Maintenance Free
Corrosion Free & maintains low resistance for a very long period, having minimal
fluctuations
Highly reliable for safety to human life
More surface area of conduction
Adequate galvanization and highly conductive
Designed to handle high peak current & maximum fault current dissipation instantly
Controls Radio Frequency Emissions & Electromagnetic interferences
Provides stable reference potentials for instrument accuracy
Discharges short circuit currents
Fit and forget solutions
The construction details of the Chemical Earthing Electrode are as bellow: There is a solid
conductor (highly galvanized), enclosed inside another highly galvanized Chemical Earthing
Electrode. The space in between is filled with anticorrosive & conductive compound. The electrode
composite system which is firmly packed / welded & sealed with sealant & is ready to use. The
basic purpose of the mineral filling compound is to resistance and to create a low resistance zone
surrounding the electrode uniform environment so that the electrode output is constant.
Use of salt & charcoal is eliminated in the method of effective earthling & instead a
specially developed, natural eco friendly material with improved properties is used. This is non
corrosive, has capacity to absorb & retain moisture from the surrounding. Being non soluble in
water, it stays at the place and in not washed out by the rain water/underground water. This mineral
filling compound is highly conductive.
“Maintains low resistance value for a long period having the bare minimum fluctuations.
And wide range of products & sizes to suit any and every earthing requirement”.
COMPANY PROFILE
Siri Earthing and
Lightning Protections
In all cases, the backfill medium should be conductive but non-corrrosive in nature, be
of a relatively small particle
article size and should, help to retain moisture for a considerable
period of time. More often than not the previous excavated soil is suitable
able as a backfill, but
should be sieved to remove any large stones and placed around the electrode,
elect taking care
to ensure that it is well compacted. The soil should maintain a pH value between 6.0
(acidic) to 10.0 (alkaline). Normal stiff clay is not a suitable backfill
ackfill material as, if
heavily compacted; it may become almost impervious to water and could remain
relatively dry. It may also form large lumps, which do not consolidate arround the electrode
avoiding to make good contact
act with soil to the electrode itself
BFC, (back fill compound) is a specially developed compound, which is capable of
absorbing and retaining the moistu
moisture for a long time, it reduces the soil resistivity, it helps
in faster dissipation of fault cur
current, least fluctuation of Ohmic value and it eliminates the
use of Salt, Charcoal etc. around
ound the Earthing Electrode. It has low solubility,
solubilit hence is not
easily washed away, and has a low resistivity (approximately 5-10 Ohm-meters in a
saturated solution). It is virtually
tually neutral, having a pH value of between 6.2 and 6.9. Should
not generally cause environmen
onmental difficulties in use. It assists in mainttaining a relatively
low resistivity over a long period of time, in areas where salts in the vicinity are dissolved
away by water movements (rainfall etc.). However, the fact that the material is not
easily dissolved will moderate the benefits achieved, since it will not permeate far into
the ground. This means that the beneficial effect will be localized for say an area
excavated around a buried electrode. This in turn means that the reduction in the
resistance value of the elect
electrode will not be dramatic but will be reasonably
easonably sustainable
Materials, which should not be used as backfill Compound, include sand, co ke-
breeze,
eeze, cinders, and power s
station ash, as many of them are
e acidic and corrosive
cor in
nature.
IS:
3043-
1987 Description from Indian standards Our comments
At above about 20 percent moisture the resistivity is
very little affected while below 20 percent the
resistivity increase very abru
abruptly with decrease in Our back fill compound
moisture content. A difference of little percent moisture will is highly hygroscopic in
therefore, make a very marked difference in the nature; it has high capacity
effectiveness of the earth connection if the moisture to absorb moisture of its
content falls below 20 percent. The normal moisture volume. Due to the water
content of soils ranges from 10 percent in dry absorption the moisture
seasons to 35 percent in wet seasons and an percentage is adequately
approximate average may be perhaps 16 to 18 maintained during dry
8.6 percent. seasons.
8.8.1 Approximately 90 present of the resistance between a Our back fill compounds filled
driven rod and earth lies within a radius of about two in vicinity to earthing electrode
meters from the rod. This should be kept in mind is highly conducting in
when applying the agents for artificial treatment of nature and have very low
soil. resistivity that helps to obtain
lower earth resistance.
Where the resistance of a single plate is higher than the
required value, two or more plates may be used in parallel
and the total resistance is than inversely proportional to
the number of employed, provided that each plate is
installed outside the resistance area of any other. This
normally requires a separation of about 10 m but for sizes For obtaining required value
of plate generally employed, a separation of 2 m is earth pit are connected in
sufficient to ensure that the total resistance will not exceed parallelconsidering the local
the value obtained from the above formula by more than soil condition and practical
9.1.1 20 percent. difficulties of installation.
Our system totally
eliminates the use of
The use of coke breeze as an infill is not charcoal and salt.we use
recommended as it may result in corrosion not only of specially developed BACK FILL
the electrode itself but also of cable sheaths, etc, to which COMPOUND for preventing
9.2.1 it may be bonded. corrosion
FS-33, FS-48, FS-63, FS-78
For conventional sizes, the resistance is approximately Models are tested
inversely proportional to the linear dimensions, not the for 7.5kA, 30 kA, 50 kA, &
surface area that is a 0.9 m x0.9 m plate would have a 75 kA respectively for 1 sec
resistance approximately 25 percent higher than a 1.2 x for short current in
1.2 m plate. The current loading capacity of a 1.2 x 1.2 m Electrical Research &
plate is of the order of 1600 A for 2 s and 1300 A for 3 Development
9.2.1 s. Association, (ERDA), Baroda
Pipes may be of cast iron of not less than 100 mm
diameter, 2.5 to 3 m long and 13 mm thick. Such pipes
cannot be driven satisfactory and may, therefore, be more
expensive to install than plates for the same effective area. We use 33mm to 77mm dia
Alternatively, mild steel water-pipes of 38 to 50 mm pipe of medium or heavy
9.2.1 diameter are employed. grade.
Care should be taken to select a material that is resistant
to corrosion in the type of soil in which it will be used. Due to use of heavy
Tests in a wide variety of soils have shown that copper, copper/galvanised plating as
whether tinned or not, is entirely satisfactory (subject to per UL standards and specially
the precautions given in this sub clause), the average loss formulated BACK FILL
in weight of specimens 150 mm x 25 mm x 3 mm buried COMPOUND the life of our
for 12 years in no case exceed 0.2 percent per year. system FLAT PATTI IN PIPE
Corresponding average losses for unprotected ferrous TECHNOLOGY exceed to more
specimens (For example, cast iron, wrought iron or mild than 15 years in normal soil
9.3 steel) used in the tests were as high as 2.2 percent per conditions.
year. Considerable and apparently permanent protection
appears to be given to mild steel by galvanizing, the test
showing galvanized mild steel to be little inferior to copper
with an average loss not greater than 0.5 percent per year.
Item APRSD TPT TML
Description of item Unit
No. No. Rate Rate
Chemical Earthing (40mm Dia GI Pipe 2 Mtrs)
9.1.10 Providing of Independent Chemical Earthing after -- Each 5721.78 5856.00
excavating an earth pit of size1.5 m X 0.9 m X 2.05
m(Top 1.50 m X 0.90 m X 0.9m & bottom 1.20 m X 0.90
m X 1.15 m) with the following specification:-
(a) The Earth Electrodes, 40mm dia, wall thickness
3.25 mm, terminal Size 25x8 mm, terminal hole dia 12
mm, 2 meter long, galvanized, including 1 bag (25Kg to
a bag) of Earth Life Compound, as per IS 3043, Base
Metal: IS marked branded mild steel pipes.
127
Item APRSD TPT TML
Description of item Unit
No. No. Rate Rate
(c) The excavated gap shall be back filled with
excavated earth, and shall be properly consolidated
with water.
(d) The top 0.25 m of Earth pipe shall be exposed into
inspection chamber of Hume pipe . The all around
inspection chamber shall be providied with 18" dia
hume pipe. Earth connections shall be given to the
Earth Elecrods with bolts, nuts & washers.
128
Item APRSD TPT TML
Description of item Unit
No. No. Rate Rate
Chemical Earthing (40mm Dia Copper 3.0 Mtrs)
129
Item APRSD TPT TML
Description of item Unit
No. No. Rate Rate
9.1.14 Providing of Independent Chemical Earthing after -- Each 7643.78 7797.22
excavating an earth pit of size1.5 m X 0.9 m X 2.05
m(Top 1.50 m X 0.90 m X 0.9m & bottom 1.20 m X 0.90
m X 1.15 m) with the following specification:-
(a) Earth Electrodes Twin Pipe With Rod Technology,
outer pipe dia 48.2 mm dia (wall thickness: 3.25 mm),
inner pipe dia: 26mm, (wall thickness: 2.6 mm) Rod 12
mm dia, terminal: 32 x 10mm, hot dip galvanized (80 to
100 microns), inner space filled with high conductive
material length : 2 meter, along with 1 bag (25Kg) of
Earth Life Compound. (As per IS 3043:1987), BASE
METAL;IS MARKED BRANDED MILD STEEL PIPE.
130
Item APRSD TPT TML
Description of item Unit
No. No. Rate Rate
b) The Earth Electrode shall be inserted into the ground
for 2.75 Mtrs. Below the inspection chamber bottom
300mm all around this Earth Electrode shall be covered
with 50 Kgs. Of Earth Life Compound.
131