Escolar Documentos
Profissional Documentos
Cultura Documentos
a r t i c l e i n f o a b s t r a c t
Article history: Radiant cooling system is a promising technique, which is suitable for independent control processes of
Received 31 May 2013 temperature and humidity. The two main benefits of radiant cooling systems include the potential to
Received in revised form save energy and improvement of indoor thermal comfort. However, both the poor heat transfer per-
22 September 2013
formance and condensation below dew point temperature restrict the widespread utilization in the
Accepted 25 September 2013
residential buildings especially in humid environment. This research was focused on comprehending
detailed performance of the radiant cooling panel when it used as an air conditioning system. Three
Keywords:
radiant cooling panels with the area of 0.16 m2 were prepared for investigation and a constant tem-
Radiant cooling
Moisture condensation
perature and humidity environment chamber employed to simulate the different indoor thermal en-
Control strategy vironments. The heat transfer performance and moisture condensation phenomenon of the radiant
Thermal comfort cooling panels were investigated. The results showed that the flow state of chilled water had the
biggest influence on the heat transfer performance of the radiant cooling panels. The temperature
difference between chilled water and the ambient was also observed to significantly affect the per-
formance. Condensation of moisture on the radiant cooling panels was noted to increase the heat
transfer quantity, but posed a challenge in using of the radiant cooling panel. Taking the performance of
heat transfer and moisture condensation into consideration, the gypsum radiant cooling panel showed
the best performance as compared to the metal radiant cooling panel and pure tube panel. The radiant
cooling panels can work more efficiently especially when proper control strategies are employed to
avoid condensation.
Ó 2013 Elsevier Ltd. All rights reserved.
0360-1323/$ e see front matter Ó 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.buildenv.2013.09.016
16 Y.L. Yin et al. / Building and Environment 71 (2014) 15e23
level of the ceiling cooling system, the floor cooling system and the
wall cooling system, which were the three usual radiant cooling
types. The results showed that the ceiling cooling provided better
comfort levels than radiant wall cooling. The results further showed
that the indoor thermal comfort level were even higher when the
radiant ceiling cooling and radiant floor cooling operated together
with radiant wall cooling system. Chiang et al. did an extensive
computational fluid dynamics (CFD) studies based on an experi-
mental radiant cooling ceiling system integrated with a mechanical
ventilation system in a typical office and validated typical condi-
tions by comparing the results to the field measured data in the
actual room. The results showed that installation of a radiant
cooling ceiling system integrated with a mechanical ventilation
system in hot and humid re could affect or complement each other.
Memon et al. [9] carried out both field assessment survey and
TRNSYS simulation to study the performance of the radiant cooling
system. The survey showed that more than 80% of occupants were
satisfied at an effective temperature of 32.5 C, which is 6.5 C
higher than the upper boundary of ASHRAE thermal comfort zone.
It was also estimated that up to 80% of energy can be saved when
Fig. 1. Schematic diagram of the radiant cooling system.
radiant cooling is used to substitute conventional air conditioning
systems to achieve indoor thermal comfort. Furthermore, radiant
cooling was considered to improve thermal comfort level owing to
a lower temperature gradient, inside the room, as compared with system was able to prevent the condensation of moisture on the
the traditional all-air system. Tian and Love [10] reported that the floor surface. Beside, responsiveness of the control system for in-
main advantage of radiant cooling was found to be reduced local door load changing was improved.
thermal discomfort with reduced vertical air temperature differ- Based on previous research done, heat transfer between radiant
ence as well as reduced draft rate. Catalina et al. [11] reported a full- panel and the ambient, as well as condensation on the radiant
scale experiment and a computational fluid dynamics (CFD) study panels have been reported as crucial aspects affecting radiant
of a radiant cooling ceiling system to analyze factors that influence cooling systems. This paper focuses on the parameters influencing
indoor thermal environment, i.e. air temperature, surface temper- heat transfer performance of the radiant cooling system. It also
ature and global temperature. The results obtained showed that analyses the moisture condensation on radiant cooling panel has
within the ankle/feet zone the air velocity could exceed 0.2 m/s, also been analyzed. In addition, analytical interactions between
with the remaining zones having air velocity of not more than heat transfer and condensation effects have been outlined. In this
0.1 m/s. Their research work showed the consistent results of high research, standard temperature and humidity of 26 C and 60% RH,
indoor thermal comfort level due to lower vertical temperature respectively were widely chosen due to the application condition of
gradient. the radiant cooling system.
Renewable and low-grade energy can be employed in radiant
cooling systems to improve the energy efficiency. Cooling could be
more efficient with independent temperature and humidity con-
trol [12]. However, for the radiant cooling system the main chal-
lenge is insufficient dehumidification capacity. For this reason, a
radiant cooling system always works together with a fresh air
system to meet the latent load and even part of sensible load
[4,13,14]. Sui and Zhang [15] reported that the energy consumption
of such a hybrid system decreased when the sensible load handled
by the radiant terminal increased. To prevent the condensation of
moisture on a radiant surface, the surface temperature of a radiant
panel needs to be higher than the indoor dew point temperature.
Based on this, the surface temperature of the radiant panel should
be considered as a significant factor for the stability of the system.
Ge et al. [16] indicated that the pre-dehumidification time is
critical to prevent condensation on the radiant cooling surface.
Three neural network models were established to predict the risk
of condensation and the optimal pre-dehumidification time in
radiant cooling system. The program gave the value of 30 min as
an optimal pre-dehumidification time for the simulated building
in Hong Kong. Shou and He [17] used the index of “dehumidifi-
cation capacity per unit mass of fresh air” to determine suitability
of a building to use radiant cooling system. It was shown that
when a fresh air system was employed to handle all latent cooling
loads, a radiant cooling system could be used in public buildings,
such as meeting rooms, markets and offices. Song et al. [18] pro-
posed a radiant floor cooling system assisted by dehumidifying
ventilation. The simulation results showed that the proposed Fig. 2. Experimental system.
Y.L. Yin et al. / Building and Environment 71 (2014) 15e23 17
Fig. 3. Photos of the three capillary radiant cooling models. (a) Pure mode, (b) metal model, (c) gypsum model.
18 Y.L. Yin et al. / Building and Environment 71 (2014) 15e23
Table 3
Main measurement sensors of the monitoring system.
It was observed that the heat transfer increased with the in-
crease in chilled water velocity ranging from 0.05 m/s to 0.25 m/s.
That was because that increase in chilled water velocity resulted in
the reduction of temperature difference between the inlet and
outlet of chilled water, leading to lower mean temperature of the
chilled water. After that, the results state that the heat transfer
increases significantly from 30 W/m2 to 62 W/m2 when the water
velocity increases from 0.25 m/s to 0.45 m/s. As the chilled water
velocity went beyond 0.45 m/s, the heat transfer rate started to
decrease. Suitable chilled water velocity was about 0.45 m/s for Fig. 5. Variation of heat transfer with the temperature of inlet chilled water.
certain capillary tube due to its best heat transfer performance.
Consequently, the heat transfer of 62 W/m2 could be obtained caused by the heat transfer between capillary tube and the
for selected radiant cooling panel at standard controlled space ambient, but also by the condensation of moisture.
temperature and relative humidity of 26 C and 60% RH, respec-
tively, and with inlet chilled water temperature and velocity of
3.2. Performance analysis of the moisture condensation
17 C and 0.45 m/s, respectively.
The temperature of inlet chilled water is another important
The water condensation phenomenon on the surface of the
parameter that significantly influences the condensation of mois-
radiant cooling panels was recorded by a macro camera (Canon
ture and heat transfer performance. If we still keep the inside
550D camera installed with an EF 100 mm f/2.8 USM focus). Fig. 6
condition of the constant temperature and humidity environment
shows the photos of condensation of moisture on the surface
chamber as 26 C and 60% RH respectively, and set the water ve-
capillary tube after 60 min operating. It was observed that with
locity at 0.45 m/s. The variation of the heat transfer performance
decrease in chilled water temperature from 16 C to 14 C, the
with the inlet chilled water temperature is as shown in Fig. 5.
amount of condensate on the capillary tube surface became more
It can be observed that, owing to the increment of temperature
and more. Besides, the sizes of condensate droplets were observed
difference between chilled water and the surrounding, the heat
to be larger with decrease in chilled water temperature. According
transfer gradually increases while the temperature of inlet chilled
to the measurement, the detailed information of condensation is
water decreases from 18 C to 16 C. The heat transfer significantly
shown in Table 4.
increases while the temperature of inlet chilled water decreases
The condensate droplets sizes on capillary tube surfaces were
from 16 C to 14 C. This was mainly due to the condensation of
measured an hour after starting the experiment. Quantized
moisture on the surface of the radiant cooling panel. That means
condensation analysis on the radiant cooling surfaces was done
part of the cooling was absorbed by the ambient moisture to
with the following assumptions:
generate water on the surface of radiant panel. For this reason, the
heat transfer between the radiant panel and the ambient is not only
(1) The shapes of the condensation of moistures were irregular.
Here, the diameters of the water droplet were calculated as:
Fig. 6. Photos of the condensation of moisture condition under different chilled water temperature when the thermal environment was 26 C, 60% RH.
Table 4 the temperature difference between the chilled water and the in-
Details of condensate droplets at different of chilled water inlet temperatures under door dew point was defined. It was observed that there was no
constant thermal environment.
condensation processes when the sub-cooled degree was lower
Temperature/ C 17 16 15 14 13 12 than 2.4 C. Little condensation could be observed when the sub-
Average diameter/mm 0 0 0.142 0.223 0.264 0.292 cooled degree was 3.2 C. In contrast, the pure model was
Average height/mm 0 0 0.122 0.203 0.234 0.265 capable of working without the risk of condensation at chilled
water inlet temperature that equals the indoor dew point tem-
perature. Fig. 9-b shows the variations in condensation under
temperature with its corresponding heat transfer performance. different sub-cooled degree when the ambient temperature and
This figure analyzed possible operation strategies that can be relative humidity were 27 C and 70% RH, respectively. It was
employed to cut down on latent heat used in condensation of the observed that water condensation occurred at a sub-cooled degree
capillary tube surface. of 2.5 C, which is 0.7 C lower than that of condition 1 (26 C, 60%
It can be seen that increase in inlet chilled water temperature RH). This showed that water condensation can easily occur under
only caused a small increment in the cooling used to improve the the environment with higher temperature and relative humidity.
indoor thermal environment. Much of the increased cooling ca- Table 5 shows the detailed information of condensation when
pacity shown in Fig. 5 resulted from the decrease in inlet chilled the ambient temperature and relative humidity were 27 C and 70%
water temperature from 16 C to 14 C which also caused genera- RH, respectively.
tion of water condensate. It can be seen that, comparing with the condensation under
Fig. 9-a shows the photos of water condensation at different standard test thermal condition, condensate droplets were not
sub-cooled degree. The sub-cooled degree (SCD) that represents easily formed, however, average dimensions of the water drops
Table 5
Detailed information of condensation at different chilled water inlet temperature
and ambient temperature and relative humidity of 27 C and 70%, respectively.
Average temperature/ C 19 18 17 16 15
Fig. 9. Photos of the water condensation phenomenon. (a) Photos of the water condensation phenomenon with different sub-cooled degree under the regular thermal environment
(26 C, 60%). (b) Photos of condensate droplets on capillary tubes surface at the sub-cooled degree of 1.8 C, 2.5 C, 3.4 C and 5.2 C, respectively under the challenge thermal
environment (27 C, 70%)
Y.L. Yin et al. / Building and Environment 71 (2014) 15e23 21
Table 6
Detailed information of water condensation process.
Time/min 10 20 30 40 50 60
of moisture was found on the gypsum panel, with the heat transfer
increasing by 36%.
For the purpose of finding the upper limit of sub-cooling degree,
experiments were done by gradually decreasing the chilled water
temperature from 17 C until the condensation of moisture
occurred. In this case, the inside temperature and humidity of the
Fig. 10. Variation of heat transfer performance with/without condensation of chamber were set to be 26 C and 60% RH, respectively. The chilled
moisture.
water velocity was set at 0.45 m/s. The photos showing water
condensation for the three radiant cooling panels at the end of
experiments are shown in Fig. 13. It was concluded that the upper
water condensate was found on the surface of pure panel while limit of sub-cooling degree for the pure tube, gypsum panel and
only a little on the surface of metal panel. For this reason, increase metal panel were 3.2 C, 6.5 C and 5.4 C, respectively. This means
in heat transfer of the metal panel was lower than that of the pure that there was no water condensation challenges on the gypsum
panel. Little condensation of moisture was found on the gypsum radiant panel on condition that the temperature of inlet chilled
panel because the moisture was immediately adsorbed by the water is higher than 11.5 C under condition of 26 C, 60% RH.
gypsum.
Fig. 12 shows the heat transfer performance of the three radiant 3.4. Strategies to prevent water condensation on the radiant cooling
cooling panels under different ambient conditions. The tempera- panel surface
tures of two conditions are 26 and 27 C, respectively with relative
humilities of 60% RH and 70% RH, respectively. In the experiments, The sub-cooled degree of the radiant cooling model under
the chilled water temperature and water velocity were kept at 17 C different thermal conditions can be used to control water
and 0.45 m/s, respectively. The results showed that heat transfer of condensation on the radiant panel surface. Fig. 14 shows the control
the pure model increased from 36 W/m2 to 92 W/m2 when the strategy to mitigate water condensation based on the sub-cooled
ambient condition changed from condition of 26 C, 60% RH to degree. The experiment employed a controller which can start/
condition of 27 C, 70% RH. The increase was mainly due to serious stop the pump by comparing the sub-cooled degree and the tem-
water condensation on the capillary tube surface. No condensation perature difference between chilled water inlet temperature and
Fig. 13. Photos of the condensation of moisture phenomenon on the surfaces of the three models.
indoor dew point temperature. For example, when the temperature temperature and humidity environment chamber was employed to
difference between the temperature of inlet chilled water and in- simulate an indoor thermal environment. A thermostat was used to
door dew point was reached to the sub-cooled degree, the generate chilled water at a constant temperature. According to the
controller will stop the pump. And turn it on again while the experimental results, the main conclusions were as follows:
temperature difference was lower than the sub-cooled degree.
To verify if the control strategy was feasible, the experimental (1) Heat transfer performance of the radiant panels is improved
tests were conducted on pure radiant cooling panel. The inner with the increase in the temperature difference between the
chamber thermal environment was set as 26 C and 70% RH. As chilled water and the surroundings as well as with the ve-
mentioned before, the sub-cooled degree was 3.2 C and the tem- locity of the chilled water.
perature for the controller shut down was set to be 15 C. Firstly, the (2) The gypsum radiant cooling panel displays the best perfor-
temperature of inlet chilled water was set as 16 C, which was mance of heat transfer as compared to the metal radiant
higher than the condensation temperature (14.4 C). And then the cooling panel and the pure tube panel. Besides, it has the best
temperature of inlet chilled water was reduced from 16 C to 13 C capability of avoiding water condensation under identical
to investigate the operation condition of the radiant cooling panel. conditions.
Finally, the temperature was increased to 17 C. Fig. 15 shows the (3) Water condensation on the radiant panels takes part of the
variations of the temperatures during the experiment. It can be cooling from the chilled water, which results in both air
seen that the pump was stopped when the temperature of the inlet pollution problem and insufficient cooling capacity.
chilled water reduce to the 15 C. It means that the controller would (4) When the ambient temperature and relative humidity are
shut down the pump while the chilled water inlet temperature 26 C and 60% RH, respectively, the limit of sub-cooled de-
decreased towards condensation temperature. The pump was gree for the pure panel, metal panel and gypsum panel are
started again when the temperature of inlet chilled water increase 3.2 C, 5.4 C and 6.5 C, respectively.
to 16 C. The control strategy was confirmed to be efficient in (5) The water condensation control strategy was raised based on
avoiding water condensation in radiant cooling systems. the ‘ub-cooled degree. The waster condensation phenome-
non can be avoided through experimental research.
4. Conclusions
Radiant cooling is potential using in residential building air
Performance of heat transfer and water condensation on three conditioning if the cooling capacity could be increased while it is
different types of radiant cooling panels was analyzed. The constant running secure. The water control strategy was proved to meet
Fig. 14. Control strategy for avoiding water condensation on the surface of the tube.
Y.L. Yin et al. / Building and Environment 71 (2014) 15e23 23
[2] Rees Simon J, Haves Philip. An experimental study of airflow and temperature
distribution in a room with displacement ventilation and a chilled ceiling.
Build Environ 2013;59:358e68.
[3] Diaz Nestor Fonseca, Lebrun Jean, Andre Philippe. Experimental study and
modeling of cooling ceiling systems using steady-state analysis. Int J Refrig
2010;33:793e805.
[4] Chiang Weihwa, Wang Chiaying, Huang Jiansheng. Evaluation of cooling
ceiling and mechanical ventilation systems on thermal comfort using
CFD study in an office for subtropical region. Build Environ 2012;48:
113e27.
[5] Ferkl Lukas, Siroky Jan. Ceiling radiant cooling: comparison of ARMAX
and subspace identification modelling methods. Build Environ 2010;45:
205e12.
[6] De Carli Michele, Scarpa Massimiliano, Tomasi Roberta, Zarrella Angelo.
A numerical model for the thermal balance of rooms equipped with radiant
systems. Build Environ 2012;57:126e44.
[7] Ren Jianbo, Zhu Li, Wang Yiping, Wang Congrong, Xiong Weicheng. Very low
temperature radiant heating/cooling indoor end system for efficient use of
renewable energies. Sol Energy 2010;84:1072e83.
[8] Eusebio ZE, Conceicao, Manuela M, Lucio JR. Evaluation of thermal comfort
conditions in a classroom equipped with radiant cooling systems and sub-
jected to uniform convective environment. Appl Math Model 2011;35:1292e
305.
[9] Memon Rizwan Ahmed, Chirarattananon Surapong, Vangtook Prapapong.
Thermal comfort assessment and application of radiant cooling: a case study.
Fig. 15. Variation of the temperatures of the system. Build Environ 2008;43:1185e96.
[10] Tian Zhen, Love James A. A field study of occupant thermal comfort and
above demands. However, water condensation could be found thermal environments with radiant slab cooling. Build Environ 2008;43:
1658e70.
under fluctuant indoor condition. For this reason, employing [11] Catalina Tiberiu, Virgone Joseph, Kuznik Frederic. Evaluation of thermal
innovative material such as hydrophobic, on the panels, is a comfort using combined CFD and experimentation study in a test room
promising technological measure which can guarantee safe and equipped with a cooling ceiling. Build Environ 2009;44:1740e50.
[12] Wang RZ, Yu X, Ge TS, Li TX. The present and future of residential
improved operation of the system. refrigeration, power generation and energy storage. Appl Therm Eng
2013;53:256e70.
Acknowledgments [13] Ansuini Roberta, Larghetti Roberto, Giretti Alberto, Lemma Massimo. Radiant
floors integrated with PCM for indoor temperature control. Energy Build
2011;43:3019e26.
This work was supported by National Natural Science Founda- [14] Hu R, Niu JL. A review of the application of radiant cooling & heating systems
tion of China under the contract No. 51276114 and Program for New in Mainland China. Energy Build 2012;52:11e9.
[15] Sui Xuemin, Zhang Xu. Effects of radiant terminal and air supply terminal
Century Excellent Talents in University No. NCET-12-0360. The devices on energy. Energy Build 2012;49:499e508.
support from The Ministry of Education Innovation Team (IRT 1159) [16] Ge Gaoming, Xiao Fu, Wang Shengwei. Neural network based prediction
is also appreciated. method for preventing condensation in chilled ceiling systems. Energy Build
2012;45:290e8.
[17] Shou Qingyun, He Jing. Research on suitable application sites of radiant
References cooling system. Energy Procedia 2012;14:1002e7.
[18] Song Doosam, Kim Taeyeon, Song Suwon, Hwang Suckho, Leigh Seung-Bok.
[1] De Carli Michele, Tonon Massimo. Effect of modelling solar radiation on the Performance evaluation of a radiant floor cooling system integrated with
cooling performance of radiant floors. Sol Energy 2011;85:689e712. dehumidified ventilation. Appl Therm Eng 2008;28:1299e311.