada tanggal Engineers, Inc., Atlanta, 2006
8 November sebesar 12,81 kilowatt (untuk massa Dossat, Roy, J. 1981.” Principle of Refrigeration”
ikan 3411 kg) dan untuk beban rata – rata perhari SI Edition. Canada: Jhon Willey and
hanya 5,89 kilowatt (untuk massa rata – rata 853 Son.1981
kg). Selisihnya adalah 2 kali lipatnya dan bahkan Holman, JP. E. Jasifi (penerjemah). Perpindahan
4 kali lipatnya untuk massa rata – rata 853 kg. Panas, Edisi Keenam. Penerbit Erlangga.
Selisih ini sangat besar yang mengakibatkan Jakarta. 1994
konsumsi daya listrik yang juga besar meskipun Lienhard, Jhon H IV / V. A Heat Transfer
beban yang ada sangat sedikit. Textbook. 3 rd Edition. Phlogiston Press.
Sebaliknya dengan melihat kapasitas Cambridge, Massach ussete, USA. 2001
evaporator yang sebesar 25,07 kilowatt ini kita
dapat menghitung berapa massa ikan yang
seharusnya bisa didinginkan oleh unit cold
storage tersebut. Yaitu sebagai berikut : Beban
panas ikan = Qe – Qwall – Qatap – Qorang –
Qmotor

= (25,07 – 0,92 – 0,56 – 0,11 – ,38) kJ/s

= 22,10 kJ/s
Massa ikan max = (22,10 kJ/s x 3600 s/jam
x 24 jam/hari) / ( h. lf + C2 x ∆T 2) kJ/kg
= (1.909.440 kJ/hari) /
(227 + 2,2 x 10) kJ/kg
= 7668 kg/hari

V. KESIMPULAN
Berdasarkan data pengukuran, perhitungan,
dan analisis yang telah dilakukan pada bab – bab
sebelumnya diatas, maka dapat diambil beberapa
kesimpulan berikut, yaitu :
• Biaya listrik yang besar untuk kedua mesin
pendingin (cold storage dan Air Blast
Freezer) yang ada tersebut dikarenakan
kapasitas pendinginannya yang besar dan
tidak dilengkapi dengan pengaturan
kapasitasnya sehingga meskipun bebannya
berubah – ubah setiap harinya tapi
konsumsi daya listriknya tetap besar.
• Untuk satu unit cold storage memiliki
kapasitas pendinginan 25,07 kilowatt, dan
kapasitas ini mampu mendinginkan dan
menyimpan ikan hingga sebanyak 7.686 kg
setiap harinya.