GENERAL NOTES: SPECIFICATIONS:


ALL ELECTRONIC WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH 1) AREA: approximately 323 sq. m.
THE NATIONAL BUILDING CODE, PROVISIONS OF THE LATEST APPROVED 2) CEILING HEIGHT: 4.2672 m.
PHILIPPINE ELECTRONICS CODE, THE LAWS AND ORDINANCES OF THE 3) SPEAKERS SPACING: 6 m or 8 m
LOCAL CODE ENFORCING AUTHORITIES AND REQUIREMENTS OF THE CONTROL ROOM
MIXER/AMPLIFIER 4) ZONES:
LOCAL ELECTRIC, TELEPHONE COMPANY AND 4)1) ZONE 1: FUNCTION HALL (1)
BUILDING ADMINISTRATION REQUIREMENTS. 4)2) ZONE 2: OFFICE ROOM (1)
1. CONTRACTOR SHALL SECURE ALL WIRING PERMIT AND ALL FEES 4)3) ZONE 3: FUNCTION HALL (2)
REQUIRED FOR THE WORKS AND FURNISH THE OWNER THE CERTIFICATE 4)4) ZONE 4: OFFICE ROOM (2)
FUNCTION HALL
OF FINAL ELECTRICAL INSPECTION, 4)5) ZONE 5: KITCHEN
2. CONTRACTOR SHALL CONDUCT EARTH GROUND TEST, WIRE 4)6) ZONE 6: CORRIDOR AND KITCHEN
INSULATION AND LOAD TEST UPON COMPLETION OF WORKS, 4)7) ZONE 7: FUNCTION HALL (3)
3. INCASE OF DISCREPANCY BETWEEN PLANS AND SITE CONDITION,
SPECIFICATIONS & REVISIONS CHANGES, THE CONTRACTOR SHOULD
IMMEDIATELY VERIFY & CONSULT WITH THE ELECTRONICS ENGINEER OF
THE PNP ENGINEERING SERVICE (PNPES),

PRODUCED BY AN AUTODESK STUDENT VERSION


4. ALL LOCATION & MOUNTING HEIGHT ARE SUBJECT TO APPROVAL
PRODUCED BY AN AUTODESK STUDENT VERSION

OF ELECTRICAL ENGINEER OF PNPES,


5. CONTRACTOR SHALL BE RESPONSIBLE IN THE PREPARATION OF
AS-BUILT PLANS DULY SIGNED AND SEALED BY PROFESSIONAL MALE'S FEMALE'S
ELECTRONICS ENGINEER, AND ELECTRONIC AUTOCAD FILES, WASHROOM WASHROOM
6. FINAL LIGHTING FIXTURES AND WIRING DEVICES SHALL BE ELEMENT DESCRIPTION
APPROVED BY PNPES, REPRESENTATIVE ENGINEER,
OFFICE ROOM
7. CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARATION OF SHOP PULLBOX
OR CONSTRUCTION DRAWING REQUIRED BY
OWNER/ARCHITECT/ENGINEER, THIS INCLUDES DEVICES AND FIXTURES AMPLIFIER(2): XH200 POWER
ELEVATION, AMPLIFIER
FIRST FLOOR SCALE: 0.007:1
8. CONTRACTOR SHALL VISIT SITE CONDITION AND INCLUDE ALL
COST NECESSARY TO COMPLETE THE SYSTEM AT NO COST TO OWNER, MIXER(2): MG06 MIXING
CONSOLE
INCLUDING COST OF CORING SERVICE AND EXPENSES FOR THE BILL OF QUANTITY BILL OF QUANTITY
RESTORATION OF ANY DAMAGE AFFECTED CIVIL ARCHITECTURAL
FINISHES OR RELOCATION OF EXISTING FACILITIES ON BUILDING, CEILING SPEAKER: PC-580RU
PC-580RU, 5W 20 6m CONDUITS 30 5W
9. CONTRACTOR SHALL LOCATE ALL SPLICING BOXES TO ACCESSIBLE
PLACE OR WITH ACCESS PANELS, 1
SC-630, 30W MOUNTING SCREWS 84 CONDUIT (1)
10. NOMINATED CONTRACTOR TO VERIFY ALL EQUIPMENTS TO BE CONDUIT (2)
INSTALLED OR PLACE WITHIN THE BUILDING, AND MAKE AN ADJUSTMENT
Q-SS9012PS 1 PULLBOX 3
WITH THE PNPES ENGINEER ARCHITECT CONSENT, LOUDSPEAKERS: BS-1030
11. THIS DRAWINGS ARE DIAGRAMATIC LAYOUT ONLY, ANY MATERIALS (facing right and left)
AND FITTINGS NOT SHOWN ON THIS PLANS BUT NEEDED TO COMPLETE MIXER/AMPLIFIER, 240W 1
THE SYSTEM AND OPERATION SHALL BE INCLUDED WITH THE HORN SPEAKER: SC-630
CONTRACTOR'S SCOPE OF Q-RM9012PS 1 30W
WORKS.
12. ALL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF BS-1030, 30W 4 SPEAKER SELECTOR:
LICENSE DULY REGISTERED ELECTRONICS ENGINEER OR REGISTERED Q-SS9012PS
MASTER ELECTRONICS ENGINEER. TRANSFORMER, 70.7V, 5W 20
13. ADDITIONAL NOTES: MIROPHONE: Q-RM9012PS
· USE OF MICA SHALL BE LIMITED TO 150mm MAXIMUM
· USE OF FLEXIBLE METALLIC CONDUTIT SHALL BE MG06 MIXING CONSOLE 1
LIMITED TO 1m MAXIMUM MIXER/AMPLIFIER 240W
· PROVIDE PROPER CONDUIT SUPPORT, G.I. WIRES AS XH200 POWER AMPLIFIER 1
SUPPORT SHALL NOT BE ALLOWED LEGEND
· PROVIDE DOUBLE COAT OF RUST PROTECTIVE PAINT
(RED OXIDE PRIMER) ON HANGERS AND SUPPORTS.
SCHOOL DATE GIVEN DATE DUE DRAFTED BY COURSE & YEAR PAGE

ST. LOUIS UNIVERSITY ENGINEERING AND ARCHITECTURE 03262019 03262019 FRANCISCO, SEAN TRISTAN D. BSECE 4 1/2
PLATE TITLE RATING SUBJECT INSTRUCTOR SCHEDULE ROOM NO.

PUBLIC ADDRESS SYSTEM - LAYOUT AND PLAN ECE 428T1L


PRODUCED BY AN AUTODESK STUDENT VERSION ENGR. PAUL ANG 1:30-4:30 T H408