SECTION 14215

ELECTRIC ELEVATORS

PART - 1 GENERAL

1.01 SECTION INCLUDES


A. Electric elevator system.
B. Passenger cab with doors and frames, hoistway entrance doors and frames.
C. Machines, controllers, hoistway equipment, and accessories.
D. Placement of elevator machine anchors in concrete, in comply with related standards
and codes.
E. Placement of special guide rail brackets and inserts for installation, casting in concrete,
in comply with related standards and codes.

1.02 RELATED SECTIONS


A. Division 01 - General requirements.
B. Division 03 - Cast-in-Place Concrete: divider beams, overhead hoist beams, and
grouting thresholds.
C. Division 04 - Unit Masonry System: Building-in and grouting hoistway door frames.
D. Division 05 - Metal Fabrications: Pit ladder, Sill supports, divider beams, overhead
hoist beams...etc
E. Division 07 - Fire stopping: Fire proofing of guide rail brackets where attached to
building structural members.
F. Division 16 - Basic Materials and Methods: Empty conduit to elevator equipment
devices remote from elevator machine room or hoistway.
G. Division 16 - Basic Materils and Methods: Empty conduit between controller cabinet (
in machine room ) to BMS.
H. Division 16 - Electrical connections for equipment.
I. Division 16 - Fire Alarm System: Fire and smoke detectors and interconnecting
devices.
J. Division 16 - Fire Alarm System: Fire alarm signal lines to elevator controller cabinet.
K. Division 16 - General Provisions for Electrical work.

1.03 STANDARDS:
Unless otherwise approved, applicable standards are as follows, in order of priority:
A. EN81 and BS5655: parts 1 to 12 – safety rules for the construction and installation of
electric lifts.
B. ANSI/ASME A17.1 - Safety Code for Elevators and Escalators.

Ministry of Commerce & Industry 14215-1


Prototype Branch in the Kingdom Cities
1.04 ELECTRICAL POWER SUPPLY
A. Electrical power shall be supplied at 380 Volts 3 phase, 60 Hz.
B. All electrically operated equipment shall be designed and derated for continuous and
prolonged operation during the worst climatic conditions experienced at project site
area along the year, including (max - average temperature per day, month and year
max. humidity , dust storms and similars).

1.05 SYSTEM DESCRIPTION


A. Electric Elevator Systems: Traction machine, overhead.
B. Characteristics of each elevator are as per the following schedule:
C. Door Control Features:
1. Program door control to open doors automatically when car arrives at floor.
2. Render "Door Close" button inoperative when car is standing at dispatching
terminal with doors open.
3. If doors are prevented from closing for approximately 15 seconds, because of an
obstruction, automatically disconnect door reopening devices, close doors more
slowly until obstruction is cleared. Sound buzzer.
4. Door Safety Devices: Moveable, retractable safety edges, quiet in operation,
equip with photo electric light rays.
D. Interconnect elevator control system with building fire alarm, building management
control system and telephone system.
E. Provide necessary provision at lift machine rooms to allow for over all system
monitoring and reprogramming facilities.

1.06 CONTROL OPERATION


A. The control system shall be capable to achieve, but not limited to the following
functions and features:-
1. If a car stops for a hall call and car button is pressed within predetermined
interval after a stop for a landing, corresponding to direction the car was
traveling, proceed in the same direction regardless of the other hall calls
registered.
2. If down hall buttons are pressed while car is traveling up, do not stop at those
landings but allow those calls to remain registered for answering by the next
down traveling car.
3. After the highest car has responded to up hall calls, reverse car automatically and
respond to down car and hall calls.
4. When traveling down, a car will not respond to up calls. Allow those up calls to
remain registered, to be answered by next available car on an up trip.
5. Include a time delay to hold car for an adjustable interval at landings where stops
are made to enable passengers to enter or leave the car. Cancel the time interval
upon registration of a car call or pressure on the car door close button.
6. Permit a registered car call to establish the direction of travel when a car has
answered the farthest car call, even if other hall calls are registered.
Ministry of Commerce & Industry 14215-2
Prototype Branch in the Kingdom Cities
1.07 INDEPENDENT SERVICE
A. Provide key operated "Independent Service" on car operating panel. Key activation will
remove that car from normal operation and cancel all pre-registered car calls.
B. Car will respond to selected floor. Car will not respond to any calls from hall call
buttons. Car will only respond to calls placed on the car operating panel. doors will
remain open at last landing requested. Doors will close with a constant pressure on
"DOOR CLOSE" button.
C. Key activation to normal operation will return car to normal operation.

1.08 EMERGENCY POWER OPERATION


A. Arrange elevator operation to operate under emergency building power when normal
power supply fails as following:
1. Group elevators: Only one elevator shall be automatically selected to stay in
service upon bringing other cars (one by one) down to main floor with its doors
open. If the pre-selected car fails to operate automatically select an other car to
operate.
B. Provide transfer switches and auxiliary contacts in accordance with specification Install
connections to power feeders.
C. Provide operational control circuitry for adapting the change from normal to emergency
power.
D. Advance one elevator at a time under emergency power operation to a pre-selected
landing, car to stop, open doors, disable operating circuits and hold in standby
condition.
E. provide manual switch to override the automatic selection procedure.

1.09 SUBMITTALS
A. Submit under provisions of Division.1
B. Shop Drawings: Indicate the following information:
1. Car, counterweight, sheaves, machine and sheave beams, guide rails, buffers,
ropes, and other components in hoistway.
2. Rail bracket spacing, maximum loads imposed on guide rails requiring load
transfer to building structural framing.
3. Individual weight of principal components, load reaction at points of support.
4. Loads on hoisting beams and location of trolley beams
5. Clearances and over travel of car and counter weight
6. Location of components.
7. Locations in hoistway of traveling cables and connections for car light and
telephone
8. Location and sizes of access doors, doors, and frames
9. Expected heat dissipation of elevator equipment.
10. Interface with building management system.
11. Electrical characteristics and connection requirements.
12. Show arrangement of equipment so rotating elements, sheaves, and other
Ministry of Commerce & Industry 14215-3
Prototype Branch in the Kingdom Cities
equipment can be removed for repairs or replaced without disturbing other
components. Arrange equipment for clear passage through access door.
13. Complete power and control wiring diagrams.
C. Product Data:Provide data on the following, items:
1. Signal and operating fixtures, operating panels indicators.
2. Cab design,dimensions, layout, and components.
3. Cab and hoistway door and frame details.
4. Electrical characteristics and connection requirements.
D. Samples: Submit Samples, illustrating cab floor material, cab interior finishes, cab and
hoistway door and frame finishes.

1.10 OPERATION AND MAINTENANCE DATA


A. Submit under provisions of division 1.
B. Include a parts catalog with complete list of equipment replacement parts, identify each
entry with equipment description and identifying code. Provide spare, in accord with
section 01730.
C. Provide technical information for servicing operating equipment.
D. Include legible schematic wiring diagrams of installed electrical equipment, and
changes made in the work. List symbols corresponding to identity or markings on
machine room and hoistway apparatus.
E. Provide one copy of master schematic and one copy of lubrication chart, each framed
with clear plastic mount on machine room wall.

1.11 QUALITY ASSURANCE


A. Perform work in accordance with BS 5655, parts 1 to 12, and as supplemented in this
section.
B. Maintain one copy of each document on site.

1.12 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing the Products specified in this
section with minimum ten years documented experience.
B. Installer: local Company specializing in performing the work of this section approved
by elevator equipment manufacturer with minimum five years documented experience,
fully qualified staff should be presented for Owner approval.

1.13 REGULATORY REQUIREMENTS


A. Conform to applicable code for manufacture and installation of elevator system.
B. Conform to provisions for the physically handicapped.
C. Products Requiring Electrical connection listed and classified by Underwriters
Laboratories, Inc, testing firm acceptable to the Owner as suitable for the purpose
specified and indicated.

1.14 PRE-INSTALLATION CONFERENCE


A. Convene one week prior to commencing work of this section, under provisions of
Ministry of Commerce & Industry 14215-4
Prototype Branch in the Kingdom Cities
Division. 1.
B. Require attendance of persons directly involved with the work of this section.
C. Review schedule of installation, installation procedures and conditions, and
coordination with related work.

1.15 FIELD MEASUREMENTS


A. Verify that field measurements are as indicated on shop drawings and instructed by the
manufacturer.

1.16 WARRANTY
A. Provide Five year manufacture's warranty under provisions of Division.1
B. Warranty: Include coverage for elevator operating equipment and devices.
C. Obtain Lioyd's Inspection Certificate and submit to Owner.

1.17 MAINTENANCE SERVICE


A. Furnish service and maintenance of elevator system and components for two year from
date of final hand-over of the project.
B. Examine system components semi-monthly Clean, adjust, and lubricate equipment.
C. Include systematic examination, adjustment, and lubrication of elevator equipment.
repair or replace parts whenever required. Use parts produced by the manufacturer of
the original equipment. Replace wire ropes when necessary to maintain the required
factor of safety.
D. Perform work without removing cars during peak traffic periods.
E. Provide 24 hours a day emergency call back service during this maintenance period.
F. Maintain locally, near the Place of the work, an adequate stock of parts for replacement
or emergency purposes. Have personnel available to ensure the fulfillment of this
maintenance service, without unreasonable loss of time.
G. Perform maintenance work using competent and qualified personnel, under the
supervision of the elevator manufacturer or original installer.
H. Maintenance service shall not be assigned or transferred to any agent or Subcontractor
without prior written consent of Owner.
I. The contractor shall furnish a programme for maintenance work for review and
approval of the owner. The programme shall provide for the daily availability of a
qualified person on site during working hours, and for maintenance to be provided by
the manufacturer or its agent which installed the lift.

Ministry of Commerce & Industry 14215-5


Prototype Branch in the Kingdom Cities
PART - 2 PRODUCTS

2.01 MANUFACTURERS
The following Manufacturers shall be referred to as a standard for quality, performance
and maintenance reference:
A. Schindler
B. Tayssen.
C. Mitsubishi - Japan
D. Otis - U.S.A

2.02 MATERIALS
A. Rolled Steel Sections, Shapes, Rods: ASTM A36
B. Sheet Steel: ASTM A366 Class (1) with matte finish. ASTM A446 Grade (B) zinc
coated to (G90)
C. Stainless Steel: ASTM A167 Type (304) No. (4) finish.
D. Aluminum: ASTM B221, extruded.
E. Plywood: APA Structural I, Grade (C-D) sanded.
F. Plastic Laminate: NEMA LD3, type, color/pattern and matte surface finish.

2.03 SCHEDULE & SPECIFICATION OF ELEVATOR

Equipment Name: Building Type B

Main data

KONE solution 1x KONE N Mono Space/ PW15/10-19

Design Electrically-operated passenger lift for the transport of


people and loads.

Carrying Capacity 1150 kg or 15 persons

Speed 1.00 m/s

Travel 4.15 m

The lift stops at 2 stops and has 2 loading points arranged


Stops
on the main access side.

Underlying standards EN81-1

Ministry of Commerce & Industry 14215-6


Prototype Branch in the Kingdom Cities
Shaft

Shaft size 2275 mm wide x 2600 mm deep ±25 mm

Shaft pit depth 1250 mm

Shaft head height 3700 mm to underside of the lifting points.

Shaft Material Concrete

Mechanical components

Counterweight Safety Gear No

Buffer Polyurethane Buffer

Car

Car measurements
1700 mm width x 1550 mm depth x 2300 mm height

The KONE Mix & Match Design Collection offers you the
greatest possible structural freedom to adapt the optical
Construction appearance of your lift to the building according you your
Car Interior: needs. The fitting out of the cabin can be freely chosen from
the material type group offered and either from Standard or
Premium material offering.

CL88 - direct lighting, roung LED spots


Car ceiling and lighting:
ST4-Silver brushed StSt

Wall B:WALLFINISH : st4


Wall C:WALLFINISH : st4
Car walls
Wall D:WALLFINISH : st4
VER - Vertical Panel

Car front wall FRONTWALLFINISH : ST4

Car floor Local Floor


23 mm
MR1-Glass mirror FW/PH Full width/Partial height Full Width
Mirror
mirror on side C

Mirror is on B and C and D Walls


Hand rail
HR64-Tube D38 w/ rounded ends F Asturias Satin

Skirting Silver Brushed

KDS300 ST4
Operating and signal elements, Car Round
1 - Yes
Door open with extended door time, button

Ministry of Commerce & Industry 14215-7


Prototype Branch in the Kingdom Cities
Doors

1000 mm width x 2100 mm internal height


High duty landing door
Door measurements
1C,Two-panel centre opening
Door type
ST4 - Silver Brushed St. St. AISI304
Design
To prevent injury to people by the self-closing doors, the Car
Car door
door is fitted with a closing force limiter. Curtain of light, fix
to door panel (CL)

Sill type Type N Sill without carpet profile


Car door sill Extruded aluminium profile (standard w/o surface treatment)

Narrow Frame
Landing door ST4 - Silver Brushed St. St. AISI304
2 hours fire rated doors
E-Expander bolt
Sill type N1 - Sill w/o carpet trim, in the well
Landing door sill Extruded aluminium profile

Operating and signal KDS300 series signalisation


LCS buttons for FC
elements, stops ST4 White In the wall
None None

Landing Doors

Floor Floor
Finish Fire Class
Number Marking

1 G Silver Brushed Stainless Steel AISI304 2 hours fire rated doors

2 1 Silver Brushed Stainless Steel AISI304 2 hours fire rated doors

Control system accessories

Alarm bell, at main floor Elevator announcer, not programmable All (CRB_C + CRB_L) Disturbance
alarm, general, potential free Emergency battery drive, monospace or minispace elevator, automatic
Emergency stop switch in shaft, two switches Fire detection, whole building, doors open Acoustic device
for arrival, on car, electronic, twice for down Emergency intercom car - machine room - control room
Elevator link, alarm, mode signals, position binary Lock with Emergency Opening Device OSS LC - Out
of service switch at landing, doors closed, lights off Parking at pre-defined floor, doors closed
TYP_FILTER_THD : L

Ministry of Commerce & Industry 14215-8


Prototype Branch in the Kingdom Cities
Machinery

The machinery is designed as a gearless, three-phase


synchronous motor with integrated traction sheave made
from abrasion-proof special casting. The electromagnetic
Machinery specification: dual circuit brake is quietly activated by a brake solenoids.
The brake linings are made from asbestos-free material. A
manual brake release device is provided for emergency
operation.

Machine output 6.70 kW

Nominal supply current 15.00 A

Starting supply current 20.00 A

Power supply, machinery 3 x 380 V, 60 Hz

Power supply, cabin light 230 V, 50 Hz

The sound-insulated drive mechanism is fitted in the shaft


head behind the guide rails, on the counterweight side,
Arrangement directly on the guide rails. Therefore there is no need for a
separate machine room, which makes considerable savings
on building costs.

Control system

Full Collective
Control system principle
Simplex.

Topmost floor
The operating elements for maintenance of the lift and for
possible emergency release are fitted in the maintenance
access panel at the top stop. As the operating elements are
locked away, they can only be activated by authorised
personnel.
Maintenance access panel Access to the operating elements must be guaranteed at all
times during the lift's operating periods. The maintenance
access panel is fitted directly to the shaft door floor frame.
The surface of the maintenance and emergency release
panel is specified in zinc-coated sheet steel, prepared for
final painting on site.
MAP on Landing wall with recess ST4

Ministry of Commerce & Industry 14215-9


Prototype Branch in the Kingdom Cities
Emergency call system

1. Battery operated emergency Landing Device


2. Intercom – 3 way
Special features 3. Emergency lighting in the car
4. automatic car light & fan shutoff
5. Door Open/Close Button

Country of Origin KONE China

Equipment Name:
Building Type C&D

Main data

KONE solution 1x KONE N Mono Space/ PW15/10-19

Electrically-operated passenger lift for the transport of


Design people and loads.

Carrying Capacity 1150 kg or 15 persons

Speed 1.00 m/s

Travel 4.15 m

The lift stops at 2 stops and has 2 loading points arranged


Stops
on the main access side.

Underlying standards EN81-1

Shaft

Shaft size 2425 mm wide x 2425 mm deep ±25 mm

Shaft pit depth 1250 mm

Shaft head height 3700 mm to underside of the lifting points.

Shaft Material Concrete

Ministry of Commerce & Industry 14215-10


Prototype Branch in the Kingdom Cities
Mechanical components

Counterweight Safety Gear No

Buffer Polyurethane Buffer

Car

Car measurements
1700 mm width x 1550 mm depth x 2300 mm height

The KONE Mix & Match Design Collection offers you the
greatest possible structural freedom to adapt the optical
Construction appearance of your lift to the building according you your
Car Interior: needs. The fitting out of the cabin can be freely chosen from
the material type group offered and either from Standard or
Premium material offering.

CL88 - direct lighting, roung LED spots


Car ceiling and lighting:
ST4-Silver brushed StSt

Wall B:WALLFINISH : st4


Wall C:WALLFINISH : st4
Car walls
Wall D:WALLFINISH : st4
VER - Vertical Panel

Car front wall FRONTWALLFINISH : ST4

Car floor Local Floor


23 mm
MR1-Glass mirror FW/PH Full width/Partial height Full Width
Mirror
mirror on side C

Mirror is on B and C and D Walls


Hand rail
HR64-Tube D38 w/ rounded ends F Asturias Satin

Skirting Silver Brushed

KDS300 ST4
Operating and signal elements, Car Round
1 - Yes
Door open with extended door time, button

Doors

1000 mm width x 2100 mm internal height


High duty landing door
Door measurements
1C,Two-panel centre opening
Door type
ST4 - Silver Brushed St. St. AISI304
Design
To prevent injury to people by the self-closing doors, the Car
Car door
door is fitted with a closing force limiter. Curtain of light, fix
to door panel (CL)

Sill type Type N Sill without carpet profile


Car door sill Extruded aluminium profile (standard w/o surface treatment)

Ministry of Commerce & Industry 14215-11


Prototype Branch in the Kingdom Cities
Narrow Frame
Landing door ST4 - Silver Brushed St. St. AISI304
2 hours fire rated doors
E-Expander bolt
Sill type N1 - Sill w/o carpet trim, in the well
Landing door sill Extruded aluminium profile

Operating and signal KDS300 series signalisation


LCS buttons for FC
elements, stops ST4 White In the wall
None None

Landing Doors

Floor Floor
Finish Fire Class
Number Marking

1 G Silver Brushed Stainless Steel AISI304 2 hours fire rated doors

2 1 Silver Brushed Stainless Steel AISI304 2 hours fire rated doors

Control system accessories

Alarm bell, at main floor Elevator announcer, not programmable All (CRB_C + CRB_L) Disturbance
alarm, general, potential free Emergency battery drive, monospace or minispace elevator, automatic
Emergency stop switch in shaft, two switches Fire detection, whole building, doors open Acoustic device
for arrival, on car, electronic, twice for down Emergency intercom car - machine room - control room
Elevator link, alarm, mode signals, position binary Lock with Emergency Opening Device OSS LC - Out
of service switch at landing, doors closed, lights off Parking at pre-defined floor, doors closed
TYP_FILTER_THD : L

Machinery

The machinery is designed as a gearless, three-phase


synchronous motor with integrated traction sheave made
from abrasion-proof special casting. The electromagnetic
Machinery specification: dual circuit brake is quietly activated by a brake solenoids.
The brake linings are made from asbestos-free material. A
manual brake release device is provided for emergency
operation.

Machine output 6.70 kW

Nominal supply current 15.00 A

Starting supply current 20.00 A

Power supply, machinery 3 x 380 V, 60 Hz

Power supply, cabin light 230 V, 50 Hz

The sound-insulated drive mechanism is fitted in the shaft


Arrangement
head behind the guide rails, on the counterweight side,
directly on the guide rails. Therefore there is no need for a

Ministry of Commerce & Industry 14215-12


Prototype Branch in the Kingdom Cities
separate machine room, which makes considerable savings
on building costs.

Control system

Full Collective
Control system principle
Simplex.

Topmost floor
The operating elements for maintenance of the lift and for
possible emergency release are fitted in the maintenance
access panel at the top stop. As the operating elements are
locked away, they can only be activated by authorised
personnel.
Maintenance access panel Access to the operating elements must be guaranteed at all
times during the lift's operating periods. The maintenance
access panel is fitted directly to the shaft door floor frame.
The surface of the maintenance and emergency release
panel is specified in zinc-coated sheet steel, prepared for
final painting on site.
MAP on Landing wall with recess ST4

Emergency call system

1. Battery operated emergency Landing Device


2. Intercom – 3 way
Special features 3. Emergency lighting in the car
4. automatic car light & fan shutoff
5. Door Open/Close Button

Country of Origin KONE China

PART - 3 EXECUTION

3.01 EXAMINATION
A. Verify that hoistway, pit, and machine room are ready for work of this section.
B. Verify hoistway shaft and openings are of correct size and within tolerance.
C. Verify location and size of machine foundation and position of machine foundation
bolts.
D. Verify that electrical power is available and of the correct characteristics.

3.02 PREPARATION
A. Arrange for temporary electrical power for installation work and testing of elevator
components.

3.03 INSTALLATION
A. Install in accordance with ANSI/ASME A17.1.
B. Install system components. Connect equipment to building Utilities.

Ministry of Commerce & Industry 14215-13


Prototype Branch in the Kingdom Cities
C. Provide conduit, boxes, wiring, and accessories.
D. Mount machine on vibration and acoustic isolators, on bed plate and concrete pad.
Place machine on structural supports and bearing plates. Securely fasten to building
supports. Prevent lateral displacement.
E. Accommodate equipment in space indicated.
F. Install guide rails using threaded bolts with metal shims and lock washers under nuts.
Compensate for expansion and contraction movement of guide rails.
G. Accurately machine and align guide rails.Form smooth joints with machined splice
plates.
H. Bolt brackets to self drilling expansion shell anchors that will perform to four times the
rated pull out load.
I. Field Welds: Chip and clean away oxidation and residue, wire brush, spot prime with
two coats.
J. Coordinate installation of hoistway wall construction.
K. Install hoistway door sills, frames, and headers in hoistway walls. Grout sills in place.
Set entrances in vertical alignment with car openings and aligned with plumb hoistway
lines.
L. Fill hoistway door frames solid with grout.
M. Adjust equipment for smooth and quiet operation.

3.04 TOLERANCES
A. Guide Rail Alignment:
Plumb and parallel to each other 3 mm in accordance with ANSI/ASME A17.1 and
ANSI/ASME A17.2.
B. Cab Movement on Aligned guide Rails:
Smooth movement, with no objectionable lateral or oscillating movement or vibration.

3.05 FIELD QUALITY CONTROL


A. Field inspection and testing will be performed under provisions of Division 1.
B. Perform tests required by ANSI/ASME A17.2.
C. Provide two weeks written notice of date and time of tests
D. Supply instruments and execute specific tests.
E. Perform the following tests in the presence of the Architect/Engineer.
1. Test elevator system by transporting at least load persons up from main floor
during a five minute period.
2. At an agreed time during the contract warranty period, and with the building
normally occupied using normal building traffic, conduct tests to verify
performance. Funish event recording of all hall call registrations, time initiated,
and response time throughout entire normal working day.
3. Time elevator travel between typical floors as recommended by Owner Measure
time from moment doors start to close until car has stopped level at next floor and
doors are opening.

Ministry of Commerce & Industry 14215-14


Prototype Branch in the Kingdom Cities
3.06 TESTS BY REGULATORY AGENCIES
A. Testing by regulatory agencies will be performed at their discretion, documented by the
Contractor under provisions of Division. 1.
B. Obtain required permits to perform tests. perform tests required by regulatory agencies.
C. Schedule tests with agencies, Owners Architect/Engineer, and Contractor present.
D. Furnish test and approval certificates issued by jurisdictional authorities.

3.07 ADJUSTING
A. Adjust for smooth acceleration and deceleration of car so not to cause passenger
discomfort.
B. Adjust automatic floor leveling feature at each floor to achieve 6 mm from flush.

3.08 CLEANING
A. Clean work under provisions of Division. 1.
B. Remove protective coverings from finished surfaces.
C. Clean surfaces and components ready for inspection.

3.09 PROTECTION OF FINISHED WORK


A. Protect finished work under provisions of Division 1.
B. Do not permit construction traffic within cab after cleaning.

END OF SECTION