3 PHASE AUTOTRANSFORMER
Coolant bores | natural convection DAL
Horizontal mounting version 2kVA … 5kVA
TYPICAL APPLICATIONS
EN61558-2-13
Screw terminals are contact proof according Max. ambient temperature 40°C
to VBG4. Degree of protection IP00 - open transformer
Transformer provides 2 loops for safe trans-
Connections Screw terminals contact proof according to VBG4
portation or craning (core sizes > 3UI150 / 65
– 4.5kVA). Ready for horizontal mounting -
including angle brackets
Other data
Final operation position must allow natural
convection through coolant bores.
©Schmidbauer GmbH • Spanberg 16 • D-84332 Hebertsfelden • Generated 05/ 2003 • Data may differ or change without notice
Phone +49 (0) 87 21-96 62-0 • Faximile +49 (0) 87 21-96 62-50 • eMail: trafo@schmidbauer.net • www.schmidbauer.net
Schmidbauer transformers. Get the power. Turn it on.
2kVA … 5 kVA
Dimensions
Power A B*) C D E F Copper weight Total weight Type and
Size
kVA approx. mm KG KG ordering no.
2.0 290 120 200 258 160 9.0 x 13.0 6.30 19.30 3UI 120 / 51 DAL0200
2.5 290 110 220 258 176 9.0 x 13.0 7.50 20.50 3UI 132 / 46 DAL0250
3.2 290 125 220 258 176 9.0 x 13.0 8.20 25.50 3UI 132 / 60 DAL0320
4.0 330 125 250 298 200 9.0 x 13.0 12.20 31.80 3UI 150 / 52 DAL0400
4.5 330 150 250 298 200 9.0 x 13.0 11.40 36.50 3UI 150 / 65 DAL0450
5.0 360 142 280 322 224 9.0 x 13.0 17.00 44.00 3UI 168 / 58 DAL0500
*)Note:
Dimension „B“ indicates a reference value Coolant bore between primary and secundary
only. Phase current and therefore size of screw winding.
terminals used depends on transformer ratio Winding on polyamide coil former.
(identical size).
©Schmidbauer GmbH • Spanberg 16 • D-84332 Hebertsfelden • Generated 05/ 2003 • Data may differ or change without notice
Phone +49 (0) 87 21-96 62-0 • Faximile +49 (0) 87 21-96 62-50 • eMail: trafo@schmidbauer.net • www.schmidbauer.net
Schmidbauer transformers. Get the power. Turn it on.
Load
...mains power may be higher
...transformed power is lower
...size can be reduced (core, copper winding)
Please note:
Equation to calculate the requested size:
Equation: Regarding input/ output „upper“
or „lower voltage“ is independant, voltage Example: 1 phase autotransformer
related only Input voltage 440V | Output voltage 400V
For 3 phase autotransformers value „Rated power“ needed for application: 5kVA
of phase voltage is important.
lower voltage
Example shows 90% power saving Size load
upper voltage
compared isolating transformers.
Identical equation works with 3 phase
transformers. Size
100% load
©Schmidbauer GmbH • Spanberg 16 • D-84332 Hebertsfelden • Generated 05/ 2003 • Data may differ or change without notice