PROJECT MUNICIPAL CORPORATION HIGHT 12 feet

ADDRESS FARIDABAD FLOOR FIRST PEOPLE 100 nos


SPACE CORPORATE BOX-31 FLOOR AREAS 667 sft LIGHT 2 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 147.6 sft x 90 btu x 0.56 = 7439.04 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Diffrenc 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Diffrenc 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 148 sft x 36 (F) x 21 (F) x 1.13 =
Partion 945 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 667 sft x 31 (F) x 16 (F) x 0.40 =
Floor 0 sft x 31 (F) x 16 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 100 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 1000 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 100 nos x 280 btu x =
Light(f) 1334.24 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 100 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 500 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 100 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 500 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 500 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

8.8 8.7
4079 3240 11.66
75.7 77.0
6.1 4.9

SUMMER MONSOON
BTU BTU
6004.4 3502.5
11713.5 6045.7
8272.3 4269.6
0.0 0.0
SUMMER MONSOON
BTU BTU
3888.0 2268.0
3888.0 2268.0
SUMMER MONSOON
BTU BTU
28000.0 28000.0
5692.2 5692.2
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
74897.4 59485.1

7489.7 5948.5
82387.2 65433.6
SUMMER MONSOON
BTU BTU
720.8 5576.0
360.4 2788.0
27000.0 27000.0
0.0 0.0
0.0 0.0
0.0 0.0
28081.2 35364.0
2808.1 3536.4
30889.3 38900.4
SUMMER MONSOON
BTU BTU
16524.0 9639.0
3063.4 23698.0

979.4 1666.9
20567 35004

105762 103974

0.73 0.63

52 52

18.7 18.7

8.8 8.7

4079 3240
PROJECT MUNICIPAL CORPORATION HIGHT 12 feet
ADDRESS FARIDABAD FLOOR FIRST PEOPLE 50 nos
SPACE CORPORATE BOX-32 FLOOR AREAS 312 sft LIGHT 2 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 72 sft x 90 btu x 0.56 = 3628.80 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Diffrenc 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Diffrenc 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 72 sft x 36 (F) x 21 (F) x 1.13 =
Partion 708 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 312 sft x 31 (F) x 16 (F) x 0.40 =
Floor 0 sft x 31 (F) x 16 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 50 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 500 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 50 nos x 280 btu x =
Light(f) 624.08 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 50 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 250 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 50 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 250 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 250 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

4.6 4.4
2166 1678 6.19
67.6 70.5
6.9 5.4

SUMMER MONSOON
BTU BTU
2929.0 1708.6
8785.2 4534.3
3869.3 1997.1
0.0 0.0
SUMMER MONSOON
BTU BTU
1944.0 1134.0
1944.0 1134.0
SUMMER MONSOON
BTU BTU
14000.0 14000.0
2662.5 2662.5
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
39762.7 30799.2

3976.3 3079.9
43739.0 33879.1
SUMMER MONSOON
BTU BTU
360.4 2788.0
180.2 1394.0
13500.0 13500.0
0.0 0.0
0.0 0.0
0.0 0.0
14040.6 17682.0
1404.1 1768.2
15444.7 19450.2
SUMMER MONSOON
BTU BTU
8262.0 4819.5
1531.7 11849.0

489.7 833.4
10283 17502

55426 53149

0.74 0.64

52 52

18.7 18.7

4.6 4.4

2166 1678
PROJECT MUNICIPAL CORPORATION HIGHT 12 feet
ADDRESS FARIDABAD FLOOR FIRST PEOPLE 50 nos
SPACE CORPORATE BOX-33 FLOOR AREAS 312 sft LIGHT 2 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 72 sft x 90 btu x 0.56 = 3628.80 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Diffrenc 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Diffrenc 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 72 sft x 36 (F) x 21 (F) x 1.13 =
Partion 708 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 312 sft x 31 (F) x 16 (F) x 0.40 =
Floor 0 sft x 31 (F) x 16 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 50 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 500 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 50 nos x 280 btu x =
Light(f) 624.08 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 50 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 250 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 50 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 250 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 250 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

4.6 4.4
2166 1678 6.19
67.6 70.5
6.9 5.4

SUMMER MONSOON
BTU BTU
2929.0 1708.6
8785.2 4534.3
3869.3 1997.1
0.0 0.0
SUMMER MONSOON
BTU BTU
1944.0 1134.0
1944.0 1134.0
SUMMER MONSOON
BTU BTU
14000.0 14000.0
2662.5 2662.5
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
39762.7 30799.2

3976.3 3079.9
43739.0 33879.1
SUMMER MONSOON
BTU BTU
360.4 2788.0
180.2 1394.0
13500.0 13500.0
0.0 0.0
0.0 0.0
0.0 0.0
14040.6 17682.0
1404.1 1768.2
15444.7 19450.2
SUMMER MONSOON
BTU BTU
8262.0 4819.5
1531.7 11849.0

489.7 833.4
10283 17502

55426 53149

0.74 0.64

52 52

18.7 18.7

4.6 4.4

2166 1678
PROJECT MUNICIPAL CORPORATION HIGHT 12 feet
ADDRESS FARIDABAD FLOOR FIRST PEOPLE 50 nos
SPACE CORPORATE BOX-34 FLOOR AREAS 312 sft LIGHT 2 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 72 sft x 90 btu x 0.56 = 3628.80 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Diffrenc 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Diffrenc 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 72 sft x 36 (F) x 21 (F) x 1.13 =
Partion 708 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 312 sft x 31 (F) x 16 (F) x 0.40 =
Floor 0 sft x 31 (F) x 16 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 50 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 500 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 50 nos x 280 btu x =
Light(f) 624.08 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 50 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 250 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 50 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 250 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 250 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

4.6 4.4
2166 1678 6.19
67.6 70.5
6.9 5.4

SUMMER MONSOON
BTU BTU
2929.0 1708.6
8785.2 4534.3
3869.3 1997.1
0.0 0.0
SUMMER MONSOON
BTU BTU
1944.0 1134.0
1944.0 1134.0
SUMMER MONSOON
BTU BTU
14000.0 14000.0
2662.5 2662.5
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
39762.7 30799.2

3976.3 3079.9
43739.0 33879.1
SUMMER MONSOON
BTU BTU
360.4 2788.0
180.2 1394.0
13500.0 13500.0
0.0 0.0
0.0 0.0
0.0 0.0
14040.6 17682.0
1404.1 1768.2
15444.7 19450.2
SUMMER MONSOON
BTU BTU
8262.0 4819.5
1531.7 11849.0

489.7 833.4
10283 17502

55426 53149

0.74 0.64

52 52

18.7 18.7

4.6 4.4

2166 1678
PROJECT MUNICIPAL CORPORATION HIGHT 12 feet
ADDRESS FARIDABAD FLOOR FIRST PEOPLE 50 nos
SPACE CORPORATE BOX-35 FLOOR AREAS 312 sft LIGHT 2 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 72 sft x 90 btu x 0.56 = 3628.80 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Diffrenc 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Diffrenc 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 72 sft x 36 (F) x 21 (F) x 1.13 =
Partion 708 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 312 sft x 31 (F) x 16 (F) x 0.40 =
Floor 0 sft x 31 (F) x 16 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 50 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 500 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 50 nos x 280 btu x =
Light(f) 624.08 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 50 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 250 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 50 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 250 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 250 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

4.6 4.4
2166 1678 6.19
67.6 70.5
6.9 5.4

SUMMER MONSOON
BTU BTU
2929.0 1708.6
8785.2 4534.3
3869.3 1997.1
0.0 0.0
SUMMER MONSOON
BTU BTU
1944.0 1134.0
1944.0 1134.0
SUMMER MONSOON
BTU BTU
14000.0 14000.0
2662.5 2662.5
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
39762.7 30799.2

3976.3 3079.9
43739.0 33879.1
SUMMER MONSOON
BTU BTU
360.4 2788.0
180.2 1394.0
13500.0 13500.0
0.0 0.0
0.0 0.0
0.0 0.0
14040.6 17682.0
1404.1 1768.2
15444.7 19450.2
SUMMER MONSOON
BTU BTU
8262.0 4819.5
1531.7 11849.0

489.7 833.4
10283 17502

55426 53149

0.74 0.64

52 52

18.7 18.7

4.6 4.4

2166 1678
PROJECT MUNICIPAL CORPORATION HIGHT 12 feet
ADDRESS FARIDABAD FLOOR FIRST PEOPLE 50 nos
SPACE CORPORATE BOX-36 FLOOR AREAS 312 sft LIGHT 2 w/sft

SOLAR GAIN THRU GLASS SUMM/MONSON DESIGN CONDITION


ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 72 sft x 90 btu x 0.56 = 3628.80 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Diffrenc 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Diffrenc 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 72 sft x 36 (F) x 21 (F) x 1.13 =
Partion 708 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 312 sft x 31 (F) x 16 (F) x 0.40 =
Floor 0 sft x 31 (F) x 16 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 50 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 500 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 50 nos x 280 btu x =
Light(f) 624.08 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 50 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 250 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 50 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 250 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 250 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

4.6 4.4
2166 1678 6.19
67.6 70.5
6.9 5.4

SUMMER MONSOON
BTU BTU
2929.0 1708.6
8785.2 4534.3
3869.3 1997.1
0.0 0.0
SUMMER MONSOON
BTU BTU
1944.0 1134.0
1944.0 1134.0
SUMMER MONSOON
BTU BTU
14000.0 14000.0
2662.5 2662.5
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
39762.7 30799.2

3976.3 3079.9
43739.0 33879.1
SUMMER MONSOON
BTU BTU
360.4 2788.0
180.2 1394.0
13500.0 13500.0
0.0 0.0
0.0 0.0
0.0 0.0
14040.6 17682.0
1404.1 1768.2
15444.7 19450.2
SUMMER MONSOON
BTU BTU
8262.0 4819.5
1531.7 11849.0

489.7 833.4
10283 17502

55426 53149

0.74 0.64

52 52

18.7 18.7

4.6 4.4

2166 1678
PROJECT MUNICIPAL CORPORATION HIGHT 12 feet
ADDRESS FARIDABAD FLOOR FIRST PEOPLE 100 nos
SPACE CORPORATE BOX-37 FLOOR AREAS 613 sft LIGHT 2 w/sft
3
SOLAR GAIN THRU GLASS SUMM/MONSON DESIGN CONDITION
ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 144 sft x 90 btu x 0.56 = 7257.60 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Diffrenc 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Diffrenc 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 0 sft x 38 btu x 0.38 = 0.00 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 144 sft x 36 (F) x 21 (F) x 1.13 =
Partion 945 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 613 sft x 31 (F) x 16 (F) x 0.40 =
Floor 0 sft x 31 (F) x 16 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 100 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 1000 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 100 nos x 280 btu x =
Light(f) 1226.64 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 100 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 500 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 100 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 500 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 500 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

8.7 8.6
4000 3182 11.43
70.7 71.6
6.5 5.2

SUMMER MONSOON
BTU BTU
5857.9 3417.1
11713.5 6045.7
7605.2 3925.2
0.0 0.0
SUMMER MONSOON
BTU BTU
3888.0 2268.0
3888.0 2268.0
SUMMER MONSOON
BTU BTU
28000.0 28000.0
5233.2 5233.2
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
73443.4 58414.8

7344.3 5841.5
80787.7 64256.3
SUMMER MONSOON
BTU BTU
720.8 5576.0
360.4 2788.0
27000.0 27000.0
0.0 0.0
0.0 0.0
0.0 0.0
28081.2 35364.0
2808.1 3536.4
30889.3 38900.4
SUMMER MONSOON
BTU BTU
16524.0 9639.0
3063.4 23698.0

979.4 1666.9
20567 35004

104163 102797

0.72 0.62

52 52

18.7 18.7

8.7 8.6

4000 3182
PROJECT MUNICIPAL CORPORATION HIGHT 12 feet
ADDRESS FARIDABAD FLOOR FIRST PEOPLE 50 nos
SPACE BUFFET DINING AND LIFT LOBB FLOOR AREAS 3120 sft LIGHT 2 w/sft
3
SOLAR GAIN THRU GLASS SUMM/MONSON DESIGN CONDITION
ITEM AREA SUN GAIN FACTOR BTU/H SUMMER
North 0 sft x 14 btu x 0.56 = 0.00 btu dB FB wB FB
East 0 sft x 12 btu x 0.56 = 0.00 btu Outdoor 110 75
South 0 sft x 90 btu x 0.56 = 0.00 btu Indoor 74 60
West 0 sft x 110 btu x 0.56 = 0.00 btu Diffrenc 36
North/east 0 sft x 12 btu x 0.56 = 0.00 btu
North/west 0 sft x 123 btu x 0.56 = 0.00 btu DESIGN CONDITION
South/east 0 sft x 12 btu x 0.56 = 0.00 btu MONSOON
South/west 0 sft x 100 btu x 0.56 = 0.00 btu dB FB wB FB
Horizontal 0 sft x 123 btu x 1.00 = 0.00 btu Outdoor 95 83
SOLAR GAIN THRU WALL AND ROOF SUMM/MONSON Indoor 74 60
ITEM AREA SUN GAIN FACTOR BTU/H Diffrenc 21
North 0 sft x 24 btu x 0.38 = 0.00 btu
East 1968 sft x 38 btu x 0.38 = 28417.92 btu RESULT
South 0 sft x 36 btu x 0.38 = 0.00 btu
West 0 sft x 32 btu x 0.38 = 0.00 btu
North/east 0 sft x 30 btu x 0.37 = 0.00 btu AIR CONDITIONING LOAD
North/west 0 sft x 26 btu x 0.38 = 0.00 btu DEHUMIDIFIED AIR (cfm).
South/east 0 sft x 38 btu x 0.38 = 0.00 btu SQ.FT AREA PER TR
South/west 0 sft x 34 btu x 0.38 = 0.00 btu CFM PER SQ.FT AREA
Roof sun 0 sft x 53 btu x 0.40 = 0.00 btu
Roof insu 0 sft x 53 btu x 0.12 = 0.00 btu
TRANSMISSION GAIN (except roof and wall)
ITEM AREA TEM/DIFF (S) TEM/DIFF (M) FACTOR
All glass 0 sft x 36 (F) x 21 (F) x 1.13 =
Partion 2952 sft x 31 (F) x 16 (F) x 0.40 =
Ceiling 3120 sft x 31 (F) x 16 (F) x 0.40 =
Floor 0 sft x 31 (F) x 16 (F) x 0.40 =
INFILTERATION AND OUT SIDE AIR
ITEM AIR QTY TEM/DIFF(S) TEM/DIFF(M) FACTOR BF
Infilteration 50 cfm x 36 (F) x 21 (F) x 1.08 x =
Out side air 500 cfm x 36 (F) x 21 (F) x 1.08 x 0.10 =
INTERNAL HEAT GAIN
ITEM UNIT/QTY HEAT GAIN FACTOR
People 50 nos x 280 btu x =
Light(f) 6240.8 w x 3.413 btu x 1.25 =
Light(in) 0 w x 3.413 btu x 1.25 =
Power 0 hp x 2545 btu x 1.0 eff =
Appliances 0 kw x 3413 btu x =
Kitchen(eq) 0 btu x 0.95 eff =
ROOM SENSIBLE HEAT SUB TOTAL
supply air duct heat gain + supply air duct
lickage loss + fan hp + safety factor = 10% =
EFFECTIVE ROOM SENSIBLE HEAT =
LATENT HEAT GAIN
ITEM UNIT/QTY HEAT GAIN MOIS.DIFF(S) MOIS.DIFF (M) FACTOR
Infilteration 50 cfm x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
Out side air 250 cfm x 0.1 BF x 10.6 gr/lb x 82.0 gr/lb x 0.68 =
People 50 nos x 270 btu =
Steam 0 lb/h x 1080 btu =
Othersourc 0 kw x 5 =
Kitchen(eq) 0 btu x 0.05 % =
ROOM LATENT HEAT SUB TOTAL
supply air duct lickage loss + safety factor = 10%
EFFECTIVE ROOM LATENT HEAT
OUT SIDE AIR HEAT GAIN
ITEM AIR/QTY DIFFER (S) DIFFER (M) BF (1-0.1) FACTOR
Sensible 250 cfm x 36 (F) 21 (F) x 0.85 x 1.08 =
Latent 250 cfm x 10.6 g/lb 82.0 g/lb x 0.85 x 0.68 =
return duct heat gain+return duct leakage
loss+pump hp+piping loss = 5%
TOTAL OUT SIDE AIR HEAT GAIN
GRAND TOTALHEAT
(total sensible+total latent+total outside air heat)
SENSIBLE HEAT FACTOR
(room sensible heat / room total heat)
SELECTED A.D.P.
(selected from chart)
DEHUMIDIFIED RISE
(inside temperature - selected ADP) x 0.9
AIR CONDITIONING LOAD
(grand total heat / 12000)
DEHUMIFIED AIR QUANTITIES CFM=
(room sensible heat / dehumidified rise) /1.08
DATE 7-Feb-18

TIME 16:00

RH% Gr/lb
20 75.0
55 64.4
10.6

RH% Gr/lb
60 153.0
55 71.0
82.0

SUMMER MONSOON

14.6 11.7
8073 6001 23.07
214.3 266.6
2.6 1.9

SUMMER MONSOON
BTU BTU
0.0 0.0
36604.8 18892.8
38693.0 19970.6
0.0 0.0
SUMMER MONSOON
BTU BTU
1944.0 1134.0
1944.0 1134.0
SUMMER MONSOON
BTU BTU
14000.0 14000.0
26624.8 26624.8
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
148228.5 110174.1

14822.8 11017.4
163051.3 121191.5
SUMMER MONSOON
BTU BTU
360.4 2788.0
180.2 1394.0
13500.0 13500.0
0.0 0.0
0.0 0.0
0.0 0.0
14040.6 17682.0
1404.1 1768.2
15444.7 19450.2
SUMMER MONSOON
BTU BTU
8262.0 4819.5
1531.7 11849.0

489.7 833.4
10283 17502

174739 140462

0.91 0.86

52 52

18.7 18.7

14.6 11.7

8073 6001