Escolar Documentos
Profissional Documentos
Cultura Documentos
OMICRON PTL
User Manual
V1.000
Content
1. General ............................................................................................................................................ 3
2. Software and Hardware Requirements........................................................................................... 3
3. Hardware ......................................................................................................................................... 4
4. Functional Range ............................................................................................................................ 6
5. XRIO Converter ............................................................................................................................... 7
5.1 Additional Information..................................................................................................................... 7
5.1.1 Trip/Alarm Output ..................................................................................................................... 7
5.1.2 Test Information........................................................................................................................ 8
6. Specific Protection Tests ................................................................................................................ 8
6.1 Stator Differential Protection ........................................................................................................... 8
6.2 Distance Protection .......................................................................................................................10
6.3 Generator Unbalance Protection ...................................................................................................11
6.4 Overcurrent Protection ..................................................................................................................11
6.5 Loss of Excitation Protection .........................................................................................................11
6.6 Volt Per Hertz Protection ...............................................................................................................12
6.7 Voltage Protection .........................................................................................................................12
6.8 Sensitive Directional Power Protection ..........................................................................................13
1. General
This user manual describes details of testing GE Multilin G60 relays with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.
A CMC test set with six current outputs is required to use the full functionality of this PTT.
3. Hardware
There are multiple possibilities of wiring a GE Multilin G60 relay to a CMC test set. The advised
connections are shown in Figure 1 and Figure 2. These connections are the default settings in the
Hardware Configuration of the PTT.
The Figure 3 shows the default application configuration shown in the instruction manual of the
Relay, in case you have different configuration, please adapt your wiring accordingly especially the
current transformer assigned to each protection function.
N (~5c,~6c,~7c)*
Offline On
VC (~7a)*
VA (~5a)*
VB (~6a)*
(H7a)
Line End N
Line End IC
Line End IA
Line End IB
CB aux. [52a]
Trip
Alarm
Neutral End IC
Neutral End N
Neutral End IB
Neutral End IA
N (~5c,~6c,~7c)*
VC (~7a)*
VA (~5a)*
VB (~6a)*
Offline On
(H7a)
Line End N
Line End IC
Line End IA
Line End IB
CB aux. [52a]
Trip
Alarm
N
IG
4. Functional Range
Supported functions:
Stator differential (ANSI 87S)
Phase distance backup (ANSI 21P)
Phase overcurrent (ANSI 50P/51P/67P)
Neutral overcurrent (ANSI 50N/51N/67N)
Ground overcurrent (ANSI 50G/51G/67G)
Phase overvoltage (ANSI 59P)
Phase undervoltage (ANSI 27P)
Neutral overvoltage (ANSI 59N)
Negative sequence overvoltage (ANSI 59_2)
Over-/underfrequency (ANSI 81)
Loss of Excitation (ANSI 40)
Volt per hertz (ANSI 24)
Sensitive directional power (ANSI 32)
Generator unbalance (ANSI 46)
Thermal overload (ANSI 49)
Accidental energization (ANSI 50/27)
Although the functions listed above are not supported by the Protection Test Template, the
Relay Parameter Section of the XRIO Converter includes all protection parameters of the relay.
As the GE Multilin G60 offers a high flexibility in setting and configuring protection functions, many
cannot be modeled in an automated way. Therefore checking the predefined PTT and adding custom
application conditions before testing may be required.
5. XRIO Converter
The Test Object already contains the GE Multilin G60 XRIO Converter, which includes setting
parameters of the modelled protection relay. The setting parameters are built as an image of the GE
EnerVista UR Setup software.
The Filter for GE Enervista.csv Settings can be used for importing settings into the Relay Parameter
Section.
General information about the converter structure can be found in the OMICRON PTL user manual. In this
chapter the specifics of the Trip/Alarm Output block and the Test Information block in the Additional
Information section of the converter are described.
The block Trip/Alarm Output contains a check box (parameter of the data type Boolean) for each element
of the supported functions listed in chapter 4. Please activate the corresponding check box manually, if an
element has an influence on the Trip or Alarm Output of your relay setting. Figure 4 shows an example for
a relay setting, where the differential protection function, zones 1 – 3 of the phase distance protection
function and Stage 1 of the generator unbalance protection are able to activate the relay’s Trip Output,
Stage 2 of the generator unbalance protection activates the relay’s Alarm Output.
The Phase Undervoltage block contains parameters for setting the test voltage of the fault state in
undervoltage trip time tests. If e.g. an inverse time curve is selected for the Phase UV1 element, the test
voltages can be decreased and thus the trip and test time. The Test Tolerance block contains an
additional test tolerance to calculate the start and end value for trip and pickup tests using the Ramping or
Pulse Ramping test module.
Because of the CT Saturation detection algorithm of the relay, the trip characteristic test is possible only
with a pickup contact. You can use the Diff Operating Characteristic test module for the test. In this case,
please route the Stator Differential Pickup signal to relay output as (for example) shown in the following
figure.
Figure 5: Routing of Stator Differential Pickup signal to the Trip Bus, example
The Prefault and Trigger Condition needed for the test are shown in the Figure 6.
Figure 6: Prefault and Trigger Condition for the Stator Diff Characteristic Test
The Stator Diff Characteristic Test can be done with a Search Test. Possible test results are shown in the
following Figure.
Example:
Fault type
o A-B-C for phase elements
o 3I0 for neutral elements
o A-N for ground elements
Test inverse time elements with 3 Test Points on the Inverse Curve
Test definite time/instantaneous elements with 2 Test Points at 0.9 and 1.1 x Pickup
Note: No test points are predefined in the module. Test points shown on following figure can be used to
test set parameters.
Note: If the test current is too high, the module may not execute the test for some points with big
impedances. This test points are out of range and are represented pink colored. In this case remove the
link of the test current and set the ITest manually.
For the trip time test the State Sequencer test module is used. Three points at 1.05, 1.10 and 1.15*Pickup
are tested for each stage. Please ensure that there is no overlapping between the stages of Volt Per Hertz
Protection for the chosen test points! In other case the test points must be adjusted accordingly.
The trip times of undervoltage and overvoltage protection elements are tested with the State Sequencer
test module. The test is divided into a pre-fault, fault and post-fault states. In the Fault state, an under- or
overvoltage condition is simulated depending on the type of the element under test. The trip time is
measured and evaluated.
The set mode Powers of the State Sequencer test module is used for trip time tests of sensitive directional
power. The trip time is measured from the beginning of the fault state until the recorded trip signal and the
result evaluated. For testing sensitive directional power protection elements, the power magnitude and
angle settings are converted into an active and reactive power quantity and linked in the fault state.
The current and voltage of the reset and pre-fault state are set to the nominal values, the angles of the
reset and pre-fault state are shifted in 180° to the fault angles.