Você está na página 1de 5

Preventing ammonium salt fouling

and corrosion
Best practices and opportunities to reduce the risk of salt
deposition and damage

BERTHOLD OTZISK, FAUSTO MAGRI, JELLE ACHTEN and SANDER HALSBERGHE


Kurita Europe

S
alt deposits and corrosion to remove water soluble salts. ponents with filming amine
can lead to damage or high For this purpose, water is fed properties that can stabilise
energy losses when crude into the top reflux, or the over- emulsions. In the event that not
oils are processed. Usually, head temperature is lowered all of the bound salts are solu-
these salts are ammonium chlo- until enough water can con- bilised in free water later, they
ride (NH4Cl) or ammonium dense to the top trays. This may remain in the hydrocarbon
bisulphide (NH4HS). This arti- usually takes several hours or phase of the product steam, to
cle describes a new approach even days. The feed rate must be transported to downstream
to prevent chloride corrosion be significantly reduced by processes.
or further deposition of ammo- 20-30% during this time. The
nium salts in order to avoid or produced naphtha, sometimes ACF technology
minimise corrosion and fouling also the light cycle oil (LCO), Kurita’s patented ACF tech-
potential. goes off-specification and has to nology pursues a completely
The use of a powerful water be reprocessed with increased different approach. Liquid for-
washing system is certainly a costs. In addition to the lower mulations of a very strong
good step in the right direc- throughput, these costs may be organic base called ACF are
tion to wash out as many salts particularly high. used. These are water sol-
as possible. Ammonium salts The addition of an oil solu- uble and do not react with
are generally readily soluble in ble salt dispersant additive can hydrocarbons. The organic
water, but can often not be com- help to prevent salt deposition base ACF has a very low pKb
pletely removed in the pres- and keep the salts transporta- value close to zero, which is
ence of hydrocarbons. Process ble, but that practice may also an indicator of a very strong
units suffering ammonium salt lead to several disadvantages. base. It reacts preferentially
fouling or corrosion are crude They work by chemically bind- with strong acids such as
distillation units, FCC units, ing to the salt deposits, where hydrochloric acid (HCl) or its
hydrocrackers, hydrotreaters the lipophilic functional group corresponding ammonium salts
and reformer units. keeps microcrystalline salts in (NH4Cl). The reaction prod-
Higher amounts of chlo- the hydrocarbon phase until uct is ACF-Cl, which is a liq-
rides in residue feedstocks or enough free water is present uid salt with a neutral pH of 7.
low main fractionator top tem- so that the salts can be solubi- ACF salts have very high mois-
peratures to produce low sul- lised later. The dispersed salts ture absorption characteristics
phur gasoline are two reasons are carried out of the system (highly hygroscopic) and can
for salt fouling in FCC units. with the hydrocarbon prod- be removed easily from the sys-
Sometimes a tower washing uct flow. Such salt dispersants tem with free water. One more
programme can be performed are often surface active com- benefit is that ACF salts have a

www.eptq.com PTQ Q4 2017 1


phate ((NH4)2SO4). In all cases,
ACF displaces the weaker base
HCI
ammonia by forming a liq-
uid salt. In the absence of free
water, the salts are transported
NH3 ACF at temperatures below 180°C
NH3 together with the hydrocar-
Metal surface bon stream. When they come
into contact with water, the
ACF ACF ACF HCI salts can be removed with the
aqueous phase. This chemical
Metal surface
programme can be applied con-
Liquid ACF-Cl
NH3 HCI NH3 HCI Excellent fluidity tinuously to prevent fouling
Low corrosion potential and corrosion or it is used at
Metal surface Metal surface higher dosing rates to remove
NH4 Cl deposit already formed salt deposits.
High corrosion potential

Case study 1: FCC main


Figure 1 Removal of ammonium salt deposition and corrosion prevention fractionator
Since it is common practice for
very low corrosivity. This is a tions, such as hydrotreaters the top temperature in FCC
significant difference compared or hydrocrackers. Only after main fractionator columns to
with conventional neutralising the conversion into ACF-Cl be lowered to produce more
amine salt reactions where the can weaker acids like hydro- low sulphur gasoline, negative
formed neutralising amines are gen sulphide (H2S) or its salts impacts are often observed. In
almost always very corrosive react with the ACF by forming most cases, salt fouling is the
and require higher amounts of the corresponding ACF reac- reason and this can also lead to
wash water for removal. tion product. The reaction with corrosion if the salts are present
The favoured reaction of ACF is shown schematically on the metal surface as a sticky,
ACF with HCl is a significant in Figure 1, which is also valid highly concentrated and viscous
advantage in process units with for other ammonium salts such solution.
naturally high H2S concentra- as NH4HS or ammonium sul- Negative impacts are:
• Increased pressure drop
• Plugged trays and product
draws
Expected
Wet gas
condensation • Increased corrosion rates
fouled
MC • Flooding of the main fraction-
section
reflux ator top section
Wet gas
condensation • Efficiency losses between gas-
ACF
SWS oline and LCO separation
• Wet gas compressor efficiency
ACF losses.
During a field trial, the
Naphtha
circulation online cleaning performance of
ACF was tested in a Western
Naphtha European refinery. Chemical
stripper injection into the main fraction-
ator overhead reflux is common
to dissolve the deposited salts
from the top trays. According
to the refiner’s experience,
Figure 2 FCC main fractionator top section naphtha circulation was also

2 PTQ Q4 2017 www.eptq.com


affected where salt deposits on
the lower trays were assumed
Usual operation ACF
to be present. Therefore ACF
was additionally injected into Heat transfer coefficient
the naphtha circulation in order Feed rate
to remove salt deposits from Differential pressure
the heat exchangers and from
the lower trays of the fraction-
ation column. Figure 2 shows
the two dosing points where
ACF was continuously injected
during the online cleaning. The 1st 2nd 3rd 4th 5th 6th
reaction with the chloride salts day day day day day day
is a stoichiometric balance and,
according to the expected high Figure 3 FCC main fractionator online cleaning results
amounts of salt deposits, a few
litres per hour of ACF were tive action, ACF was injected extended with an additional
dosed at both locations to mobi- between the second and third function of film forming prop-
lise high amounts of salts. heat exchangers after the reac- erties. The metal surfaces are
After the dosage had been tor with the aim of stopping thus directly protected from
started, first successes were corrosion in the third feed/ acid attack and, because of the
observed within less than 30 effluent exchanger and airline smooth and clean metal sur-
minutes. Figure 3 shows some coolers. Since the treatment face, any salt deposition is pre-
recorded results from the con- was started, large amounts of vented. The result is longer time
trol room with basic data before chlorides were collected in the in operation with clear energy
the treatment and significant water boot of the accumulator savings. The duty calculations
changes during the online from where they could be fre- and hot approach tempera-
cleaning. The differential pres- quently removed. Despite the ture (HAT), where the thermo-
sure of the main fractionator higher chloride concentration in dynamics of heat recovery can
column as a direct key indica- the accumulator, the corrosion be determined by superimpos-
tor for fouling, the FCC feed potential was significantly low- ing the curves showing heat
rate, and the heat transfer coef- ered since ACF salts have a very demand from the reactor feed
ficient of the naphtha circula- low corrosion potential. Figure 4 and heat release from the reac-
tion are displayed graphically shows the location where ACF tor effluent, are good key per-
in Figure 3. The rapid increase is continuously dosed with a formance indicators.
in the heat transfer coefficient low ppm injection rate into the Figure 5 shows the heat
and the main fractionator dif- effluent product stream. exchanger duty trends and
ferential pressure drop impres- After some months of opera- calculated energy savings in
sively demonstrate that higher tion, when no damage occurred, comparison to the previous
amounts of salt deposits were the ACF programme was operational mode over a period
dissolved and mobilised in a of two years since the applica-
short period of time. To
tion was started. The success of
reactor Feed the treatment is demonstrated
Case study 2: hydrotreater From by the fact that no further cor-
feed/effluent exchangers reactor
rosion damage has occurred so
In a naphtha hydrotreater ACF far, as well as by an improved
operating with several feed/ energy balance of the feed/
effluent heat exchangers, corro- effluent exchangers.
sion problems occurred in the
space of a few years, mainly Case study 3: debutaniser
due to the formation of ammo- Figure 4 Naphtha hydrotreater cleaning
nium salt deposits. As a correc- feed/effluent exchangers Severe flooding problems were

www.eptq.com PTQ Q4 2017 3


per day from the overhead
8.0 accumulator to report the sta-
ACF treatment
7.5 7.29 tus of the online cleaning. The
Blank run
7.0 pH, conductivity, chloride
and ammonium concentra-
Duty, MMkcal/h

6.5
6.38 tions and total nitrogen con-
6.0
tent were analysed. During the
5.5
5.47 5.47 online cleaning, the pH value
5.0 stayed relatively stable at the
4.5 same level of approximately
4.0
8.5 because of the presence of
NH3. Directly after the start of
3.5 3.65 the injection, the conductivity
3.0 immediately leapt up as a func-
0 365 730
tion of dissolved chloride salts.
Days of operation
A slight increase in the pH at
the end of the online cleaning
Figure 5 Feed/effluent exchanger energy savings was a direct indicator that injec-
tion could be stopped. This was
observed in the debutaniser not an option this time because also confirmed by the fact that
column of a naphtha hydro- it would involve a shutdown of the debutaniser was again run-
treater unit. The results of a the reformer and isomerisation ning under normal operating
root cause analysis pointed out unit. Mechanical cleaning of the conditions.
that mainly ammonium salts debutaniser column would also
and corrosion products such as result in unwanted shutdowns Conclusions
iron sulphides were the orig- of the reformer and isomerisa- Each oil refinery is aware of the
inators. The debutaniser col- tion unit for three to five days. high risks of ammonium salt
umn is equipped with valve For these reasons, online clean- deposits, which can quickly
trays, where it was expected ing with ACF was selected to lead to corrosion damage to
that many of the top trays were put the debutaniser back on plant equipment and represent
heavily fouled and blocked. track. a ubiquitous risk for the con-
This resulted in a high differen- High amounts of fouling tinuous operation of a process
tial pressure increase, excessive deposits were expected in the unit. Water washing is a first
liquid return to the bottom sec- top section of the debutaniser step in the right direction, but
tion, and a significantly reduced column. To reach that area for sometimes with only mediocre
throughput. Clear indicators direct contact of ACF with the success. Therefore there is great
for flooding were the high lev- fouled salts, there was only one interest in avoiding corrosion
els of C5 hydrocarbons in the C4 possible location for the injec- attack and in finding powerful
section, due to a decline in sep- tion, which was the suction side opportunities for the removal or
aration (off-spec production), of the overhead reflux pump. prevention of fouling materials
and the high Reid vapour pres- While about 80% of the liquid such as ammonium salts.
sure of the isomerate. The debu- phase returns back to the debu- Kurita´s ACF technology is
taniser bottom reboilers had taniser top section, about 20% is a completely new approach,
to be stopped to keep the unit passed via a reflux pump to the where corrosive HCl or ammo-
running. LPG unit. nium salts are directly chemi-
Previously, water wash- Taking this into account, the cally binded. The formed ACF
ing had been carried out with ACF dosage was started and salts have a low corrosivity and
only mediocre success, where showed immediate improve- can be removed easily with free
not all fouling deposits were ments. Over a period of six water. This approach is com-
removed and the naphtha days, ACF was injected con- pletely different to technologies
hydrotreater had to be stopped tinuously, where water sam- where additives with dispers-
for one to two days. This was ples were taken several times ing properties are used that

4 PTQ Q4 2017 www.eptq.com


simply shift the salts to another References Fausto Magri is Key Account Manager for
location. In a refinery, there are 1 Melin M, Baillie C, McElhiney G, Salt refinery and petrochemical applications
many opportunities to use ACF deposition in FCC gas concentration with Kurita Europe, Italy.
during online cleaning or for units, PTQ Q4, 2009. Email: fausto.magri@kurita.eu
continuous corrosion protection 2 W A Al-Naim, Ammonium bisulphide
corrosion in hydrocrackers, PTQ Winter Jelle Achten is Area Manager for Benelux
and fouling removal treatment.
1999/2000. with Kurita Europe, Germany.
For the operating refinery, this Email: jelle.achten@kurita.eu
represents significant added Berthold Otzisk is Senior Product
value since production losses Manager for refinery and petrochemical Sander Halsberghe is Project Engineer
caused by fouling or corrosion applications with Kurita Europe, Germany. for Benelux with Kurita Europe, Germany.
can be reduced to a minimum. Email: berthold.otzisk@kurita.eu Email: sander.halsberghe@kurita.eu

www.eptq.com PTQ Q4 2017 5

Você também pode gostar