CPT application in Active Power Filtering


Cristina Alexandra Pătraúcu*, Constantin Vlad Suru*, Mircea Dobriceanu*
*University of Craiova/Faculty of Electrical Engineering, Craiova, Romania, apatrascu@em.ucv.ro
*
University of Craiova/Faculty of Electrical Engineering, Craiova, Romania, vsuru@em.ucv.ro
*
University of Craiova/Faculty of Electrical Engineering, Craiova, Romania, mdobriceanu@em.ucv.ro

Abstract - The current decomposition, based on the In this paper, the current decomposition, using the CPT
Conservative Power Theory (CPT), includes, beside the will be analyzed [3] – [5]. In the first stage, the current
active, reactive and void components, an unbalanced computation was verified by simulation and after that the
component too. This way it is possible for the active filter to implementation feasibility was experimentally tested on
compensate only the unbalanced component, if desired. This
paper analyzes the feasibility of decomposing the current in
an active filtering system.
three-phase, three-wire systems using the CPT. Thus, II. CPT CURRENT COMPONENTS FOR SHUNT
several case studies were created to verify the current ACTIVE FILTERING
computation. In the first stage, the current decomposition
The actual section will present the current components
accuracy was tested by simulation in Matlab/Simulink
environment, using a non-linear load, balanced and
definition based on the CPT, in order to use them for the
unbalanced. After interpreting the results obtained by compensating current computation. The current terms are
simulation, the computation algorithm was experimentally defined collectively, by making reference to an
tested on an active filtering system. It will be noticed that for equivalent balanced load absorbing the same active
all the studied cases, the CPT theory leads to correct results power and reactive energy of the analyzed load.
both through simulation and experimental analysis. Hence, The load current is the sum of the active, reactive and
even if the load is unbalanced (different RMS values, of the void currents [3] – [5].
load current, per phases), after compensation, using the
implemented current computation, the load current will i L ia  ir  iv , (1)
have the same RMS value on each phase. Moreover, it is where the notation i means the column vector containing
possible to eliminate the reactive and the distorted the three phase components of i (iR, iS, iT).
component if they will be added to the compensating Each current component is defined as follows [3] – [5]:
current relation. Thus, the CPT has proven its performance 1a) Balanced active current:
in the active filtering current compensation, irrespective of
b P
the load. ia u Gb u , (2)
Keywords - current components; Conservative Power U2
Theory; unbalanced loads; active filter; total and partial where:
compensation. - P is the three-phase active power of the load:

I. INTRODUCTION
P PR  PS  PT ; (3)
- U is the RMS grid voltage defined as follows:
The use of home consumers, as well as of industrial
consumers, especially static converters, leads to high U U R2  U S2  U T2 ; (4)
harmonic distortion in the power grid. In order to obtain b
- G is the equivalent balanced conductance.
the desired waveform and to eliminate the phase shift of 1b) Unbalanced active current (accounts for the
the grid current, a shunt active filter can be used. asymmetrical behavior of the various phases):
Shunt power filters work as a generator, injecting
harmonic currents which correspond to the harmonic ia
u b
i a  i a Ÿ i an
u
G n
 G b u n , n 1 y N (5)
components of the load. Therefore, current concerns 2a) Balanced reactive current:
regarding shunt power filters are directed towards new 
b u, i  W  
algorithms for the compensating currents [1], [2], [6] - i r 2 u  u Bb u (6)
[8]. The compensating current will be calculated u U2
according to the compensation goal.
An active shunt compensator offers the possibility to where:
T
compensate not only the current harmonic distortion and  1 
T ³0
reactive component, but also, the current asymmetry. u, i u ˜ i dt is the internal product;
It must be mentioned that the above features depend,
not only on the compensator, but also, on the  § t 1 T t ·
compensating current computation algorithm. In order to u Z ˜ ¨ ³ u (W )dW  ³ ³ u (W )dWdt ¸¹ is the time
compensate only the current asymmetry, the © 0 T 0 0

compensating current computation algorithm must integral;


contain the unbalanced current component which can be - W is the three-phase reactive energy absorbed by the
added, if desired, to the compensating current. load and Bb is the equivalent balanced susceptance.

78
_____________________________________________________________
Annals of the University of Craiova, Electrical Engineering series, No. 37, 2013; ISSN 1842-4805

i
R R RST signa l rm s
U 15.09
RS
u signa l rm s
S U sincro
S R
N 15.09
R
T signa l rm s
S R 15.09
T
N T signa l rm s
Non-sinusoidal 11.76
Voltage and Current S
power grid
Measurement signa l rm s
Continuous
11.76
pow ergui AC voltage signa l rm s
T converter 11.76

t iS
Non-linear load
u
RST Conservative

Clock i
LRST
Power i* iS,iL u_RST
F
Theory
comp
0 i_RST
1 - total compensation
0 - partial compensation

Fig. 1. The virtual filtering system

2b) Unbalanced reactive current: The case studies were created for a three-phase non-

i
u
r ir  i Ÿ i
b
r
u
rn b

Bn  B u n , n 1 y N (7) sinusoidal voltage system, in which the current had been
calculated with the CPT definitions.
3) Void current is defined by subtracting the active First of all, the CPT current computation was verified
and reactive current from the load current. by simulation using Matlab/Simulink environment.
iv iL  ia  ir (8) Subsequently, the computation algorithm was
experimentally tested on an active filtering system.
The compensating current will be calculated from the
This section will be related to the simulation study, the
load current depending on the compensation goals, as
following one being dedicated to the experimental
follows:
results.
- total compensation – the active filter will
compensate the entire non-active current: A. Symmetrical non-linear load
i*F i L  ia (9) The symmetrical non-linear
(16) load consists of a three
- partial compensation – the active filter will phase AC voltage converter, with an inductive passive
compensate only the distorted component: load, which absorbs a RMS value of 15 A, being supplied
by a non-sinusoidal voltage system (THDu = 2.3%)
i*F i L  ia  ir (10) (Fig. 1). The analyzed load being non-linear, the load
current and the grid voltage have not identical shape and
phase (Fig. 2).
III. CASE STUDIES Compensating the reactive and the distorted
components, it will remain only the active current, whose
There were analyzed several case studies containing a
value is zero because of the inductive character
symmetrical, as well as, an unbalanced non-linear load.
corresponding to the passive load (Fig. 3).
iLR iLS iLT
4 400

2 200
[A]

uR [V]
RST

0 0
iS

-2 -200

-4 -400

0.06 0.07 0.08 0.09 t [s]


Fig. 2. The grid voltage and the non-linear load currents Fig. 3. The grid voltage and the source currents for total compensation

79
Annals of the University of Craiova, Electrical Engineering series, No. 37, 2013; ISSN 1842-4805
_____________________________________________________________

iSR iSS iST iSR iSS iST

Fig. 4. The grid voltage and the source currents for partial compensation Fig. 6. The grid voltage and the source currents for partial compensation

In the partial compensation case, the distorted


IV. EXPERIMENTAL RESULTS
component was removed, the RMS value of the current
being reduced from 15.09 A to 11.76 A. The obtained
As it was mentioned, after the simulation analysis, the
result can be validated by the current waveform which,
after the compensation, is sinusoidal and keeps the phase CPT computation was experimentally tested on an active
shift because the reactive current was not eliminated filtering system consisting of:
- the three-wire power inverter;
(Fig. 4).
- the 1st order interface filter consisting of three special
B. Unbalanced non-linear load coils having an inductance of 4.4 mH;
- the control system based on the dSPACE DS1103
In order to prove that the CPT gives good results, even acquisition board;
if the load is unbalanced, it was analyzed the same non- -the analyzed non-linear load, which is a three phase
linear load which was mentioned at section A, but this AC voltage converter, with an inductive passive load.
time, the phase current RMS values were different as The command and control section of the system is a
follows: 15, 15 and 10 A (Fig. 5). Matlab/Simulink model which uses DS1103 specific
The waveforms corresponding to the total library blocks (Fig. 8).
compensation mode will not be presented in this case This model is compiled and loaded to the DS1103
because, as it was mentioned previously, compensating program memory.
the reactive and the distorted components, it will remain The adopted current controller is a three-phase fixed
only the active current, whose value is zero (because of band hysteresis controller. The hysteresis band is set up
the inductive character corresponding to the passive to 1 A, considering the maximum current value of 25 A.
load). The blocks which determine the three-phase current
On the other hand, after the partial compensation, the and voltage systems are necessary because the
current RMS value of each phase was modified to the experimental active filter has only two transducers for
values corresponding to a balanced current system: 9.85, each measured current or voltage system. So, because the
9.85, 9.85 A, proving the CPT capability of efficiently power inverter has a three-wire configuration, the blocks
compensating not only the current distortion, but also, the compute the third component of the current using the two
current unbalance (Fig. 6). measured components.

iLR iLS iLR iLS iLT


iLT

Fig. 5. The grid voltage and the unbalanced non-linear load currents Fig. 7. The grid voltage and the non-linear load currents

80
Annals of the University of Craiova, Electrical Engineering series, No. 37, 2013; ISSN 1842-4805
_____________________________________________________________

Compensating
current computation
RTI Data
partial / total u
RST
iL Conservative
RST
sin / nesin Power i*
comp mode Theory F

MUX ADC grid voltage

DS1103MUX_ADC_CON1
DS1103DAC_C3
u_RS
u_RST i i
MUX ADC u_RT Fa Fb
Current hysteresis controller DAC
i * K
DS1103MUX_ADC_CON4 F 2

-K- u DAC
RST
MUX ADC
u DS1103DAC_C1
c
DS1103MUX_ADC_CON3 K
1
iL
RST
BIT #0
MUX ADC is RST
start start BIT #1
DS1103MUX_ADC_CON2 Virtual Front Panel load BIT #2
load pulses out
Grid RMS Current
BIT #3
compensation
ADC -iL_S
BIT #4
iL_RST compensation
-iL_T
DS1103ADC_C19 BIT #5

BIT #6
ADC
BIT #7

DS1103ADC_C17 DS1103BIT_OUT_G0

Fig. 8. The Simulink model which implements the active filter current computation and control algorithm

For the grid voltage, the three phase voltages are After the total compensation all the non-active
obtained using the measured line voltages (uRS, uRT). components of the load were eliminated.
Moreover, because of the transducers position, the Thus, the RMS value of the current being absorbed
currents absorbed by the non-linear load are measured from the grid dropped to 1.61, 1.51 and 1.68 A (Fig. 9).
with opposite sign to the real. This was because the analyzed load could not absorb
A. Symmetrical non-linear load active power, absorbing only reactive and distorted
power. The load was designed for testing the active
For the 1st analyzed case, the non-linear load which is
power filter operation.
a three phase AC voltage converter, with an inductive
passive load, absorbs a RMS value of approximately The total harmonic distortion factor, after the total
15 A per phase. The exactly current RMS values of each compensation, is not edifying because the grid current
phase are: 14.74, 13.68 and 14.44 A. Thus, comparing RMS value is very low being given only by the losses in
these values to the simulation case, they are different the power inverter and by the auxiliary current necessary
among the phases, the calculated asymmetry factor of the for the control and protection stages.
grid current having a value of 6.01%. In this case, the In addition, to emphasize the CPT capability of
load can be considered as a symmetric one, the compensating the distorted component, the harmonic
asymmetry being too low. RMS current was also computed. Thus, it dropped from
The specified asymmetry can be also observed by 10.94, 10.07 and 10.67 A to 0.93, 0.89 and 1.08 A.
analyzing the load current waveforms, for each phase,
which are illustrated in Fig. 7.
40 400
iSR iSS iST
20 200
[A]

uR [V]

0 0
RST
iS

-20 -200

-40 -400
0.04 0.05 0.06 0.07 t [s]
Fig. 9. The grid voltage and the source currents for total compensation Fig. 10. The grid voltage and the source currents for partial
compensation

81
Annals of the University of Craiova, Electrical Engineering series, No. 37, 2013; ISSN 1842-4805
_____________________________________________________________

In case of partial compensation, only the distorted 40 400


component was eliminated (Fig. 10), the grid current
RMS value decreasing to 10.74, 10.3 and 10.73 A.
The grid current shapes are almost sinusoidal, the 20 200
partial harmonic distortion factor (for the first 51th

[A]

uR [V]
harmonics) being reduced from 65.32, 60.30 and 64.58%
0 0

RST
to 5.26, 5.12 and 5.52%. Having the PHD values, the

iS
resulted filtration efficiency per phase is: 12.4, 11.78 and
11.69.
-20 -200
Because the RMS values of the load current were
different among the phases, another important factor was
computed, i.e. the asymmetry factor. Thus, after the
-40 -400
compensation, the value of the above factor dropped from 0.04 0.05 0.06 0.07 t [s]
6.01% to 2.56%.
It is worth mentioning that the asymmetry factor of the Fig. 12. The grid voltage and the source currents for total compensation
grid voltage had a value of 1.73%. Therefore, the The resulted grid current shapes are approximately
remaining unbalance is due to the grid voltage sinusoidal and the PHD factor decreases from 69.66,
asymmetry, the RMS grid voltage values being: 225.7, 68.62, 44.76% to 5.29, 5.69 and 4.89%. These values
222.8 and 229.6 V. lead to a filtration efficiency of 13.16, 12.04 and 9.15.
B. Unbalanced non-linear load Even if the asymmetry is much higher than before, i.e.
an asymmetry factor of 33.31%, the CPT capability of
In order to prove the good results of the CPT compensating the current unbalance is proved one more
implementation, regarding the asymmetry compensation, time. Thus, after the compensation, the asymmetry factor
it was considered the previously load, this time with a dropped to 5.16%.
higher unbalance. So, the RMS load current values for As it was noticed before, the remaining unbalance of
each phase are: 15, 14.46 and 9.32 A, having the the current was because of the grid voltage asymmetry.
waveforms illustrated in Fig. 11. The measured grid voltage RMS values were:
The load was analyzed for both partial and total UR = 225.9V, US = 223.2V, UT = 229.5V, obtaining a
compensation mode. When the compensating current was grid voltage asymmetry factor of 1.6%.
calculated using relation (9), all the non-active currents The fact that the remaining unbalance of the current is
were removed (Fig. 12). Talking about the same not due to the compensation method inefficiency can be
non-linear load, which did not absorb active power, the proved by analyzing the simulation results obtained using
value of the remaining current is very low, almost zero. Matlab/Simulink environment (Fig. 6).
After compensation, the harmonic RMS current was The grid current RMS values, after the compensation,
reduced from 10.95, 10.39 and 6.25 A to 0.96, 0.50 and are equal for all phases (9.85 A), the grid voltage RMS
0.90 A. values being equal, so that the grid current system is
For partial compensation, the compensating current is equilibrated.
calculated with relation (10), and the phase shift between In the experimental case, taking into consideration the
the grid voltage and current shows that the reactive grid current asymmetry factor reduction, it can be
component is still present (Fig. 13). The grid current concluded that the grid current system is equilibrated
RMS values were reduced, by compensation, to 9.63, after compensation.
8.81 and 9.38 A.

iLR iLS iSR iSS


iLT iST

Fig. 11. The grid voltage and the unbalanced non-linear load currents Fig. 13. The grid voltage and the source currents for partial
compensation

82
Annals of the University of Craiova, Electrical Engineering series, No. 37, 2013; ISSN 1842-4805
_____________________________________________________________

V. CONCLUSIONS ACKNOWLEDGMENT
The results obtained by the Conservative Power The authors gratefully acknowledge the contributions
Theory implementation, in active filtering, are good in of Prof. Alexandru Bitoleanu and Prof. Mihaela Popescu
the simulation case, as well as, in the experimental one. It for their work on the original version of this document.
was shown that the CPT method, by its current REFERENCES
components, allowed both partial and total compensation,
[1] H. Akagi, E. H. Watanabe, M. Aredes, “Instantaneous Power
being an advantage when the reactive power Theory and Applications to Power Conditioning,” Wiley-IEEE
compensation is not necessary. Press, 2007.
Moreover, an unbalanced current component is [2] L. S. Czarnecki, “Currents’ Physical Components (CPC) in
defined, thus, it can be compensated, if desired, only the Circuits with Nonsinusoidal Voltages and Currents (Part 2: Three-
unbalanced current. Phase Linear Circuits)”, EPQU Journal, Vol. XXII, No. 1, 2006,
pp. 3-13.
The result obtained by simulation are good, the current
[3] P. Tenti, “Conservative Power Theory Seminar: A theoretical
waveform, after the compensation, being sinusoidal. In background to understand energy issues of electrical networks
case of partial compensation it keeps the phase shift under non-sinusoidal conditions and to approach
because the reactive current is not eliminated. measurement,accountability and control problems in smart grids”,
UNICAMP – UNESP Sorocaba, August 2012.
On the other hand, for total compensation, because of
[4] P. Tenti, P. Mattavelli, “A Time-Domain Approach to Power
the inductive character of the passive load, the current Term Definitions under Non-Sinusoidal Conditions”, 6th
absorbed from the grid is zero, all the non-active International Workshop on Power Definitions and Measurements
components being removed. under Non-Sinusoidal Conditions, Milano, October 13-15, 2003.
The experimental results are also positive, the current [5] P. Tenti, P. Mattavelli, Tedeschi Elisabetta, “Compensation
harmonic distortion factor and also the load current Techinques Based on Reactive Power Conservation” , Electrical
Power Quality and Utilisation, Journal vol. XIII, No. 1, 2007.
asymmetry being reduced, after compensation. It must be
[6] Popescu Mihaela, A. Bitoleanu, M. Dobriceanu, “Compensation-
mentioned that, because of the grid voltages asymmetry, Based Current Decomposition”, Proceedings of World Academy
the resulted grid current system has not the same RMS of Science, Engineering and Technology, vol. 37, January 2009,
value for each phase. pp. 598-603.
However, taking into consideration the grid current [7] Popescu Mihaela, Bitoleanu A., Dobriceanu M., “On the Current
Decomposition Based on Instantaneous Apparent Power Vector”,
asymmetry factor reduction, it can be concluded that the Proc. of the 10th IASTED International Conference on Power and
grid current system is equilibrated, after compensation. Energy System, Baltimore, Maryland, USA, April 16-18, 2008, pp.
Thus, the CPT capability of efficiently compensating 120-125.
not only the current distortion, but also, the current [8] Y. Xu, L. M. Tolbert, J. D. Kueck, D. T. Rizy, “Voltage and
unbalance was validated by simulation, as well as by the Current Unbalance Compensation Using a Parallel Active Filter”,
Power Electronics Specialists Conference, June 2007, pp. 2919 –
experimental results. 2925.