Você está na página 1de 5

COLUMN  ENGINEER’S NOTEBOOK

This article was published in ASHRAE Journal, February 2019. Copyright 2019 ASHRAE. Posted at www.ashrae.org. This article may not be
copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit
www.ashrae.org.
Daniel H. Nall

Selecting Cooling Coils


For Maximized
Energy Efficiency
BY DANIEL H. NALL, P.E., BEMP, HBDP, FELLOW/LIFE MEMBER ASHRAE

This column describes how cooling coils can be selected to maximize energy effi-
ciency while minimizing the additional first cost that might accrue from the selec-
tion. Too often, cooling coils are selected with a fixed set of parameters that are used
time and time again, without any thought of the impact of varying those parameters.
As a result, cooling coil selections can frequently be less than optimal. This article
suggests that a more comprehensive examination of these parameters in the course
of the design can result in vastly improved selections. Note that these studies are
relevant to areas that require dehumidification because they have summer dew-point
design temperatures in excess of 62°F (16.7°C). Most of the Eastern, Midwestern, and
Southwestern portions of the United States experience these conditions, along with
many other areas around the world.
Cooling coils are heat transfer devices and heat increased temperature differential of the supply air
transfer is driven by temperature differential. Higher to the room, thus reducing airflow to meet the cooling
temperature differential drives a higher rate of heat load. (Sometimes partially offset by increased dehumid-
transfer if the thermal coupling between the heat ification load and reduced hours of economizer);
source and the heat sink is kept constant. Because an 2. Providing the same supply air temperature with an
increase in the thermal coupling often entails some increased temperature differential in the chilled water,
additional first cost, engineering designs often rely thus reducing pumping energy; and
upon a higher temperature differential to drive the 3. Providing the same supply air temperature with
desired rate of heat transfer while minimizing the an elevated chilled water supply temperature, thus in-
thermal coupling. While these heat transfer processes creasing chiller efficiency and, if waterside economizer
can be considered almost 100% efficient, in that the is used, increased the number of hours of availability.
value of the heat input and the heat output are virtu- The two most important factors of coil selection by the
ally identical, no matter what the temperature differ- design engineer for decreasing the approach of the leav-
ential, optimizing the thermal coupling between the ing air temperature to the entering chilled water tem-
heat transfer fluid and the air can result in significant perature are: heat transfer area, specifically number of
improvements in energy efficiency. coil rows and density of coil fins (typically measured in
fins per inch), and the residency time of the air on the
Cooling Coils heat transfer surface, a function of the air velocity across
Optimal selection of cooling coils can decrease energy the coil.
consumption in three ways:
1. Reducing the supply air temperature, enabling an Daniel H. Nall, P.E., FAIA, is director at Daniel Nall Consultant, LLC.

52 A S H R A E J O U R N A L   a s h r a e . o r g   F E B R U A R Y 2 0 19
ThisfileislicensedtoKautukDikshit(aseaind@gmail.com).CopyrightASHRAE2019.
COLUMN  ENGINEER’S NOTEBOOK

The impact of reduced coil face velocity on first cost TABLE 1  


Base case coil selection parameters.
and annual energy cost has been documented, but the Coil Entering Air Conditions 80°F DBT/67°F WBT
ability of the enhanced heat transfer to achieve greater Outdoor Airflow 4,000 cfm
thermal coupling between the air and the chilled water
Outoor Air Condition 89.6°F DBT/72.5°F WBT
was not considered.1
RA Condition 78°F DBT/63.5°F WBT
Other design factors that influence the approach,
Total Coil Airflow 20,000 cfm
including fin pattern and coil circuiting, are typically
Coil Face Velocity 500 fpm
controlled by the coil vendor. Design engineers should
be careful that their performance specifications do not CHWTS/CHWTR 44°F CHWTS/56°F CHWTR

add unnecessary expense or reduced effectiveness of the


coil. For example, limiting the chilled water tempera- calculation modules from the open source community.2
ture rise through the coil may result the vendor provid- The base case was selected to use conventional input
ing a more complex and expensive circuiting design that parameters as listed in Table 1.
meets the precise chilled water temperature rise, while As can be seen in Table 2, these parameters result in
actually decreasing the thermal coupling of the chilled a fairly typical coil selection of six-row and 14 fins per
water to the airflow. The design engineer can use coil inch (1.8 mm fin spacing). Air pressure drop through
selection software to determine the impact of optimiz- the coil is fairly high at 1.22 in. w.c. (305 Pa), while water
ing these design parameters. Allowing the program to pressure drop is low at 7.66 ft (22.9 kPa). The face veloc-
Auto-select for coil circuiting, specifying actual values of ity through the MERV 13 filter bank is assumed to be the
chilled water flow while leaving the chilled water leaving same as that through the coil. Filter pressure drop is
temperature free is one path to finding an optimal coil assumed to be 0.86 in. w.c. (215 Pa), reflecting a partially
selection. loaded condition.
Several factors impact the conventional values used On many projects, this selection would stand without
for face velocity and coil density, with space require- further examination. An optimization process, with a
ments and first cost likely the most important. Lowering step-by-step process as shown Table 2, will likely result
coil face velocity is often seen as entailing a prohibitive in a significantly different coil selection from the base
increase in the space required for air-handling units, case: Note that in some cases, the coil sensible loads are
along with a significant increase in first cost, of the air- not exactly the same because the coil selection program
handling unit, including coil, filter and air-handling provides slightly different coil leaving temperature for
unit cabinet. Similarly, more robust coils, more rows each selection.
or a denser fin spacing are seen as entailing significant Case 2: Reduce Coil Face Velocity, Keeping All other
additional first cost. Parameters. The first step is to look at the impact of
All of these more obvious changes, however, must be reducing coil face velocity, in this case, a fairly substan-
incorporated with other indirect changes, such as the tial decrease to 363 fpm (1.84 m/s). With this reduction
size of the chilled water distribution, changes to the in coil face velocity, achieved by increasing the coil face
required chilled water capacity and size of supply fan, area from 40 ft2 (3.7 m2 ) to 55 ft2 (5.1 m2 ), the required
and ductwork. The synergistic relationship of these fac- coil becomes four rows and 10.5 fpi (2.42 mm fin spac-
tors, however, enable them to be optimized, resulting ing). Filter pressure drop is assumed to be 0.52 in. w.c.
in superior performance without significant increase, (130 Pa), reflecting the reduced face velocity through
either to first cost or space requirements. The study the partially loaded condition. Reduction in the depth
that follows will demonstrate the synergistic interac- of the coil and density of the fins, along with the reduc-
tion of these parameters and will suggest an approach to tion in coil face velocity results in a significant reduc-
achieving superior performance. tion in fan energy 4.7 kW, along with a slight increase in
chilled water pump energy and chiller energy because
Cooling Coil Study of the increased latent cooling capacity of the coil at low
This study was performed using a widely used com- face velocity. While this strategy results in the greatest
mercial coil selection program that incorporates various reduction in transport (fan and pump) power, it has

F E B R U A R Y 2 0 19   a s h r a e . o r g   A S H R A E J O U R N A L 53
ThisfileislicensedtoKautukDikshit(aseaind@gmail.com).CopyrightASHRAE2019.
COLUMN  ENGINEER’S NOTEBOOK

the potential for the largest TABLE 2  Results of coil optimization study.
impact on first cost and space
REDUCED FACE VELOCITY
requirements.
INCREASED THERMAL COUPLING
Case 3. Reduce Coil Face
1 2 3 4 5 5R
Velocity, Increase Chilled (BASE CASE) (SAME SAT) (ELEVATED CHWT) (MIN. SAT) (OPT SAT, CHW FLOW) (#5 AT 80% PL)
Water Supply Temperature. Rows 6 4 8 8 8 8
The next step is to look at the Fins (fpi) 14 10.5 10 10 10 10
impact of increasing the sup- Face Velocity(fpm) 500 364 364 364 364 291
ply chilled water temperature
Airflow (cfm) 20,000 20,000 20,000 14,926 16,047 12,838
from 44°F (6.7°C) to 50°F
Sensible Cap (Btu/h) 555,636 551,200 560,000 551,981 552,994 436,735
(10.0°C), while keeping that
Total Capacity (Btu/h) 786,909 799,387 781,600 849,494 833,047 698,088
same supply air temperature
Supply DBT(°F) 54.7 54.9 54.6 47.8 49.7 49.7
and coil area as Case 2. Coil
Supply WBT (°F) 54.2 53.7 54.3 47.7 49.5 49.7
density is increased to eight-
row and 10 fpi (2.5 mm coil CHWTS/CHWTR (°F/°F) 44/56.1 44/56.1 50/62.1 44/56.0 44/59.3 44/61.4
spacing) with two-thirds cir- Coil Size(ft2) 40.0 55.0 55 41.1 44.1 44.1
cuit water feed, for the 20,000 Air Pressure Drop (in. w.c.) 1.22 0.42 0.82 0.82 0.82 0.57
cfm unit. These rows and fins Water Pressure Drop (ft w.c.) 7.66 17.59 10.58 23.20 11.59 8.55
were selected because they Water Flow (gpm) 127.36 132.12 126.72 144.94 105.91 80.24
are the most robust coils that Delta Fan Power (kW) 0.0 (4.70) (3.00) (4.50) (4.10) (8.33)
comply with the cleanabil- Delta Pump Power (kW) 0.00 0.54 0.10 1.04 (0.37) (1.05)
ity standard discussed in Delta Chiller Power (kW) 0.00 0.62 (6.51) 3.31 2.44 na
ASHRAE Standard 62.1-2016.3 Delta Total Power (kW) 0.00 (3.54) (9.41) (0.15) (2.03) na
This provision, Paragraph
5.11.2, established a maximum pressure drop for dry coils Case 4. Reduce Coil Face Velocity, Minimize Supply
at 500 fpm (2.54 m/s), which is met by this coil. Thus, this Air Temperature. The next case seeks to minimize sup-
case suffers from the same issues of increased first cost ply air temperature from 55°F (12.8°C) to 47.8°F (8.8°C).
and space requirements as Case 2. This option results in The coil is essentially the same as in case 3 with the same
some reduction in fan energy due to the decreased face number of row, fin spacing and circuiting. As a result of
velocity, but, the more robust coil lessens the reduction, this supply temperature reduction the required airflow
and has a slight increase the pumping energy for the to meet the required space sensible cooling load is only
same reasons as Case 2. It offers a very significant reduc- 14,926 cfm (7,044 l/s). The reduced airflow requirement
tion, however, in the amount of energy that the chiller enables the coil face area to be reduced to almost the
consumes to produce chilled water. A simple estimate, of same size as the base case, almost eliminating additional
the impact of increasing chilled water temperature, based space requirements and first cost, with the exception of
upon previous chiller selections, is on the order of 0.1 kW/ the more robust coil. Use of such a low supply air tem-
ton (0.03 kW/kW). For this air handling unit, the reduc- perature requires special consideration for the devices
tion would be on the order of 6.5 kW. The increase of the by which the air is delivered to the space, and may
supply chilled water temperature, also entails another require modification of the type of duct insulation used.
possibility for first cost savings, in that the capacity of a Strategies such as fan-powered terminals and induc-
chiller operating at 50°F (10.0°C) is at least 10% greater tion diffusers may reduce the energy savings accrued at
than the capacity of that same chiller operating at 44°F the air-handling unit with this strategy. Another impact
(6.7°C). Whether that savings can be realized, is depen- of this strategy is a significant increase in the latent
dent on the specific design of the chiller plant itself. If the load seen by the coil. The very low coil-air-leaving dew-
space is available, and budget issues can be overcome, this point temperature will result in drier conditions within
strategy results in the greatest energy savings among all the space, which, in summer, may result in increased
the alternatives studied. occupant comfort. While the interior latent load is only

54 A S H R A E J O U R N A L   a s h r a e . o r g   F E B R U A R Y 2 0 19
ThisfileislicensedtoKautukDikshit(aseaind@gmail.com).CopyrightASHRAE2019.
COLUMN  ENGINEER’S NOTEBOOK

slightly dependent upon the relative humidity level Further Practical Considerations
maintained in the space, this strategy will result in sig- Most of the studied alternatives that resulted in energy
nificant additional dehumidification of the incoming savings involved a reduction in supply air temperature.
ventilation air, and, thus, additional latent load and This strategy mitigated additional first cost and addi-
increased chiller energy consumption. As a result, the tional space requirements. The ability to meet loads with
chiller and cooling tower will likely be about 8% larger. lower temperature supply air could result in a reduc-
Case 5. Reduce Coil Face Velocity, Increase Chilled tion of most of the air supply network in the building,
Water Temperature Rise. This case seeks to maintain but that savings may come with an energy cost. In areas
the advantages of the previous case with respect to the with a significant number of hours of the year with tem-
minimized coil face area while reducing the chilled peratures lower than 55°F (12.8°C), airside economizer
water flow required to meet the load, through enabling can be a significant energy conservation measure. The
a larger chilled water temperature rise through the impact of lower supply air temperature on airside econ-
coil. Once again, the same coil is used; only its operat- omizer usage has been documented in a previous study.4
ing parameters are changed. This strategy may be the If a project is located in such an area, and the building
best compromise among all, in that the face area of configuration enables airside economizer, reducing the
the coil is only increased 10% compared with the base size of the air distribution network to reflect the lower
case, and total energy savings is second to the elevated supply air temperature should be evaluated based upon
chilled water case. The chiller and cooling tower capac- the reduced hours of airside economizer operation that
ity requirements are increased by about 6%, but this would be entailed from having a lower required supply
strategy provides an opportunity for first cost savings in air temperature. Reducing the airflow capacity of the
the chilled water distribution system as required chilled distribution system in interior zones, whose loads are
water flow is 17% less than the base case. Chiller energy not sensitive to outdoor conditions would most likely
may be further reduced, because the logarithmic mean result in reduced hours of economizer operation. A good
temperature of the chilled water in the evaporator is strategy would be to size the distribution system to the
increased by the elevated return water temperature, interior zone as if the supply air were at the conven-
thus reducing compressor energy required to meet the tional 55°F (12.8°C) condition, or higher, while sizing
cooling load. Supply air temperatures are not quite as the perimeter zones for a supply temperature of 52°F
extreme as Case 4, possibly precluding special mea- (11.1°C), between the conventional case and the expected
sures for space air diffusion. The additional latent load supply temperature at design conditions, assuming that
is reduced, and transport energy (fan and pump) is perimeter loads, and thus airflow requirements may
reduced. This strategy will also keep some of the advan- be somewhat reduced in conditions that enable airside
tage of lowering space humidity levels, which, based economizer. Paragraph 6.5.3.5 of ASHRAE/IES Standard
on personal anecdotal experience, tends to reduce the 90.1-2016 requires that zones that are expected to expe-
number of discomfort complaints. rience relatively constant loads shall be designed for the
Case 5R. Part Load (80%) Operation of Case 5. This fully reset supply temperature, a description that would
case examines what happens to the Case 5 strategy when apply to the interior zones of many buildings.5
it is operated at 80% part load supply airflow. Supply Another implication of reduced supply air tempera-
air temperature is controlled at the same level as Case ture is difficult with space air diffusion, especially dur-
5. The assumption is that the outdoor air conditions ing reduced-flow part-load operation. Diffusers should
are the same as for the design case, an assumption that be selected, such that they do not “dump” because of low
is likely far too conservative. As a result, chiller energy flow of unusually cold air.
is not calculated, as milder outdoor conditions could Case 3 may be of interest for projects that spatially
significantly reduce latent, and, thus, total cooling cannot accommodate airside economizer, or projects
loads. One important observation that should be made in locations that have few hours of low wet-bulb tem-
is that chilled water temperature rise through the coil perature that would enable waterside economizer with
increases at part load, further reducing required chilled conventional chilled water temperature. A coil designed
water flow and pump energy. to provide 55°F (12.8°C) supply air with 50°F (10.0°C)

56 A S H R A E J O U R N A L   a s h r a e . o r g   F E B R U A R Y 2 0 19
ThisfileislicensedtoKautukDikshit(aseaind@gmail.com).CopyrightASHRAE2019.
COLUMN  ENGINEER’S NOTEBOOK

chilled water at design conditions, can supply that same different alternatives will be particular to the project, to
temperature supply air with 54°F (12.2°C) chilled water the external air pressure drop in the air delivery system,
during outdoor conditions that would enable water- to the total pressure drop in the chilled water distribu-
side economizer. Meeting the supply air temperature tion system, and to the climate, building configuration
requirement with much higher temperature chilled and occupancy parameters. The optimal solutions will
water, in some climates, will significantly increase the certainly be specific to each project, as will importance
number of hours of waterside economizer operation. of space requirement differences and the magnitude of
The additional first cost and space requirements for this first cost differences. The design engineer is encouraged
strategy then may be justified for some projects that nec- to explore different options to find the best solution for
essarily must rely on waterside economizer. each project. Coil selection programs, available from
a variety of sources at no cost, enable the designer to
Conclusion examine different alternatives for coil selection, to bet-
This short study has been designed to demonstrate ter make decisions about both desired coil configuration
the advantages of investigating different values for the and operating strategies.
standard parameters of chilled water coil selection.
The two strategies of reducing coil face velocity and References
increasing the robustness of the cooling coil have been 1. Peterson, K. 2014. “Fan velocity considerations in air handler
selection.” ASHRAE Journal (5).
shown the potential to provide some energy efficiency 2. USA Coil and Air. 2018. EZ Coil Software Package, V. 1.0.0.310.
improvements without necessarily accruing significant 3. ASHRAE Standard 62.1-2016, p.8.
4. Duda, S. 2016. “A critical look at cold supply air systems,”
additional first cost or space requirements. The mag- ASHRAE Journal (12).
nitude of energy savings between the base case and the 5. ASHRAE/IES Standard 90.1-2016, p. 97.

Advertisement formerly in this space.

F E B R U A R Y 2 0 19   a s h r a e . o r g   A S H R A E J O U R N A L 57
ThisfileislicensedtoKautukDikshit(aseaind@gmail.com).CopyrightASHRAE2019.

Você também pode gostar